Akytec SPK207 User manual

akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
SPK207
Control Panel
User guide
SPK207_2017.04_0200_EN
© All rights reserved
Subject to technical changes and misprints

akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
1
Contents
1Description......................................................................................................................................................2
1.1 Function ...................................................................................................................................................2
1.2 Ordering Key............................................................................................................................................2
1.3 Hardware .................................................................................................................................................2
1.3.1 Front Panel ..........................................................................................................................................2
1.3.2 Rear Panel...........................................................................................................................................3
1.3.3 Side View.............................................................................................................................................4
1.3.4 Touchscreen ........................................................................................................................................4
1.3.5 Battery..................................................................................................................................................5
2Specifications .................................................................................................................................................6
2.1 Environmental conditions.........................................................................................................................7
3Safety...............................................................................................................................................................8
3.1 Intended use ............................................................................................................................................8
4Installation.......................................................................................................................................................9
4.1 Requirements ..........................................................................................................................................9
4.2 Mounting ..................................................................................................................................................9
5Wiring ............................................................................................................................................................10
5.1.1 Signal lines.........................................................................................................................................10
5.1.2 Ethernet .............................................................................................................................................10
6Starting ..........................................................................................................................................................11
7Service Menu ................................................................................................................................................12
7.1 Touchscreen Calibration........................................................................................................................12
7.2 Configuration .........................................................................................................................................12
7.2.1 Network Settings................................................................................................................................14
7.2.2 Interface Settings...............................................................................................................................14
7.2.3Date and Time ...................................................................................................................................15
7.2.4 New Password...................................................................................................................................15
7.2.5 Additional ...........................................................................................................................................16
7.3 Factory settings .....................................................................................................................................16
7.4 CODESYS project update .....................................................................................................................16
8Maintenance..................................................................................................................................................18
9Transportation and Storage ........................................................................................................................19
10 Scope of delivery .....................................................................................................................................20
Appendix A Dimensions ...................................................................................................................................21
Appendix B Pin assignment .............................................................................................................................22
Appendix C Connection with PC and CODESYS ...........................................................................................24

Description
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
2
1 Description
1.1 Function
The Control Panel SPK207 is a PLC with a TFT touchscreen, freely programmable with
CODESYS V3.5 software.
It is designed and manufactured for industrial applications and can be used as an opera-
tor or a control terminal.
1.2 Ordering Key
Supply voltage:
24 24 (18…32) V DC
230 230 (90…264) V AC; 50 (47…63) Hz
Serial ports:
03 RS232, 2x RS232/RS485 configurable
Software installed:
CS CODESYS on Linux
Web Visualization:
WEB Integrated web visualization
1.3 Hardware
– RISC processor 800 MHz
– 128 MB dynamic memory (RAM)
– 128 MB persistent memory (Flash)
– Real Time Clock, battery backed
– Buzzer
1.3.1 Front Panel
– TFT color display with resistive touchscreen
– LED POWER
– LED RUN, lights while running user application
– 3 LEDs P1, P2, P3, blinks if data exchange is in progress on the serial ports COM1,
COM2, COM3: green indicates data reception (RxD), red indicates data transmission
(TxD)
– 6 LED-lit function buttons: SYS, F1…F5. The functions of the buttons and LEDs can
be set in the user application.

Description
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
3
Fig. 1.1 Front Panel
1.3.2 Rear Panel
The rear panel is shown in the Fig. 1.2 and Fig. 1.3.
– USB-Host
– USB-Device
– Debug interface RS232 (RJ12) (service function)
– Ethernet 10/100 Mbit/s (RJ45)
– RS232 COM1 (DE9M)
– 2x RJ45 for the RS232 and RS485 interfaces (COM2 and COM3)
– 3-pin terminal block for the power supply
– Operation mode selector RUN (service function)
– Button RESET (recessed). The button can be pressed by a thin, pointed object of
max. Ø3 mm.
The interface USB Host and SD slot can be used as a terminal for various Mass Storage
Devices.
The interface of the serial port COM2 depends on the device model (Table 2.2).
The serial ports COM2 and COM3 are galvanically isolated and can be configured as
follows:
SPK207-xxx.03
– The ports COM2 and COM3 can be configured as RS232 or RS485.
The pin assignments for all interfaces are shown in Appendix B.
Restart
The restart occurs in case of:
– switching the power supply off and on again
– pressing the RESET button
– touching a REBOOT key in the configuration mode
Only in the case of using a REBOOT key the data is backed up. Otherwise, the current
process is terminated without data backup.

Description
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
4
Fig. 1.2 SPK207-24.03 rear panel
1.3.3 Side View
On the right side of the device (Fig. 1.3):
– SD-Slot
– Audio output
Fig. 1.3 SPK207 right side
1.3.4 Touchscreen
The touchscreen detects a finger touch or a touch with a stylus (not included in package).
►
NOTICE
The resistive touchscreen can be damaged by pointed or sharp objects. Therefore, it is
recommended to touch the screen only with your finger or a non-damaging object!
RESET
USB
Host
USB
Device
COM2
RS-485
COM3
RS-485
Debug COM2 COM3 +_
24 V DC
LAN COM1
D+ D_
RUN
I
0
D+ D_
SD

Description
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
5
It is possible to use protecting coatings for resistive displays.
The PLC is delivered with a calibrated touchscreen. In case of malfunction, the
touchscreen can be recalibrated (see 6.1).
1.3.5 Battery
The battery is located on the motherboard. Switch off the device, loose four screws and
remove the rear case to replace the battery. When replacing the battery, the polarity must
be observed.
►
NOTICE When replacing the battery, the data in the retain memory will be deleted!

Specifications
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
6
2 Specifications
Table 2.1 General specifications
System
CPU
ARM Cortex™-A8, 800 MHz
Memory
RAM
128 MB
Flash
128 MB
Real Time Clock
Battery-backed (CR2032)
Backup time
360 hours at 20 ± 5 ºС (1)
Operating system
Linux
Programming software
CODESYS v3.5
HMI
Display
TFT 7“
Colors
65536
Resolution
800 x 480 pixel (WVGA)
Display work area (W x H)
152 x 91 mm
Backlight
LED
Touch
resistive
LED-lit function keys
6
Audio output
3.5 mm, > 16 ohm
Power supply
SPK207-24
24 (18…32) V DC
Power consumption
power on
< 20 W
operation
< 15 W
SPK207-230
230 (90…264) V AC; 50 (47…63) Hz
Power consumption
power on
< 40 VA
operation
< 20 VA
Interfaces
Basic
USB-Host
USB-Device
Ethernet (10/100 Mbit/s)
Debug (RS232)
COM1 (RS232)
COM2, COM3 (2)
SPK207-xxx.03
2x RS232 / RS485 configurable
Baud rate
RS232, RS485
1.2…115.2 kbit/s
RS232, RS485 parameters
Data length
5, 6, 7, 8
Stop bits
1, 1,5, 2
Parity
none, even, odd, mark (1), space (0)
Flow Control COM1
RTS, CTS, DTR, DSR, DCD, RI,
XON/XOFF or none
COM2, COM3 none
Mechanical characteristics
Material
Plastic
Dimensions
228 x 152 x 59 mm
Weight
approx. 0.7 kg
(1) The buffer time is reduced if the ambient temperature is close to the limit of the operat-
ing temperature.
(2) The design of the interfaces is shown in Table 2.2.

Specifications
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
7
Table 2.2 Design of the serial ports
Device
Port
Interface
Connector
SPK207-xxx.03
COM1
RS232
DE9M
COM2
RS232
RJ45
RS485
RJ45 or 3-pin terminal block
COM3
RS232
RJ45
RS485
RJ45 or 3-pin terminal block
2.1 Environmental conditions
The device is designed for natural convection cooling that should be taken into account
when choosing the installation site.
The following environment conditions must be met:
– clean, dry and controlled environment, low dust level
– closed non-hazardous areas, free of corrosive or flammable gases
Table 2.3 Environmental conditions
Conditions Permissible range
Ambient temperature
-20…+50 °C
Storage temperature
-25…+55 °C
Relative humidity
up to 80% (at +35°C, non-condensing)
IP Code
IP20, front IP64
Altitude
up to 2000 m above sea level

Safety
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
8
3 Safety
Explanation of the symbols and keywords used:
DANGER
DANGER indicates an imminently hazardous situation which, if not avoided, will result in
death or serious injury.
WARNING
WARNING indicates a potentially hazardous situation which, if not avoided, could result in
death or serious injury.
CAUTION
CAUTION indicates a potentially hazardous situation which, if not avoided, could result in
minor or moderate injury.
►
NOTICE
NOTICE indicates a potentially harmful situation which, if not avoided, may result in dam-
age of the product itself or of adjacent objects.
3.1 Intended use
The device has been designed and built solely for the intended use described in this
guide, and may only be used accordingly. The technical specifications contained in this
guide must be observed.
The device may be operated only in properly installed condition.
Improper use
Any other use is considered improper. Especially to note:
– This device should not be used for medical devices which receive, control or other-
wise affect human life or physical health.
– The device should not be used in an explosive environment.
– The device should not be used in an atmosphere with chemically active substance.

Installation
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
9
4 Installation
CAUTION
Improper installation
Improper installation can cause serious or minor injuries and damage the control panel.
Installation must be performed only by fully qualified personnel.
For the dimension drawings see Appendix A.
4.1 Requirements
– The device is designed for front mounting.
– The mounting panel must be accessible from both sides.
– A rectangular mounting cutout is required.
– The mounting enclosure must provide a clean, dry and controlled environment.
– The seal contact surface must be clean and smooth, so that the protection IP64 can
be provided.
– The mounting panel can be placed at any angle.
– The device has been designed for natural convection cooling. Make sure that the
cabinet provides sufficient clearance for natural convection.
4.2 Mounting
Mounting sequence:
– Make a cutout in the mounting panel for the device
– Make sure that the device is provided with the mounting seal.
– Fit the device into the cutout
– Insert the 4 fastening clips into the slots on the top and the bottom of the device.
– Insert the screws and tighten them to fix the device.

Wiring
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
10
5 Wiring
WARNING
Dangerous voltage
Electric shock could kill or seriously injure.
All electrical connections must be performed by a fully qualified electrician.
Ensure that the mains voltage matches the voltage marked on the nameplate!
Ensure that the device is provided with its own power supply line and electric fuse!
WARNING Switch on the power supply only after wiring of the device has been completed.
– The pin assignments are shown in Appendix B.
– The maximum conductor cross-section for power supply is 1.5 mm2.
►
NOTICE
Ensure that the functional ground (FE) is connected to the appropriate pin of the power sup-
ply terminal block (see Table B.1). Functional grounding is required to meet EMC level im-
munity.
►
NOTICE
The device is not provided with an On/Off switch. If the external switch is not installed, the
device will start up (boot) as soon as it is connected to the power supply.
5.1.1 Signal lines
►
NOTICE Signal cables should be routed separately or screened from the supply cables.
►
NOTICE Only a shielded cable may be used for signal lines.
A twisted pair cable should be used to connect an external device to the RS232 / RS485
interface. The cable lengths should not be exceeded:
– RS485 – 1200 m
– RS232 – see table 4.1
Table 5.1 RS232 connection cable length
max. baud rate
max. length
2.400
900 m
4.800
300 m
9.600
152 m
19.200
15 m
57.600
5 m
115.200
2 m
5.1.2 Ethernet
Use a CAT5 shielded twisted pair cable (STP) to connect device to Ethernet.
– Connection of one device to another: crossover cable
– Connecting to the hub / switch: 1:1 patch cable
– Maximum cable length: 100 m.

Starting
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
11
6 Starting
►
NOTICE
Starting
Before switching on ensure that the unit was stored at the ambient temperature (-20… + 50 °С)
at least 30 minutes.
– After switching on the device starts booting. The process takes 25 seconds.
– After the boot process has been completed the message TAP 3 TIMES TO SERVICE
MENU appears for 3 seconds.
– If you touch the display 3 times within 3 seconds, the service menu will appear.
Fig. 6.1 Start screen
– Then the most important parameters can be set and the basic functions of the device
can be used. For the detailed description of the service menu see sec. 6.
– If you don’t touch the display within 3 seconds or you left the service menu, and there
is a user program on the PLC, it will be immediately executed.
– If no user program is on the PLC, the display looks after booting as follows:
Fig. 6.2 Display without user program
– The PLC must be connected via Ethernet cable to the PC with CODESYS to load a
user program. For details see Appendix C.
– Once the user program has been loaded to the PLC, it will be executed.
– For the programming instructions refer to the CODESYS documentation.

Service Menu
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
12
7 Service Menu
In this menu the most important parameters can be set and the basic functions of the
device can be used.
Use the short touch to navigate between the individual menu items.
Use the long touch to select a menu item.
Fig. 7.1 Service Menu
Service Menu items:
– RESCAN USB DRIVE
Enables USB mass storage device
– FIRMWARE UPDATE
Firmware update from a USB mass storage device
– CALIBRATE TOUCH-SCREEN
Touchscreen calibration (see 7.1)
– SPK SETUP
Access to configuration menu
Network parameters, COM interfaces, date, time, password and other important
parameters of the device can be set (see 7.2).
– UPDATE PROJECT
CODESYS project update (see 7.4).
– EXIT
Exit menu
7.1 Touchscreen Calibration
The resistive touch is already calibrated. However, in case of touchscreen malfunction,
recalibrate the touchscreen. To recalibrate the touchscreen:
– select CALIBRATE TOUCH-SCREEN
– touch the crosses that appears consecutively exactly at its center
– When the calibration is complete, the user program will be executed.
7.2 Configuration
– Select SPK SETUP.

Service Menu
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
13
– The access is password protected. Enter the password using the on-screen keyboard
on the Main Screen (Fig. 7.2). The default password is 12345. Use the Shift key as a
Caps Lock key.
– Touch OK after the password input. If the password is correct, the configuration dia-
log will appear (Fig. 7.3).
Fig. 7.2 Configuration Mode - Main Screen
Fig. 7.3 Configuration Mode - SPK207
In these dialog network and serial interfaces parameters, date and time can be set and
the password can be changed. The configuration parameters are divided into groups:
– Network Settings
Network parameters for the connection to PC (see 7.2.1)
– Interface Settings
Select the RS232 or RS485 interface from the drop-down list for serial ports COM2
and COM3 (see 7.2.2)
– Date and Time
Real Time Clock settings (see 7.2.3)
– Control
Access to the dialogs New Password, Additional and the keys Exit and Reboot
– New Password

Service Menu
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
14
Password change (see 7.2.4)
– Additional
Additional features (see 7.2.5)
– Exit
Return to the main screen
– Reboot
Exit the configuration dialog and reboot the PLC
Changes to parameter take effect immediately without confirmation.
7.2.1 Network Settings
The IP address, the SubnetMask and the standard gateway can be set.
Use the Setup key to change the parameters. The following mask appears:
Fig. 7.4 Input mask "Network Settings"
– If DHCP is disabled, the PLC uses a static IP address. The IP address, the Subnet-
Mask and the standard gateway must be defined. If DHCP is enabled (green DHCP
key), a DHCP server will assign IP address automatically.
– In the field Device Name the PLC name can be changed. The name will be used by
CODESYS after network scan. Enter the name using numerals, Latin letters and un-
derscore only.
– The DNS field can be used to enter domain names instead of IP addresses.
– Use Close key to exit the dialog.
– Use RESET key to apply the factory settings (see 7.3).
7.2.2 Interface Settings
The serial ports COM2 and COM3 can be used as RS232 and RS485 interfaces.
Use the Setup key to change the interface. The following screen appears:
Fig. 7.5 Input mask "Interface Settings"

Service Menu
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
15
Use the Close key to exit the dialog.
Use the RESET key to apply the factory settings (see 7.3).
The numbering of the serial ports should be observed in the CODESYS project.
Table 7.1 Serial ports in CODESYS
Port
COM1
COM2
COM3
Number
2
3
4
7.2.3 Date and Time
Use the Setup key for setting the real-time clock. The following screen appears:
Fig. 7.6 Input mask "Date and Time"
Use the on-screen NumPad, that appears if you touch white field or the +/-keys to
change the settings.
Use the Close button to exit the dialog.
7.2.4 New Password
Use the New Password key to change the factory set password (see 7.2).
Enter the new password using the on-screen keyboard.
Use the OK key to save the new password.
Fig. 7.7 On-screen keyboard "Password"

Service Menu
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
16
7.2.5 Additional
Fig. 7.8 Dialog "Additional Settings"
The additional features include:
– Cursor Settings
oOn – pointer is always visible
oOff – pointer is invisible
oAuto – pointer becomes invisible if the display is not touched within 10 sec-
onds
– Display Rotation
Image on the display can be rotated 90° counterclockwise.
– Devices Info
Information about the memory usage of the PLC flash memory (ROM), the con-
nected USB mass storage device and SD card
The memory devices are scanned every 10 seconds.
– Remove
Safely remove mass storage device
The function is available when a mass storage device is connected.
– Format
Format mass storage device to FAT32
The function is available when a mass storage device is connected.
Use the Close key to exit the dialog.
7.3 Factory settings
IP address 10.0.6.10
SubnetMask 255.255.0.0
Gateway 10.0.6.1
COM2, COM3 RS485
Use the Exit key to exit the configuration dialog.
Use the Reboot key to restart PLC.
7.4 CODESYS project update
The CODESYS project can be updated using a USB mass storage device. To transfer a
new CODESYS project to the PLC the following steps must be taken:

Service Menu
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
17
– format the USB mass storage (16 GB max.) to FAT32
– create a folder named APP in the root directory
– open the project in CODESYS and select Build -> Build in the menu
– select Online -> Create Boot Application in the menu to create a boot application
for PLC
– select a folder on the PC drive in the pop-up dialog box Save As ... to save the boot
application
– copy the content of the selected folder in the folder APP on the USB mass storage
– connect the USB mass storage to the PLC
– power on the PLC and enter the Service Menu
– select RESCAN USB DRIVE
– select UPDATE PROJECT
The new project is transferred to the SPK and will be executed immediately.

Maintenance
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
18
8 Maintenance
The maintenance includes:
– cleaning of the housing and terminal blocks from dust, dirt and debris
– checking the fastening of the device
– checking the wiring (connecting leads, fastenings, mechanical damage).
The device should be cleaned with a damp cloth only. No abrasives or solvent-containing
cleaners may be used. The safety information in section 3 must be observed when carry-
ing out maintenance.

Transportation and Storage
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
19
9 Transportation and Storage
Pack the device in such a way as to protect it reliably against impact for storage and
transportation. The original packaging provides optimum protection.
If the device is not taken immediately after delivery into operation, it must be carefully
stored at a protected location. The device should not be stored in an atmosphere with
chemically active substances.
Permitted storage temperature: -25...+55 °C
►
NOTICE
Transport damage, completeness
The device may have been damaged during transportation.
Check the device for transport damage and completeness!
Report the transport damage immediately to the shipper and akYtec GmbH!
Table of contents
Popular Control Panel manuals by other brands

BFT
BFT ZARA BTL2 installation manual

Rockwell Automation
Rockwell Automation Allen-Bradley OptixPanel 2800C AS Series user manual

Matrix Switch Corporation
Matrix Switch Corporation MSC-CP16X1E product manual

Pepperl+Fuchs
Pepperl+Fuchs VisuNet FLX RM-320P Series manual

Honeywell
Honeywell Notifier NFS-320 Document

Clarion
Clarion M202RC-RET Owner's manual & installation guide