Akytec PD111 User manual

akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
PD111
Pressure transmitter for
general industrial application
User guide
PD111_2018.04_0281_EN
© All rights reserved
Subject to technical changes and misprints

akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
1
Contents
1. Intended use ...................................................................................................................................................2
2. Safety...............................................................................................................................................................3
3. Specification ...................................................................................................................................................4
4. Wiring ..............................................................................................................................................................6
5. Connector mounting......................................................................................................................................7
6. Maintenance and cleaning.............................................................................................................................8
7. Transport and storage ...................................................................................................................................9
8. Faults.............................................................................................................................................................10
9. Dimensions ...................................................................................................................................................11
10. Ordering code ..........................................................................................................................................12

Intended use
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
2
1. Intended use
The PD111 is a pressure transmitter with internal diaphragm made of stainless steel AISI
316L and with a silicon measuring cell. The transmitter is applied for gauge pressure
measurement in liquid and gaseous media compatible with stainless steel AISI 316L /
1.4435 (AISI 304L / 1.4307). The pressure is converted into an electrical signal 4-20mA.
Restrictions on process medium:
– process medium may not corrode the wetted parts of the transmitter
– process medium may not crystallize or harden in process connection
– process medium temperature must be between -40 and +100 °C
The pressure transmitters described in this guide may be operated only in explosion proof
areas without aggressive vapors and gases.

Safety
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
3
2. Safety
Explanation of the symbols and keywords used:
DANGER
DANGER indicates an imminently hazardous situation which, if not avoided, will
result in death or serious injury.
WARNING
WARNING indicates a potentially hazardous situation which, if not avoided, could
result in death or serious injury.
CAUTION
CAUTION indicates a potentially hazardous situation which, if not avoided, could
result in minor or moderate injury.
►
NOTICE
NOTICE indicates a potentially harmful situation which, if not avoided, may re-sult
in damage of the product itself or of adjacent objects.

Specification
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
4
3. Specification
Table 3.1 Specification
Measuring ranges
Nominal pressure, bar
0...-1
0...-0,6
0...-0,4
0...-0,25
0...-0,16
Max. working pressure (MWP),
bar
2...-1 2...-1 2...-1 0,7...-0,7 0,7...-0,7
Burst pressure (OPL*), bar
4
4
4
1,4
1,4
Nominal pressure, bar
0...0,16
0...0,25
0...0,4
0…0,6
0...1
Max. working pressure (MWP),
bar
0,7 0,7 2 2 2
Burst pressure (OPL*), bar
1,4
1,4
4
4
4
Nominal pressure, bar
0...1,6
0...2,5
0...4
0...6
0...10
Max. working pressure (MWP),
bar
10 10 10 20 20
Burst pressure (OPL*), bar
20
20
20
40
40
Nominal pressure, bar
0...16
0…25
0...40
0...60
0...100
Max. working pressure (MWP),
bar
60 60 200 200 200
Burst pressure (OPL*), bar
120
120
400
400
400
Vacuum resistance
PN≥ 1 bar
unlimited vacuum resistance
P
N
< 1 bar
on request
Power supply
12...36 V DC
Current consumption, max.
70 mA
Output signal
4-20 mA
Accuracy
standard
± 0.5 % FSO
option**
± 0.25 % FSO
Permissible load
0...1200 ohm
Influence effects
supply
0.01 % FSO / 10 V
load
0.05 % FSO / 1 kohm
Temperature influence
≤ 0,1 % / 10 °C
Response time
≤ 100 ms
Short circuit protection
yes
Reverse polarity protection
yes
Permissible temperatures
process media
-40...+100 °C
ambient
-40...+80 °C
storage
-40...+80 °C
IP Code
IP65
Electromagnetic compatibility
(EMC)
EMI and interference immunity according to EN
61326
Shock resistance
480 g / 1 ms (according to EN 60068-2-27)
Vibration resistance
9 g at 25..2000 Hz (according to EN 60068-2-6)
Materials
Process connection
Stainless steel 1. 4307
Enclosure
Stainless steel 1. 4307
Sealing
no sealing (laser-welding diaphragm)
Diaphragm
Stainless steel 1.4435
Media wetted parts
Process connection and diaphragm
Lifetime
> 500 000 Horas
Process connection
M20x1.5; G1/2”; G1/4" (look Chapter 9)

Specification
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
5
Electrical connection EN 175301-803 A
ISO 4400
Supply +
1
Supply -
2
Shield
Ground contact
Mounting position
any
Dimensions
92 x 52 x 34 mm
Weight
approx. 400 g
CE conformity
EMC Directive: 2004/108/EC
Note * OPL – over pressure limit
** except the following ranges: 0...-0.16; 0…0.16; 0...60; 0...100 (bar)
1
2
3

Wiring
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
6
4. Wiring
The transmitter is connected in accordance with the wiring diagram (Fig. 4.1) considering
the load resistance requirements.
►
NOTICE Signal cables should be routed separately or screened from the supply cables.
►
NOTICE Only a shielded cable may be used for the signal lines.
Fig. 4.1 Wiring diagram
Use the diagram (Fig. 4.2) to select the permissible load resistance.
Recommendation:
U = 24 ± 2 V
R = 500 ± 50 ohm
Fig. 4.2 Load diagram
►
NOTICE
Switch on the power supply only after the wiring of the device has been complete-
ly performed.
+
+
+
1
212...36 V
SUPPLY
PROCESSING
R
PD111
20
10
200
400
600
800
1000
1200
300
Load (ohm)
Power supply (V DC)
Operating range

Connector mounting
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
7
5. Connector mounting
– Strip approx. 35 mm of the cable and remove approx. 5 mm insulation from each wire
end.
– Loosen the screw 1.
– Lever the terminal holder 5 out of the enclosure 2 using the mounting hole on the seal
6.
– Unscrew the cable fitting 4 and take out the cable seal 3.
– Lead the cable through the cable fitting 4 and the cable seal 3 in the enclosure 2.
►
NOTICE
Inproper mounting.
Enclosure seal can become damaged.
Do not push the terminal holder 5 out using the screw hole or the cable fitting 4.
– Unscrew the cable fitting 4 and take out the cable seal 3.
– Lead the cable through the cable fitting 4 and the cable seal 3 in the enclosure 2.
– Connect the cable ends in accordance with the wiring diagram (Fig. 4.1).
– Loosen the screw terminals of the terminal holder 5, connect the stripped wire ends in
accordance with the wiring diagram (Fig. 4.1) and screw the screw terminals in tight.
– Put the terminal holder 5 and snap the connector seal 6 in the enclosure 2.
– When screwing the cable fitting 4, make sure the cable fitting 4 with the cable seal
are assembled correctly and the cable seal 3 is not damaged.
– Plug the socket (2+5+6) to the contacts 7.
– Tighten the screw 1.
Fig. 5.1 Angular connector according to EN 175301-803
1
5
6
7
8
3
2
4

Maintenance and cleaning
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
8
6. Maintenance and cleaning
The pressure transmitter PD111 is maintenance-free. If needed the housing of the device
can be cleaned using a damp cloth and non-aggressive cleaning solutions, in switched-
off state.
When cleaning the diaphragm, the following is to observe:
−The device may be cleaned only after placing the device out of service correctly.
−The diaphragm can usually be cleaned carefully with a non-aggressive cleaning solu-
tion and a soft brush or sponge.

Transport and storage
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
9
7. Transport and storage
The device packaging must ensure a shockproof transport and storage. The original
packaging offers an optimal protection.
If the device is not taken into service immediately after delivery, it must be carefully stored
in a safe and protected place.
Storage temperature range: -40...+80 °C.
WARNING
Remove all the adherent media rests on the process connection before storing
the device after operation. This is particularly important if the medium is hazard-
ous to health, e.g. radioactive, carcinogenic, toxic, caustic, etc.
►
NOTICE
The device may have been damaged while shifting.
Check the device for transport damages and completeness!
Report the transport damage immediately to the shipper and akYtec GmbH!

Faults
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
10
8. Faults
Table 8.1 Faults
Fault Possible cause Remedy
No output signal
Cable breakdown
Check the cable line
Electrical short in power
supply circuit Check the cable line
Voltage reversal Reverse polarity
Output signal is unsta-
ble or remains con-
stant even if pressure
is changing
Process connection is
blocked up
Clean the connection*
Loss of pressure integrity in
the process connection Find the leakage and fix it
Missing electrical contact
Switch off power supply and
check the contacts
* Nota: When cleaning the process connection any mechanical influence on the dia-
phragm must be avoided.

Dimensions
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
11
9. Dimensions

Ordering code
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
12
10.Ordering code
PD111
–
–
–
Input
[bar]
0…-1
*V
1
P
0
B
0...-0.6
V
6
0
0
M
0...-0.4
V
4
0
0
M
0...-0.25
V
2
5
0
M
0...-0.16
V
1
6
0
M
0...0.16
*G
1
6
0
M
0...0.25
G
2
5
0
M
0…0.4
G
4
0
0
M
0...0.6
G
6
0
0
M
0...1
G
1
P
0
B
0...1.6
G
1
P
6
B
0...2.5
G
2
P
5
B
0...4
G
4
P
0
B
0...6
G
6
P
0
B
0...10
G
0
1
0
B
0...16
G
0
1
6
B
0...25
G
0
2
5
B
0...40
G
0
4
0
B
0...60
G
0
6
0
B
0…100
G
1
0
0
B
-0.125...0.125
*C
1
2
5
M
-0.2...0.2
C
2
0
0
M
-0.3...0.3
C
3
0
0
M
-0.5…0.5
C
5
0
0
M
-0.8...0.8
C
8
0
0
M
-1...1
C
1
P
0
B
-1...3
C
3
P
0
B
-1...5
C
5
P
0
B
-1...9
C
9
P
0
B
-1...15
C
0
1
5
B
-1…24
C
0
2
4
B
Accuracy
0.5 %
5
0.25 %
2
Process connection
G1/2"
7
G1/4"
8
M20 x1,5
1
Note *V – vacuum, *G – gauge, *C – combined.
Table of contents
Other Akytec Transmitter manuals
Popular Transmitter manuals by other brands

Pepperl+Fuchs
Pepperl+Fuchs HiD2024 quick start guide

IFM Electronic
IFM Electronic Efector 600 TA3233 installation instructions

Maxital
Maxital TXFO-IFTV user manual

IDTOLIGHT
IDTOLIGHT MILWAUKEE installation instructions

Canon
Canon Wireless File Transmitter WFT-E2 II A instruction manual

Link
Link HD manual