Air Products & Controls HS-100-N Technical specifications

AIR PRODUCTS AND CONTROLS INC.
INSTALLATION AND MAINTENANCE INSTRUCTIONS
FOR HS-100 SERIES PLENUM DUCT SMOKE DETECTORS
NO-FLOW • LOW-FLOW • SPECIAL APPLICATION
You in Control
AND
AIR PRODUCTS
CONTROLS
HS-100-N 4-Wire,IonizationType
HS-100-P 4-Wire,PhotoelectricType
PRODUCT OVERVIEW
PRODUCT APPLICATION
HS-100 Series plenum / duct smoke detectors provide early
detection of smoke and products of combustion present in air
moving at no or low ow through an HVAC duct supply, return,
or both in commercial, industrial, and residential applications.
These devices are designed to prevent the recirculation of smoke
in areas by the air handling system’s fans and blowers. Complete
systems may be shut down in the event of smoke detection.
The HS-100 is designed specically for applications where our
standard external mount duct detectors cannot be utilized.
Examples include air shafts, plenum spaces or applications requiring
extremely low or no air velocity ≤ 100 ft/min. A compatible Listed
MS- or MSR- Series remote indicator must be installed in a visible
position with the HS-100.
NOTE: For the correct installation of a duct smoke unit, please
refer to the NFPA 72 (National Fire Alarm Code), NFPA 90A (Standard
for Installation of Air Conditioning and Ventilation Systems),NFPA 92A
(Recommended Practice for Smoke Control Systems.), NFPA 5000
(Building Construction and Safety Code), IMC (International Mechanical
Code), and IFC (International Fire Code).
This detector is not intended for open area protection nor should
it be used for early warning detection or replace a regular re
detection system.
PRODUCT DESCRIPTION
The HS-100 Series smoke detector is tted with a mounting
base that will accept an ionization smoke detector head
model 55000-225 or photoelectric smoke detector head
model 55000-328. The duct unit supports one set of form “C”
alarm contacts, one form “A” alarm contact and one form “B”
trouble contact. The trouble contact supervises the presence of
the input power and the removal of the smoke detector head.
The trouble contacts will not operate in the event of a smoke alarm.
The HS-100 Series duct detector will operate from various input
voltage sources; namely 24VAC, 24VDC, 115VAC and 230VAC.
SAMPLING
The operating principle of this duct detector is based on air owing
through the duct and passing over the detector head. When the
concentration of smoke particles suspended in the air stream reach
the alarm threshold of the detector head, the unit will go into alarm.
The duct smoke detector units are designed to operate in spaces
with an air velocity between 0 to 3,000 feet per minute. To verify
correct installation, the air velocity should be measured using a
velocity meter. An acceptable reading is between 0 and 2,000 ft/min
for the HS-100-N; between 0 and 3,000 ft/min for the HS-100-P.
To minimize the impact of air turbulence and stratication on
performance, a duct smoke detector should be located as far
as possible downstream from any obstruction (i.e. deector
plates, elbows, etc.). In plenum space applications, turbulent areas
would be preferred over areas considered “dead spots”, or areas
that do not have active velocity when typical system airow is
present. In all situations, conrmation of velocity is required.
REMOTE ACCESSORIES
Audible and visual alarm indicators, remote status indicators,
and remote reset/test switches can be accommodated by the
HS-100 Series duct units by connecting to DC voltage output
terminals as described on Page 3. These terminals are not
supervised and the voltage/current will only be present when
the detector unit is in alarm. The remote pilot (green) LED
will be permanently illuminated when connected to the output
terminals as long as input power and detector head are present.
HS-100 AT-A-GLANCE
MODEL NUMBER:
HS-100-N 4-Wire Ionization Duct Smoke Detector
HS-100-P 4-Wire Photoelectric Duct Smoke Detector
DETECTOR HEAD MODEL NUMBER:
Ionization Detector Head: 55000-225
Photoelectric Detector Head: 55000-328
POWER REQUIREMENTS: 60 Hz
STANDBY CURRENT ALARM CURRENT
24VAC 54.4mA 24VAC 139mA
24VDC 15mA 24VDC 48mA
115VAC 31mA 115VAC 34mA
230VAC 18mA 230VAC 20mA
UNIT RATINGS:
Alarm contacts: 1 Set form “C” rated at 10A@115VAC resistive
1 form “A” rated at 2A
Trouble contact: 1 form “B” rated at 10A @ 115VAC resistive
Air velocity: 0 to 3,000 ft/min.
Ambient temperature
: HS-100-N: 32°F to 158°F (0°C to 70°C)
HS-100-P: 32°F to 140°F (0°C to 60°C)
Humidity: 0% to 85% RH Non-Condensing/Non-Freezing
Material: White plastic base/housing and detector
(Makrolon 94V-0)
Dimensions:
6.0" Dia X 4.0" H Overall / 2.6" H from back box front
Max. net wt.: 1.0 lb.
Radioactive element:
HS-100-N (Ionization) - Americium 241, 0.9 micro curie.
Mounting: Standard 4" square back box (by others)
Do not expose to corrosive atmospheres.
1

LOCATION PREREQUISITES
This guideline contains general information
on duct smoke detector installation, but
does not preclude the NFPA and/or ICC
documents listed. Air Products and Controls
assumes no responsibility for improperly
installed plenum/duct smoke detectors. To
determine the correct installation position
for an HS-100 Series duct smoke detector,
the following factors must be considered.
1) The airow present at the HS-100 unit
must be a representative sample of the air
moving through the HVAC system (NOT in
a “dead spot”). The airow must be between
0 ft/min. to 3,000 ft/min. To determine
duct velocities for in-duct applications
(shown top right), examine the engineering
specications that dene the expected
velocities or use an Alnor model 6000AP
velocity meter (or equivalent).
To determine fpm velocities in plenum
spaces such as the return in a rooftop
package unit (shown bottom right), divide
the cfm velocity by the plenum space
in square feet at the desired mounting
location of the HS-100 unit (multiply the
linear foot measurement of height by the
linear foot measurement of width). For
example:
30 ton Package Unit puts out 12,000cfm
24in high x 30in wide = 2ft x 2.5ft = 5ft2
12,000cfm ÷ 5 ft2 plenum = 2,400 fpm
2) To minimize the impact of air turbulence and stratication
on performance, a duct smoke detector should be located
as far as possible downstream from any obstruction (i.e.
deector plates, elbows, etc.). In all situations, conrmation of
velocity within specications is required.
3) Identify a code compliant location (supply or return side,
or both) for the installation of the duct unit that will permit
easy access for inspection and serviceability.
4) When installing on the return side, install duct units prior
to the air being exhausted from the building or diluted with
outside “fresh” air.
5) When installing duct smoke units downstream of lters,
res occurring in the lters will be detected, but if the lters
become blocked, insufcient air ow through the duct unit
will prevent the correct operation of the duct detector. Duct
units installed in the supply air side may monitor upstream
equipment and/or lters.
6) Where possible, install duct detectors upstream of air
humidiers and downstream of dehumidiers.
7) To prevent false alarms, the duct detector should not be
mounted in areas of extreme high or low temperatures, in
areas where high humidity exists, or in areas where the duct
may contain gases or excessive dust.
MOUNTING
Remove the detector from its twist-in base. Remove the two
mounting base plate-to-shroud screws. After securing the
mounting base plate to the 4" square back box, wire the mounting
base plate as appropriate. Re-assemble the shroud/detector base
to the mounting base plate. Re-install the detector head. Proceed
to testing.
When mounted, it is critical that the smoke-sensor is situated
such that the airstream ows through the head and not directly at
the head (see below).
2 INST AP-332 C100909
MECHANICAL INSTALLATION
Testing/Maintenance
Access Plate
HS-100
4" Square
back box,
conduit and
hardware
by others
}
Air Flow Direction
return air in
supply
lter
HS-100 evaporator
coil blower heat exchanger
compressor
condenser coil
airow
airow
✘ ✔

3 INST AP-332 C100909
ELECTRICAL INSTALLATION
TERMINAL AND POWER CONNECTIONS
Prior to connecting input power to the duct unit, determine the correct input voltage/current availability and ensure it is connected
to the correct terminals.
WIRING
In the event of a re alarm, certain equipment may be required to be shut down. For example, shut down may be achieved by
interrupting the supply source to that particular piece of equipment when wired as indicated on Page 4.
CAUTION: Do not use looped wire under terminals. Break wire run to provide for proper supervision of connections.
8 9 10
ALM - N.O.
ALM - COM
ALM - N.C.
10A @ 115 VAC
ALARM FACP
*
* Trouble contacts shown in “normal” unit energized state
16 17 18 18 19 19
TRB - COM
TRB - N.C.
ALM - COM
ALM - COM
ALM - N.O.
ALM - N.O.
trouble alarm
10 A @ 115 VAC 2.0A @ 30VDC
Ground to Back Box
1 Neutral
2 115V
115VAC
50/60 HZ
0.1A MAX.
GND
N
H
Ground to Back Box
1 Neutral
2
3 230V
230VAC
50/60 HZ
0.1A MAX.
GND
H2
H1
AC
AC
24VAC
50/60 HZ
0.2A MAX.
24V 5
0/N 4
24VDC
0.1A MAX.
(+)
(–)
24V 5
0/N 4
HIGH VOLTAGE LOW VOLTAGE
11 12 13 14 15
TB+
C–
AL+
P+
T/R+
HS-100
C+ 7
TB+
C–
AL+
P+
T/R+
C+
MSR
REMOTE
REMOTE ACCESSORY OUTPUTS
MSR-SERIES MS-SERIES
HS-100
MS REMOTE
11 12 13 14 15
TB+
C–
AL+
P+
T/R+
C+ 7
GREEN
PILOT
LED
RED
BLACKRED
RED
BLACK
BLACK
BLACK
BLACK
N.O.
TEST/RESET
SWITCH
YELLOW
TROUBLE
LED
RED ALARM LED
AND/OR HORN
HORN/STROBE
DRY CONTACT OUTPUTS
CONNECTIONS SHOWN FOR ALL POSSIBLE TERMINAL STYLE
CONFIGURATIONS. CONNECT ONLY THOSE TERMINALS
AVAILABLE ON THE MSR REMOTE ACCESSORY CONTROL ASSEMBLY

4
INST AP-332 C100909
FIRE ALARM CONTROL PANEL WIRING
SAMPLE CONTROL PANEL WIRING - STYLE “D” / CLASS “A” IDC (Supervised - A fault condition will not inhibit an alarm response)
UL Listed
Conventional
Fire Alarm
Control Panel
16 17 16 17
19 19 18 18 19 19 18 18
HS-100
Detector #1 HS-100
Detector #X
SAMPLE CONTROL PANEL WIRING - STYLE “B” / CLASS “B” IDC (Supervised - A fault condition will not inhibit an alarm response)
UL Listed
Conventional
Fire Alarm
Control Panel
16 17 16 17
19 19 18 18 19 19 18 18
HS-100
Detector #1 HS-100
Detector #X
EOL
End
of
Line
INTERCONNECTION WIRING FOR COMMON FUNCTIONS
+
–
+
–
+
–
Detector
#1
Detector
#2
Detector
#X
6 6 6
13 13 13
12 12 12
7 7 7
All alarm relays operate with single alarm.
Individual horn/strobe units operate on
alarmed detector only. 30 detectors max.
Detector
#1
Detector
#2
Detector
#X
+
–
+
–
+
–
6 6 6
12 12 12
7 7 7
All alarm relays operate with single alarm.
All horn/strobe units operate on any single
alarm. 10 detectors max.
15 15 15
Detector
#1
Detector
#2
Detector
#X
7 7 7
Common test/reset. 30 detectors max.
(Use normally open test/reset switch)
Detector
#1
Detector
#2
Detector
#X
6 6 6
7 7 7
All alarm relays operate wiht single alarm.
30 detectors max.
NOTE: A common power supply must be used for all interconnected detectors.
ALARM CONTACT USE EXAMPLE
10 9 8
M
DAMPER SUPPLY SOURCE
NC COM NO
In alarm 10 and 9 will open,
interrupting voltage supply to
damper causing it to close.
ALARM

5 INST AP-332 C100909
OPERATIONAL TESTING
To determine the correct operation of the HS-100 Series duct
smoke detector, ensure input power is connected and the LED
on the detector head of both the ionization and photoelectric
models is ashing while the unit is in standby mode. The LED on
the smoke detector head will be permanently illuminated when
smoke is detected and the head is in alarm.
Above: The LED will be permanently illuminated when the unit is in alarm.
Cause a detector alarm via magnet or smoke testing procedures
detailed under functional testing below with the air handling unit
shut down (not connected). The red alarm LED on the detector
will be illuminated and the alarm relay outputs will change state.
Using a multimeter set to OHMS (or continuity buzzer function
on the meter) place the meter probes on the following terminals,
and ensure the contacts are closed (continuity) (19-18) and (8-9).
When removing the magnet or clearing the detector chamber of
test gas and twisting the head loose manually and locking it back
into position these contacts will again open and the unit will be
back in the normal standby state.
The trouble contacts (16,17) on the HS-100 detector will not
change state in the event of a re alarm, operational, or functional
testing. The trouble contacts can be tested by rotating the smoke
detector head counter-clockwise or completely removing the
detector head. This action will extinguish the ashing red LED
and cause the trouble contacts to change state, and (16-17) will
be open circuit. Replacing the detector head and rotating it
clockwise until it locks will cause the red LED to be illuminated
ashing and the unit will be operational; terminals (16-17) will be
closed (continuity).
FUNCTIONAL TESTING
Once operational testing is concluded the unit requires functional
testing to determine the correct operation of the detector head.
MAGNET TESTING: Place the magnet provided with the
installation kit on top of the shroud or detector head roughly
opposite the LED. Allow at least ve seconds for alarm initiation.
Remove magnet and reset detector.
SMOKE TESTING: Using smoke test canister with spray
testing nozzle (available from Air Products and Controls Inc.
part number TG-1000), spray the test gas into the detector.
CAUTION: DO NOT SPRAY GAS FOR MORE
THAN ½ SECOND. OVERUSE OF TEST GAS FACILITY
MAY RESULT IN DETECTOR CONTAMINATION.
After 15 to 20 seconds the detector head will go into alarm,
illuminating the detector head LED and causing the duct unit
functions to operate, alarm relays will change state, and the alarm
related remote accessories, if attached, will function.
If no test gas is available to conduct functional testing, blow smoke
from a cotton wick or punk directly at the head to cause an alarm.
The alarm indicator should illuminate within one minute.
Should additional testing also be required for simulated re
conditions, smoke bombs placed in the duct may not be suited for
the particular detector head (photoelectric or ionization) selected
and installed. Consult the smoke bomb data for proper use and
compatibility with detector type.
The S65A ionization detector head (55000-225) utilizes a
radioactive source as its means of detection and will detect smoke
particles of between .1 and 1 micron in size.
The S65A photoelectric detector head (55000-328) operates on
the principle of light scatter and will detect smoke particles of
between 1 and 10 microns in size.
When purchasing smoke bombs for additional required functional
testing, ensure smoke particle sizes comply with the criteria as
described above.
NOTE: In situations that require a duct smoke detector to be
held in an alarm condition for an extended period of time, the
magnet test or smoke test methods should be used to ensure the
detector is locked into alarm.
MAINTENANCE
Each installation location must be assessed on its own merits. If
the protected area is of a very dirty nature then the HS-100 duct
unit(s) will have to be checked and cleaned on a quarterly basis or
when cleaning is required.
As a guideline the smoke detector head should be cleaned every
six months or as required. The best methods of cleaning are to
vacuum the detector head thoroughly or to blow the detector
head out using clean, dry compressed air.
Do not use chemicals or non-conforming air to clean the detector
head housing as this could contaminate the detector head and
damage the casing.
Consult your local code and AHJ requirements for required
maintenance schedules.
TESTING AND MAINTENANCE PROCEDURES

HS-100-N 4-Wire,IonizationType
HS-100-P 4-Wire,PhotoelectricType
You in Control
AND
AIR PRODUCTS
CONTROLS HS-100 SERIES
PLENUM/DUCT SMOKE DETECTORS
NO-FLOW • LOW-FLOW • SPECIAL APPLICATION
INSTALLATION AND MAINTENANCE
INSTRUCTIONS
NOTICE: The information contained in this document is the most current available at the time of shipment of accompanying product,
and is subject to change without notice. Future references should always be made to the most current revision of this document. The
information contained in all this document should be considered before installing or using the product. Any example applications shown
are subject to the most current enforced local/national codes, standards, approvals, certications, and/or the authority having jurisdic-
tion. All of these resources, as well as the specic manufacturer of any shown or mentioned related equipment, should be consulted
prior to any implementation. For further information or assistance concerning this product, contact Air Products and Controls Inc.
Air Products and Controls Inc. reserves the right to change any and all documentation without notice.
© Air Products and Controls Inc. 2006
A COPY OF THESE INSTRUCTIONS SHOULD BE LEFT WITH THE EQUIPMENT UNTIL
INSTALLATION BY ALL TRADES IS FULLY COMPLETE. FOLLOWING FINAL INSPECTION,
A COPY SHOULD BE LEFT WITH THE OWNER/USER.
FOR TECHNICAL SUPPORT CALL TOLL FREE 888-332-2241 OR 248-332-3900
You in Control
AND
AIR PRODUCTS
CONTROLS
AIR PRODUCTS AND CONTROLS INC.
1749 E. Highwood • Pontiac, MI 48340 USA
Telephone: (248) 332-3900 • www.ap-c.com
Technical Support: (888) 332-2241
AVAILABLE ACCESSORIES FOR USE WITH
HS-100 SERIES DUCT SMOKE DETECTORS
MSR- SERIES REMOTE ACCESSORIES
Visual Indicators: Alarm, Pilot, Trouble • Buzzer: Programmable for Alarm and Trouble
Buzzer Silence: Visual Notication and Ringback • Detector Test/Reset: Key Operated
LED/Buzzer Test: Push-Button Operated
MSR-100R/W White Face Plate
MSR-100R/R Red Face Plate
MSR-100R/S Stainless Steel Face Plate
MSR-100RS/W/C White Face Plate; Strobe with Clear Lens
MSR-100RS/W/O White Face Plate; Strobe with Opaque Lens
MSR-100RS/R/C Red Face Plate; Strobe with Clear Lens
MSR-100RS/R/O Red Face Plate; Strobe with Opaque Lens
MSR-100RS/S/C Stainless Steel Face Plate; Strobe with Clear Lens
MSR-100RS/S/O Stainless Steel Face Plate; Strobe with Opaque Lens
MS- and SHP- SERIES REMOTE ACCESSORIES
MS-RA Remote Alarm
MS-RA/R Remote Alarm, push button Test/Reset Switch
MS-RA/P/R Remote Alarm, Pilot, push-button Test/Reset Switch
MS-KA/R Remote Alarm, key-operated Test/Switch
MS-KA/P/R Remote Alarm, Pilot, key-operated Test/Reset Switch
MS-RA/P Remote Alarm, Pilot
MS-RH Remote Alarm Horn
MS-RH/KA/P/R Remote Alarm, Pilot, Horn, key-operated Test/Reset Switch
MS-RH/P/A Remote Alarm, Pilot, Horn
MS-RH/KA/P/A/T Remote Alarm, Trouble, Pilot, Horn, key-operated Test/Reset Switch
MS-RA/P/T Remote Pilot, Trouble
MS-RA/FT/P Remote Pilot, Trouble, push-button Test/Reset Switch
MS-KA/P/R/T Remote Pilot, Trouble, key-operated Test/Reset Switch
MS-RD Remote Alarm
MS-F/T Remote Trouble
SHP24-1575R Horn/Strobe, red housing, clear cover
SHP24-1575O Horn/Strobe, white housing, opaque cover
SHP24-1575W Horn/Strobe, white housing, clear cover
SMOKE TEST GAS
TG-1000 Solo Aerosol Test Gas with Spray Nozzle
REPLACEMENT SMOKE DETECTOR HEADS
55000-225 S65 Ionization Detector Replacement Head
55000-328 S65 Photoelectric Detector Replacement Head
POWER SUPPLIES
T-PB 202-1 24VAC @ 4.0A Class I Power Supply
T-PB 202-0 24VAC @ 4.0A Class I Power Supply
T-PB 303-1 24VAC @ 3.0A Class I Power Supply
T-PB 303-0 24VAC @ 3.0A Class I Power Supply
This manual suits for next models
1
Table of contents
Other Air Products & Controls Smoke Alarm manuals