4.1 Input“03”to read the command of single register
Users input”03” to read the command of register value. Below is the command to read the value of baud rate:
To read the address of register
To read the length of register
Send above command via the serial assistant to module, then below value will be returned:
The value of 40034 is 3,which means
the baud rate is 9600,see more
details in baud rate value table.
Note: With the known baud rate, to use FF monitoring address can read the unremembered register value, Such as, send FF 03 00 21 00 01
c1de to read the address of device. CRC parity check code can be calculated by CRC16 system, the assistant software can be downloaded
in official website.
4.2 Input“03”to read the command of multiple registers
Users input”03” to read the command of register value. Below is the command to read the address of 40034 to 40036:
To read the address of register
To read the length of register
Send above command via the serial assistant to module, then below value will be returned:
The value of 40034 is 3,
which means the baud
rate is 9600,see more
details in baud rate value
table.
The value of 40035 is 0,
the parity bit of device
is no parity, see more
details in parity check
code table.
4.3 Input “06” to write the command of register
Input “06”to write single command, below is the command to change the baud rate as 19200:
The write value of 40034 is 4, the
corresponding baud rate is 19200,
see more details in baud rate table
If the revision is successful, module will return 01 06 00 21 00 04 d803.
4.4 Factory default value
9600,that is, 40034 address is 3
No parity check:40035 address is 0