Air Monitor Corporation ELECTRA-flo Manual

Installation, Operation,
and Maintenance Manual
ELECTRA-flo
ThermalAirFlowMeasurementTransmitter
Version 1.1X
Installation, Operation & Maintenance
Air Monitor Corporation provides complete
technical support between the hours of
7 a.m. and 5 p.m. PST, M-F
Contact our Service Department
Toll Free: 1-800-AIRFLOW
or fax us at 1-707-526-2825
Air Monitor Corporation
116-053-00.P65(7/06) ELECTRA-flo-IO&MManual


ELECTRA-flo Version 1.16 Addendum.doc 6/28/2007
ADDENDUM
This addendum to the ELECTRA-flo Installation, Operation & Maintenance Manual is applicable to software version 1.16.
This software version differs from version 1.15 and earlier, in that all menus are accessed via a 4 pushbutton sequence rather
than simultaneously pressing 2 buttons.
Use the following in place of the applicable portion of Section 5.5 – PUSHBUTTON DEFINITION (page 9).
Displays ELECTRA-flo and software version number. While software version is
displayed, press and work order number and serial number will be
displayed. Press and ID (if any) will be displayed. Press and the
display will go back to the Normal operation mode.
Activates the Operator menu.
Activates the Supervisor menu.
Activates Password selection menu.
Additionally, note the above changes affect the following:
Step 1 of Section 5.6 – CONFIGURATION PROGRAMMING
Step 1 of Section 6 – SUPERVISOR MENU
then
DN
ESC
ENT UP then DN then ENT
UP
thenENT ESC then UP then ENT
then
ENT ESC then DN then ENT
then
UP DN then UP then ESC

ELECTRA-flo
Air Monitor Corporation
116-053-00.P65(7/06) ELECTRA-flo-IO&MManual
TABLEOFCONTENTS
TABLEOF CONTENTS
INSTRUMENTWARRANTY ........................................................................................................................i
SECTION 1 – GENERAL INFORMATION
1.1 DESCRIPTION ...................................................................................................................................1
1.2 THEORYOFOPERATION.................................................................................................................1
SECTION 2 – PERFORMANCE SPECIFICATIONS
2.1 ACCURACY.......................................................................................................................................2
2.2 RANGE..............................................................................................................................................2
2.3 PROBE ASSEMBLY..........................................................................................................................2
2.4 TRANSMITTER ..................................................................................................................................2
2.5 POWER.............................................................................................................................................2
SECTION 3 – FEATURES
3.1 OPERATORMENU ...........................................................................................................................3
3.2 DATADISPLAY ..................................................................................................................................3
3.3 LARGEOPERATION RANGE ...........................................................................................................3
3.4 ENCLOSURE ....................................................................................................................................3
3.5 MULTIPLEOPERATING POWERSELECTIONS...............................................................................3
SECTION 4 – INSTALLATION
4.1 RECEIVINGANDINSPECTION .........................................................................................................4
4.2 LOCATION .........................................................................................................................................4
4.3 MOUNTING........................................................................................................................................5
4.4 PROCESSCONNECTIONS ..............................................................................................................5
4.5 POWER/SIGNALCONNECTIONS ....................................................................................................6
4.6 DISPLAYCONTRASTADJUSTMENT ................................................................................................6
SECTION 5 – OPERATION
5.1 INTRODUCTION.................................................................................................................................7
5.2 START-UP..........................................................................................................................................7
5.3 NORMALOPERATION ......................................................................................................................8
5.4 CONFIGURATION ..............................................................................................................................8
5.5 PUSHBUTTONDEFINITION ..............................................................................................................9
5.6 CONFIGURATIONPROGRAMMING........................................................................................... 10-11
5.7 OPERATORPASSWORD SELECTION ..........................................................................................12
5.8 FLOWCONFIGURATION ...........................................................................................................13-14
5.9 DISPLAYCONFIGURATION .......................................................................................................15-17
5.10 OUTPUT2PARAMETERSELECTION ............................................................................................18
5.11 LOWPASS FILTER .........................................................................................................................19
5.12 TRANSMITTEROUTPUTCALIBRATION ....................................................................................19-21
5.13 K-FACTORCONFIGURATION ....................................................................................................22-23

TABLEOF CONTENTS
SECTION 6 – SUPERVISOR MENU ........................................................................................................24
6.1 SUPERVISORPASSWORDSELECTION.......................................................................................25
6.2 SENSOR MANAGEMENT ..........................................................................................................26-28
6.3 DIAGNOSTICDISPLAY SELECTION...............................................................................................29
6.4 DIAGNOSTICALERTDETERMINATION ......................................................................................30-31
6.5 POWERCYCLESENSORNETWORK...........................................................................................32
SECTION7–MAINTENANCE
7.1 CLEANLINESS ................................................................................................................................33
7.2 MECHANICAL .................................................................................................................................33
7.3 ELECTRICAL ...................................................................................................................................33
SECTION8– CUSTOMER SERVICE
8.1 CUSTOMERSERVICE/ TECHNICAL SUPPORT ...........................................................................34
8.2 REPAIRS/RETURNS .....................................................................................................................34
8.3 WARRANTYREPAIRS /RETURNS ................................................................................................34
8.4 NON-WARRANTYREPAIRS / RETURNS .......................................................................................34
8.5 FIELDSERVICE ..............................................................................................................................34
TABLEOFCONTENTS
ELECTRA-flo
Air Monitor Corporation
116-053-00.P65(7/06) ELECTRA-flo-IO&MManual

ELECTRA-flo
Air Monitor Corporation
116-053-00.P65(7/06) ELECTRA-flo-IO&MManual
i
INSTRUMENT WARRANTY
NOTICE OF PROPRIETARYRIGHTS
Thisdocument contains confidentialtechnical data, includingtrade
secretsandproprietaryinformationwhicharethesolepropertyofAir
MonitorCorporation. Theuseofsaiddata is solely limited to use as
specified herein. Any other use is strictly prohibited without the
priorwritten consent ofAir Monitor Corporation.
INSTRUMENTWARRANTY
AirMonitorCorporation (hereinafterreferredtoas“Seller”)
warrants that at the time of shipment, products sold
pursuant to this contract will be free from defects in
materials and workmanship, and will conform to the
specifications furnished or approved in writing by Seller.
Nowarranty is giventhat delivered products will conform
to catalog sheets, data sheets, and the like, which are
subject to change without notice.
Seller will repair or replace, at its option, any products
listedunderthiswarrantywhichisreturnedfreightprepaid
to Seller within the earlier of three (3) years after start-up
or thirty-nine (39) months after shipment that, upon test
andexamination,provesdefectivewithin the terms of this
warranty. The warranty period for any item repaired or
replaced shall be for the time remaining on the warranty
periodof the original components. Purchasershall notify
Seller in writing of such defect within sixty (60) days of
discoveryof the defect.
This warranty does not extend to any product sold by
Seller which has been the subject of misuse, neglect,
accident, damage or malfunction caused by
interconnectionwithequipment manufactured by others,
improper installation or storage, or used in violation of
instructions furnished by Seller, nor does it extend to any
product which has been repaired or altered by persons
notexpresslyapproved by Seller. Nor doesSellerwarrant
equipmentagainstnormaldeteriorationduetoenvironment;
noritemssuch as lamps, glass,andsimilar items subject
towearorburnoutthroughusage. Adjustmentsforitems
or equipment not manufactured by Seller shall be made
totheextentofanywarrantyofthemanufacturerorsupplier
thereof.
Seller shall not be liable for any special or consequential
damagesor forlossofdamage, directlyorindirectlyarising
from the use of the products. Seller's warranty shall be
limited to replacement of defective equipment and shall
notinclude field removal andinstallation expenses.
Thewarrantysetforthaboveisinlieuofallotherwarranties
eitherexpressor implied and constitutes thefullextentof
Air Monitor Corporation’s liability to the customer, or any
otherparty for breachofwarranty.
THEREARENOEXPRESSWARRANTIESEXCEPTAS
SET FORTH HEREIN AND THERE ARE NO IMPLIED
WARRANTIES OF MERCHANTABILITY OF FITNESS
FOR ANY PARTICULAR PURPOSE, WHICH ARE
PARTICULARLYDISCLAIMED.


ELECTRA-flo
Air Monitor Corporation
116-053-00.P65(7/06) ELECTRA-flo-IO&MManual
1
SECTION1 – GENERAL INFORMATION
1 – GENERAL INFORMATION
1.1 – DESCRIPTION
The ELECTRA-flo ThermalAir Flow Transmitter is used in conjunction with ELECTRA-flo Probe(s). One Transmitter
canreceive up to32 individual flowsensors measuring a single ducted airflow orfan.
TheTransmitter'smicroprocessoraveragesflowandtemperaturesignalsfromallsensorsandoutputsananalogsignal
and local display of these averages. The Transmitter serves as the interface for all configuration and diagnostic
functions.
1.2 – THEORY OF OPERATION
The ELECTRA-flo utilizes thermal dispersion
technology to measure airflow. As air moves across
the surface of an elevated temperature sensor, heat is
transferred from the sensor to the airflow in a
mathematically defined relationship between heat
transfer rate and airflow velocity.
Each ELECTRA-flo sensing node utilizes a pair of
precision matched thermistors. One functions as a
reference sensor measuring the ambient air
temperatureat the sensing nodelocation, and the other
thermistoris heated toa preset temperaturedifferential
(∆T)above the ambientairtemperature.Airflowvelocity
is determined using the measured ambient air
temperature, the known heat transfer characteristics
of the heated thermistor, and the power consumed to
maintain the ∆T between the two thermistors.
Using a combination of Computational Fluid
Dynamics (CFD) modeling and extensive full-scale
wind tunnel verification, the aerodynamically
optimized cross section of the sensing node aperture
prevents error inducing turbulence typical of sharp
edged sensing tubes. The aperture’s injection molded shape has been
engineered to minimize the angular flow effects
naturally present in any duct. The flared aperture
captures a representative sample of the ducted airflow,
while the contoured leading edges prevent the creation
of vortices. The center cross section of the aperture
functions in the same manner as a venturi. It stabilizes
and flattens the velocity profile at the point of
measurement ensuring the airflow maintains full
contact with the sensing thermistors. The flow
conditioning characteristic of the aperture
compensates for turbulent airflow with pitch and/or yaw
angles up to ±30 degrees and produces an accuracy
of ±2% of reading for each ELECTRA-flo sensor.

ELECTRA-flo
Air Monitor Corporation
116-053-00.P65(7/06) ELECTRA-flo-IO&MManual
2
SECTION2 – PERFORMANCE SPECIFICATIONS
2 – PERFORMANCE SPECIFICATIONS
2.4 – TRANSMITTER
Display.
3 line, backlit graphical display. Flow on Line 1 is
double height and width for improved visibility. Lines 2
and 3 are standard size and are user selectable.
Output.
Dualanalogoutputs(0-5VDC,0-10VDC,4-20mA)
userselectableand configurable.
Configuration.
Viacovermounted membrane keypad
Filter.
Analog outputs filtered via user selectable digital low
pass filter.
Temperature Limits.
–20ºFto 180ºF Storage
–20ºFto 140º Operating
Humidity Limits.
0to 95% RH,non-condensing
2.5 – POWER
Power.
16to 90VA dependenton number ofsensor nodes (1
to32 maximum)
Circuit Protection.
Power input is isolated, fused, and reverse polarity
protected.
2.1 – ACCURACY
SensorAccuracy.
Velocity: ±2%ofReading
Temperature: ±0.1ºF
Overall System Accuracy.
Flow: ±2-3% ofActual Flow
Temperature: ±0.1ºFofAirTemperature
2.2 – RANGE
Velocity Calibration Range. 0 to 5,000 FPM
2.3 – PROBE ASSEMBLY
Mounting.
4" x 4" aluminum plate with four 0.25" holes for
fastenersandneoprenegasket.
Length.
8" up to 120"
Sensors Per Probe.
Maximumof16
Connection.
ProbetoProbe via RJ-45 cableforsignal and power.
ProbetoTransmitterviashieldedcable with RJ-45
connection. 10' length standard with optional 50' and
100'lengths.
Temperature Limits.
–20ºFto 180ºF Storage
–20ºFto 140º Operating
Humidity Limits.
0to 95% RH,non-condensing.

ELECTRA-flo
Air Monitor Corporation
116-053-00.P65(7/06) ELECTRA-flo-IO&MManual
3
SECTION 3 – FEATURES
3 – FEATURES
3.1 – OPERATOR MENU
Themicroprocessor program contains aOperator menu systemforselecting parameters. Four
pushbuttons , , , and allow the operator access to the menu for setting configuration modes
andvalues. Refer to the ConfigurationProgramming (Section 5.6) instructionsfor operation details.
Also contained in the Operator menu is an output calibration feature. The calibration method is completely digital
and contains no analog potentiometer adjustments which are susceptible to drift. Non-volatile memory is used for
storingall setup parametersand calibration values, and willremain unchanged afterset, even whenpower to theunit
isoff.
3.2 – DATA DISPLAY
The ELECTRA-flo Thermal Air Flow Transmitter utilizes a high visibility backlit graphical LCD. 3/4" x 2-1/2" display
with three lines of process data, selectable for U.S. or S.I. units. Also used for configuration interface.
3.3 – LARGE OPERATION RANGE
TheELECTRA-flo ThermalAir Flow System can maintain accurate and linear output of flows from 0 to 5,000 FPM.
3.4 – ENCLOSURE
TheELECTRA-floThermalAirFlow Transmitter is housed in an aluminumNEMA 1 enclosure with hinged front cover
for access to power and signal terminals for field connection.
3.5 – MULTIPLE OPERATING POWER SELECTIONS
TheELECTRA-floThermalAirFlowTransmittercanbepoweredbyeither 24VAC or 24VDC.
UP DN ENT ESC

ELECTRA-flo
Air Monitor Corporation
116-053-00.P65(7/06) ELECTRA-flo-IO&MManual
4
4 – INSTALLATION
SECTION4 – INSTALLATION
4.1 – RECEIVING AND INSPECTION
•Carefullyremove the ELECTRA-floProbe(s) or Station,andTransmitter from the shippingcontainerand inspect for
any damage. If any damage has occurred in transit, contact freight carrier.
•Reviewthe Factory Set-Up InformationSheetprovided separately and verifythe W.O. # andSerial# match those on
theELECTRA-flo. Verify that the configuration recorded on the Factory Set-Up Information Sheet is correct for your
application. Ifnot,contactAir Monitor'sCustomer Service Department at1-800-AIRFLOW for furtherguidance.
Note:TheELECTRA-flo has been configured to customer provided parameters (see"Factory Setup
InformationSheet" provided separately), and requiresno field calibration/verification prior toinstallation.
4.2 – LOCATION
•Thestandardversion of the ELECTRA-floTransmitterisaNEMA1enclosuresuitable for mostcleanindoorlocations.
Ifadditional protection isrequired, mount theTransmitter in an enclosure with adequate NEMArating.
•Theambient temperature ofthe selected mounting locationmust be between-20ºF to 140ºF. Consideration should
be given to units exposed to direct sunlight.
•Theselected mounting locationshould be rigidand free ofvibration.

ELECTRA-flo
Air Monitor Corporation
116-053-00.P65(7/06) ELECTRA-flo-IO&MManual
5
4.3 – MOUNTING
Probes. See separate Installation Instructions for the installation/mounting of ELECTRA-flo Probes and Stations.
Transmitter. This section may be skipped if the unit is an ELECTRA-flo/CM or ELECTRA-flo/M, as the Transmitter
may have been ordered Factory mounted to the Station.
–ToolsRequired: Electricdrill;#25(0.1495")bit;screwdriverornutdriver;andfour#8-32self-tapping machine screws.
–The ELECTRA-flo can be mounted in any position provided it is secured using all four mounting holes.
–Reasonableconsideration should begiven to clearances forelectrical connections.
–Once a suitable location is found, use the unit as a template to mark the centers of the four mounting holes.
–Drill four pilot holes at the marked locations. With the unit in position, install the four #8-32 screws.
Figure4.1
4.4 – PROCESS CONNECTIONS
See separate Installation Instructions provided with the ELECTRA-flo Probes for information on connecting cables
from the Probes or Station to the Transmitter.
ELECTRA-flo/CM and ELECTRA-flo/M has cables already installed.
SECTION4 – INSTALLATION
OFF ON
Thermal Mass Flow Transmitter
ORPORATION
IR ONITORM
C
A
ELECTRA-flo

ELECTRA-flo
Air Monitor Corporation
116-053-00.P65(7/06) ELECTRA-flo-IO&MManual
6
SECTION4 – INSTALLATION
4.5 – POWER/SIGNAL CONNECTIONS
Power wiring is done at terminal strip P8, and signal wiring is done at terminal strip P7. Both P7 and P8 are located in
thelowerportionof the unit and areaccessiblebyopeningthefrontcover. SeeFigure4.2 for location ofP7andP8. Two
conduitopeningsare provided for the powerandsignalwiring.
Figure4.2
WIRING. Itis recommended that powerwiring be 14 awgto 18 awg, andsignal wiring should be14 awg to 22awg. 14
awg is the maximum wire gauge that the terminals can accommodate. No more than two wires should be connected
toanyoneterminal. Toaidinthewiringofbothpowerandsignal wires, P7 and P8 are removable by pulling the terminal
strip straight up and off the circuit board. Once wiring has been completed, replace the terminal strip by aligning with
receptacleandpressing firmly.
POWER 24 VAC/DC (Terminals L and N, P8). Power required by the ELECTRA-flo must be connected to the two
terminals labeled L(+) and N(–). Earth ground should be connected to the terminal labeled G. Power Supply must be
20-28VACor20-40VDC.
OUTPUT #1 (Terminals 1 and 2, P7). This output represents the measured airflow and is sourced (powered) by the
ELECTRA-flo. Output can be configured for 0-5VDC, 0-10VDC, or 4-20mADC. Review Factory Set-Up Information
Sheetforyour configuration.
If output is to be 0-5VDC: Position both jumpers on J3. See Figure 4.2.
If output is to be 0-10VDC: Position both jumpers on J2. See Figure 4.2.
If output is to be 4-20mADC: Position both jumpers on J4. See Figure 4.2.
OUTPUT #2 (Terminals 3 and 4, P7). Thisoutputcanrepresent the measured temperature andissourced (powered)
bytheELECTRA-flo. Outputcanbeconfigured for 0-5VDC, 0-10VDC, or 4-20mADC. Review Factory Set-Up Informa-
tionSheetfor your configuration.
If output is to be 0-5VDC: Position both jumpers on J6. See Figure 4.2.
If output is to be 0-10VDC: Position both jumpers on J5. See Figure 4.2.
If output is to be 4-20mADC: Position both jumpers on J7. See Figure 4.2.
4.6 – DISPLAY CONTRAST ADJUSTMENT
Tocompensatefor different ambient lightingconditionsand viewing angles, theELECTRA-flodisplay's contrast can be
adjustedforoptimum visibility. Contrast is adjusted usingpotentiometerR13. TurnR13clockwisetoincrease contrast
(darkencharacters relative to background)or counterclockwise to decreasecontrast.

ELECTRA-flo
Air Monitor Corporation
116-053-00.P65(7/06) ELECTRA-flo-IO&MManual
5.1 – INTRODUCTION
The ELECTRA-flo has been configured at the Factory to customer specified parameters which are recorded on the
ELECTRA-floFactoryInformationSet-UpSheet,providedseparately. ReviewthisinformationandverifythattheELECTRA-
floset-upis correct for yourapplication. Ifanyproblems or discrepancies aredetected,contactAir Monitor's Customer
ServiceDepartmentat1-800-AIRFLOW prior toproceeding.
5.2 – START-UP
1. AfterInstallationhasbeenverified in accordance with Section 4,turnpowerswitchlocatedatthe lower front side to
the ON position (see Figure 4.1).
2. Display will briefly indicate:
ELECTRA-flo
Thanks for Choosing
AIR MONITOR
Followed by:
1 8 16 24 32
Sensors Found: 8
Xmitter Total: 1
After 5 seconds, display will indicate:
1 8 16 24 32
Enabled Sensors: 8
Total Sensors: 8
after 5 seconds the display will return to Normal display mode, and the dot in the upper right of the display
indicatingCPUActivatedwillblinkrapidly(4 times per second). This is Normal operationmodeandnofurtheruser
interface is required. If, however, user would like to verify configuration or change user selectable parameters,
continuetoSection5.4entitled"CONFIGURATION".
0 ACFM l*
TEMP 68.0”F
VELO 0 AFPM
Normal display mode
7
SECTION 5 – OPERATION
5 – OPERATION
Thenumberof active sensors willbe
represented by the bar graph and listed
below. There are 8 active sensors in
this example.
Thenumberof enabled sensors willbe
represented by the bar graph and listed
below. There are 8 active sensors in
this example.
*Dot flashes 4 times a second, indicating
that CPU is active. If ALERT flashes
instead of Dot, see section for Diagnostics.

ELECTRA-flo
Air Monitor Corporation
116-053-00.P65(7/06) ELECTRA-flo-IO&MManual
8
5.3 – NORMAL OPERATION
Under Normal operation, the ELECTRA-flo Transmitter will continuously display flow as volume or velocity, and
temperature.
5.4 – CONFIGURATION
TheELECTRA-flo onboardmicroprocessorcontrolsConfiguration: Operating parameterselection;input/outputactivation
and scaling, and display scaling.
Thecustomer canverifyconfigurationandchange certainparameters(withindefinedranges) byenteringtheELECTRA-
floConfigurationmode. This is accomplishedusingthefourmembranepushbuttonslocated on theELECTRA-flocover.
See Figure 4.1 for location of pushbuttons.
SECTION 5 – OPERATION

ELECTRA-flo
Air Monitor Corporation
116-053-00.P65(7/06) ELECTRA-flo-IO&MManual
9
SECTION 5 – OPERATION
5.5 – PUSHBUTTON DEFINITION
The four pushbuttons used to interface with the ELECTRA-flo are as follows:
In addition to use during Configuration programming, pushbuttons can be used for certain functions when in the Normal
operation mode. The following list describes the pushbutton function when in the Normal operation mode and in the User
Setup (programming).
WheninNormal Operation Mode.
Displays ELECTRA-flo and software version number. While software version is displayed,
press and work order number and serial number will be displayed. Press and
ID (if any) will be displayed. Press and the display will go back to the Normal operation
mode.
Activatesthe Operator menu.
Activatesthe Supervisor menu.
Activates Password selection menu.
Whenin User Setup.
Use to scroll to the desired Main Menu item.
Use to scroll to the value or mode within a parameter.
Enters user into specific selection sub-menu from Main Menu Selection.
Displayscurrentsetting ofselected Parameter. Enterstheselected valueor settingintomemory.
Useasan escape key to exit back toMain Menu selection to avoid scrolling to"Returnto MAIN
MENU".
The following pushbutton combinations can be used to more quickly set user selected values (i.e. Process Min and Max
Values,etc.).
Increases the second column digit.
Decreases the second column digit.
Increases the third column digit. XXXXX
Decreases the third column digit.
Increases the fourth column digit.
Decreases the fourth column digit.
*Must be pressed and held before other button(s) are pressed.
Note: Pushbuttons are momentary type and should be quickly pressed and released to initiate desired change, unless
otherwise instructed to press and hold.
2ndColumn
3rdColumn
4thColumn
*
*
*
*
*
*
+
+
DN
then then
UP DN ENT ESC
UP
ESC
ESC ENT
UP DN
ESC DN
UP DN ESC
orUP DN
ENT
ESC
+UP ESC
+DN ESC
+UP DN
+DN UP
and
UP ESC DN
+
and
DN ESC UP
+
+

ELECTRA-flo
Air Monitor Corporation
116-053-00.P65(7/06) ELECTRA-flo-IO&MManual
10
5.6 – CONFIGURATION PROGRAMMING
1. With power ON and initialization complete (see Section 5.2), press + simultaneously. The display
will indicate:
ENTER PASSWORD FOR
OPERATOR MENU
XXXX
Note: If Operator Menu password has been bypassed, display will indicate as shown in Step 3 below.
2. Using and , scroll to the numeric password for the Operator Menu. From the Factory, password is set
for1,111.
3. Once password is displayed, press and display will indicate:
OPERATOR MENU
4. Press , and display will indicate:
OPERATOR PASSWORD
SELECTION
By using and , the user can scroll through the following selections:
5. Once the desired selection is displayed, press to enter its sub-menu.
SECTION 5 – OPERATION
ESC ENT
ENT
ENT
®
UP DN
ENT
MAINMENUSELECTION
Operator Password Selection
Flow Configuration
Display Configuration
Output 2 Parameter Selection
Low Pass Filter Selection
Transmitter Output Calibration
K-factor Configuration
Operator Menu Exit
DESCRIPTION
Allows for the selection of password for the Operator Menu, and the bypassing of the
password.
Allows for the configuration of process variable such as: Duct size and shape, process
type, process maximum/units, and percent lockdown.
Allows the selection of parameter to be displayed on Lines 2 and 3, and display filter.
Allows the selection Output 2 parameter.
Selects amount of filtering applied to transducer output and to the display.
Allows for the zeroing and spanning of transmitter analog Outputs
Turns K-factor ON or OFF and allows for the calculation or selection of gain and bias values.
Returns display to Normal operation.
UP DN

ELECTRA-flo
Air Monitor Corporation
116-053-00.P65(7/06) ELECTRA-flo-IO&MManual
SECTION 5 – OPERATION
5.6 – CONFIGURATION PROGRAMMING (con't)
Once the desired Selection is displayed, its sub-menu can be entered by pressing .
To better understand the process of Configuration Programming, arrows with pushbutton designations have been included
on the following flow chart of Display Configuration. This will aid in the navigation of the Configuration Programming
Process.
This example of navigation is similar for all Operator Menu selections.
The remainder of this Section details steps to verify or change Configuration Programming of all Operator Menu
Selections.
At any time while in the Operator Menu, User can return to Normal operation mode by pressing or scrolling to:
OPERATOR MENU and pressing .
EXIT
11
ENT
ENT
ESC
- Flow Configuration
→
Display Configuration
- Output 2 Parameter Selection
Default selection shown. Available selections:
- Display Filter Selection
- Line 2 Parameter Selection
- Line 2 Custom Text Selection
1
- Line 3 Parameter Selection
- Line 3 Custom Text Selection
1
- Return to MAIN MENU
Display Configuration
Return to
MAIN MENU
Display Filter
0 (None)
0 (None) to
5 (Maximum)
1Not available if Process Type is D.P.
(see Transmitter Scaling & Config.)
1 Available only if Parameter is CUSTOM TEXT.
Line 2 Parameter
VELOCITY
TEMPERATURE,
CUSTOM TEXT,
or VELOCITY
Line 2 Custom Text
_
see ASCII
Character Chart for
selection
Line 3 Parameter
TEMPERATURE
TEMPERATURE,
CUSTOM TEXT,
or VELOCITY
Line 3 Custom Text
_
see ASCII
Character Chart for
selection
Operator Menu

ELECTRA-flo
Air Monitor Corporation
116-053-00.P65(7/06) ELECTRA-flo-IO&MManual
SECTION 5 – OPERATION
12
5.7 – OPERATOR PASSWORD SELECTION
Allows the selection of an Operator Menu password, and the option of bypassing the password.
1. While in Operator Menu, use or to scroll to: Operator Password
Selection
2. Press to enter Operator password menu. Display will indicate: Password
Selection
3. Press and display will indicate current password.
Note: From the Factory, password is set for 1,111.
4. Use or to change password. Once desired password is displayed, press . New password will be
stored in memory and display will return to previous menu (see Step 2).
Caution: If password is changed, write it down, and retain in case it is forgotten.
Note: If user desires not to change password and return to password menu, press . Unit will remain
programmed as it was originally.
5. Use to select Bypass Password if desired.
6. Follow Steps 3 and 4 to make changes.
7. To return to Main Menu, select Return to MAIN MENU in the Operator Password Selection menu, and press
.
UP
®
ENT
DN
UP DN
ENT
ESC
- OPERATOR MENU EXIT
→
Operator Password Select
- Flow Configuration
Operator Password Menu
- Password Selection
- Bypass Password? Selection
- Return to MAIN MENU
Password
1,111
NO or YES
Available selections:
Return to
MAIN MENU
Bypass Password?
NO
Default selection shown.
0 to 9,999
Þ
ENT
UP
ENT

ELECTRA-flo
Air Monitor Corporation
116-053-00.P65(7/06) ELECTRA-flo-IO&MManual
SECTION 5 – OPERATION
5.8 – FLOW CONFIGURATION
This Operator Menu selection is where all application specific data is entered to configure the ELECTRA-flo for a unique
application. Typical data includes: Units of Measure, Duct Type and Size, Flow Type, Units and Conditions, and Output
Lockdown.
Note: The Factory has entered data in this section based on customer supplied information. Data can be reviewed
and verified by scrolling through the individual menu items or reviewing the Factory Set-Up Information sheet
provided separately. Review this information BEFORE making any changes, as they can have a significant
effect on the operation of the ELECTRA-flo.
13
- OPERATOR MENU Exit.
→
Flow Configuration
- Display Configuration
Default selection shown. Available selections:
- Dimensional Units Selection
- Temperature Units Selection
- Duct Shape Selection
- Duct Height Selection
1
- Duct Width Selection
1
- Duct Diameter Selection
2
- Duct Area Selection
3
- Actual or Standard Selection
- Site Elevation Selection
- Volume Units Selection
- Design Full Range Selection
- Input Lockdown Selection
- Return to MAIN MENU
Flow Configuration
Return to
MAIN MENU
Dimensional Units
U.S.
U.S. or METRIC
1
Available only if RECTANGULAR or OVALROUND is
selected as Shape.
2
Available only if ROUND is selected as Shape.
Dimensional Units
°F
°F or °C
Duct Shape
RECTANGULAR
RECTANGULAR,
ROUND, OVAL or
OTHER
Duct Height
XX.XX in.
0.00 to 300.00 in.
0 to 10,000 mm.
Duct Width
XX.XX in.
0.00 to 300.00 in.
0 to 10,000 mm.
Duct Area
XX.XX Sq. Ft.
0.00 to 100.00 Sq.Ft.
0.000 to 10.000 Sq.M.
Actual or Standard
ACTUAL
Actual or
Standard
Site Elevation
0 Feet
0 to 15,000 Feet
0 to 4,572 Meters
Volume Units
ACFM
See UNITS list for
available
selections
3
Available only if OTHER is selected as Shape.
Design Full Range
XX,XXX ACFM
Maximum Full Range
XX,XXX ACFM
4
Input Lockdown
4.0% Max Velocity
Operator Menu
Design value
adjustable up to
maximum value.
0.0% to 100.0%
Duct Diameter
XX.XX in.
0.00 to 300.00 in.
0 to 10,000 mm.
4
Maximum Full Range is
based on the duct area.
Table of contents
Other Air Monitor Corporation Transmitter manuals
Popular Transmitter manuals by other brands

PRECISION DIGITAL
PRECISION DIGITAL PDW30 instruction manual

BECKER-Antriebe
BECKER-Antriebe Centronic PLUS EC548 PLUS Assembly and operating instructions

RKI
RKI 65-2320RK Operator's manual

Peiying
Peiying URZ0481 owner's manual

Crestron
Crestron DM-TX-4K-100-C-1G Do guide

Bosch
Bosch RF3401E installation instructions

SMC Networks
SMC Networks IT Series instruction manual

Moore Industries
Moore Industries Temperature Concentrator System user manual

SGM LEKTRA
SGM LEKTRA FLOWMETER Technical documentation

Zonda Hobby
Zonda Hobby ECH6 user manual

Harman
Harman AMX DX-TX-DWP-4K60-BL Hardware reference manual

Extron electronics
Extron electronics DTP T FB 232 Setup guide