10
6. ACCESSORIES COMPATIBILTY TABLE
ACCESSORIES
ANL
MODELS
100 150
ANTI-VIBRATION MOUNTS VERSION 100 150
VT
Group of four anti-vibration mounts to be installed under the sheet steel base in the prepared points.
They are used to reduce vibrations produced by the compressor whilst functioning.
A1515
MODUCONTROL
CONTROL PANEL
5.4. CONTROL AND SAFETY COMPO-
NENTS
High pressure pressure switch (HP)
With fixed calibration, placed on high
pressure side of cooling circuit, inhibits
functioning of compressor if abnormal
work pressure occurs.
Low pressure transducer (TBP)
Heat pump (H)
Placed on low pressure side of cooling
circuit, it communicates the work pres-
sure to the control board, generating a
pre-alarm if abnormal pressure occurs.
High pressure transducer (TAP)
Placed on high pressure side of cooling
circuit, it communicates the work pres-
sure to the control board, generating a
pre-alarm if abnormal pressure occurs.
5.5. ELECTRIC COMPONENTS
Electric Control Board
Contains the power section and the
management of controls and safety
devices. It is in compliance with the IEC
60204-1 Standard and the Directives re-
garding electromagnetic compatibility
EMC 89/336/EEC and 92/31/EEC.
Door-lock isolating switch
The electric control board can be ac-
cessed by removing the voltage. Act on
the opening lever of the control board
itself. This lever can be locked using one
or more padlocks during maintenance
interventions to prevent the machine
being powered up accidentally.
Control board
Allows complete control of the appli-
ance.
For a more in-depth description please
refer to the user manual.
−compressors magnet circuit-breaker
protection.
−fans magnet-circuit breakers protec-
tion;
−auxiliary magnet circuit-breaker
protection
−Heat exchanger inlet/outlet water
temperature probes
−Gas temperature probe one on the
for pressing line and coil
−External air temperature probe WITH
DCPX ACCESSORY
5.6. ELECTRONIC MODU CONTROL
ADJUSTMENT
MODU_CONTROL
Temperature control of the outlet water
with proportional-integral algorithm:
maintains average outlet temperature
at value set
−
Self-adapting differential
switch: guarantees minimum func-
tioning times of the compressor in
systems with low water content.
−Intelligent defrosting for pressure
reduction: allows to determine
when the coil is effectively defrosted,
avoiding useless defrosting
−Hot gas injection defrosting: In this
way the machine consumes less
energy, increases heating capacity,
keeps efficiency high and prevents
temperature drops at the terminals
(very important in plants with low
water content Emergency defrost-
ing by cooling cycle reversing: to
overcome more serious conditions
−Set-point compensation with exter-
nal temperature (with external air
probe accessory): reduces energy
consumption
−Condensation check based on the
pressure rather than on temperature
for absolute stability (with DCPX revs.
adjuster accessory)
−Inverse condensation check for the
heat pump functioning mode also
in summer (withDCPX revs. adjuster
accessory).
−Pre-alarms with automatic reset: in
the case of alarm, a certain number
of re-starts are allowed before the
definitive block.
−Alarm on the∆T: to identify wiring
errors (reverse rotation) or blocked
cycle reversing valve.
−Compressor functioning hours count
−Compressor peak count.
−Historical alarms
−Autostart after voltage drop.
−Local or remote control
Display of unit status:
a.Voltage presence
b.Compressor ON/OFF
c. Functioning mode (hot/cold)
d.Alarm active
Probes, transducers and parameters
display
a.Water outlet
b.Water inlet
c. Coil temperature (heat pumps)
d.Pressing line gas temperature
e.External air temperature (heat pumps,
cooling only with DCPX and probe)
f. Flow pressure (heat pumps)
g.Intake pressure (heat pumps)
h.Temperature error (sum of the propor-
tional and integral error)
i. Stand-by times for start-up/switch-off
of the compressor
Alarms management
a.Low pressure
b.High pressure (primary alarm: the
pressure switch directly blocks power
supply to compressor)
c. High discharge temperature
d.Anti-freeze
e.Water differential flow meter/pressure
switch
f. Alarm on the ∆T
−
Alarms with automatic reset with
limited number of re-starts before
blockin
−ON/OFF from external contact
−Change season from external con-
tact
ATTENTION:
►DCPX not supplied
►
For further information please refer to
user manual