- 4 - NetWaySP1BT Series
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local
codes and authorities having jurisdiction. All units should be installed by a trained service personnel.
Installation:
NetWaySP1BT:
1. Mount NetWaySP1BT in desired location utilizing the mounting hole (Fig. 1a, pg. 4). Use a proper fastener
and/or wall anchor when securing NetWaySP1BT with screw through its mounting hole to the wall.
NetWaySP1BTWPN, NetWaySP1BTWP, NetWaySP1BTWPX:
2. Remove backplane from enclosure prior to drilling. Do not discard hardware.
Note: Make sure that hardware will not interfere with components of the circuit board.
3. Mark and drill desired inlets on the enclosure to facilitate wiring. Maximum NEMA type 4X rated fittings
to be used are 0.5”. Follow manufacturer’s specifications for the appropriate size opening.
Note: Inlets for conduit fittings should only be made on the bottom of the enclosure.
To facilitate wire entry utilize weather-tight NEMA rated connectors (supplied), bushings, and cable.
4. Clean out the inside of enclosure before remounting circuit boards/backplane.
5. Mounting NEMA4/4X rated enclosure (Enclosure Dimensions, pg. 10, 11, 12):
Wall mount: Mount unit in desired location. Mark and drill holes to line up with the top and bottom
hole of the enclosure flange. Secure enclosure with appropriate fasteners (e. g. screws
and anchors; bolts and locking nuts, etc.) that are compatible with mounting surface and
are of sufficient length/construction to ensure a secure mount (Fig. 6, pg. 8).
Pole Mount: Refer to Fig. 7 - 11, pg. 8.
6. Mount backplane in enclosure with hardware.
Power Connection:
NetWaySP1BT, NetWaySP1BTWPN:
1. Use external 48-55V UL Listed ITE power supply, carefully observing correct polarity (Fig. 1, 2, pg. 4).
NetWaySP1BTWP, NetWaySP1BTWPX:
Before powering unit, set input voltage selection switch to proper Input Voltage position (Fig. 3a, pg. 4).
Units are factory set for 115VAC.
2. Connect AC power from overcurrent protective device circuit breaker
(20A @ 115VAC, 60Hz or 16A @ 230VAC, 50/60Hz) to the terminals marked [L, N] on power supply
board (Fig. 3, pg. 5). Connect ground lug to earth or green branch wire on backplane (12AWG min.).
Use 14AWG or larger for all power connections (Battery, DC output, AC input).
Keep power-limited wiring separate from non power-limited wiring by utilizing separate knockouts/
inlets. Minimum 0.25” spacing must be provided.
CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing
equipment. There are no user serviceable parts inside. Refer installation and servicing to qualified
service personnel.
3. Battery Backup (if desired): Connect four (4) 12VDC batteries wired in series to terminals marked
[– BAT +] (Fig. 3, pg. 5), carefully observing polarity.
When use of stand-by batteries is desired, they must be lead acid or gel type.
Note: When batteries are not used, a loss of AC will result in the loss of output voltage.
NetWaySP1BT
802.3bt Converter/Injector
Input: 48–56VDC
Output: IEEE 802.3bt (90W)
48-56VDC
-- Input +
48-56VDC
-- Input +
802.3bt
Output Data
Port
Fiber
Signal
PoE
SignalSFP
NetWaySP1BT
802.3bt Converter/Injector
Input: 48–56VDC
Output: IEEE 802.3bt (90W)