AirTechnic ENERGY BOX-TE 4.000 User manual

1
ΜΟΝΑΔΑ ΑΝΑΚΤΗΣΗΣ ΕΝΕΡΓΕΙΑΣ
V. 4
Energy Recovery Ventilator
ENERGY BOX TE
ENERGY BOX-TE 4.000 | ENERGY BOX-TE 6.000 | ENERGY BOX-TE 8.000
ΤΥΠΟΙ / MODELS

CONTENTS
Safety notes
Installation notes
Electrical installation
Wiring diagram
Commissioning
Controller instructions
Modbus address
SW4 dial switch positions
Maintenance
3
6
9
13
15
17
20
27
30
2
ENERGY BOX TE

3
ΕΛ EN
/ Safety indications
The following symbols indicate potential levels of caution.
WARNING ATTENTION
Situations with a risk or death or
serious injury.
Situations with a risk of injury or
equipment / property damage.
The following symbols indicate compliance which must be observed.
Not allowed or
forbidden.
Must follow.
WARNING
Unit must be installed strictly following the rules of this manual
and mounted to a weight bearing surface.
During maintenance or repair, the power supply must be disconnected.
Otherwise electric shock could occur.
the equipment by themselves.
Installation engineers must follow this manual strictly. Improper action can create a health hazard
Obliged.
ENERGY BOX TE

Electrical connections must be made in accordance with regulations, the manual and using suitable
Ground wire must not be connected to gas pipe, water pipe, lighting rod or telephone line etc.
Incorrect grounding can cause electric shock.
Ensure there are no obstructions to or in the ducts.
areas where hazardous vapors are present.
Use only approved installation hardware and accessories. Failure to comply
The outdoor ducts must be installed facing downwards to prevent rain water from entering.
Improper installation can cause water leakage.
Insulation between the metal ducting and wall penetration must be installed if the duct penetrates
metal wall cladding, to avoid risk of electric shock or current leakage.
ATTENTION
ENERGY BOX TE

5
Do not install the unit in an extremely humid conditions, as it may result
Do not install the device in areas where poisonous or caustic gases are present.
require insulation depending on the dew point conditions.
Do not use this device as the kitchen’s primary air extraction system. Grease accumulation
In a hot and humid enviroment, the unit must be installed in the highest possible position.
.
ENERGY BOX TE

6
ΕΛ EN
type ENERGY BOX - TE
4.000
ENERGY BOX - TE
6.000
ENERGY BOX - TE
8.000
3 4.600 6.400 7.800
Static pressure (Pa) 100
Enthalpy
(%)
Cooling 60
Heating 61
(%) 73
Noise 59 70
Power Supply (V)
Input Power
Power Cable 2
Control Cable 2
Control
Standard
Yes
Fan Type EC Fan
Supply Fan Speed 10 Speed Fan Control
Exhaust Fan Speed 10 Speed Fan Control
Summer Bypass
Defrost
Control2
Fan Boost Contact
Fire Shutdown
Night Free Cooling operation
Weight 355 395 557
Size
Duct Size
ENERGY BOX TE

7
ΕΛ EN
Model
695
63065
510
External static pressure [Pa]
Air supply [m3
1
2
3
4
5
6
7
10
8
9
1 10
÷Speed
ENERGY BOX TE

ΕΛ EN
Model
765
70065
External static pressure [Pa]
Air supply [m3
1
2
3
4
5
6
7
10
8
9
1 10
÷Speed
ENERGY BOX TE

9
ΕΛ EN
Model
700
100
External static pressure [Pa]
Air supply [m3
1
2
3
4
5
6
7
10
8
9
1 10
÷Speed
ENERGY BOX TE

10
1.
2.
3.
4.
Prepare suitable threaded hangers with adjustable
nuts and gaskets.
Install the unit properly oriented with the inlet and
outlet ducts. The unit must be leveled and securely
fastened.
damage and excessive vibration.
operation.
Screw suspender
Nut
Nut
Spacer
Spacer
Suspending part
ΕΛ EN
Protect the unit and accessories during installation, or
storage, to prevent dust or other foreign objects from
entering. A service area of at least 500 mm should be
reserved to allow access for maintenance.
1.
2.
3.
Unit must not be installed close to boiler ducts.
It is recommended to avoid using the following duct
arrangements.
Severe bends
Multiple direction changes
Multiple reducers /
crimped duct work
ENERGY BOX TE

11
ΕΛ EN
national and local regulations.
The unit must not be exposed to ambient temperature
above 40
Take actions to avoid the formation of condensation and
frost.
to ensure that the operating conditions are kept
condensation or ice formation.
Saturation curve
Dry Bulb Temperature [oC]
Absolute Humidity 3]
To avoid the outdoor exhaust air cycling back indoor, the
distance between the two vents installed on the outside
wall should be over 1.000 mm.
If heater is equipped to the unit, the operation of the
heater should be synchronous with the unit, so that the
heater starts to work only when the unit starts.
Duct sound attenuator may be considered if the user
wants indoor noise to be minimized.
ENERGY BOX TE

12
ΕΛ EN
WARNING WARNING
Power supply must be disconnected during installation
and maintenance to avoid injury by electric shock. Cable
otherwise it may cause performance failure, electric
the electrical box cover, connect the wires to the
terminals and the control panel to the board using the
supplied cable, according to the wiring diagram. It is
recommended to secure the power cable on the wall or
the unit.
make sure the direction is according the labeling.
Our company does not accept any liability for any
problems caused by the user’s unauthorized tampering
of the electrical and control systems.
ENERGY BOX - TE
4.000
ENERGY BOX - TE
5.000
Model
22
ENERGY BOX - TE
6.000
ENERGY BOX TE

13
ΕΛ ENΕΛ EN
Model
Supply fan
Exhaust fan
Running signal output
Fault signal output
Fire alarm signal input
External switch
Diferrential pressure switch
/temp. RA
/temp. OA
/temp. FR (EA)
/temp. SA
/sensor CO2
Control panel ports
/ports
Humidity sensor
Control panel
Electrical heater signal
Joint of control panel and cable
/ length 5 m
Terminal on the Energy Box
ENERGY BOX TE

ΕΛ EN
Check that all cable sizes, circuit breakers and wire
connections are correct before following starting up the
unit.
Press the power button ON / OFF once for starting and
twice for shutting down. In ON status, the light of power
Set the correct fan speeds according your ERV model.
Press MODE for 6 seconds to enter parameter settings.
The parameter number is shown in the middle of the
screen . Press SET until you reach parameter No. 21
to enter the parameter’s settings. The default value
UP or DOWN to change the code according the model
Code Model
1
2
3
Check the mode and fan speed switches. Press MODE
to switch between rR, oR or SR mode. Check whether
the temperature of the corresponding mode is correct.
Press FAN to switch the fan speed in rR and SR mode
and check if the indication changes from 1 to 10 (number
Check the bypass operation. The default opening
temperature is 19 to 21
check the oR temperature. If it’s 19 to 21 0C, the bypass
will open automatically. If the outdoor temperature is not
within this range, then adjust the opening temperature
according the current conditions in order to check the
bypass function. To adjust the opening temperature
press MODE more than 6 seconds to enter parameter
settings. Press SET twice to go from parameter 00 to
02. The temperature value is shown at the right corner
and the default is 19. Press MODE again to modify
the value according to the current oR temperature by
pressing UP or DOWN and afterwards SET to save the
selection. Check if the bypass is opened or not. Please
return the opening temperature to default values after
the check.
ENERGY BOX TE

15
Use only rated power voltage.
Disconnect the power supply when you clean the exchanger.
Don’t change, disassemble or repair the unit by yourself.
Injury may be caused by the rotation of the impeller.
Don’t install the fresh air duct in hot and humid conditions,
The air supply must not be in a close proximity to a burner,
If fuel burning appliances exist in the installation please consult the guidelines and regulations relating to
incomplete combustion in order to install the unit in a position that’s not inderfering
with their proper operation.
ENERGY BOX TE

16
ΕΛ EN
The intelligent controller is suitable for wall mounting
and comes with an LCD display screen. The standard
connection cable is 5 meters long, but the installer can
use extra cable if required.
120
120
60
17
31
10
59
59
ENERGY BOX TE

17
(-)
ENERGY BOX TE

ΕΛ EN
MODE
oA / rA / SA / Fr
FAN
rA
SA
SET
EXIT
DAY
SET
EXIT
TIMER ON
DAY
SET
EXIT
TIMER ON
/ 2
MODE
TIMER OFF
press button once for starting;
twice for closing. In ON status, the light of power
indicator is on, and the unit begins to run. In OFF status,
press to choose to display the
oA / / SA / status.
press button to adjust the
air velocity. Users can set the return air velocity in “”
status, and set the supply air velocity in “SA” status. Fan
press the CLOCK button, when the
to adjust the hour; then press the CLOCK button again
to adjust the minute in the same way, the interval is 10
minutes. After setting, please press SET button to save
the data or press EXIT to leave the operation without
display will disappear and all settings are invalid.
press the DAY button, when the day
SET to save
data or press EXIT to leave the operation without saving
will disappear and all settings are invalid.
DAY
SET
EXIT
/ 2
.
ENERGY BOX TE

19
ΕΛ ENΕΛ EN
DAY
SET
EXIT
TIMER OFF
/ 2
MODE
DAY
TIMER
ON TIMER OFF
10.
11.
SA
DAY
SET
EXIT
/ 2
.
press D AY button, and press
or button to check the automatic activation
/ deactivation time.
the control system
will record the current time. The ventilator starts to run
automatically when the timer is on, if the unit is already
running, it remains active. The unit stops when the timer
Controller settings are kept after restarting from
after connecting the electrical
temperature by temperature increase and decrease
buttons. When SA temperature lower than setting
temperature then electrical heater on.
1st stage heater on, 2nd
st and
2nd stage heater on.
12.
MODE
SET
MODE
SET
The control panel enters parameter setting mode via
pressing the button more than 6 seconds. In the
parameter setting mode, the parameter number (00 / 01
is shown in the middle of the screen. Press SET button
to switch the parameter number. Then press to
enter the parameter settings. The default value at the
the data. After setting, press SET button to save all the
data. After 10 seconds, the control panel begins to record
the parameters. The setting is proved to be successful if
ENERGY BOX TE

20
ΕΛ EN
00 1
01 0
Auto restart function
Description
02 19
03 3
No.
05
06 10
07 66
1
30
Minutes
23 2
0
25
21 0
Range
Default
Unit
Electrical heater available
Defrosting interval
Defrosting entering temperature
Defrosting duration time
2
CO2sensor function value
Energy Box models match / selection
Fan speed display selection
Multiple function setting
Filter alarm timer
speed
speed
speed
Filter alarm clearance
Weekly timer clearance
days
days
days
days
Minutes
Main control
Main control
Main control
Main control
Main control
Main control
Main control
Main control
Main control
Main control
Main control
0
Position
ENERGY BOX TE
This manual suits for next models
2
Table of contents
Other AirTechnic Fan manuals