
Set: 21.0°C
1
ZONE:
ROOM 1
Set: 20.0°C
Mode: LOCAL
Prg: 0
Room (1)
1
A
B
B
C
D
E
A
F
ItalianoEnglish
rançais
eutsc
Españo
Modify single zone status
In the window for modifying the operating parameters of a zone (always identified by
its indicator
E
and the name assigned to the zone
F
), you can modify the following
settings:
A
Set the heating setpoint: press the (increase) and (decrease) keys
on the same line as the setpoint you want to change. By pressing , you can also
choose whether to make the setpoint modification available via the zone thermostat
(VMF-E2 or VMF-E4), as follows:
• (lock open): the system allows the user to modify the setpoint (+/- 3°C or
+/-6°C) via the zone thermostat
• (lock closed): the system does not allow modifications to the setpoint via
the zone thermostat
B
Set the cooling setpoint: press the (increase) and (decrease) keys
on the same line as the setpoint you want to change. By pressing , you can also
choose whether to make the setpoint modification available via the zone thermostat
(VMF-E2 or VMF-E4), as follows:
• (lock open): the system allows the user to modify the setpoint (+/- 3°C or
+/-6°C) via the zone thermostat
• (lock closed): the system does not allow modifications to the setpoint via
the zone thermostat
C
Operating mode: use the key to choose whether to make the thermostat
work with the settings given directly by the user interface associated with it (this op-
tion is activated with “LOCAL”), or force operation in one of the other modes (“AUTO“,
“V1”, “V2”, “V3” or “AUX”)
C
Type of heating: press the key to choose which type of heating to activate
in the selected zone (this option is only available in the case of a radiant system and
with correctly wired VMF-REB expansions):
• : zone heating with the fancoil only
• : zone heating with the fancoil and radiant floor
• : zone heating with the radiant floor only
WARNING: in cooling mode, the system will only activate the fancoil!
D
The timed program active on the selected fancoil: to modify the timed pro-
gram, press the (increase) and (decrease) keys on the same line as the set-
point you want to change. By pressing , you can also choose whether to unlock
a possible OFF in the timed program, as follows:
• (lock open): if the fancoil is OFF according to the timed program, but is
modified by the user (setpoint or operating mode, directly via the incorporated
thermostat), the fancoil will abandon the timed program control for 45 minutes
(function only available with VMF-E19/E19I thermostats or GLFxN/M grilles)
• (lock closed): the system does not allow the fancoil to abandon the timed
program
By pressing the key on the lower part of the screen, you can copy the settings
of the page in ALL the system zones (a drop-down window will appear, asking for
confirmation of the operation).
To move on to the next page, press . To return to the previous page, press . The
homepage will be restored automatically if 5 minutes elapse with no interventions.
Modifying the name associated with the zone
In the window for modifying the name of a fancoil (always identified by its
indicator A), you can modify the string identifying the zone ( B).
To return to the previous page, press the key. The homepage will be re-
stored automatically if 5 minutes elapse with no interventions. 4