AERMEC GR3 User manual

USAGE MANUAL
Electronic regulation for chillers
and air and water cooled heat pumps
ISO 9001 - Cert. n° 0128/4
IGR3FX. 0810. 4724210_00
GR3
MANUEL D'UTILISATION
Réglage électronique pour producteurs d'eau glacée
et pompes à chaleur à condensation par air et par eau
BEDIENUNGSANLEITUNG
Elektronische Regelvorrichtung für Kaltwassersätze
und Wärmepumpen mit Luft- und Wasserkondensation
MANUAL DE USO
Regulación electrónica para enfriadores
y bombas de calor condensadas por aire y por agua
Il codice 4724210_00
sostituisce i seguenti codici:
6872102_01 • 6872103_01 • 4572701 •
4572702 • 4844510 • 6872120
ItalianoItaliano ItalianoItaliano
English Français Deutsch Español

2

1. Characteristics of the regulation............................ 3
2. User interface................................................................. 3
3. Control panel description ........................................... 4
4. Reading menu.................................................................. 5
5. Turning on/off (local mode)....................................... 7
6. Season change................................................................ 7
7. Working temperature setting.................................. 8
8. Setting menu..................................................................13
9. Control settings for remote panel........................15
10. Alarms ..............................................................................16
Summary
iThe device must be installed in compliance with the local legislation currently
in force in the country of destination.

4
possible to control, from a distance, the
turning on and off, the setting of working
mode (cold-hot), and the visualisation of
the alarms summary with a red indicator
light (alarms).
• PR3
Simplified remote panel, follows the
base controls that can be operated
remotely from up to 30m.
CHARACTERISTICS OF THE REGULATION1.
The command panel of the unit allows the
quick setting of the machine's operating
parameters, their visualisation at any
time, and the immediate summary of the
machine's operating status. The display
is made up of 3 figures and 4 LEDs to
signal, the type of working, the visualisa-
tion of the parameters set or measured,
and any alarms that have been activated.
The card memorises all the settings
saved with each modification and used
for re-ignition after a switch-off owing
to lack of voltage. With the installation
of the remote control panel PR3, it is
Remote connections
USER INTERFACE2.

5
CONTROL PANEL DESCRIPTION3.
Key Meaning
1Visualisation of machine probe readings
2Visualisation of triggered alarm list
3Visualisation of operational parameters menu
4Key to change operational parameters
5 and 6 Navigation keys
7
Sets the unit control, which can be local (L), from the panel on board the machine, or remote (R), from
remote panel or supervisor. The active setting is indicated by the switching on of the corresponding
indicator light.
8Sets heating or cooling mode;
9Turns the machine on or off by setting it to STAND-BY, (only the electronic card and the electric heater
are powered);
10 Cancels machine alarms and restarts it (for further information, see alarm table)
11 Led indicator of current alarms
12 Led indicator of current defrosting mode
13 Led indicator of operating compressor
FIRST TIME THE MACHINE IS SWITCHED ON
The first time the machine is switched on, it carries out a self-
configuration operation and a series of checks through which
operating parameters and electrical connections of the ma-
chine are checked. After the autotest, the company logo and
the machine type are displayed for some seconds. Then, the
panel is prepared for displaying the machine probe readings
(key activated).

6
Reading acronym Meaning NRA NRC NRL NBW NLW
TIA Read temperature at the evaporator inlet
TIAH Temperature read at the condenser inlet
TAE Outside air temperature
TUA C1
Temperature read at evaporator outlet for
circuit 1 (or the single-evaporator model)
DELTA C1
Temperature between evaporator inlet and
outlet for circuit 1 (or the single-evaporator
model)
TUAH C1 Temperature read at the condensator
outlet for circuit 1 or single-condenser.
DELTA C1
Temperature between condenser inlet and
outlet for circuit 1 (or the single-evaporator
model)
P.B.C1 Low-pressure reading in circuit 1
P.A.C1 High-pressure reading in circuit 1
TL C1 Liquid temperature in circuit 1
P.IN S1 Calculation of defrosting initial pressure
for circuit 1
ATTESA C1 Minimum waiting time to restart
compressor 1
ATTE.C1A Minimum waiting time to restart
compressor 1A
ATTE.C1B Minimum waiting time to restart
compressor 1B
P.B.C2 Low pressure reading in circuit 2
TUAH C2 Temperature read at the condenser
outlet for circuit 2
P.A.C2 High-pressure reading in circuit 2
TL C2 Liquid temperature in circuit 2
READING MENU4.
4 4 4
4
4 4
4 4
4 4 4 4 4
4 4 4 4 4
4 4 4 4 4
4 4 4 4 4
4 4 4 4 4
4 4 4 4 4
4 4 4 4 4
4 4 4 4 4
j j
j j
j j
j
j
j
j
j
j
j
j
j
CPx6
CPx6
CPx6
Cx2 Cx2

7
Reading acronym Meaning NRA NRC NRL NBW NLW
P.IN S2 Calculation of defrosting initial pressure
for circuit 2
ATTESA C2 Minimum waiting time to restart
compressor 2
ATTE. C2A Minimum waiting time to restart
compressor 2A
ATTE. C2B Minimum waiting time to restart
compressor 2B
SBRINA C1 Minimum waiting time before defrosting
circuit 1
SBRINA C2 Minimum waiting time before defrosting
circuit 2
TEV1 Gas temperature read at evaporator
inlet of circuit 1
TEV2 Gas temperature read at evaporator
inlet of circuit 2
TAC Temperature read in storage
TIR Reading of inlet temperature for heat
recovery
TUR1 Temperature read at the outlet for heat
recovery of circuit 1
TUR2 Temperature read at the outlet for heat
recovery of circuit 2
TFC Temperature read at the freecooling
battery inlet
4 4 4 4 4
4 4 4 4 4
4 4 4 4 4
4 4 4 4 4
j j
j
j j
j
j j
j
4 4
CPx6CPx6CPx6
4 4 4
ver T ver T
ver T
ver T ver T
ver T ver T
ver T
ver T ver T
ver T ver T
ver T
ver T ver T
d
Free
d
Free
d
Free
KEY
Reading available both in cooling only and heat pump models
Reading available only in 6-compressor models
Reading present in all versions, but available only in heat pump models
Reading available only in bi-condenser models
Reading available in models with Total Recovery
Reading available only in FREE COOLING models
4
j
Cx2
ver T
d
Free
CPx6

8
TURNING ON/OFF (5. local mode)
SEASON CHANGE6.
Image Procedure to be adopted
TURNING ON:
For unit commissioning, press only ON key. When the led is on,
the unit is ready for operation.
TURNING OFF:
Turn it off immediately with the same button.
Only if the PR3 accessory is installed, the unit shall be completely
off after seven seconds.
Image Procedure to be adopted
To activate the season change, just press the key indicated next.
So that the operation is correctly finished, the machine shall be
activated both in remote or in local.
Two symbols are present in the "season change" key:
- The symbol identifies the heat pump operation;
- the symbol identifies cooling operation.
SET
C1
C2
R
LR
SET
C1
C2
R
LR
DISPLAY OF THE FUNCTIONING PARAMETERS
For displaying operation parameters, the key
SET
is pressed;
the indicator light key
SET
is on and the parameters indicated
in chapter “SETTING MENU” are displayed. Parameters can be
sequentially displayed by using the arrow keys
++
e
+
-
. The
writing “Set Setting” appears on the first line and the set value
on the second line.
To change the set parameter, press the key and the key
led will also be on. The setting displayed can be modified by using
the arrow keys.
The wording on the first line changes to “Modified Setting”. By
pressing the key again, the modification is saved and, by
using the arrow keys, it is possible to scan set parameters again
to find a new parameter to be changed.

9
WORKING TEMPERATURE SETTING7.
HEATING SET POINT SETTING
Image Procedure to be adopted
To access the parameter menu, first press the SET key and
browse through by means of the arrow keys up to "Heating Set".
Then, to set the COOLING SET value, just press the screwdriver
key and enter into the modification of the set involved.
At this stage, by increasing or decreasing its value, the parameter
can be changed by means of the arrows (+ and -). Once the desired
temperature is decided, just confirm the operation by pressing
again the screwdriver key.
SET
C1
C2
R
LR
SETTING
Hot Set +50.0"C
SET
C1
C2
R
LRSETTING ADJUST
Hot Set +50.0"C
SET
C1
C2
R
LR
SETTING ADJUST
Hot Set +49.9"C
COOLING SET POINT SETTING
Image Procedure to be adopted
To access the parameter menu, first press the SET key and
browse through by means of the arrow keys up to "Cooling Set".
Then, to set the COOLING SET value, just press the screwdriver
key and enter into the modification of the set involved.
At this stage, by increasing or decreasing its value, the parameter
can be changed by means of the arrows (+ and -). Once the desired
temperature is decided, just confirm the operation by pressing
again the screwdriver key.
SET
C1
C2
R
LR
SETTING
Cold Set +20.0"C
SET
C1
C2
R
LRSETTING ADJUST
Cold Set +20.0"C
SET
C1
C2
R
LR
SETTING ADJUST
Cold Set +19.9"C
N.B.
There is a second cooling operation set point (parameter: 2nd C.
set). and a second heating working set point (parameter: 2nd H.
set). Both parameters (2nd C. set - 2nd H. set) can be operated
when the digital input (M11 3-4) is closed. For further information,
consult the installer or the Technical After Sales Service.
Cooling set
point values
Minimum -10 °C
Maximum 20°C
Heating set
point values
Minimum 30°C
Maximum 50°C

10
SETTING OF TIME AND DAY OF THE WEEK (available with PGS accessory only)
Image Procedure to be adopted
To access the parameter menu, first press the SET key and
browse through by means of the arrow keys up to TIME and DAY
visualisation.
To set the TIME and DAY, just press the screwdriver key. At this
stage the writing "ENTER CODE" will be displayed. The code is that
by default (00 00 00).
Just press the screwdriver key to confirm. Thus, the modification
of the set involved is accessed.
By means of the arrow keys, first the time is modified (first led on).
Once the time is decided, press the key SET to confirm and the
third led will be automatically on. Then, modify the day of the week
with the arrow keys.
Press the screwdriver key and the display visualisation will shift to
DAY, MONTH and YEAR setting. With the arrow keys and the first
led on, the day can be modified; with the second led on, the month
is modified and with the third, the year.
Once time, day, month and year are set, just press the screwdriver
key again to save the set values. The display will return to the initial
screen.
SET
C1
C2
R
LR
SETTING
00:00 Monday
SET
C1
C2
R
LR
INSERT CODE
00 00 00
SET
C1
C2
R
LRSETTING ADJUST
00:00 Monday
SET
C1
C2
R
LR
SETTING
15:30 Monday
SET
C1
C2
R
LR
SETTING ADJUST
10 07 08
SET
C1
C2
R
LR
SETTING
15:30 Monday

11
TIMER OPERATION MODE (available with PGS accessory only)
Image Procedure to be adopted
To access the parameter menu, first press the SET key
and browse through by means of the arrow keys up to the
parameter "Timer".
Press the screwdriver key. At this stage, the writing "ENTER
CODE" will be displayed. The code is the one by default (00
00 00). Just press the screwdriver key for a second time
to confirm.
By acting on the arrows, move to the programming mode
desired. There are three alternatives:
(NONE - DAY -WEEK).
NONE mode:
The programming timer is disabled.
DAY mode:
It is possible to set, along the day, two operation time bands.
- The Daily setting is visualised
- Monday to Sunday settings are not visualised.
WEEK mode:
It is possible, for each day of the week, two operation time
bands.
- Monday to Sunday settings are visualised.
- The Daily setting is not visualised
SET
C1
C2
R
LR
SETTING
Timer NONE
SET
C1
C2
R
LRINSERT CODE
00 00 00
SET
C1
C2
R
LR
SETTING
Timer NONE
SET IMPOSTATO
Timer NONE
SET IMPOSTATO
Timer DAY
SET IMPOSTATO
Timer WEEK
Once the desired option is selected, con-
firm by pressing the screwdriver key.
N.B. ON/OFF TIMER:
To program the timer, it is necessary
to have access either to the remote
or the local panel.

12
TIME BAND SETTING
Day mode
Image Procedure to be adopted
Press the SET key, act on the arrow keys until the “Daily” setting
is visualised.
Press the screwdriver key. At this stage, the writing "ENTER CODE"
will be displayed. The code is that by default (00 00 00).
Just press the screwdriver key a second time to confirm. At this
stage, the menu to modify time bands is entered.
Then, act on arrow keys to change START 1 values (at the same
time, STOP 1 values will be also in progress). Confirm with the
screwdriver key to modify only the STOP 1.
With the arrow keys, modify STOP 1 values and provide final
confirmation by pressing the screwdriver key.
The second time band is now visualised. Act on arrow keys to
change START 2 values (at the same time, STOP 2 values will
be also in progress). Confirm with the screwdriver key to modify
only the STOP 2.
With the arrow keys, modify STOP 2 values and provide final
confirmation by pressing the screwdriver key.
SET
C1
C2
R
LR
SETTING
Day
SET
C1
C2
R
LR
INSERT CODE
00 00 00
SET
C1
C2
R
LR
START 1 00:00<
STOP 1 00:00
SET
C1
C2
R
LR
START 1 00:20<
STOP 1 00:20
SET
C1
C2
R
LR
START 1 00:20
STOP 1 00:50<
SET
C1
C2
R
LR
START 2 06:00<
STOP 2 06:00
SET
C1
C2
R
LR
START 2 06:00
STOP 2 06:30<

13
TIME BAND SETTING
Week mode
Image Procedure to be adopted
Press the SET key, act on the arrow keys until the “Monday”
setting is visualised. With the arrow keys, the days from "Monday"
to "Sunday" will sequentially appear.
Press the screwdriver key to select the day. Thus, the menu for
that day is entered.
Then, act on arrow keys to change START 1 values (at the same
time, STOP 1 values will be also in progress). Confirm with the
screwdriver key to modify only the STOP 1.
With the arrow keys, modify STOP 1 values and provide final
confirmation by pressing the screwdriver key.
The second time band is now visualised. Act on arrow keys to
change START 2 values (at the same time, STOP 2 values will
be also in progress). Confirm with the screwdriver key to modify
only the STOP 2.
With the arrow keys, modify STOP 2 values and provide final
confirmation by pressing the screwdriver key.
The display visualisation will return to the initial "SET SETTING -
Monday". At this stage, it is possible to move the rest of the days
one by one and program the timer with the procedure previously
shown.
SET
C1
C2
R
LR
SETTING
Monday
SET
C1
C2
R
LR
SETTING
Monday
SET
C1
C2
R
LR
START 1 00:00<
STOP 1 00:00
SET
C1
C2
R
LR
START 1 00:20<
STOP 1 00:20
SET
C1
C2
R
LR
START 1 00:20
STOP 1 00:50<
SET
C1
C2
R
LR
START 2 06:00<
STOP 2 06:00
SET
C1
C2
R
LR
START 2 06:00
STOP 2 06:30<

14
INSTALLATOR SET
Description Default value
Tot. diff. Proportional temperature band within which the compressors
are activated and deactivated 5°C
Set AG
Antifreeze Alarm temperature, EV side (water outlet temperature).
3°C
Esc.B.P. Low Pressure Alarm bypass time, after the compressor start-
up. 3’
AG Evap Antifreeze setting for evaporator input gas temperature.
Can be overridden. -8 °C
B.AG Evap Evaporator antifreeze alarm bypass from On CP, end defrosting. 20 sec.
CP1 Power
% power of compressor 1 compared with the machine 100% value.
25%
CP2 Power
% power of compressor 2 compared with the machine 100% value.
25%
CP1A Power
% power of compressor 1A compared with the machine 100% value.
25%
CP2A Power
% power of compressor 2A compared with the machine 100% value.
25%
CP1B Power
% power of compressor 1B compared with the machine 100% value.
0
CP2B Power
% power of compressor 2B compared with the machine 100% value.
0
CP 1 Time Compressor 1 operating hours.
This value can only be reset. 0
CP 2 Time Compressor 2 operating hours.
This value can only be reset. 0
OreCP1A Number of worked hours for the 1A compressor.
This value can only be reset. 0
OreCP2A Number of worked hours for the 2A compressor.
This value can only be reset. 0
OreCP1B Compressor 1B operating hours.
This value can only be reset. 0
OreCP2B Compressor 2B operating hours.
This value can only be reset. 0
SETTING MENU8. SET
USER SETTING Description Min. Default Max. Water/Air
Water/Water
Cold Setting Water inlet temperature in Cold
mode operation. -10 °C 7.0°C 20°C
Heating Setting Water inlet temperature in Cold
mode operation. 30°C 50°C 50°C
2nd C. Set Second Cooling set. -10 °C 11°C 20°C
2nd H. Set SECOND HEATING SET. 30°C 45°C 50°C
4
4
4
4
4
4
j
j
Remember that the range within which these parameters are set
is provided by the machine operating limits. The minimum and
maximum values to be set only represent one characteristic of
regulation.
WARNING
The settings listed in the following table can be visualised by the user,
but they can be only modified by the technical After Sales Service.
If these settings are modified by non-authorised personnel, the war-
ranty shall be considered void.

15
INSTALLATOR SET
Description Default value
Cond.low Condensation regulation setting corresponding to the external
temperature T.C.low 17 bar
Diff.low Condensation regulation differential setting corresponding to the
external temperature T.C.low 20 bar
Cond.hig Condensation regulation setting corresponding to the external
temperature T.C.high 17 bar
Diff.hig Condensation regulation differential setting corresponding to the
external temperature T.C.high 12 bar
Cond. PC Corresponding condensation regulation setting in the heat pump 45 bar
Diff. PC
Condensation regulation differential corresponding to the heat pump
5 bar
T.C.low Low outside temperature limit for the selection of the setting and
selection differential -5 °C
T.C.high High outside temperature limit for the selection of the setting and
selection differential 40°C
Volt Min Minimum DCP output voltage when cold 1V
DcpR Off High pressure value below which DCP output is 0 volts during low
temperature pre-ventilation. 22 bar
DcpR On High pressure value above which DCP output is 10 volts during
low temperature pre-ventilation 23 bar
S. R Heating Thermostat setting to manage the water inlet recovery. 50°C
D.Tot.R Setting to determine the distance between one step and the
following one, in the recovery operation setting. 5°C
T. OutS. Temperature (read by the probe on the fluid) above which the
DEFROSTING action can END 20°C
Number of
resistors
Number of supplementary heaters (number of steps).
0
Set Res External air setting under which electrical elements are enabled 5°C
Power Res % power of each supplementary heater step compared with the
machine 100 % value 0
Set Ta CP
Setting in comparison with the external air. Below this value,
compressors will be disabled if P.C. supplementary heaters are
present. -5 °C
Numb. of pumps Total number of evaporator pumps 0
Numb. of pumps
ON No. of pumps switched on at the same time. 0
In/Out H20 Temperature regulation selection on the water inlet/outlet IN
Time Int Integration time (integral error calculation) for regulation in water
outlet. 600
CP1-CP2B
Compressor override mask if the power limit control is active:
CP1-CP2-CP1A-CP2A-CP1B-CP2B 111111
V.max FC Maximum DCP voltage in freecooling 10V
AG pump Enabling of the pump powering up as antifreeze protection together
with the evaporator electrical elements. OFF
MultiTRIO Enabling at the multichiller control (network control of more than
one chiller with master and slaves) OFF
Language Language selections used: Italian, English, German, and French - - -

16
INSTALLATOR SET
Description Default value
Code New access code to modify protected Settings.
Initially the code is 00-00-00. 000000
Time * Time, day of the week, month, year - - -
Timer Setting *Timer operation mode:
disabled, daily, weekly none
Daily *Timer setting: daily
Visualised if Timer Setting =Day. - - -
Monday *Weekly timer setting
Visualised if Timer Setting =Week. - - -
Tuesday *Weekly timer setting
Visualised if Timer Setting =Week. - - -
Wednesday *Weekly timer setting
Visualised if Timer Setting =Week. - - -
Thursday *Weekly timer setting
Visualised if Timer Setting =Week. - - -
Friday *Weekly timer setting
Displayed if Timer Setting =Week. - - -
Saturday *Weekly timer setting
Visualised if Timer Setting =Week. - - -
Sunday *Weekly timer setting
Visualised if Timer Setting =Week. - - -
*Available with PGS accessory
CONTROL BOARD SETTING
The command "remote" must be set
on the machine control board. The
timer operates either in local or re-
mote mode. In both cases, the timer is
ignored if the machine is in OFF. More-
over, the remote panel must be set to
“ON”; otherwise, the machine remains
off (OFF) in spite of the timer approval.
The remote panel is used to manage
ON/OFF and Cooling/Heating com-
mands from a distance.
CONTROL SETTINGS FOR REMOTE PANEL9.
Component Description
1simplified remote control panel PR3
2On/Off switch
3Yellow ON/OFF indicator light
when the yellow led is on =ON
4
Shift to COOLING/HEATING operation mode
=cooling operation
=heat pump operation
5Operation mode (bicolour indicator light)
Blue indicator light =it is operating in cold mode
Red indicator light =it is operating in heat pump mode
6Red indicator light: when on, it indicates alarm status

17
ALARMS10.
HISTORY OF SAFETIES
The safety management records the last
Pre-alarms or Alarms occurred. This list is
always active. Once the parameter is set,
press the key to visualise the list and,
for scrolling, press the arrow keys ++
and
+
-
. The following visualisations will
appear on the display depending on wheth-
er the electronic card has or not the PGS
accessory.
With PGS
In the first line, the first letter shows the
intervention type (Afor Alarm or Wfor
Pre-alarm). Then, and only with PGS, the
date (dd/mm/yy) and the time, on the
right end, are indicated. If the PGS is not
present, the compressor operation time
shall be shown on the right end.
In the second line, the pair of figures
shows the page number (from 01 to 999)
and occurred alarms and pre-alarms are
listed at the centre of the line.
N.B. = although page enumeration is up to
999, all these pages cannot be saved. The
number of saving operations (minimum
25) may change according to the type of
memory with which the electronic card
has been provided.
A10.1. larm history page format with PGS accessory
A10.2. larm history page format without PGS accessory
A 15 03 04 17:35
03 FLOSWITCH
Date
A =alarm
W =prealarm
No. of alarm
sequences Safety description
Month Year Time
No. of alarm
sequences
A 00167
03 FLOSWITCH
Safety description
Time compressor 1
A =alarm
W =prealarm

18
VISUALISATION OF OCCURRED ALARMS
Alarm Water/air Water/water Description
Flow switch
Intervention of water differential pressure switch and/or flow switch
Cond. Pump/FL Intervention of condenser pump thermal protection/flow switch
MT CP 1
Intervention of compressor magneto-thermal 1
MT CP 2
Intervention of compressor magneto-thermal 2
MT CP 1A
Intervention of compressor magneto-thermal 1A
MT CP 2A
Intervention of compressor magneto-thermal 2A
MT CP 1B
Intervention of compressor magneto-thermal 1B
MT CP 2B
Intervention of compressor magneto-thermal 2B
Low Pres. 1
Intervention of pressure switch/low-pres. transducer circuit 1
Low Pres. 2
Intervention of pressure switch/low-pres. transducer circuit 2
High Pres. 1
Intervention of pressure switch/high-pres. transducer circuit 1
High Pres. 2
Intervention of pressure switch/high-pres. transducer circuit 2
Antifreeze 1
Intervention of antifreeze circuit 1
Antifreeze 2
Intervention of antifreeze circuit 2
MT MV 1 Intervention of fan magneto-thermal circuit 1
MT MV 2 Intervention of fan magneto-thermal circuit 2
Probe 1
Probe alarm circuit 1
Probe 2
Probe alarm circuit 2
Monitor
Intervention of power supply control
Pumpdown 1
Failure when unloading compressor cylinders of circuit 1
Pumpdown 2
Failure when unloading compressor cylinders of circuit 2
Eprom
Abnormal operation of the electronic board
Ram
Abnormal operation of the electronic board
Flow Recovery
Flow switch of heat recovery circuit (only D and T versions)
MT MPOE 1
Intervention of the evaporator pump magneto-thermal 1
MT MPOE 2 Intervention of the evaporator pump magneto-thermal 2
MP MPOE 3 Intervention of the evaporator pump magneto-thermal 3
B.AG Evap1
Evaporator outlet gas anti-freeze alarm 1
B.AG Evap 2
Evaporator outlet gas anti-freeze alarm 2

19
Image Procedure
To reset the unit on board the machine af-
ter an alarm, press the specified key. Once
pressed, the unit will restart automatically
and save the alarms in the history (alarm
history).
Image Procedure
To reset the unit from a remote panel after
an alarm, press the OFF (0) key and the key
ON (1). Both operations must carried out in
5 seconds.
M10.3. anual reset on board the machine
M10.4. anual reset from remote panel
SET
C1
C2
R
LR
R
WARNING
Repeated and consecutive
manual resets may seriously
damage the unit.
ON
OFF

20
Table of contents
Languages: