Air Products & Controls SL-DA4R Series User manual

INST AP-330 D140113
1
You in Control
AND
AIR PRODUCTS
CONTROLS
SL-DA4R-N 4-Wire Analog Addressable, Ionization Type
SL-DA4R-P 4-Wire Analog Addressable, Photoelectric Type
AIR PRODUCTS AND CONTROLS INC.
SL-DA4R SERIES DUCT SMOKE DETECTORS
INSTALLATION AND MAINTENANCE INSTRUCTIONS
PRODUCT OVERVIEW
PRODUCT APPLICATION
SL-DA4R Series duct smoke detectors provide early detection of smoke and
products of combustion present in air moving through an HVAC duct supply,
return, or both in commercial, industrial, and residential applications. These
devices are designed to prevent the recirculation of smoke in areas by the air
handling system’s fans and blowers. Complete systems may be shut down in
the event of smoke detection, via the alarm relay contacts provided and/or the
building’s fire alarm control panel (FACP).
NOTE:For the correct installation of a duct smoke unit, please refer to
the NFPA 72 (National Fire Alarm Code), NFPA 90A (Standard for Installation of Air
Conditioning and Ventilation Systems), NFPA 92A (Recommended Practice for Smoke
Control Systems.), NFPA 5000 (Building Construction and Safety Code), IMC (International
Mechanical Code), and IFC (International Fire Code).
This detector requires a UL Listed compatible FACP as well as a separate power
supply (for 4-wire functionality) to operate properly. Refer to FACP documentation
to ensure compatiblity.
This detector is not intended for open area protection nor should it be used for
early warning detection or replace a regular fire detection system.
PRODUCT DESCRIPTION
The SL-DA4R Series smoke detector is fitted with a mounting base that
will accept an ionization smoke detector head Apollo model 55000-550 or
photoelectric smoke detector head Apollo model 55000-650. The detector
provides a cover removal switch, which supervises the removal of the
detector cover.
This detector is equipped with a cover removal switch that
instantly provides a trouble condition at the FACP upon removal of
the clear cover. For all testing and inspection with the cover removed,
the cover removal switch (designated as SW1 on PCB) must be
manually depressed to simulate normal standby operation.
The SL-DA4R Series duct detector will operate from a compatible FACP supplied
voltage/protocol source (nominally, 17-28VDC). The control board is additionally
supplied with a separate 24VDC or 24VAC power source for 4-wire functionality.
SAMPLING TUBES
The operating principle of a duct detector is based on the Venturi effect. Two
tubes extend into the HVAC duct. Air flowing through the duct is forced into
the air intake (inlet) tube via the air intake holes, (facing the airflow) and passes
over the detector head. The air will be drawn out via the exhaust tube back into
the HVAC duct. (A 7” exhaust tube is provided in the installation kit.) When the
concentration of smoke particles suspended in the air stream reach the alarm
threshold of the detector head, the unit will go into alarm.
The duct smoke detector units are designed to operate in duct widths from 6”
to 10’ wide with an air velocity between 100 to 4,000 feet per minute. To verify
correct installation, the pressure differential between the sampling (high side) and
exhaust (low side) tubes should be measured using a Magnehelic pressure gauge
or equivalent. An acceptable reading is between 0.01 and 1.2 inches of water.
To minimize the impact of air turbulence and stratification on performance,
a duct smoke detector should be located as far as possible downstream
from any obstruction (i.e. deflector plates, elbows, dampers, etc.). In
all situations, confirmation of velocity and pressure differential within
specifications is required.
REMOTE ACCESSORIES
Remote alarm indicators and remote test switches may be accommodated
by the SL-DA4R Series duct units by connecting to DC voltage output
terminals as described on Page 3.
DUCT PREPARATION
Remove mounting template from the installation kit. Remove paper
backing from the mounting template and affix it to the duct at the
desired location. Using the template as a guide, drill (2) mounting
holes, 3/32” (2.5mm) for the #12 X ½” sheet metal screws packaged
in the installation kit. Drill or punch (2) 1¼” (32mm) holes for inlet
sampling and exhaust tubes, using the template as a guide. Clean all
holes.
SL-DA4R AT-A-GLANCE
MODEL NUMBER:
SL-DA4R-N 4-Wire Analog Addressable
Ionization Duct Smoke Detector
SL-DA4R-P 4-Wire Analog Addressable
Photoelectric Duct Smoke Detector
DETECTOR HEAD MODEL NUMBER:
Ionization Detector Head: Apollo 55000-550
Photoelectric Detector Head: Apollo 55000-650
DETECTOR VOLTAGE REQUIREMENTS:
Operating Voltage Range: 17-28VDC (24VDC Nominal)
CONTROL BOARD CURRENT REQUIREMENTS:
Operating Voltage: 24VDC 24VAC
Standby Current: 26mA 105mA
Alarm Current: 54mA 195mA
GENERAL SPECIFICATIONS:
Air velocity: 100 to 4,000ft/min.
Ambient temperature:SL-DA4R-N: 32°F to 150°F (0°C to 66°C)
SL-DA4R-P: 32°F to 140°F (0°C to 60°C)
Humidity: 10% to 85% RH Non-Condensing/Non-Freezing
Material: Gray plastic back box with clear plastic cover
(Makrolon 94V-0)
Dimensions: 13½” L X 4½” W X 2¼” D
Max. net wt.: 2.25 lbs.
Radioactive element: SL-DA4R-N (Ionization) - Americium 241,
0.9 micro curie.
Do not expose to corrosive atmospheres.
U.S. Patents 6,741,181 and Patents Pending
!
!

INST AP-330 D140113
2
LOCATION PREREQUISITES
This guideline contains general information on duct smoke detector
installation, but does not preclude the NFPA and/or ICC documents
listed. Air Products and Controls assumes no responsibility for improperly
installed duct detectors. To determine the correct installation position
for an SL-DA4R Series duct smoke detector, the following factors must
be considered.
1. A uniform non-turbulent (laminar) airow between 100 ft/min. to
4,000 ft/min. must be present in the HVAC duct.To determine duct
velocities, examine the engineering specications that dene the
expected velocities or use an Alnor model 6000AP velocity meter
(or equivalent).
2. To minimize the impact of air turbulence and stratication on
performance, a duct smoke detector should be located as far as
possible downstream from any obstruction (i.e. deector plates,
elbows, dampers, etc.). In all situations, conrmation of velocity and
pressure differential within specications is required.
The pressure differential between the input sampling (high pressure)
tube and exhaust (low pressure) tube for the SL-DA4R Series smoke
duct detector should be greater than 0.01 inches of water and less
than 1.2 inches of water.
3. Identify a code compliant location (supply or return side, or both)
for the installation of the duct unit that will permit easy access for
viewing and serviceability.
4. When installing on the return side, install duct units prior to the air
being exhausted from the building or diluted with outside“fresh” air.
5. When installing duct smoke units downstream of lters, res
occurring in the lters will be detected, but if the lters become
blocked, insufcient air ow through the duct unit will prevent the
correct operation of the duct detector. Duct units installed in the
supply air side may monitor upstream equipment and/or lters.
6. Where possible, install duct detectors upstream of air humidiers
and downstream of dehumidiers.
7. To prevent false alarms, the duct detector should not be mounted
in areas of extreme high or low temperatures, in areas where high
humidity exists, or in areas where the duct may contain gases or
excessive dust.
SAMPLING TUBE ASSEMBLY
The SL-DA4R Series duct smoke detectors employ a specially notched
sampling tube, which may be ordered separately in one of four standard
lengths or packaged as FAST Tubes.
STN-1.0 For duct widths of 6” TO 1.0’
STN-2.5 For duct widths of 1.0’ TO 3.0’
STN-5.0 For duct widths of 3.0’ TO 5.0’
STN-10.0 For duct widths of 5.0’ TO 10.0‘
FAST Tubes Sectional tubes for duct widths up to 8.0’
Standard sampling tubes are steel tubes with air intake holes drilled
the entire length of the tube. FAST Tubes are a recognized plastic with
an open slot along the length. These tubes can be cut to length and
must span at least 80% of the duct width (spanning the entire width is
suggested). Sampling tubes over 3.0’ must be supported on the opposite
side of the duct. To ensure the correct operation of the sensing tube,
the red end cap (red stopper in installation kit) must be inserted in the
end of the air intake sampling tube. For custom duct widths, always use
the next longest standard size and cut down to the exact requirement.
MECHANICAL INSTALLATION
“NO-TOOLS” TUBE INSTALLATION
The SL-DA4R Series duct smoke detector provides a unique, patented
mechanism for installation and/or removal of the sampling and exhaust
tubes from either the front or rear of the detector housing.
Once the airflow direction has been determined, insert the inlet and
exhaust tubes into the duct smoke detector. If the cover is in place, the
tubes may be inserted into the back of the detector via the key-slots
provided. Simply push the tube into place against the spring loaded
retainer, and turn into the correct position, allowing the key to “lock”
the tube in the desired orientation. For front side installation, simply
rotate the tube retainer until the tube may be inserted and oriented
properly. Once the tube is installed, rotate the retainer back into place
to lock down the tube. Ensure air intake sampling tube is positioned so
that the inlet holes (or Fast Tube slot) are directly facing the airflow.
INLET TUBE
HOLES FACE
AIR FLOW
DUCT WIDTH AIR FLOW DIRECTION
INSERT RED STOPPER
THIS END OF INLET TUBE
EXHAUST TUBE INSTALLED
DOWNSTREAM OF AIRFLOW
DO NOT INSERT RED STOPPER
NOTE:Mountings shown
are typical. Detectors can
be installed side, bottom
or top of duct as long as
proper tube operation and
flow/pressure performance
is maintained
Tube Support Hole only for Ducts Greater than 3 Feet Wide
MOUNTING
After securing the sampling and exhaust tubes to the duct smoke unit,
(or initially placing the tubes through the 1¼” holes drilled or punched
in the HVAC duct to accept the inlet sampling and exhaust tubes and
then attaching them to the duct unit), hold the duct unit assembly in
position and use (2) # 12 X ½” sheet metal screws (packaged in the
installation kit) to secure the duct smoke detector to the HVAC duct
sheet metal.
AIR SAMPLING VERIFICATION
To ensure correct operation of the duct unit use a Magnehelic
differential pressure gauge, Dwyer 2000 or 4000 Series (or equivalent)
to determine the differential pressure between the inlet (high side) and
exhaust (low side) tubes. The differential pressure between the two
tubes should be greater than 0.01 inches of water and less than 1.2
inches of water. This duct smoke detector is shipped with a velocity
adapter insert, either factory installed (SL-DA4R-P), or found in the
installation kit (SL-DA4R-N). When installed, this adapter will allow
the duct detector to operate at extremely low air velocities. To install
the adapter, simply insert it into the slots provided inside the detector
housing so that the adapter fits snugly over the smoke detector head.
For Ionization models only: Unless your system is consistently
operating in the slower velocity range (where the adapter is specifically
required), we recommend that the adapter not be inserted. If you
experience false alarms at higher velocities with the adapter in place, the
adapter should be removed.

INST AP-330 D140113
3
ELECTRICAL INSTALLATION
WIRING
Prior to connecting the detector, determine and ensure you are connecting
to the correct terminals.
NOTE: Consult the FACP documentation for compatibility and
capacity of detectors and accessories on analog addressable (SLC) type
smoke detector circuits.
REMARQUE: Consultez la documentation de FACP pour la compatibilité
et la capacité des détecteurs et accessoires sur adressable analogique (SLC)
de type circuits de détection de fumée.
CAUTION: Do not use looped wire under terminals. Break wire
run to provide for proper supervision of connections.
MISE EN GARDE: Ne pas enrouler le fil sous les bornes. Pour assurer la
supervision electrique des raccordements, il faut couper les fils.
100 ft/min 300 ft/min 500 ft/min 1,000 ft/min 2,000 ft/min 3,000 ft/min 4,000 ft/min
SL-DA4R-N
SL-DA4R-P UL Listed with insert installed (100-4,000 ft/min)
UL Listed without insert installed (1,000-4,000 ft/min)
UL Listed with insert installed (100-2,000 ft/min)
UL Listed without insert installed (300-4,000 ft/min)
AIR SAMPLING VERIFICATION (CONT’D)
Please use the following chart for guidance on when the velocity adapter should be used. For reference, the speeds indicated are intended to represent
the velocity of air within the duct under normal operational conditions.
FIRE ALARM CONTROL PANEL WIRING
SAMPLE CONTROL PANEL WIRING - STYLE “6” / “7” SLC (Supervised - A single open/ground condition will not inhibit an alarm response)
SL-DA4R
Detector #1
SL-DA4R
Detector #X
UL Listed
Compatible
Analog
Addressable
Fire Alarm
Control Panel
SLC
L1
D
(-)
(-)
(+)
(+)
L2 L1 C+ T/R+ P+ AL+ C- TB+ NC COM NO 24V N/O
FACP
SLC
REMOTE
ACCESSORY
ALARM
RELAY
POWER
24AC/DC
UL LISTED
COMPATIBLE
FACP SLC
(LOOP)
+-
SUPERVISED
UNSUPERVISED
AC/+ N/0
ALARM
CONTACT
10A@115VAC
+
OUT
+
IN
TEST
+
OUT
PILOT
+
OUT
ALRM
-
OUT
+
OUT
TRBL
TERMINAL
CONNECTIONS
REMOTE ACCESSORIES
C+
T/R+
P+
AL+
C-
TB+
C+
T/R+
P+
AL+
C-
TB+
SL-D4R MSR- SERIES
REMOTE
ACCESSORIES
BLACK
BLACK
RED
KEY OR
PUSH BUTTON
TEST SWITCH
BLACK
RED
RED
GREEN
PILOT LED
RED ALARM
LED AND/OR
STROBE/HORN
YELLOW
TROUBLE LED
MS- SERIES
REMOTE
ACCESSORIES
L2 L1 C+ T/R+ P+ AL+ C- TB+ NC COM NO 24V N/O
FACP
SLC
REMOTE
ACCESSORY
ALARM
RELAY
POWER
24AC/DC
UL LISTED
COMPATIBLE
FACP SLC
(LOOP)
+-
SUPERVISED
UNSUPERVISED
AC/+ N/0
ALARM
CONTACT
10A@115VAC
+
OUT
+
IN
TEST
+
OUT
PILOT
+
OUT
ALRM
-
OUT
+
OUT
TRBL
TERMINAL
CONNECTIONS
REMOTE ACCESSORIES
C+
T/R+
P+
AL+
C-
TB+
C+
T/R+
P+
AL+
C-
TB+
SL-D4R MSR- SERIES
REMOTE
ACCESSORIES
BLACK
BLACK
RED
KEY OR
PUSH BUTTON
TEST SWITCH
BLACK
RED
RED
GREEN
PILOT LED
RED ALARM
LED AND/OR
STROBE/HORN
YELLOW
TROUBLE LED
MS- SERIES
REMOTE
ACCESSORIES
With detector head removed, connect to the applicable terminals (see
diagrams this page). Replace detector head and depress the cover removal
switch (SW1) and the unit will be energized. The detector’s red alarm LED
will be flashing intermittently (as SLC is scanned by the FACP), and upon
releasing the cover removal switch, the detector’s red alarm LED will cease
flashing.
In the event of a fire alarm, certain equipment may be required to be shut
down. These functions may be accomplished via the FACP or with the alarm
relay contacts provided on the control board.
L2
L1
D
L2
!
!

INST AP-330 D140113
4
SAMPLE CONTROL PANEL WIRING - STYLE “4” SLC (Supervised - A single open condition will inhibit an alarm response)
UL Listed
Compatible
Analog
Addressable
Fire Alarm
Control Panel
SLC (+)
(-)
SL-DA4R
Detector #X
OPERATIONAL TESTING
To determine the correct operation of the SL-DA4R Series duct smoke
detector, ensure the UL Listed, compatible FACP is properly connected and
the red alarm LED is flashing in the normal standby mode.
Each SL-DA4R duct detector is supplied with an XPERT Card. In order
to determine the proper address, consult the addressing guide. Place a
screwdriver in the pips slit and give it a firm twist. Removal of the proper pips
completes the addressing procedure. Slide the coded XPERT Card into the
side of the base, making sure it locks into position. Once the detector head is
placed into the base, the remaining pips will operate the address-buttons on the
detector head and the address will be read by the head’s electronics.
Factory pre-programmed XPERT Cards which have the appropriate address
pips removed, and the address number silk screened on the protruding tab can
be purchased if desired.
The LED on the detector head of both the ionization and photoelectric models
will not flash while the unit is in standby mode. The LED on the smoke detector
head will be permanently illuminated when smoke is detected and the head is
in alarm. Note: When the detector head is in an alarm state, a complete reset
on the Fire Alarm Control Panel is needed to restore it to the standby mode.
With the air handling unit shut down, and the clear cover removed, press and
hold the cover removal switch on the SL-DA4R. The red alarm LED on the
detector head will be flashing and the FACP will be in the normal standby state.
The trouble operation may be tested by one of three methods:
1. Releasing the cover removal switch.
2. Depressing the cover removal switch after rotating the smoke detector
head counter-clockwise and removing the detector head.
3. Removal of control board operating power.
TESTING AND MAINTENANCE PROCEDURES
These actions will cause a trouble condition at the FACP. By reversing
these conditions the unit will be operational. The trouble condition on the
FACP will be (or will be allowed to be) cleared.
The alarm functionality on the control board may be tested by either smoke
testing the detector head, operating the on-board test switch, or operating
a connected remote test switch.
FUNCTIONAL TESTING
Once operational testing is concluded the unit requires functional testing to
determine the correct operation of the detector head.
SMOKE TESTING: Using smoke test canister with testing nozzle (available
from Air Products and Controls Inc. part number TG-2000), insert the test gas
nozzle into the test port on the unit cover. Press can against cover to release
gas into the chamber.
CAUTION: DO NOT SPRAY GAS FOR MORE THAN ½
SECOND. OVERUSE OF TEST GAS FACILITY MAY RESULT IN
DETECTOR CONTAMINATION.
MISE EN GARDE: NE VAPORISEZ PAS DE GAZ POUR PLUS DE
½ SECONDE. SURUTILISATION DES GAZ DE TEST
INSTALLATION PEUT ENTRAÎNER LA CONTAMINATION DU
DÉTECTEUR.
After 15 to 20 seconds the detector head will go into alarm, illuminating
the detector head LED and causing an alarm condition at the FACP. If
attached, any alarm related remote accessories will also function.
If no test gas is available to conduct functional testing, remove cover and,
while holding down the cover removal switch, blow smoke from a cotton
wick or punk directly at the head to cause an alarm.The alarm indicator
should illuminate within one minute.
Should additional testing also be required for simulated re conditions,
smoke bombs placed in the duct may not be suited for the particular
detector head (photoelectric or ionization) selected and installed.
Consult the smoke bomb data for proper use and compatibility with
detector type.
The XP95A ionization detector head (55000-550) utilizes a radioactive
source as its means of detection and will detect smoke particles of
between .1 and 1 micron in size.
The XP95A photoelectric detector head (55000-650) operates on the
principle of light scatter and will detect smoke particles of between 1 and
10 microns in size.
When purchasing smoke bombs for additional required functional testing,
ensure smoke particle sizes comply with the criteria as described above.
Above: The LED will be permanently illuminated when the unit is in alarm.
SL-DA4R
Detector #1
L1
D
L2
L1
D
L2
!

INST AP-330 D140113
5
MAINTENANCE
Each installation location must be assessed on its own merits. If the
protected area is of a very dirty nature then the SL-DA4R Duct unit(s) will
have to be checked and cleaned on a quarterly basis or when cleaning is
required.
As a guideline the smoke detector head should be cleaned every six
months or as required. The best methods of cleaning are to vacuum the
detector head thoroughly or to blow the detector head out using clean,
dry compressed air.
Do not use chemicals or non-conforming air to clean the detector head
housing as this could contaminate the detector head and damage the casing.
Sensing tubes must be inspected and cleaned in accordance with the
schedule as determined above, to allow the free flow of air through both
inlet and exhaust tubes.
Consult your local code and AHJ requirements for required maintenance
schedules.
XPERT CARD PROGRAMMING
Analog addressable Discovery and XP95A bases employ a unique, simple
mechanism for hardware addressing (Fig. 1 ). The XPERT Card provides
a series of seven removable pips, which when removed in proscribed
patterns, corresponding to binary system digits, and can represent numbers
1 through 126. Factory set and labeled XPERT Cards are available.
NOTE: No buttons removed (address 0) or multiple like addresses on an
SLC will cause an FACP Trouble/Fault condition.
NOTE: Remove the XPERT Card, select the desired address and remove
the pips indicated in black with a small screwdriver. Replace the XPERT
Card and twist the detector head into place to complete programming
(Fig. 2).
X-pert Card
XXX
Address Label Space
1
2
4
8
16
32
64
Address label spaces
Fig. 1 XPERT Card
1
2
4
8
16
32
64
1
1
1
2
4
8
16
32
64
10
10
1
2
4
8
16
32
64
9
9
1
2
4
8
16
32
64
8
8
1
2
4
8
16
32
64
7
7
1
2
4
8
16
32
64
6
6
1
2
4
8
16
32
64
5
5
1
2
4
8
16
32
64
4
4
1
2
4
8
16
32
64
3
3
1
2
4
8
16
32
64
2
2
1
2
4
8
16
32
64
11
11
1
2
4
8
16
32
64
20
20
1
2
4
8
16
32
64
19
19
1
2
4
8
16
32
64
18
18
1
2
4
8
16
32
64
17
17
1
2
4
8
16
32
64
16
16
1
2
4
8
16
32
64
15
15
1
2
4
8
16
32
64
14
14
1
2
4
8
16
32
64
13
13
1
2
4
8
16
32
64
12
12
1
2
4
8
16
32
64
21
21
1
2
4
8
16
32
64
30
30
1
2
4
8
16
32
64
29
29
1
2
4
8
16
32
64
28
28
1
2
4
8
16
32
64
27
27
1
2
4
8
16
32
64
26
26
1
2
4
8
16
32
64
25
25
1
2
4
8
16
32
64
24
24
1
2
4
8
16
32
64
23
23
1
2
4
8
16
32
64
22
22
1
2
4
8
16
32
64
31
31
1
2
4
8
16
32
64
40
40
1
2
4
8
16
32
64
39
39
1
2
4
8
16
32
64
38
38
1
2
4
8
16
32
64
37
37
1
2
4
8
16
32
64
36
36
1
2
4
8
16
32
64
35
35
1
2
4
8
16
32
64
34
34
1
2
4
8
16
32
64
33
33
1
2
4
8
16
32
64
32
32
1
2
4
8
16
32
64
41
41
1
2
4
8
16
32
64
50
50
1
2
4
8
16
32
64
49
49
1
2
4
8
16
32
64
48
48
1
2
4
8
16
32
64
47
47
1
2
4
8
16
32
64
46
46
1
2
4
8
16
32
64
45
45
1
2
4
8
16
32
64
44
44
1
2
4
8
16
32
64
43
43
1
2
4
8
16
32
64
42
42
1
2
4
8
16
32
64
51
51
1
2
4
8
16
32
64
60
60
1
2
4
8
16
32
64
59
59
1
2
4
8
16
32
64
58
58
1
2
4
8
16
32
64
57
57
1
2
4
8
16
32
64
56
56
1
2
4
8
16
32
64
55
55
1
2
4
8
16
32
64
54
54
1
2
4
8
16
32
64
53
53
1
2
4
8
16
32
64
52
52
1
2
4
8
16
32
64
63
63
1
2
4
8
16
32
64
62
62
1
2
4
8
16
32
64
61
61
1
2
4
8
16
32
64
124
124
1
2
4
8
16
32
64
126
126
1
2
4
8
16
32
64
125
125
1
2
4
8
16
32
64
80
80
1
2
4
8
16
32
64
79
79
1
2
4
8
16
32
64
78
78
1
2
4
8
16
32
64
77
77
1
2
4
8
16
32
64
76
76
1
2
4
8
16
32
64
70
70
1
2
4
8
16
32
64
69
69
1
2
4
8
16
32
64
68
68
1
2
4
8
16
32
64
67
67
1
2
4
8
16
32
64
66
66
1
2
4
8
16
32
64
65
65
1
2
4
8
16
32
64
64
64
1
2
4
8
16
32
64
71
71
1
2
4
8
16
32
64
75
75
1
2
4
8
16
32
64
74
74
1
2
4
8
16
32
64
73
73
1
2
4
8
16
32
64
72
72
1
2
4
8
16
32
64
81
81
1
2
4
8
16
32
64
90
90
1
2
4
8
16
32
64
89
89
1
2
4
8
16
32
64
88
88
1
2
4
8
16
32
64
87
87
1
2
4
8
16
32
64
86
86
1
2
4
8
16
32
64
85
85
1
2
4
8
16
32
64
84
84
1
2
4
8
16
32
64
83
83
1
2
4
8
16
32
64
82
82
1
2
4
8
16
32
64
91
91
1
2
4
8
16
32
64
100
100
1
2
4
8
16
32
64
99
99
1
2
4
8
16
32
64
98
98
1
2
4
8
16
32
64
97
97
1
2
4
8
16
32
64
96
96
1
2
4
8
16
32
64
95
95
1
2
4
8
16
32
64
94
94
1
2
4
8
16
32
64
93
93
1
2
4
8
16
32
64
92
92
1
2
4
8
16
32
64
101
101
1
2
4
8
16
32
64
110
110
1
2
4
8
16
32
64
109
109
1
2
4
8
16
32
64
108
108
1
2
4
8
16
32
64
107
107
1
2
4
8
16
32
64
106
106
1
2
4
8
16
32
64
105
105
1
2
4
8
16
32
64
104
104
1
2
4
8
16
32
64
103
103
1
2
4
8
16
32
64
102
102
1
2
4
8
16
32
64
111
111
1
2
4
8
16
32
64
120
120
1
2
4
8
16
32
64
119
119
1
2
4
8
16
32
64
118
118
1
2
4
8
16
32
64
117
117
1
2
4
8
16
32
64
116
116
1
2
4
8
16
32
64
115
115
1
2
4
8
16
32
64
114
114
1
2
4
8
16
32
64
113
113
1
2
4
8
16
32
64
112
112
1
2
4
8
16
32
64
123
123
1
2
4
8
16
32
64
122
122
1
2
4
8
16
32
64
121
121
Fig. 2 XPERT Card addressing for Discovery and XP95

INST AP-330 D140113
6
You
in Control
AND
AIR PRODUCTS
CONTROLS
INSTALLATION AND MAINTENANCE
INSTRUCTIONS
A COPY OF THESE INSTRUCTIONS SHOULD BE LEFT WITH THE EQUIPMENT
UNTIL INSTALLATION BY ALL TRADES IS FULLY COMPLETE. FOLLOWING FINAL INSPECTION,
A COPY SHOULD BE LEFT WITH THE OWNER/USER.
AIR PRODUCTS AND CONTROLS INC.
25 Corporate Drive, Auburn Hills, MI 48326 USA
Telephone: (248) 332-3900 www.ap-c.com
AVAILABLE ACCESSORIES FOR USE WITH
SL-DA4R SERIES DUCT SMOKE DETECTORS
MSR- SERIES REMOTE ACCESSORIES
Remote Alarm,Trouble, Pilot LEDs; Programmable Buzzer with Silence Switch, Indication, and
Ring-Back; Key-Operated Test/Reset Switch; LED/Buzzer Test Switch
MSR-100
MSR-50
MSR-AV
MS-- SERIES REMOTE ACCESSORIES
MS-RA Remote Alarm
MS-RA/R Remote Alarm, push button Test/Reset Switch
MS-RA/P/R Remote Alarm, Pilot, push-button Test/Reset Switch
MS-KA/R Remote Alarm, key-operated Test/Switch
MS-KA/P/R Remote Alarm, Pilot, key-operated Test/Reset Switch
MS-RA/P Remote Alarm, Pilot
MS-RH Remote Alarm Horn
MS-RH/KA/P/R Remote Alarm, Pilot, Horn, key-operated Test/Reset Switch
MS-RH/P/A Remote Alarm, Pilot, Horn
MS-RH/KA/P/A/T Remote Alarm,Trouble, Pilot, Horn, key-operated Test/Reset Switch
MS-RA/P/T Remote Pilot,Trouble
MS-RA/FT/P Remote Pilot,Trouble, push-button Test/Reset Switch
MS-KA/P/R/T Remote Pilot,Trouble, key-operated Test/Reset Switch
MS-RD Remote Alarm
MS-F/T Remote Trouble
SMOKE TEST GAS
TG-2000 No Climb SOLOA4 Aerosol Test Gas with
UGS 20001TN Nozzle for Test Port
NOTCHED SAMPLING TUBES
STN-1.0 For duct widths of 6” TO 1.0’
STN-2.5 For duct widths of 1.0’ TO 3.0’
STN-5.0 For duct widths of 3.0’ TO 5.0’
STN-10.0 For duct widths of 5.0’ TO 10.0’
FAST TUBE Sectional tubes for duct widths up to 8.0’
WEATHERPROOF ENCLOSURES
WP-2000 Space Age Electronics WJ1261 3R Weatherproof Enclosure
REPLACEMENT SMOKE DETECTOR HEADS
55000-550 Apollo XP95A Ionization Detector Replacement Head
55000-650 Apollo XP95A Photoelectric Detector Replacement Head
POWER SUPPLIES
T-PB 202-1 24VAC @ 4.0A Class I Power Supply
T-PB 202-0 24VAC @ 4.0A Class I Power Supply
T-PB 303-1 24VAC @ 3.0A Class II Power Supply
T-PB 303-0 24VAC @ 3.0A Class II Power Supply
NOTICE: The information contained in this document is the most current available at the time of shipment of accompanying product, and is subject to
change without notice. Future references should always be made to the most current revision of this document. The information contained in all this
document should be considered before installing or using the product. Any example applications shown are subject to the most current enforced local/
national codes, standards, approvals, certifications, and/or the authority having jurisdiction. All of these resources, as well as the specific manufacturer
of any shown or mentioned related equipment, should be consulted prior to any implementation. For further information or assistance concerning this
product, contact Air Products and Controls Inc. Air Products and Controls Inc. reserves the right to change any and all documentation without notice.
© Air Products and Controls Inc. 2006
SL-DA4R SERIES
DUCT SMOKE DETECTORS
You
in Control
AND
AIR PRODUCTS
CONTR
OLS
SL-DA4R-N Ionization Type, 4-Wire Analog Addressable
Duct Smoke Detector with Relay
SL-DA4R-P Photoelectric Type, 4-Wire Analog Addressable
Duct Smoke Detector with Relay
This manual suits for next models
2
Table of contents
Other Air Products & Controls Smoke Alarm manuals