Air Products & Controls Multi-Flex Series User manual

You in Control
AND
AIR PRODUCTS
CONTROLS
© Air Products and Controls Inc. 2009 Page 1 INST APD0281 D090201
guidelines should be observed. The detector used with this base
must be tested and maintained regularly in accordance with NFPA
72 requirements. Canadian Installations must comply with the
Canadian Standard for installation for Fire Alarm System CAN/
ULC-S524 and the Canadian Electrical Code C22.1, Part 1.
NOTE: A COPY OF THIS GUIDE SHOULD BE LEFTWITH
THE OWNER/USER OF THIS EQUIPMENT.
INSTALLATION (CONVENTIONAL)
Connect zone circuit (IDC) to wiring terminals L1 and L2 on detec-
tor mounting base. (see Fig. 1). Provide regulated or unregulated
24VDC external power supply to sounder base terminals as shown
in Fig.1. Power supply must be UL Listed for Fire Protective Signal-
ing Systems. Please also refer to Fig. 6 and Fig. 7. for zone wiring.
INSTALLATION (ANALOG ADDRESSABLE)
Connect analog addressable loop (SLC) to wiring terminals L1 and
L2 on detector mounting base.(see Fig.3). Provide regulated or un-
regulated 24VDC external power supply to sounder base terminals
as shown in Fig.3. Power supply must be UL Listed for Fire Protec-
tive Signaling Systems. Please also refer to Fig. 8. for loop wiring.
PRODUCT DESCRIPTION
The Multi-Flex family of smoke detector sounder bases and syn-
chronization modules provide today’s most advanced functionality
and performance, delivering exible notication capabilities for
any installation.
The bases offer selectable steady or temporal pattern output and
selectable high or low volume levels. The three-pulse temporal
pattern is required by NFPA 72 for re alarm evacuation for com-
mercial and residential applications.
Available (SM) synchronization modules allow temporal pattern
sounder base circuits to be completely synchronized and installed
in almost limitless congurations, and also provide an on-board
latching test function.
The sounder base requires an external 24VDC power supply. In the
absence of a synchronization module,a means for polarity reversal
is required for test and general alarm functionality. The connec-
tions for the external power supply and the communication loop
are opto-isolated to prevent electrical interaction between them.
The 6-inch diameter sounder base mounts to 4-inch octagonal
and 4-inch square boxes. When mounting detectors on a ceiling,
install at least 4 inches from a wall. When mounting detctors on
a wall, install 4 to 12 inches from ceiling.
COMPATIBILITY
The Multi-Flex series is compatible withApollo analog addressable
(XP95A and Discovery Series) and conventional (Series 60A and
Series 65) smoke detectors,including heat,photoelectric and ion-
ization types. Please refer to the individual detector documentation
for more information.
The smoke detectors and bases are designed to operate in con-
junction with UL Listed FireAlarm Control Panels (FACP). Refer
to the FACP manual for guidance on maximum allowable devices
per loop. Contact Air Products and Controls or refer to your
FACP manual for approved compatibility.
The MB-SDRT-CV is fully compatible with the previous genera-
tion MB-SDR-S60 sounder base. Likewise, the MB-SDRT-AA is
also backwards compatible with the MB-SDR-XP95 sounder
base and MB-RLY-XP95 relay base models. The bases are also
compatible with the new MB-RLYT-CV and MB-RLYT-AA relay
bases, respectively.
BEFORE INSTALLING
Ensure familiarity with requirements for detector spacing, place-
ment,zoning,wiring and special applications. NFPA 72 and NEMA
AIR PRODUCTS AND CONTROLS INC.
INSTALLATION GUIDE FOR MULTI-FLEX®FAMILY
SOUNDER BASES AND SYNCHRONIZATION MODULES
MB-SDRT-AA Analog Addressable Detector Sounder Base
MB-SDRT-CV Conventional Detector Sounder Base
MB-SDRT-SM Synchronization Module
24VDC
L2
-R
+R
L1
NEG POS
xxx
ALIGNMENT MARK
EXTERNAL
24VDC SUPPLY
(UL LISTED)
+
-
ADDRESS
LABEL
SPACE
JP1
VOL.
HIGH
/LOW
JP2
TEMP
3 OR
CONT
24VDC
L2
-R
L1
IN
L1
OUT
NEG POS
ALIGNMENT MARK
EXTERNAL
24VDC SUPPLY
(UL LISTED)
+
-
JP1
VOL.
HIGH
/LOW
JP2
TEMP
3 OR
CONT
NEG POS NEG POS
NORMAL OPERATION TEST /FORCED FUNCTION
External 24VDC
Connections
External 24VDC
Connections
L2
-R
+R
L1
NEG POS
L2
-R
+R
L1
NEG POS
-
+
-
+
TO PANEL DCC/EARTH/GROUND
NOT SUPERVISED *
UL/ULC LISTED 24V
EOL PAM-4 RELAY
(NOT INCLUDED)
OPTIONAL REMOTE
LED ANNUNCIATOR
UL/ULC LISTED
24VDC
POWER SUPPLY
UL/ULC LISTED
COMPATIBLE
FIRE ALARM
CONTROL PANEL
+
-
SUPERVISED
BY FIRE ALARM
CONTROL PANEL
SUPERVISED BY
EOL RELAY/FACP
*
N.O. CONTACT
HELD CLOSED
TO FIRE ALARM
CONTROL PANEL IDC
OR A/A MONITOR
INPUT MODULE
RED
BLK
BLU
ORG
EOL
End of Line
Resistor
IF REQUIRED:
TO NEXT 2-WIRE
A/A DEVICE (OR
BACK TO FACP
SLC FOR STYLE
"6" OR "7" / CLASS
"A" CIRCUIT)
CAUTION: DO NOT USE LOOPED WIRE UNDER TERMINALS L1, L2, +, AND -.
BREAK WIRE RUN TO PROVIDE SUPERVISION OF CONNECTIONS.
FIG. 8: TYPICAL CLASS B/A, STYLE 4/6 CIRCUIT WIRING FOR MB-SDRT-AA SOUNDER BASE
SLC
L2
-R
L1
OUT
NEG POS
L2
-R
NEG POS
-
+
-
+
TO PANEL DCC/EARTH/GROUND
NOT SUPERVISED *
UL/ULC LISTED 24V
EOL PAM-4 RELAY
(NOT INCLUDED)
OPTIONAL REMOTE
LED ANNUNCIATOR
UL/ULC LISTED
24VDC
POWER SUPPLY
+
-
SUPERVISED
BY FIRE ALARM
CONTROL PANEL
*
N.O. CONTACT
HELD CLOSED
RED
BLK
BLU
ORG
CAUTION: DO NOT USE LOOPED WIRE UNDER TERMINALS L1, L2, +, AND -.
BREAK WIRE RUN TO PROVIDE SUPERVISION OF CONNECTIONS.
FIG. 6: TYPICAL CLASS B, STYLE B CIRCUIT WIRING FOR MB-SDRT-CV SOUNDER BASE
IDC
L1
IN
L1
OUT
L1
IN
UL/ULC LISTED
COMPATIBLE
FIRE ALARM
CONTROL PANEL
SUPERVISED BY
EOL RELAY/FACP
L2
-R
L1
OUT
NEG POS
L2
-R
NEG POS
-
+
-
+
TO PANEL DCC/EARTH/GROUND
NOT SUPERVISED *
UL/ULC LISTED 24V
EOL PAM-4 RELAY
(NOT INCLUDED)
OPTIONAL REMOTE
LED ANNUNCIATOR
UL/ULC LISTED
24VDC
POWER SUPPLY
+
-
SUPERVISED
BY FIRE ALARM
CONTROL PANEL
*
N.O. CONTACT
HELD CLOSED
RED
BLK
BLU
ORG
FIG. 7: TYPICAL CLASS A, STYLE D CIRCUIT WIRING FOR MB-SDRT-CV SOUNDER BASE
IDC
L1
IN
L1
OUT
L1
IN
UL/ULC LISTED
COMPATIBLE
FIRE ALARM
CONTROL PANEL
SUPERVISED BY
EOL RELAY/FACP
+
-
OUT
RETURN
Resistor
CAUTION: DO NOT USE LOOPED WIRE UNDER TERMINALS L1, L2, +, AND -.
BREAK WIRE RUN TO PROVIDE SUPERVISION OF CONNECTIONS.
ATTENTION: NE PAS UTILISER EN BOUCLE FIL TERMINAUX SOUS L1, L2, + ET -.
BREAK FIL RUN POUR ASSURER LA SURVEILLANCE DES CONNEXIONS.
ATTENTION: NE PAS UTILISER EN BOUCLE FIL TERMINAUX SOUS L1, L2, + ET -.
BREAK FIL RUN POUR ASSURER LA SURVEILLANCE DES CONNEXIONS.
ATTENTION: NE PAS UTILISER EN BOUCLE FIL TERMINAUX SOUS L1, L2, + ET -.
BREAK FIL RUN POUR ASSURER LA SURVEILLANCE DES CONNEXIONS.
Fig. 1 MB-SDRT-CV Conventional Sounder Base
X-pert Card
XXX
Address Label Space
1
2
4
8
16
32
64
XPERT CARD
Address label spaces
Fig. 2 XPERT Card

© Air Products and Controls Inc. 2009 Page 2 INST APD0281 D090201
1
2
4
8
16
32
64
1
1
1
2
4
8
16
32
64
10
10
1
2
4
8
16
32
64
9
9
1
2
4
8
16
32
64
8
8
1
2
4
8
16
32
64
7
7
1
2
4
8
16
32
64
6
6
1
2
4
8
16
32
64
5
5
1
2
4
8
16
32
64
4
4
1
2
4
8
16
32
64
3
3
1
2
4
8
16
32
64
2
2
1
2
4
8
16
32
64
11
11
1
2
4
8
16
32
64
20
20
1
2
4
8
16
32
64
19
19
1
2
4
8
16
32
64
18
18
1
2
4
8
16
32
64
17
17
1
2
4
8
16
32
64
16
16
1
2
4
8
16
32
64
15
15
1
2
4
8
16
32
64
14
14
1
2
4
8
16
32
64
13
13
1
2
4
8
16
32
64
12
12
1
2
4
8
16
32
64
21
21
1
2
4
8
16
32
64
30
30
1
2
4
8
16
32
64
29
29
1
2
4
8
16
32
64
28
28
1
2
4
8
16
32
64
27
27
1
2
4
8
16
32
64
26
26
1
2
4
8
16
32
64
25
25
1
2
4
8
16
32
64
24
24
1
2
4
8
16
32
64
23
23
1
2
4
8
16
32
64
22
22
1
2
4
8
16
32
64
31
31
1
2
4
8
16
32
64
40
40
1
2
4
8
16
32
64
39
39
1
2
4
8
16
32
64
38
38
1
2
4
8
16
32
64
37
37
1
2
4
8
16
32
64
36
36
1
2
4
8
16
32
64
35
35
1
2
4
8
16
32
64
34
34
1
2
4
8
16
32
64
33
33
1
2
4
8
16
32
64
32
32
1
2
4
8
16
32
64
41
41
1
2
4
8
16
32
64
50
50
1
2
4
8
16
32
64
49
49
1
2
4
8
16
32
64
48
48
1
2
4
8
16
32
64
47
47
1
2
4
8
16
32
64
46
46
1
2
4
8
16
32
64
45
45
1
2
4
8
16
32
64
44
44
1
2
4
8
16
32
64
43
43
1
2
4
8
16
32
64
42
42
1
2
4
8
16
32
64
51
51
1
2
4
8
16
32
64
60
60
1
2
4
8
16
32
64
59
59
1
2
4
8
16
32
64
58
58
1
2
4
8
16
32
64
57
57
1
2
4
8
16
32
64
56
56
1
2
4
8
16
32
64
55
55
1
2
4
8
16
32
64
54
54
1
2
4
8
16
32
64
53
53
1
2
4
8
16
32
64
52
52
1
2
4
8
16
32
64
63
63
1
2
4
8
16
32
64
62
62
1
2
4
8
16
32
64
61
61
1
2
4
8
16
32
64
124
124
1
2
4
8
16
32
64
126
126
1
2
4
8
16
32
64
125
125
1
2
4
8
16
32
64
80
80
1
2
4
8
16
32
64
79
79
1
2
4
8
16
32
64
78
78
1
2
4
8
16
32
64
77
77
1
2
4
8
16
32
64
76
76
1
2
4
8
16
32
64
70
70
1
2
4
8
16
32
64
69
69
1
2
4
8
16
32
64
68
68
1
2
4
8
16
32
64
67
67
1
2
4
8
16
32
64
66
66
1
2
4
8
16
32
64
65
65
1
2
4
8
16
32
64
64
64
1
2
4
8
16
32
64
71
71
1
2
4
8
16
32
64
75
75
1
2
4
8
16
32
64
74
74
1
2
4
8
16
32
64
73
73
1
2
4
8
16
32
64
72
72
1
2
4
8
16
32
64
81
81
1
2
4
8
16
32
64
90
90
1
2
4
8
16
32
64
89
89
1
2
4
8
16
32
64
88
88
1
2
4
8
16
32
64
87
87
1
2
4
8
16
32
64
86
86
1
2
4
8
16
32
64
85
85
1
2
4
8
16
32
64
84
84
1
2
4
8
16
32
64
83
83
1
2
4
8
16
32
64
82
82
1
2
4
8
16
32
64
91
91
1
2
4
8
16
32
64
100
100
1
2
4
8
16
32
64
99
99
1
2
4
8
16
32
64
98
98
1
2
4
8
16
32
64
97
97
1
2
4
8
16
32
64
96
96
1
2
4
8
16
32
64
95
95
1
2
4
8
16
32
64
94
94
1
2
4
8
16
32
64
93
93
1
2
4
8
16
32
64
92
92
1
2
4
8
16
32
64
101
101
1
2
4
8
16
32
64
110
110
1
2
4
8
16
32
64
109
109
1
2
4
8
16
32
64
108
108
1
2
4
8
16
32
64
107
107
1
2
4
8
16
32
64
106
106
1
2
4
8
16
32
64
105
105
1
2
4
8
16
32
64
104
104
1
2
4
8
16
32
64
103
103
1
2
4
8
16
32
64
102
102
1
2
4
8
16
32
64
111
111
1
2
4
8
16
32
64
120
120
1
2
4
8
16
32
64
119
119
1
2
4
8
16
32
64
118
118
1
2
4
8
16
32
64
117
117
1
2
4
8
16
32
64
116
116
1
2
4
8
16
32
64
115
115
1
2
4
8
16
32
64
114
114
1
2
4
8
16
32
64
113
113
1
2
4
8
16
32
64
112
112
1
2
4
8
16
32
64
123
123
1
2
4
8
16
32
64
122
122
1
2
4
8
16
32
64
121
121
Fig. 4 XPERT card addressing for Discovery and XP95
XPERT CARD PROGRAMMING
Analog addressable Discovery and XP95A bases employ a unique,
simple mechanism for hardware addressing (Fig. 2). The XPERT
Card provides a series of seven removable pips, which when
removed in proscribed patterns, corresponding to binary system
digits,and can represent numbers 1 through 126. Factory set and
labeled XPERT Cards are available.
NOTE: No buttons removed (address 0) or multiple like ad-
dresses on an SLC will cause an FACP Trouble/Fault condition.
NOTE: Remove the XPERT Card, select the desired address
and remove the pips indicated in black with a small screwdriver.
Replace the XPERT Card and twist the detector head into place
to complete programming (Fig. 4).
SOUNDER BASE PROGRAMMING
Program the desired volume and format of the sounder by con-
guring jumpers “JP1” and “JP2” on the sounder base PCB. JP1
controls the volume level, and is left ON for high level (85dB) or
taken OFF for low level (75dB). JP2 controls the format of the
sound, and is taken OFF for a continuous tone, or left ON for
temporal (code 3) pattern.
NOTE: If synchronization of the temporal pattern between two
or more sounder bases is required, an optional synchronization
module (SM) is required, as described below. When selecting the
temporal pattern with no synchronization,the sounders will “free
run” on an individual basis.
OPERATION
When a sounder base’s associated detctor goes into the alarm
state, the sounder will sound a continuous or temporal (code 3)
pattern,as programmed. This pattern will continue until the detec-
tor is succesfully reset to the normal standby state.
24VDC
L2
-R
+R
L1
NEG POS
xxx
ALIGNMENT MARK
EXTERNAL
24VDC SUPPLY
(UL LISTED)
+
-
ADDRESS
LABEL
SPACE
JP1
VOL.
HIGH
/LOW
JP2
TEMP
3 OR
CONT
24VDC
L2
-R
L1
IN
L1
OUT
NEG POS
ALIGNMENT MARK
EXTERNAL
24VDC SUPPLY
(UL LISTED)
+
-
JP1
VOL.
HIGH
/LOW
JP2
TEMP
3 OR
CONT
NEG POS NEG POS
NORMAL OPERATION TEST /FORCED FUNCTION
External 24VDC
Connections
External 24VDC
Connections
L2
-R
+R
L1
NEG POS
L2
-R
+R
L1
NEG POS
-
+
-
+
TO PANEL DCC/EARTH/GROUND
NOT SUPERVISED *
UL/ULC LISTED 24V
EOL PAM-4 RELAY
(NOT INCLUDED)
OPTIONAL REMOTE
LED ANNUNCIATOR
UL/ULC LISTED
24VDC
POWER SUPPLY
UL/ULC LISTED
COMPATIBLE
FIRE ALARM
CONTROL PANEL
+
-
SUPERVISED
BY FIRE ALARM
CONTROL PANEL
SUPERVISED BY
EOL RELAY/FACP
*
N.O. CONTACT
HELD CLOSED
TO FIRE ALARM
CONTROL PANEL IDC
OR A/A MONITOR
INPUT MODULE
RED
BLK
BLU
ORG
EOL
End of Line
Resistor
IF REQUIRED:
TO NEXT 2-WIRE
A/A DEVICE (OR
BACK TO FACP
SLC FOR STYLE
"6" OR "7" / CLASS
"A" CIRCUIT)
CAUTION: DO NOT USE LOOPED WIRE UNDER TERMINALS L1, L2, +, AND -.
BREAK WIRE RUN TO PROVIDE SUPERVISION OF CONNECTIONS.
FIG. 8: TYPICAL CLASS B/A, STYLE 4/6 CIRCUIT WIRING FOR MB-SDRT-AA SOUNDER BASE
SLC
L2
-R
L1
OUT
NEG POS
L2
-R
NEG POS
-
+
-
+
TO PANEL DCC/EARTH/GROUND
NOT SUPERVISED *
UL/ULC LISTED 24V
EOL PAM-4 RELAY
(NOT INCLUDED)
OPTIONAL REMOTE
LED ANNUNCIATOR
UL/ULC LISTED
24VDC
POWER SUPPLY
+
-
SUPERVISED
BY FIRE ALARM
CONTROL PANEL
*
N.O. CONTACT
HELD CLOSED
RED
BLK
BLU
ORG
CAUTION: DO NOT USE LOOPED WIRE UNDER TERMINALS L1, L2, +, AND -.
BREAK WIRE RUN TO PROVIDE SUPERVISION OF CONNECTIONS.
FIG. 6: TYPICAL CLASS B, STYLE B CIRCUIT WIRING FOR MB-SDRT-CV SOUNDER BASE
IDC
L1
IN
L1
OUT
L1
IN
UL/ULC LISTED
COMPATIBLE
FIRE ALARM
CONTROL PANEL
SUPERVISED BY
EOL RELAY/FACP
L2
-R
L1
OUT
NEG POS
L2
-R
NEG POS
-
+
-
+
TO PANEL DCC/EARTH/GROUND
NOT SUPERVISED *
UL/ULC LISTED 24V
EOL PAM-4 RELAY
(NOT INCLUDED)
OPTIONAL REMOTE
LED ANNUNCIATOR
UL/ULC LISTED
24VDC
POWER SUPPLY
+
-
SUPERVISED
BY FIRE ALARM
CONTROL PANEL
*
N.O. CONTACT
HELD CLOSED
RED
BLK
BLU
ORG
FIG. 7: TYPICAL CLASS A, STYLE D CIRCUIT WIRING FOR MB-SDRT-CV SOUNDER BASE
IDC
L1
IN
L1
OUT
L1
IN
UL/ULC LISTED
COMPATIBLE
FIRE ALARM
CONTROL PANEL
SUPERVISED BY
EOL RELAY/FACP
+
-
OUT
RETURN
Resistor
CAUTION: DO NOT USE LOOPED WIRE UNDER TERMINALS L1, L2, +, AND -.
BREAK WIRE RUN TO PROVIDE SUPERVISION OF CONNECTIONS.
ATTENTION: NE PAS UTILISER EN BOUCLE FIL TERMINAUX SOUS L1, L2, + ET -.
BREAK FIL RUN POUR ASSURER LA SURVEILLANCE DES CONNEXIONS.
ATTENTION: NE PAS UTILISER EN BOUCLE FIL TERMINAUX SOUS L1, L2, + ET -.
BREAK FIL RUN POUR ASSURER LA SURVEILLANCE DES CONNEXIONS.
ATTENTION: NE PAS UTILISER EN BOUCLE FIL TERMINAUX SOUS L1, L2, + ET -.
BREAK FIL RUN POUR ASSURER LA SURVEILLANCE DES CONNEXIONS.
Fig. 3 MB-SDRT-AA Analog Addressable Sounder Base
24VDC
L2
-R
+R
L1
NEG POS
xxx
ALIGNMENT MARK
EXTERNAL
24VDC SUPPLY
(UL LISTED)
+
-
ADDRESS
LABEL
SPACE
JP1
VOL.
HIGH
/LOW
JP2
TEMP
3 OR
CONT 24VDC
L2
-R
L1
IN
L1
OUT
NEG POS
ALIGNMENT MARK
EXTERNAL
24VDC SUPPLY
(UL LISTED)
+
-
JP1
VOL.
HIGH
/LOW
JP2
TEMP
3 OR
CONT
NEG POS NEG POS
NORMAL OPERATION TEST /FORCED FUNCTION
External 24VDC
Connections
External 24VDC
Connections
L2
-R
+R
L1
NEG POS
L2
-R
+R
L1
NEG POS
-
+
-
+
TO PANEL DCC/EARTH/GROUND
NOT SUPERVISED *
UL/ULC LISTED 24V
EOL PAM-4 RELAY
(NOT INCLUDED)
OPTIONAL REMOTE
LED ANNUNCIATOR
UL/ULC LISTED
24VDC
POWER SUPPLY
UL/ULC LISTED
COMPATIBLE
FIRE ALARM
CONTROL PANEL
+
-
SUPERVISED
BY FIRE ALARM
CONTROL PANEL
SUPERVISED BY
EOL RELAY/FACP
*
N.O. CONTACT
HELD CLOSED
TO FIRE ALARM
CONTROL PANEL IDC
OR A/A MONITOR
INPUT MODULE
RED
BLK
BLU
ORG
EOL
End of Line
Resistor
IF REQUIRED:
TO NEXT 2-WIRE
A/A DEVICE (OR
BACK TO FACP
SLC FOR STYLE
"6" OR "7" / CLASS
"A" CIRCUIT)
CAUTION: DO NOT USE LOOPED WIRE UNDER TERMINALS L1, L2, +, AND -.
BREAK WIRE RUN TO PROVIDE SUPERVISION OF CONNECTIONS.
FIG. 8: TYPICAL CLASS B/A, STYLE 4/6 CIRCUIT WIRING FOR MB-SDRT-AA SOUNDER BASE
SLC
L2
-R
L1
OUT
NEG POS
L2
-R
NEG POS
-
+
-
+
TO PANEL DCC/EARTH/GROUND
NOT SUPERVISED *
UL/ULC LISTED 24V
EOL PAM-4 RELAY
(NOT INCLUDED)
OPTIONAL REMOTE
LED ANNUNCIATOR
UL/ULC LISTED
24VDC
POWER SUPPLY
+
-
SUPERVISED
BY FIRE ALARM
CONTROL PANEL
*
N.O. CONTACT
HELD CLOSED
RED
BLK
BLU
ORG
CAUTION: DO NOT USE LOOPED WIRE UNDER TERMINALS L1, L2, +, AND -.
BREAK WIRE RUN TO PROVIDE SUPERVISION OF CONNECTIONS.
FIG. 6: TYPICAL CLASS B, STYLE B CIRCUIT WIRING FOR MB-SDRT-CV SOUNDER BASE
IDC
L1
IN
L1
OUT
L1
IN
UL/ULC LISTED
COMPATIBLE
FIRE ALARM
CONTROL PANEL
SUPERVISED BY
EOL RELAY/FACP
L2
-R
L1
OUT
NEG POS
L2
-R
NEG POS
-
+
-
+
TO PANEL DCC/EARTH/GROUND
NOT SUPERVISED *
UL/ULC LISTED 24V
EOL PAM-4 RELAY
(NOT INCLUDED)
OPTIONAL REMOTE
LED ANNUNCIATOR
UL/ULC LISTED
24VDC
POWER SUPPLY
+
-
SUPERVISED
BY FIRE ALARM
CONTROL PANEL
*
N.O. CONTACT
HELD CLOSED
RED
BLK
BLU
ORG
FIG. 7: TYPICAL CLASS A, STYLE D CIRCUIT WIRING FOR MB-SDRT-CV SOUNDER BASE
IDC
L1
IN
L1
OUT
L1
IN
UL/ULC LISTED
COMPATIBLE
FIRE ALARM
CONTROL PANEL
SUPERVISED BY
EOL RELAY/FACP
+
-
OUT
RETURN
Resistor
CAUTION: DO NOT USE LOOPED WIRE UNDER TERMINALS L1, L2, +, AND -.
BREAK WIRE RUN TO PROVIDE SUPERVISION OF CONNECTIONS.
ATTENTION: NE PAS UTILISER EN BOUCLE FIL TERMINAUX SOUS L1, L2, + ET -.
BREAK FIL RUN POUR ASSURER LA SURVEILLANCE DES CONNEXIONS.
ATTENTION: NE PAS UTILISER EN BOUCLE FIL TERMINAUX SOUS L1, L2, + ET -.
BREAK FIL RUN POUR ASSURER LA SURVEILLANCE DES CONNEXIONS.
ATTENTION: NE PAS UTILISER EN BOUCLE FIL TERMINAUX SOUS L1, L2, + ET -.
BREAK FIL RUN POUR ASSURER LA SURVEILLANCE DES CONNEXIONS.
Fig. 5 Polarity reversal for testing or forced operation

© Air Products and Controls Inc. 2009 Page 3 INST APD0281 D090201
TESTING AND FORCED OPERATION
A group of sounder bases may be tested or force activated by
reversing the polarity of the 24VDC external supply. (Fig. 5). This
causes the sounder to activate. It is not necessary to have the
detctor head installed or in alarm for this operation. Note that
when doing a forced (or test) alarm operation, the sounder(s)
will continue to sound until the poalrity is returned to normal or
power is restored.
NOTE: All wiring must be installed in compliance with the
national electric code and the local codes having jurisdiction. Wires
must not be of such size or length which would cause the base to
operate outside of its published specications. The conductors
used to connect smoke detectors to re alarm control panels and
acccessory devices should be color coded to reduce the liklihood
of wiring errors. Improper connecitons can prevent a system from
responding properly in the event of a re.
For signal wiring (the wiring between interconnected detectors or
modules),it is recommended that the wire size be no smaller than
18 gauge (1.0 square mm),despite the terminals having capability to
accept smaller gauge wires. Wire sizes up to 12 gauge (2.5 square
mm) may be used with the base and modules. For best system
performance, the power (24VDC +/-) wires and the communica-
tion circuit should be twisted pair or shielded cable installed in
separate grounded conduit to protect the communication loop
from electrical interference.
Make wire connections by stripping about ⅜” of insulation from
the end of the wire. Then, slide the bare end of the wire under
the clamping plate, and tighten the clamping plate screw.
The zone wiring of the detector base should be veried before
the detector head is installed. Check the wiring for continuity
and polarity in the base.
NOTE: DO NOT USE LOOPED WIRE CONNECTIONS.
BREAK WIRE UNDER ALL TERMINALS TO ENSURE CIRCUIT
SUPERVISION.
NOTE:NE PAS UTILISER EN BOUCLE FIL FIL CONNECTIONS.
BREAK SOUS TOUS LES TERMINAUX POUR ASSURER LA SU-
PERVISION DU CIRCUIT.
SYNCHRONIZATION MODULE
PRODUCT DESCRIPTION
The Multi-Flex (SM) synchronization module is designed to work
with the Multi-Flex family of conventional and analog addressable
sounder bases to provide the following:
1) A means of synchronizing the temporal (code 3) sound pattern be-
tween a number of bases in a common area (a group).
2) A means of testing or force activating the group of bases both from
the synchronization module (via the onboard test switch) and remotely
via the FACP.
3) A means of powering a group of bases (≤2A @ 24VDC nominal).
4) A means of silencing a group of bases from the FACP,with subsequent
alarm capability.
5) A means of triggering and silence agging connected secondary pro-
grammed SM synchronization modules and their associated sub-groups
of bases from a SM synchronization module.
The module is also compatible with the fully listed and approved
relay products from Air Products and Controls as shown in the
wiring diagrams to provide a fully code-compliant,supervised sub-
system. Each synchronization module can accomodate a circuit of
up to 61 sounder bases.
The Multi-Flex synchronization module is also designed to work
with the Multi-Flex analog addressable and conventional relay
bases, MB-RLYT-AA and MB-RLYT-CV, respectively. Please note
that when using these relay bases:
1) Synchronization is not a concern, as no pulsed pattern is provided
by the relays.
2) A test or forced (general alarm) operation will activate all connected
relay bases.
3) A silence operation will not effect the relays’ “ON” status.
When using the Multi-Flex synchronization module with the previ-
ous generation MB-SDR-S60, MB-SDR-XP95 and MB-RLY-XP95
sounder and relay bases, certain design limitations of the older
designs will not allow for:
1) temporal pattern synchronization on the older bases, as they are
continuous tone only devices.
2) silencing operations with sub-sequent alarm.
When replacing older model sounder bases where temporal
pattern is not required, simply set the Multi-Flex sounder base to
continuous pattern mode.
NEG POS NEG POS
-
+
-
+
*UL LISTED 24V
EOL PAM-4 OR
RIC-3 RELAY
(NOT INCLUDED)
UL LISTED
24VDC
POWER SUPPLY
(≤2A @ 24VDC)
UL LISTED
COMPATIBLE
FIRE ALARM
CONTROL PANEL
SUPERVISED
BY FIRE ALARM
CONTROL PANEL
N.O. CONTACT
HELD CLOSED*
TO FIRE ALARM
CONTROL PANEL IDC
OR A/A MONITOR
INPUT MODULE
EOL
End of Line
Resistor
SLC
- SIL.NAC + GEN ALM NO
+SYNC OUT- + 24VDC -
MB-SDRLT-MM
Main
Synchronization
Module (MSM)
-SYNC OUT+ -SYNC IN+
GEN ALM NO + 24VDC -
MB-SDRLT-SM
Secondary
Synchronization
Module (SSM)
In From
FACP
General
Alarm
In From
FACP
Silenceable
NAC
UL Listed
24VDC
Power
Supply
UL Listed
24VDC
Power
Supply
In From
FACP
General
Alarm
THIS NOT THIS
- SIL.NAC + GEN ALM NO
+SYNC OUT- + 24VDC -
MB-SDRLT-MM
Main
Synchronization
Module (MSM)
OR
TO MB-SDRT-SM
SSM(S) “SYNC IN”
TERMINALS
N.O. CONTACT
HELD CLOSED*
TO FIRE ALARM
CONTROL PANEL IDC
OR A/A MONITOR
INPUT MODULE
EOL
End of Line
Resistor
NEG POS
Out to
Sounder
Base
Group
and/or
SSM
Out to
Sounder
Base
Group
and/or
SSM
In From
MSM
Sounder
Base
Group
NEG POS NEG POS
-
+
-
+
*UL LISTED 24V
EOL PAM-4 OR
RIC-3 RELAY
(NOT INCLUDED)
UL LISTED
24VDC
POWER SUPPLY
(≤2A @ 24VDC)
UL LISTED
COMPATIBLE
FIRE ALARM
CONTROL PANEL
SUPERVISED
BY FIRE ALARM
CONTROL PANEL
N.O. CONTACT
HELD CLOSED*
TO FIRE ALARM
CONTROL PANEL IDC
OR A/A MONITOR
INPUT MODULE
EOL
End of Line
Resistor
SLC
- SIL.NAC + GEN ALM NO
+SYNC OUT- + 24VDC -
MB-SDRLT-MM
Main
Synchronization
Module (MSM)
-SYNC OUT+ -SYNC IN+
GEN ALM NO + 24VDC -
MB-SDRLT-SM
Secondary
Synchronization
Module (SSM)
In From
FACP
General
Alarm
In From
FACP
Silenceable
NAC
UL Listed
24VDC
Power
Supply
UL Listed
24VDC
Power
Supply
In From
FACP
General
Alarm
THIS NOT THIS
- SIL.NAC + GEN ALM NO
+SYNC OUT- + 24VDC -
MB-SDRLT-MM
Main
Synchronization
Module (MSM)
OR
TO MB-SDRT-SM
SSM(S) “SYNC IN”
TERMINALS
N.O. CONTACT
HELD CLOSED*
TO FIRE ALARM
CONTROL PANEL IDC
OR A/A MONITOR
INPUT MODULE
EOL
End of Line
Resistor
NEG POS
Out to
Sounder
Base
Group
and/or
SSM
Out to
Sounder
Base
Group
and/or
SSM
In From
MSM
Sounder
Base
Group
Label AP-336 A060404 (MB-SDRT-SM Label)
1.9”wide x .75” tall
Prints black only on white smudgeproof adhesive stock
Main Mode: For setup
of group of bases with
general alarm and silence
capabilities, plus operating
power.
Secondary Mode: For
extension of the above
groups by providing an
additional operating
power input point.
Sync Only Mode: For
setup of a subgroup of
the above group of bases
with their own distinct
seperate general alarm
and silence capabilities, as
well as operating power.
Off-Main
sync only
secondary
{
{
JP1
( ) = Polarity in alarm

© Air Products and Controls Inc. 2009 Page 4 INST APD0281 D090201
CONVENTIONAL ZONE WIRING
ANALOG ADDRESSABLE LOOP WIRING
24VDC
L2
-R
+R
L1
NEG POS
xxx
ALIGNMENT MARK
EXTERNAL
24VDC SUPPLY
(UL LISTED)
+
-
ADDRESS
LABEL
SPACE
JP1
VOL.
HIGH
/LOW
JP2
TEMP
3 OR
CONT
24VDC
L2
-R
L1
IN
L1
OUT
NEG POS
ALIGNMENT MARK
EXTERNAL
24VDC SUPPLY
(UL LISTED)
+
-
JP1
VOL.
HIGH
/LOW
JP2
TEMP
3 OR
CONT
NEG POS NEG POS
NORMAL OPERATION TEST /FORCED FUNCTION
External 24VDC
Connections
External 24VDC
Connections
L2
-R
+R
L1
NEG POS
L2
-R
+R
L1
NEG POS
-
+
-
+
TO PANEL DCC/EARTH/GROUND
NOT SUPERVISED
*
UL/ULC LISTED 24V
EOL PAM-4 RELAY
(NOT INCLUDED)
OPTIONAL REMOTE
LED ANNUNCIATOR
UL/ULC LISTED
24VDC
POWER SUPPLY
UL/ULC LISTED
COMPATIBLE
FIRE ALARM
CONTROL PANEL
+
-
SUPERVISED
BY FIRE ALARM
CONTROL PANEL
SUPERVISED BY
EOL RELAY/FACP
*
N.O. CONTACT
HELD CLOSED
TO FIRE ALARM
CONTROL PANEL IDC
OR A/A MONITOR
INPUT MODULE
RED
BLK
BLU
ORG
EOL
End of Line
Resistor
IF REQUIRED:
TO NEXT 2-WIRE
A/A DEVICE (OR
BACK TO FACP
SLC FOR STYLE
"6" OR "7" / CLASS
"A" CIRCUIT)
CAUTION: DO NOT USE LOOPED WIRE UNDER TERMINALS L1, L2, +, AND -.
BREAK WIRE RUN TO PROVIDE SUPERVISION OF CONNECTIONS.
FIG. 8: TYPICAL CLASS B/A, STYLE 4/6 CIRCUIT WIRING FOR MB-SDRT-AA SOUNDER BASE
SLC
L2
-R
L1
OUT
NEG POS
L2
-R
NEG POS
-
+
-
+
TO PANEL DCC/EARTH/GROUND
NOT SUPERVISED
*
UL/ULC LISTED 24V
EOL PAM-4 RELAY
(NOT INCLUDED)
OPTIONAL REMOTE
LED ANNUNCIATOR
UL/ULC LISTED
24VDC
POWER SUPPLY
+
-
SUPERVISED
BY FIRE ALARM
CONTROL PANEL
*
N.O. CONTACT
HELD CLOSED
RED
BLK
BLU
ORG
CAUTION: DO NOT USE LOOPED WIRE UNDER TERMINALS L1, L2, +, AND -.
BREAK WIRE RUN TO PROVIDE SUPERVISION OF CONNECTIONS.
FIG. 6: TYPICAL CLASS B, STYLE B CIRCUIT WIRING FOR MB-SDRT-CV SOUNDER BASE
IDC
L1
IN
L1
OUT
L1
IN
UL/ULC LISTED
COMPATIBLE
FIRE ALARM
CONTROL PANEL
SUPERVISED BY
EOL RELAY/FACP
L2
-R
L1
OUT
NEG POS
L2
-R
NEG POS
-
+
-
+
TO PANEL DCC/EARTH/GROUND
NOT SUPERVISED
*
UL/ULC LISTED 24V
EOL PAM-4 RELAY
(NOT INCLUDED)
OPTIONAL REMOTE
LED ANNUNCIATOR
UL/ULC LISTED
24VDC
POWER SUPPLY
+
-
SUPERVISED
BY FIRE ALARM
CONTROL PANEL
*
N.O. CONTACT
HELD CLOSED
RED
BLK
BLU
ORG
FIG. 7: TYPICAL CLASS A, STYLE D CIRCUIT WIRING FOR MB-SDRT-CV SOUNDER BASE
IDC
L1
IN
L1
OUT
L1
IN
UL/ULC LISTED
COMPATIBLE
FIRE ALARM
CONTROL PANEL
SUPERVISED BY
EOL RELAY/FACP
+
-
OUT
RETURN
Resistor
CAUTION: DO NOT USE LOOPED WIRE UNDER TERMINALS L1, L2, +, AND -.
BREAK WIRE RUN TO PROVIDE SUPERVISION OF CONNECTIONS.
ATTENTION: NE PAS UTILISER EN BOUCLE FIL TERMINAUX SOUS L1, L2, + ET -.
BREAK FIL RUN POUR ASSURER LA SURVEILLANCE DES CONNEXIONS.
ATTENTION: NE PAS UTILISER EN BOUCLE FIL TERMINAUX SOUS L1, L2, + ET -.
BREAK FIL RUN POUR ASSURER LA SURVEILLANCE DES CONNEXIONS.
ATTENTION: NE PAS UTILISER EN BOUCLE FIL TERMINAUX SOUS L1, L2, + ET -.
BREAK FIL RUN POUR ASSURER LA SURVEILLANCE DES CONNEXIONS.
24VDC
L2
-R
+R
L1
NEG POS
xxx
ALIGNMENT MARK
EXTERNAL
24VDC SUPPLY
(UL LISTED)
+
-
ADDRESS
LABEL
SPACE
JP1
VOL.
HIGH
/LOW
JP2
TEMP
3 OR
CONT
24VDC
L2
-R
L1
IN
L1
OUT
NEG POS
ALIGNMENT MARK
EXTERNAL
24VDC SUPPLY
(UL LISTED)
+
-
JP1
VOL.
HIGH
/LOW
JP2
TEMP
3 OR
CONT
NEG POS NEG POS
NORMAL OPERATION TEST /FORCED FUNCTION
External 24VDC
Connections
External 24VDC
Connections
L2
-R
+R
L1
NEG POS
L2
-R
+R
L1
NEG POS
-
+
-
+
TO PANEL DCC/EARTH/GROUND
NOT SUPERVISED
*
UL/ULC LISTED 24V
EOL PAM-4 RELAY
(NOT INCLUDED)
OPTIONAL REMOTE
LED ANNUNCIATOR
UL/ULC LISTED
24VDC
POWER SUPPLY
UL/ULC LISTED
COMPATIBLE
FIRE ALARM
CONTROL PANEL
+
-
SUPERVISED
BY FIRE ALARM
CONTROL PANEL
SUPERVISED BY
EOL RELAY/FACP
*
N.O. CONTACT
HELD CLOSED
TO FIRE ALARM
CONTROL PANEL IDC
OR A/A MONITOR
INPUT MODULE
RED
BLK
BLU
ORG
EOL
End of Line
Resistor
IF REQUIRED:
TO NEXT 2-WIRE
A/A DEVICE (OR
BACK TO FACP
SLC FOR STYLE
"6" OR "7" / CLASS
"A" CIRCUIT)
CAUTION: DO NOT USE LOOPED WIRE UNDER TERMINALS L1, L2, +, AND -.
BREAK WIRE RUN TO PROVIDE SUPERVISION OF CONNECTIONS.
FIG. 8: TYPICAL CLASS B/A, STYLE 4/6 CIRCUIT WIRING FOR MB-SDRT-AA SOUNDER BASE
SLC
L2
-R
L1
OUT
NEG POS
L2
-R
NEG POS
-
+
-
+
TO PANEL DCC/EARTH/GROUND
NOT SUPERVISED
*
UL/ULC LISTED 24V
EOL PAM-4 RELAY
(NOT INCLUDED)
OPTIONAL REMOTE
LED ANNUNCIATOR
UL/ULC LISTED
24VDC
POWER SUPPLY
+
-
SUPERVISED
BY FIRE ALARM
CONTROL PANEL
*
N.O. CONTACT
HELD CLOSED
RED
BLK
BLU
ORG
CAUTION: DO NOT USE LOOPED WIRE UNDER TERMINALS L1, L2, +, AND -.
BREAK WIRE RUN TO PROVIDE SUPERVISION OF CONNECTIONS.
FIG. 6: TYPICAL CLASS B, STYLE B CIRCUIT WIRING FOR MB-SDRT-CV SOUNDER BASE
IDC
L1
IN
L1
OUT
L1
IN
UL/ULC LISTED
COMPATIBLE
FIRE ALARM
CONTROL PANEL
SUPERVISED BY
EOL RELAY/FACP
L2
-R
L1
OUT
NEG POS
L2
-R
NEG POS
-
+
-
+
TO PANEL DCC/EARTH/GROUND
NOT SUPERVISED
*
UL/ULC LISTED 24V
EOL PAM-4 RELAY
(NOT INCLUDED)
OPTIONAL REMOTE
LED ANNUNCIATOR
UL/ULC LISTED
24VDC
POWER SUPPLY
+
-
SUPERVISED
BY FIRE ALARM
CONTROL PANEL
*
N.O. CONTACT
HELD CLOSED
RED
BLK
BLU
ORG
FIG. 7: TYPICAL CLASS A, STYLE D CIRCUIT WIRING FOR MB-SDRT-CV SOUNDER BASE
IDC
L1
IN
L1
OUT
L1
IN
UL/ULC LISTED
COMPATIBLE
FIRE ALARM
CONTROL PANEL
SUPERVISED BY
EOL RELAY/FACP
+
-
OUT
RETURN
Resistor
CAUTION: DO NOT USE LOOPED WIRE UNDER TERMINALS L1, L2, +, AND -.
BREAK WIRE RUN TO PROVIDE SUPERVISION OF CONNECTIONS.
ATTENTION: NE PAS UTILISER EN BOUCLE FIL TERMINAUX SOUS L1, L2, + ET -.
BREAK FIL RUN POUR ASSURER LA SURVEILLANCE DES CONNEXIONS.
ATTENTION: NE PAS UTILISER EN BOUCLE FIL TERMINAUX SOUS L1, L2, + ET -.
BREAK FIL RUN POUR ASSURER LA SURVEILLANCE DES CONNEXIONS.
ATTENTION: NE PAS UTILISER EN BOUCLE FIL TERMINAUX SOUS L1, L2, + ET -.
BREAK FIL RUN POUR ASSURER LA SURVEILLANCE DES CONNEXIONS.
24VDC
L2
-R
+R
L1
NEG POS
xxx
ALIGNMENT MARK
EXTERNAL
24VDC SUPPLY
(UL LISTED)
+
-
ADDRESS
LABEL
SPACE
JP1
VOL.
HIGH
/LOW
JP2
TEMP
3 OR
CONT
24VDC
L2
-R
L1
IN
L1
OUT
NEG POS
ALIGNMENT MARK
EXTERNAL
24VDC SUPPLY
(UL LISTED)
+
-
JP1
VOL.
HIGH
/LOW
JP2
TEMP
3 OR
CONT
NEG POS NEG POS
NORMAL OPERATION TEST /FORCED FUNCTION
External 24VDC
Connections
External 24VDC
Connections
L2
-R
+R
L1
NEG POS
L2
-R
+R
L1
NEG POS
-
+
-
+
TO PANEL DCC/EARTH/GROUND
NOT SUPERVISED *
UL/ULC LISTED 24V
EOL PAM-4 RELAY
(NOT INCLUDED)
OPTIONAL REMOTE
LED ANNUNCIATOR
UL/ULC LISTED
24VDC
POWER SUPPLY
UL/ULC LISTED
COMPATIBLE
FIRE ALARM
CONTROL PANEL
+
-
SUPERVISED
BY FIRE ALARM
CONTROL PANEL
SUPERVISED BY
EOL RELAY/FACP
*
N.O. CONTACT
HELD CLOSED
TO FIRE ALARM
CONTROL PANEL IDC
OR A/A MONITOR
INPUT MODULE
RED
BLK
BLU
ORG
EOL
End of Line
Resistor
IF REQUIRED:
TO NEXT 2-WIRE
A/A DEVICE (OR
BACK TO FACP
SLC FOR STYLE
"6" OR "7" / CLASS
"A" CIRCUIT)
CAUTION: DO NOT USE LOOPED WIRE UNDER TERMINALS L1, L2, +, AND -.
BREAK WIRE RUN TO PROVIDE SUPERVISION OF CONNECTIONS.
FIG. 8: TYPICAL CLASS B/A, STYLE 4/6 CIRCUIT WIRING FOR MB-SDRT-AA SOUNDER BASE
SLC
L2
-R
L1
OUT
NEG POS
L2
-R
NEG POS
-
+
-
+
TO PANEL DCC/EARTH/GROUND
NOT SUPERVISED
*
UL/ULC LISTED 24V
EOL PAM-4 RELAY
(NOT INCLUDED)
OPTIONAL REMOTE
LED ANNUNCIATOR
UL/ULC LISTED
24VDC
POWER SUPPLY
+
-
SUPERVISED
BY FIRE ALARM
CONTROL PANEL
*
N.O. CONTACT
HELD CLOSED
RED
BLK
BLU
ORG
CAUTION: DO NOT USE LOOPED WIRE UNDER TERMINALS L1, L2, +, AND -.
BREAK WIRE RUN TO PROVIDE SUPERVISION OF CONNECTIONS.
FIG. 6: TYPICAL CLASS B, STYLE B CIRCUIT WIRING FOR MB-SDRT-CV SOUNDER BASE
IDC
L1
IN
L1
OUT
L1
IN
UL/ULC LISTED
COMPATIBLE
FIRE ALARM
CONTROL PANEL
SUPERVISED BY
EOL RELAY/FACP
L2
-R
L1
OUT
NEG POS
L2
-R
NEG POS
-
+
-
+
TO PANEL DCC/EARTH/GROUND
NOT SUPERVISED
*
UL/ULC LISTED 24V
EOL PAM-4 RELAY
(NOT INCLUDED)
OPTIONAL REMOTE
LED ANNUNCIATOR
UL/ULC LISTED
24VDC
POWER SUPPLY
+
-
SUPERVISED
BY FIRE ALARM
CONTROL PANEL
*
N.O. CONTACT
HELD CLOSED
RED
BLK
BLU
ORG
FIG. 7: TYPICAL CLASS A, STYLE D CIRCUIT WIRING FOR MB-SDRT-CV SOUNDER BASE
IDC
L1
IN
L1
OUT
L1
IN
UL/ULC LISTED
COMPATIBLE
FIRE ALARM
CONTROL PANEL
SUPERVISED BY
EOL RELAY/FACP
+
-
OUT
RETURN
Resistor
CAUTION: DO NOT USE LOOPED WIRE UNDER TERMINALS L1, L2, +, AND -.
BREAK WIRE RUN TO PROVIDE SUPERVISION OF CONNECTIONS.
ATTENTION: NE PAS UTILISER EN BOUCLE FIL TERMINAUX SOUS L1, L2, + ET -.
BREAK FIL RUN POUR ASSURER LA SURVEILLANCE DES CONNEXIONS.
ATTENTION: NE PAS UTILISER EN BOUCLE FIL TERMINAUX SOUS L1, L2, + ET -.
BREAK FIL RUN POUR ASSURER LA SURVEILLANCE DES CONNEXIONS.
ATTENTION: NE PAS UTILISER EN BOUCLE FIL TERMINAUX SOUS L1, L2, + ET -.
BREAK FIL RUN POUR ASSURER LA SURVEILLANCE DES CONNEXIONS.

© Air Products and Controls Inc. 2009 Page 5 INST APD0281 D090201
TYPICAL SYNCHRONIZED CIRCUIT WIRING DIAGRAM
TO FACP IDC
OR
SLC VIA A/A
MONITOR INPUT
MODULE
TROUBLE MONITORING
FACP
NAC
GENERAL ALARM
(ACTIVATE
REQUEST CIRCUIT)
STEADY OR PULSED
FACP
NAC
SILENCEABLE
(SILENCE REQUEST)
STEADY OR PULSED
FACP
NAC
SILENCEABLE
GENERAL ALARM
STEADY OR PULSED
EOL EOL EOL
SUPERVISED
SUPERVISED
SUPERVISED
SUPERVISED
EOL
OR
JP1
JP1
JP1
JP1
JP2
JP2
JP2
MB-SDRT-SM
SYNCHRONIZATION
MODULE
(PROGRAMMED AS “MAIN”)
( ) = POLARITY IN ALARM
UL LISTED
POWER SUPPLY
SOUNDER BASE
MB-SDRT-AA
OR MB-SDRT-CV
SOUNDER BASE
MB-SDRT-AA
OR MB-SDRT-CV
ON HIGH DB ON TEMP 3
OFF LOW DB OFF STEADY
ON HIGH DB ON TEMP 3
OFF LOW DB OFF STEADY
ON HIGH DB ON TEMP 3
OFF LOW DB OFF STEADY
SOUNDER BASE
MB-SDRT-AA
OR MB-SDRT-CV
NEG POS
NEG POS
NEG POS
POS NEG
TO END OF LINE
SUPERVISORY RELAY
MR-RIC-300 OR RIC-3
OR
ADDITIONAL
MB-SDRT-SM MODULE(S)
PROGRAMMED AS
“SECONDARY” OR
“SYNC ONLY”
AB
SEE PAGE 6
LINE LOAD
STABILITY RESISTOR
1.8K 1 WATT
(PACKED WITH EACH
MB-SDRT-SM)
NOTE: MAXIMUM SYNC OUT
CIRCUIT WIRE SPECIFICATIONS PER
MB-SDRT-SM:
REMARQUE: LES SPÉCIFICATIONS
MAXIMUM SYNC CIRCUIT DE CÂBLES
PAR MB-PDT-SM:
• MAX RESISTANCE = 40 OHMS
TOTAL (20 OHMS “+” OUT AND
20 OHMS “–” BACK)
• MAX CAPACITANCE = 2µF
• VOLTAGE DROP FROM NOMINAL
24VDC AT END OF 60 MB-SDRT
SOUNDER BASES ≤3.6VDC

© Air Products and Controls Inc. 2009 Page 6 INST APD0281 D090201
TYPICAL SYNCHRONIZED CIRCUIT WIRING DIAGRAM (CONTINUED)
TO FACP IDC
OR
SLC VIA A/A
MONITOR INPUT
MODULE
TROUBLE MONITORING
A
B
EOL
SUPERVISED
SUPERVISED
SUPERVISED
NC C NO
24+/AC –/NCN
MR-RIC-300
RIC-3
OR
AB
SUPERVISED
RED WHITE
BLUE
ORANGE
YELLOW
TO FACP IDC
OR
SLC VIA A/A
MONITOR INPUT
MODULE
TROUBLE MONITORING
If at last MB-SDRT-SM module:
If adding MB-SDRT-SM module(s):
SECONDARY
SYNC ONLY
Off-Main
TO FACP IDC
OR
SLC VIA A/A
MONITOR INPUT
MODULE
TROUBLE MONITORING
AB
EOL
SUPERVISED
JP1
SUPERVISED
SECONDARY
SYNC ONLY
Off-Main
TO FACP IDC
OR
SLC VIA A/A
MONITOR INPUT
MODULE
TROUBLE MONITORING
AB
JP1
EOL
SUPERVISED
SUPERVISED
MB-SDRT-SM
SYNCHRONIZATION MODULE
(PROGRAMMED AS “SECONDARY”)
MB-SDRT-SM
SYNCHRONIZATION MODULE
(PROGRAMMED AS “SYNC ONLY”)
OR
SEE PAGE 5
SEE PAGE 5
SEE PAGE 5
SEE PAGE 5

© Air Products and Controls Inc. 2009 Page 7 INST APD0281 D090201
TYPICAL SYSTEM OVERVIEW DIAGRAM (CLASS B, STYLE B/4)
Alarm 1
SLC/IDC
General Alarm 1
NAC
SIL 1
NAC Power Supply 1 Supervisory 1
SLC/IDC
General Alarm 2
NAC
SIL 2
NAC
Power Supply 2
Power Supply 3 or
2,1
Power Supply 4 or
3 if above used 2,1
IF IDC EOL
RIC-3 or
MR-RIC-300 IF IDC EOL
Main
SLC INPUT
MODULE
SUPERVISORY
EOL
SECONDARY
SYNC ONLY
SECONDARY
NAC EOL
JP1
JP1
SLC INPUT
MODULE
SUPERVISORY
EOL
NAC EOL
NAC EOL
SLC INPUT
MODULE
SUPERVISORY
EOL
SLC INPUT
MODULE
SUPERVISORY
EOL
JP1
JP1
SUB-GROUP GROUP
WHY: Start of major
group where GA/SIL
control is needed and
sync for group and any
subsequent sub-groups.
Always “start” with.
WHY: Add independent
GA/SIL control plus
power but keep overall
sync.
WHY: Add power plus
will follow above GA/SIL
control and sync.
NOTE: All wiring is supervised and wiring faults are indicated on the supervisory SLC/IDC as appropriate.
REMARQUE: Tout le câblage est supervisée et les erreurs de câblage sont indiquées sur la surveillance SLC / IDC, le cas échéant.
UL Listed, Compatible FACP
**
*
*
*
*
*
*
X
X X
X X
X = Not Used
WHY: Add
power plus will
follow above
GA/SIL control
and sync.
detector
detector
detector
detector
m
b
-
s
d
r
-
a
a
/
c
v
m
b
-
s
d
r
-
a
a
/
c
v
m
b
-
s
d
r
-
a
a
/
c
v
m
b
-
s
d
r
-
a
a
/
c
v
LLSR
LLSR
LLSR
LLSR

© Air Products and Controls Inc. 2009 Page 8 INST APD0281 D090201
MULTI-FLEX
BASE COMPATIBLE SMOKE DETECTOR SPECIFICATIONS
DISCOVERY
Detector Head Part Number 58000-550 58000-650 58000-450 58000-750
Detector Type Ionization Photoelectric Heat Multi-Sensor (Photo/Heat)
Detector Alarm Current
LED Illuminated 3.5mA 3.4mA 3.4mA 3.5mA
Detector Standby
Current
500µA average;
750µA peak
400µA average;
650µA peak
500µA average;
750µA peak
500µA average;
750µA peak
Detector Test Procedure Aerosol Test Gas TG-1000 or Gemini #501 Heat Gun Heat Gun, Aerosol Test Gas
or Gemini #501
Environmental 32°F to 100°F (0°C to 38°C)
0% to 85% RH; Non-Condensing / Non-Freezing
Employs integral 135°
rated heat sensor
Control Panel See control panel SLC wiring card for compatibility indentier and maximum number of detectors per SLC.
Contact Air Products and Controls Inc. for a list of compatible re alarm control panels.
XP95A
Detector Head Part Number 55000-550 55000-650 55000-450 55000-886
Detector Type Ionization Photoelectric Heat Multi-Sensor (Photo/Heat)
Detector Alarm Current
LED Illuminated 2mA 4mA 2mA 4mA
Detector Standby
Current
280µA average;
500µA peak
340µA average;
600µA peak
250µA average;
500µA peak
500µA average;
750µA peak
Detector Test Procedure Aerosol Test Gas TG-1000 or Gemini #501 Heat Gun Heat Gun, Aerosol Test Gas
or Gemini #501
Environmental 32°F to 100°F (0°C to 38°C)
0% to 85% RH; Non-Condensing / Non-Freezing
Employs integral 135°
rated heat sensor
Control Panel See control panel SLC wiring card for compatibility indentier and maximum number of detectors per SLC.
Contact Air Products and Controls Inc. for a list of compatible re alarm control panels.
SERIES 65A
Detector Head Part Number 55000-225 55000-325
55000-138
55000-141
55000-142
Detector Type Ionization Photoelectric Heat
Detector Operating Volt-
age 9-33VDC
Detector Average
Alarm Current 17mA @ 9VDC; 52mA @ 24VDC
Detector Average
Standby Current
50µA @ 9VDC;
55µA 24VDC
40µA @ 9VDC;
45µA 24VDC
50µA @ 9VDC;
55µA 24VDC
Detector Test Procedure Aerosol Test Gas TG-1000 or Gemini #501 Heat Gun
Environmental 32°F to 100°F (0°C to 38°C)
0% to 85% RH; Non-Condensing / Non-Freezing
Control Panel
See control panel’s IDC (zone) wiring card for compatibility indentier and maximum number of detectors per IDC.
Contact Air Products and Controls Inc. for a list of compatible re alarm control panels.
Note that most FACP’s will only guarantee a singe 2-wire detector in alarm simultaneously on a single IDC.
SERIES 60A
Detector Head Part Number 55000-250 55000-350
55000-150
55000-151
55000-152
55000-153
55000-380
Detector Type Ionization Photoelectric Heat Multi-Sensor (Photo/Heat)
Detector Operating Volt-
age 9-33VDC 16-34VDC
Detector Average
Alarm Current 17mA @ 9VDC; 52mA @ 24VDC 100mA @ 24VDC
Detector Average
Standby Current
50µA @ 9VDC;
55µA 24VDC
40µA @ 9VDC;
45µA 24VDC
50µA @ 9VDC;
55µA 24VDC 185µA @ 24VDC
Detector Test Procedure Aerosol Test Gas TG-1000 or Gemini #501 Heat Gun Heat Gun, Aerosol Test Gas
or Gemini #501
Environmental 32°F to 100°F (0°C to 38°C)
0% to 85% RH; Non-Condensing / Non-Freezing
Control Panel
See control panel’s IDC (zone) wiring card for compatibility indentier and maximum number of detectors per IDC.
Contact Air Products and Controls Inc. for a list of compatible re alarm control panels.
Note that most FACP’s will only guarantee a singe 2-wire detector in alarm simultaneously on a single IDC.
NOTICE:
The information contained in this document is the most current available at the time of shipment of accompanying product, and is subject to change without notice. Future references should always be made to the most current revision
of this document. The information contained in all this document should be considered before installing or using the product. Any example applications shown are subject to the most current enforced local/national codes, standards, approv-
als, certications, and/or the authority having jurisdiction. All of these resources, as well as the specic manufacturer of any shown or mentioned related equipment, should be consulted prior to any implementation. For further information or
assistance concerning this product, contact Air Products and Controls Inc. Air Products and Controls Inc. reserves the right to change any and all documentation without notice.

© Air Products and Controls Inc. 2009 Page 9 INST APD0281 D090201
MULTI-FLEX
SOUNDER BASE SPECIFICATIONS
Sounder Base
Part Number MB-SDRT-AA MB-SDRT-CV
Firmware Code SFT0002, revA060118
Compatible Smoke Detectors Analog Addressable (Discovery or XP95A) Conventional (Series 65 or Series 60A)
Sounder Base Operating Voltage 17-30VDC (24VDC nominal)
Sounder Base Alarm Currents External Supply: 17mA @ 24VDC : Associated Detector: 8mA @ 24VDC
Sounder Base Standby Current 0.15µA @ 24VDC
Sounder Base Audible Intensity High Volume Selection: 85dB @ 10 feet : Low Volume Selection: 75dB @ 10 feet
Wiring Solid or Stranded; #12 to #22 AWG Terminals
Environmental 32°F to 100°F (0°C to 38°C) • 0% to 85% RH; Non-Condensing / Non-Freezing
Material Makrolon 6455 or 6555; 94V-0
Dimensions 6” L x 6”W x 1.6” D (152mm x 152mm x 41mm)
Approvals UL Listed File #S2829 • CSFM Listed (7300-1004:117) • MEA Acceptance (73-93-E Vol. 38)
MULTI-FLEX
SYNCHRONIZATION MODULE SPECIFICATIONS
SSM Module
Part Number MB-SDRT-SM/G MB-SDRT-SM/G/R MB-SDRT-SM/T MB-SDRT-SM/C MB-SDRT-SM/C/R
Firmware Code SFT0001 revA060629
Two-Gang Box
Mounted (H x W x D)
3.3” (83.82mm)
2.6” (66.04mm)
0.77” (19.56mm)
Track Mounted
(H x W x D)
3.4" (87mm)
2.75" (69.85mm)
1.22" (30.99mm)
Enclosure Mounted
(H x W x D) 5.13” (131mm) x 3.13” (80mm) x 2.5” (64mm)
Cover Material White ABS Plas-
tic; 94V-0
Red ABS Plastic;
94V-0
Gray ABS Plastic;
94V-0 Red ABS Plastic; 94V-0
Enclosure / Mounting Details Metal 2-Gang Mounting Chassis with
Appropriate Wall Plate Cover
Low-Prole
Snap-Track with
Provided Mount-
ing Screws
18Ga. CRS, Plated with ½” Conduit Knockouts,
Top and Bottom
Operating Voltage Range
and Current Requirements
Power Input Circuit, 17-30VDC: 17mA Standby; 16mA Alarm (MB-SDRT-SM Sync Module Only)
MB-SDRT-SM with Sounder and Relay Bases: ≤ 2A Max. (61 units max.)
Sync Out Circuit, 17-30VDC: 4mA Standby; 15mA Alarm
MB-SDRT-SM with Sounder and Relay Bases: ≤ 2A Max. (61 units max.)
Sync In Circuit, 17-30VDC: 4mA Standby; 15mA Alarm
Horn Enable/General Alarm NAC Circuit, 16-33VDC:
7.5mA Standby; 2mA Alarm
Input / Output Details
TROUBLE: Always FACP monitored and reported as trouble or supervisory in all program modes. Dry N.O.
contact held closed by the POWER 24VDC input being present and the internal module circuitry being fully
operational. Also supervises the presence of a SYNC IN signal when module is programmed in the “secondary”
or “sync only” modes. It is not used when the module is programmed in the “main” mode.
GENERAL ALARM: 24VDC steady or pulsed, silenceable or non, polarized FACP NAC Input. This input is used
only when the module is programmed in the “main” or “sync only” modes. When the connected NAC is in the
alarm state the module will provide a general alarm signal to all associated sounder/relay bases, causing them
to sound if a HORN ENABLE alarm input is also present.
HORN ENABLE: 24VDC steady or pulsed, silenceable polarized FACP NAC input. This input is used only when
the module is programmed in the “main” or “sync only” modes. When the connected NAC is in the alarm state
the module will be active and ready to accept a GENERAL ALARM input. The status of the connected NAC will
also be monitored for subsequently being silenced from the FACP and will provide that signal to all associated
sounder bases, causing them to silence. Subsequent alarms will resound as signalled from the FACP NAC con-
nected to this input.
SYNC IN: 24VDC/protocol feed input from associated module programmed in the “main”, “secondary” or “sync
only” mode. This input is always used when the module is programmed in the “secondary” or “sync only” modes.
It is not used when the module is programmed in the “main” mode.
SYNC OUT: 24VDC/protocol feed output from module in all modes. When the module is programmed in the
“main” or “sync only” modes, also provides distinct HORN ENABLE and GENERAL ALARM status information to all
associated sounder/relay bases and any modules programmed as “secondary”. Included line load stability resistor
must be installed.
POWER 24VDC: 24VDC power feed in, always required in all modes (to boost power available to bases due
to long wire runs and possibly the need to increase Db output). When the module is programmed in the “sync
only” mode this input could be from a shared power supply with the associated “main” programmed module.
When the module is programmed in the “secondary” mode this input will always be supplied from a new ad-
ditional power source since that is the only reason it is being installed.
Intelligent Trouble
Reporting
Trouble LED: ON - Test Mode SINGLE BLINK - Sync In (when in “main” mode)
DOUBLE BLINK - No Sync In (when in “secondary” mode) TRIPLE BLINK - Output Short
Wiring Solid or Stranded; #12 to #22 AWG Terminals
Environmental 32°F to 100°F (0°C to 38°C) • 0% to 85% RH; Non-Condensing / Non-Freezing
Approvals UL Listed File #S9055 • CSFM Listed (7300-1004:117) • MEA Acceptance (73-93-E Vol. 38)

© Air Products and Controls Inc. 2009 Page 10 INST APD0281 D090201
MB-SDRT-AA Analog Addressable Detector Sounder Base
MB-SDRT-CV Conventional Detector Sounder Base
MB-SDRT-SM Synchronization Module
You in Control
AND
AIR PRODUCTS
CONTR
OLS MULTI-FLEX FAMILY
SOUNDER BASES AND
SYNCHRONIZATION
MODULES
INSTALLATION AND MAINTENANCE
INSTRUCTIONS
NOTICE: The information contained in this document is the most current available at the time of shipment of accompanying product,
and is subject to change without notice. Future references should always be made to the most current revision of this document. The
information contained in all this document should be considered before installing or using the product.Any example applications shown
are subject to the most current enforced local/national codes, standards, approvals, certications, and/or the authority having jurisdic-
tion. All of these resources, as well as the specic manufacturer of any shown or mentioned related equipment, should be consulted
prior to any implementation. For further information or assistance concerning this product, contact Air Products and Controls Inc.
Air Products and Controls Inc. reserves the right to change any and all documentation without notice.
© Air Products and Controls Inc. 2006
A COPY OF THESE INSTRUCTIONS SHOULD BE LEFT WITH THE EQUIPMENT UNTIL
INSTALLATION BY ALL TRADES IS FULLY COMPLETE. FOLLOWING FINAL INSPECTION,
A COPY SHOULD BE LEFT WITHTHE OWNER/USER.
FOR TECHNICAL SUPPORT CALL TOLL FREE 888-332-2241 OR 248-332-3900
You in Control
AND
AIR PRODUCTS
CONTROLS
AIR PRODUCTS AND CONTROLS INC.
25 Corporate Dr. • Auburn Hills, MI 48326 USA
Telephone: (248) 332-3900 • www.ap-c.com
Technical Support: (888) 332-2241
AVAILABLE ACCESSORIES FOR USE WITH
MULTI-FLEX® FAMILY SOUNDER BASES & SYNC MODULES
SMOKE TEST GAS
TG-1000 Solo Aerosol Test Gas with Spray Nozzle
REPLACEMENT SMOKE DETECTOR HEADS
55000-250 S60 Ionization Detector Replacement Head
55000-350 S60 Photoelectric Detector Replacement Head
55000-150 S60 Heat Detector Replacement Head
55000-151 S60 Heat Detector Replacement Head
55000-152 S60 Heat Detector Replacement Head
55000-153 S60 Heat Detector Replacement Head
55000-380 S60 Multi-Sensor (Photo/Heat) Replacement Head
55000-225 S65 Ionization Detector Replacement Head
55000-325 S65 Photoelectric Detector Replacement Head
55000-138 S65 Heat Detector Replacement Head
55000-141 S65 Heat Detector Replacement Head
55000-142 S65 Heat Detector Replacement Head
55000-550 XP95A Ionization Detector Replacement Head
55000-650 XP95A Photoelectric Detector Replacement Head
55000-450 XP95A Heat Detector Replacement Head
55000-886 XP95A Multi-Sensor (Photo/Heat) Replacement Head
58000-550 DISC Ionization Detector Replacement Head
58000-650 DISC Photoelectric Detector Replacement Head
58000-450 DISC Heat Detector Replacement Head
58000-750 DISC Multi-Sensor (Photo/Heat) Replacement Head
Distributed By:
FEATURES
❖Compatible with panel silence functions
❖ Sync network “self tests” to ensure synchronized
output if “upstream” sync signal is lost
❖Sounders will operate in “failsafe” mode if sync
network is compromised
MULTI-FLEX FAMILY
SOUNDER BASES AND
SYNCHRONIZATION MODULE
PRODUCT DESCRIPTION
The Multi-Flex family of smoke detector sounder bases and
synchronization modules provide today’s most advanced functionality
and performance, delivering flexible notification capabilities for Apollo
conventional and analog addressable systems.
The bases offer selectable steady or temporal pattern output and
selectable high or low volume levels. The three-pulse temporal pattern
is required by NFPA 72 for fire alarm evacuation for commercial and
residential applications.
Available synchronization modules (SM)
allow temporal pattern sounder base
circuits to be completely synchronized
and installed in almost limitless
configurations, and also provide an on-
board latching test function.
The sounder base requires an external 24VDC power supply. In the absence of a
synchronization module, a means for polarity reversal is required for test and gerneral
alarm functionality. The connections for the external power supply and the communication
loop are opto-isolated to prevent electrical interaction between them.
Air Products and Controls Inc.
1749 E. Highwood
Pontiac, MI 48340
(248) 332-3900 Phone
(888) 332-2241 Toll free
(248) 332-8807 Fax
www.ap-c.com
You in Control
AND
AIR PRODUCTS
CONTROLS
PRODUCT SPECIFICATIONS
MULTI-FLEX
SOUNDER BASE SPECIFICATIONS
Sounder Base
Part Number MB-SDRT-AA MB-SDRT-CV
Compatible
Smoke Detectors
Analog Addressable
(Discovery or XP95A)
Conventional
(Series 65 or Series 60A)
Sounder Base
Operating Voltage 17-30VDC (24VDC nominal)
Sounder Base
Alarm Currents
External Supply: 29mA @ 24VDC
Associated Detector: 8mA @ 24VDC
Sounder Base
Standby Current 0.03mA @ 24VDC
Sounder Base
Audible Intensity
High Volume Selection: 85dB @ 10 feet
Low Volume Selection: 75dB @ 10 feet
Wiring Solid or Stranded; #12 to #22 AWG Terminals
Environmental 32°F to 100°F (0°C to 38°C)
0% to 85% RH; Non-Condensing / Non-Freezing
Material Makrolon 6455 or 6555 (polycarbonate); 94V-0
Dimensions 6” L x 6”W x 1.6” D (152mm x 152mm x 41mm)
Approvals UL Listed File Pending • CSFM Pending • MEA Pending
❖ Sync modules available in MR-1 enclosures, snap track or
chassis mount for standard 2-gang box
❖ Intelligent trouble reporting via on-board Trouble LED
Distributed By:
FEATURES
❖Compatible with panel silence functions
❖ Sync network “self tests” to ensure synchronized
output if “upstream” sync signal is lost
❖Sounders will operate in “failsafe” mode if sync
network is compromised
MULTI-FLEX FAMILY
SOUNDER BASES AND
SYNCHRONIZATION MODULE
PRODUCT DESCRIPTION
The Multi-Flex family of smoke detector sounder bases and
synchronization modules provide today’s most advanced functionality
and performance, delivering flexible notification capabilities for Apollo
conventional and analog addressable systems.
The bases offer selectable steady or temporal pattern output and
selectable high or low volume levels. The three-pulse temporal pattern
is required by NFPA 72 for fire alarm evacuation for commercial and
residential applications.
Available synchronization modules (SM)
allow temporal pattern sounder base
circuits to be completely synchronized
and installed in almost limitless
configurations, and also provide an on-
board latching test function.
The sounder base requires an external 24VDC power supply. In the absence of a
synchronization module, a means for polarity reversal is required for test and gerneral
alarm functionality. The connections for the external power supply and the communication
loop are opto-isolated to prevent electrical interaction between them.
Air Products and Controls Inc.
1749 E. Highwood
Pontiac, MI 48340
(248) 332-3900 Phone
(888) 332-2241 Toll free
(248) 332-8807 Fax
www.ap-c.com
You in Control
AND
AIR PRODUCTS
CONTROLS
PRODUCT SPECIFICATIONS
MULTI-FLEX
SOUNDER BASE SPECIFICATIONS
Sounder Base
Part Number MB-SDRT-AA MB-SDRT-CV
Compatible
Smoke Detectors
Analog Addressable
(Discovery or XP95A)
Conventional
(Series 65 or Series 60A)
Sounder Base
Operating Voltage 17-30VDC (24VDC nominal)
Sounder Base
Alarm Currents
External Supply: 29mA @ 24VDC
Associated Detector: 8mA @ 24VDC
Sounder Base
Standby Current 0.03mA @ 24VDC
Sounder Base
Audible Intensity
High Volume Selection: 85dB @ 10 feet
Low Volume Selection: 75dB @ 10 feet
Wiring Solid or Stranded; #12 to #22 AWG Terminals
Environmental 32°F to 100°F (0°C to 38°C)
0% to 85% RH; Non-Condensing / Non-Freezing
Material Makrolon 6455 or 6555 (polycarbonate); 94V-0
Dimensions 6” L x 6”W x 1.6” D (152mm x 152mm x 41mm)
Approvals UL Listed File Pending • CSFM Pending • MEA Pending
❖ Sync modules available in MR-1 enclosures, snap track or
chassis mount for standard 2-gang box
❖ Intelligent trouble reporting via on-board Trouble LED
This manual suits for next models
3
Table of contents
Other Air Products & Controls Smoke Alarm manuals
Popular Smoke Alarm manuals by other brands

KALO
KALO PRIMUS i quick start guide

brennenstuhl
brennenstuhl BR 1201 operating instructions

Ei Electronics
Ei Electronics Ei 105C Optical User instructions

Global Fire Equipment
Global Fire Equipment GFE-AD Series Installation Wiring Diagram

Elko
Elko iNELS Air AirSD-100L quick start guide

FIBARO
FIBARO FIBEFGSD-002 quick start guide