
- 2 - ANC1BBU Annunciator Installation Guide
Overview:
Altronix CommBatt, ANC1BBU Annunciator is designed to provide compliance with the requirements of UL 2524
for in-building 2 Way Emergency Radio Communication Systems.
It allows local and remote annunciation of various trouble conditions of BDA (Bi-Directional Amplier) and BBU
(Battery Backup Unit) and reporting those conditions to the FACP through the separate set of dry contacts, visual
and audible indicators.
Specifications:
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all
local codes and authorities having jurisdiction. Product is intended for indoor use only.
1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with mounting hardware;
level and secure. Mark the position of the lower two holes. Drill the lower holes and install two fasteners.
Install the two lower screws and make sure to tighten all screws (Enclosure Dimensions, pg. 8).
Secure enclosure to earth ground using ground stud inside.
2. Connect [Power +] and [Power –] terminals to 12-24VDC power source UL listed for the application (Altronix
CommBatt1 or similar). 400mA are required. Use [+ AUX –] terminals of CommBatt1.
Carefully observe polarity, damage may occur.
3. Connect Inputs to the equipment to be monitored, use 10K end of line resistor mounted at the equipment
end for monitoring of integrity of the connections. Altronix CommBatt1 power supply provides special
terminals that allow easy mounting of EOL resistors. Connect BDA, Donor Antenna Fail and Donor Antenna
Disconnect terminals to equipment to be monitored. Inputs not used must be terminated with 10K end of line
resistors connected directly to specific input terminals. See Terminal Identification, pg. 4.
4. Connect relay outputs to the FACP or other monitoring equipment. If it is located not in the same enclosure,
supervision must be provided. Use the end of line resistor recommended by the equipment that facilitates the
supervision and connect those to terminals marked EOL. Connect the equipment to output relay terminals.
See detailed instructions below.
5. Connect FACP contacts to Fire Alarm Control panel to provide trouble supervision.
6. Please ensure that the cover is secured with the provided lock.
Agency Listings:
• UL2524 Standard for In-Building 2-Way
Emergency Radio Communication
Enhancement Systems
Input:
• 12-24 VDC, 400mA input power.
• Input Fuse Rating: non field-replaceable 2A fuse.
Supervised Inputs:
• Nine (9) 10K EOL supervised inputs to connect to
power supply and other equipment that require
annunciation of trouble conditions:
- AC Fail
- Low Battery
- Charger Fail
- Component Fail
- Ground Fault
- RF Emitter Failure
- Donor Antenna Disconnect
- Donor Antenna Malfunction.
- RF Emitter Component Failure.
Relay Outputs (Dry NC contacts relays):
• Ten (10) Form “C” output contacts to connect to
FACP and other monitoring equipment with
convenient end of line resistor wiring terminals.
Use to report trouble conditions to FACP or
other equipment:
- AC Fail
- Low Battery
- Charger Fail
- Component Fail
- Ground Fault
- RF Emitter Failure
- Donor Antenna Disconnect
- Donor Antenna Malfunction
- FACP Reporting
- Communication Failure
Visual Indicators (See LED Diagnostics Table):
• 10 bicolor visual indicators of trouble conditions
visible through the observation window of
the enclosure.
Enclosure Dimensions (H x W x D):
11.8” x 9.84” x 5.9” (300mm x 250mm x 150mm).
NEMA4X stainless steel red color enclosure.