16 Aermec 13_01. 5641300_00
NRL 0280-0750 60Hz
EN
Model 0280 0300 0330 0350 0500 0550 0600 0650 0700 0750
Cooling capacity HA Alls Tons - - - - 24,85 28,95 35,15 40,78 45,13 49,56
HE Alls tons 13,05 15,44 17,54 22,15 - - - - - -
Total power input HA Alls kW - - - - 30,10 36,10 42,80 49,40 55,80 60,70
HE Alls kW 15,60 18,10 20,80 26,80 - - - - - -
Total power input
with LOW PUMP
HA 230V|460V kW - - - - 31,94 37,94 45,0 51,6 58,8 63,7
HE 230V|460V kW 17,01 19,51 22,21 28,21 - - - - - -
Total power input
with HIGH PUMP
HA 230V|460V kW - - - - 31,95 39,30 45,80 52,40 58,80 64,70
HE 230V|460V kW 17,95 20,45 23,15 29,15 - - - - - -
Total power input
with LOW - PUMP
HA 575V kW - - - - 31,20 37,20 45,00 51,60 58,80 63,70
HE 575V kW 16,70 19,20 21,90 27,90 - - - - - -
Total power input
with HIGH - PUMP
HA 575V kW - - - - 31,60 38,30 45,80 52,40 58,80 64,70
HE 575V kW 17,10 19,60 22,30 28,30 - - - - - -
Water flow HA Alls gpm - - - - 60 69 84 98 108 119
HE Alls gpm 31 37 42 53 - - - - - -
Total pressure drops HA Alls p.s.i. - - - - 3 4 5 7 8 9
HE Alls p.s.i. 2 3 2 3 - - - - - -
Useful head
with LOW - PUMP
HA 230V|460V p.s.i. - - - - 23 21 22 19 17 16
HE 230V|460V p.s.i. 22 20 20 19 - - - - - -
Useful head
with HIGH - PUMP
HA 230V|460V p.s.i. - - - - 37 35 34 31 28 34
HE 230V|460V p.s.i. 29 29 29 25 - - - - - -
Useful head
with LOW - PUMP
HA 575V p.s.i. - - - - 18 15 22 19 17 16
HE 575V p.s.i. 25 24 23 20 - - - - - -
Useful head
with HIGH - PUMP
HA 575V p.s.i. - - - - 27 25 34 31 28 34
HE 575V p.s.i. 32 30 30 27 - - - - - -
Heating capacity HA Alls BTU/h - - - - 310778 358582 430885 481999 549901 600571
HE Alls BTU/h 165967 196710 220561 267341 - - - - - -
Total power input HA Alls kW - - - - 31,48 37,69 44,70 51,04 58,10 61,35
HE Alls kW 16,08 19,08 21,39 28,45 - - - - - -
Total power input
with LOW PUMP
HA 230V|460V kW - - - - 33,32 39,53 46,90 53,24 61,10 64,35
HE 230V|460V kW 17,49 20,49 22,80 29,86 - - - - - -
Total power input
with HIGH PUMP
HA 230V|460V kW - - - - 33,33 40,89 47,70 54,04 61,10 65,35
HE 230V|460V kW 18,43 21,43 23,74 30,80 - - - - - -
Total power input
with LOW PUMP
HA 575V kW - - - - 32,58 38,79 46,90 53,24 61,10 64,35
HE 575V kW 17,18 20,18 22,49 29,55 - - - - - -
Total power input
with HIGH PUMP
HA 575V kW - - - - 32,98 39,89 47,70 54,04 61,10 65,35
HE 575V kW 17,58 20,58 22,89 29,95 - - - - - -
Water flow HA Alls gpm - - - - 69 80 96 107 122 133
HE Alls gpm 37 44 49 59 - - - - - -
Total pressure drops HA Alls p.s.i. - - - - 4 4 6 7 10 10
HE Alls p.s.i. 2 3 3 3 - - - - - -
Useful head
with LOW - PUMP
HA 230V|460V p.s.i. - - - - 21 19 19 17 14 12
HE 230V|460V p.s.i. 21 19 19 17 - - - - - -
Useful head
with HIGH - PUMP
HA 230V|460V p.s.i. - - - - 35 32 33 31 26 28
HE 230V|460V p.s.i. 30 29 29 27 - - - - - -
Useful head
with LOW - PUMP
HA 575V p.s.i. - - - - 15 11 19 17 14 12
HE 575V p.s.i. 24 21 21 18 - - - - - -
Useful head
with HIGH - PUMP
HA 575V p.s.i. - - - - 25 23 33 31 26 28
HE 575V p.s.i. 30 28 28 25 - - - - - -
ENERGETIC INDEX
EER HA Alls BTU/h/W - - - - 9,92 9,63 9,86 9,91 9,71 9,81
HE Alls BTU/h/W 10,05 10,25 10,13 9,93 - - - - -
COP HA Alls W/W - - - - 2,89 2,79 2,83 2,77 2,77 2,87
HE Alls W/W 3,03 3,02 3,02 2,75 - - - - - -
IPLV -Alls BTU/h/W 13,32 13,42 13,39 13,22 14,75 14,45 15,27 15,16 14,34 14,21
8. TECHNICAL DATA "HA - HE" VERSION
HEATING (AHRI CONDITIONS)
Inlet water temperature 40°C / 104 °F
Outlet water temperature 45°C / 113 °F
External air temperature 7°C b.s / 6°C b.u.
COOLING (AHRI CONDITIONS)
Outlet water temperature 6,7°C / 44,06°F
Flow rate 0,043l/s per kW
External temperature 35°C / 95°F
(1) data refered no pump version
AHRI conditions: leaving water 6,7°C / 44,06°F
flow rate 0,043 l/s per kW (full load)
Load 100% air 35°C / 95°F
Load 75% air 26,7°C / 80°F
Load 50% air 18,3°C / 65°F
Load 25% air 12,8°C / 55°F