4 Technical specifications
Unsafe practices and other important information are emphasized in this manual.
Warnings are emphasized by means of special signs. All warnings in the manual are summarized on this page.
Pay special attention to the instructions below so that severe personal injury or damage to the top unit are avoided.
4.1 ThinkTop ® DeviceNet TM features
2
1
345
6
8
7
9
11 10 12
13
16
17
18
19
15 20
14
TD 800-267
1. Sensor unit
2. PLC, feedback
3. Sensor board
4. PLC interface board
5. IR Remote control
6. IR Rx
7. Serial link
8. LEDs
9. +5 V
10. Terminals
11. Terminals
12. ASI +
13. ASI -
14. Bus Connection
15. Internal connections
16. Solenoid signals (DC)
17. Solenoid common
18. External seat-lift (PNP)
19. Supply sensors
20. External connections
Type: Alfa Laval “No Touch” System. For wire connections: See 5.4 Electrical connection, internal“.
F
- Tolerance programmes.
- Self adjustment programme (SRC/ARC valves only).
- Built-in maintenance monitor.
- Setup by internal push buttons or remote control (IR Keypad).
- Setup and local fault supervision.
- Setup saved at power shutdown.
- Visual LED Indicator lights.
Unique “No Touch” sensor system without any mechanical sensor adjustments. A magnet (indication pin) is mounted on the
valve stem and the magnetic field (axial) is detected by sensor chips inside the sensor board. The measuring angle from each
chip is used to locate the current position of the valve stem with an accuracy of ± 0.1mm. Note that the distance to the
indication pin can be 5 mm ± 3 mm.
Input signals (produced by the sensor unit) transmitted over the DeviceNetTM -class4.
Five feedback signals: Closed valve, open valve, seatlift 1, seatlift 2 and status.
The status signal is used for five purposes:
• To indicate that a setup is in progress (LED D).
• To indicate an error condition (LED D), (flashing = software error), (steady = hardware error).
• To indicate that maintenance is required (LED F).
• To indicate if there is a conflict in the self adjustment programme (LED F).
• To indicate if no communication exists between ThinkTop® and PLC (LED D, steady).
Individual programme according to valve types.
Type 0: ...............................Bypass valve type / keep present valve type.
Type 1: ...............................SRC/ARC and Series 700 valves, only when self adjustment is enabled - Not recommended.
Type 2: ...............................LKB (LKLA-T).
Type 3: ...............................Unique Mixproof, SMP-SC Spillage-Free, and SRC-PV.
Type 4: ...............................SMP-SC, SMP-TO, SMP-BC, SMP-BCA, SBV, SRC, ARC, Unique SSV,
Unique SSV Aseptic, Unique-TO and Series 700 valves.
Type 5: ...............................All Parameters Set To Default (also valid for MH valve and SMP-EC
(seat-lift indication not possible for SMP-EC)).
Preset and reset values: Tolerance programme No./Type 5 (± 5mm) and all functions are disabled.
Important to select the right tolerance programme in order to ensure optimum controlled closeness of valves.