amiad ADI-P Manual

ADI-P 910101-000992 / 05.2020 Page 1 of 21
AMIAD Water Systems Ltd.
ADI-P - Smartphone Operated Controller
for Filtration Systems
Installation, Operation and Maintenance
Instructions
Original Instructions
Patent Pending Ref: 05/2020

ADI-P 910101-000992 / 05.20 02 Page 2 of 21
Amiad Water Systems Ltd.
ADI-P - Patent Pending Smartphone Operated Controller for Filtration Systems
Amiad’s ADI-P is a smartphone operated controller for filtration systems that is available in two main configurations:
•An integrated device for controlling one or two new filters
•A standalone device for controlling one or two existing filters
The ADI-P system consists of two major components: The ADI-P Controller and the ADI-P Mobile Application.
In this document, you will find the ADI-P Controller features including updates starting from firmware version #1.1.14.
Disclaimer:
Copyright © 2018 Amiad Water Systems Ltd. All rights reserved.
The contents of this document, including without limitation all information and materials, images, illustrations, data, drawings, names
and any other such materials that appear in this document are the sole property of Amiad Water Systems Ltd., including any
intellectual property rights, whether registered or not, and all know-how contained or embodied therein. Amiad may alter, remove or
change the Content without any further notice. You may not reproduce, copy, modify, create derivative works from, sell or participate
in any sale of, or exploit in any way, in whole or in part, any of this document or its content.
The confidential nature of and/or privilege in the file enclosed is not waived or lost as a result of a mistake or error in this file.If you
This document does not replace any certified drawing, procedure or information provided by Amiad in reference to a specific customer,
site or project.
Amiad assumes that all users understand risks involved within this file and/or its attached materials.This document is given in good
faith and is not intended to impose any obligation to Amiad. While every effort has been made to ensure the information in this
manual is accurate and complete, we would appreciate if you can bring any errors or omissions to the knowledge of Amiad or consult
Amiad experts or its authorized representatives if you have any questions.
Amiad Water Systems Ltd. D.N. Galil Elyon 1, 1233500, Israel Tel: 972 4 690 9500 | Fax: 972 4 814 1159 Email: info@amiad.com

ADI-P 910101-000992 / 05.20 02 Page 3 of 21
Table of Contents
Safety First........................................................................................................................................................................................ 4
General Safety Instructions .............................................................................................................................................................. 4
Installation........................................................................................................................................................................................ 4
Commissioning ................................................................................................................................................................................. 5
Operation and Control...................................................................................................................................................................... 5
Before any maintenance or non-standard operation....................................................................................................................... 5
Introduction...................................................................................................................................................................................... 6
ADI-P Controller Quick Guide ........................................................................................................................................................... 6
Screens Details: .............................................................................................................................................................................. 10
Download and Export Reports: ...................................................................................................................................................... 13
Specifications Table........................................................................................................................................................................ 14
ADI-P Terminal Blocks Connections................................................................................................................................................ 15
Annex A. Chaining ADI-P Controllers:............................................................................................................................................. 16
Annex B. Remarks on connecting the ADI-P Controller to an AC/DC Adaptor:.............................................................................. 19
Amiad Limited Warranty ................................................................................................................................................................ 20

ADI-P 910101-000992 / 05.20 02 Page 4 of 21
Safety First
General Safety Instructions
➢The manufacturer's filtration products always operate as components in a larger system. System designers, installers
and operators must comply with all relevant safety standards.
➢Prior to installation, operation, maintenance and/or any other type of action carried out on the controller, carefully
read these installation and operation instructions.
➢During installation, operation and/or maintenance of the controller all conventional safety instructions must be
observed in order to avoid danger to the workers, the public and/or to property in the vicinity.
➢The system is for use for non-hazardous liquids only!
➢Please note: The filter controlled by the controller enters the flushing mode automatically without any prior warning.
➢No change or modification to the equipment is permitted without written notification given by the manufacturer or by
its representative(s) on the manufacturer’s behalf.
➢Always observe standard safety instructions and good engineering practices whilst working in the filter’s vicinity.
➢Use the controller only for its intended use as designed by the manufacturer only. Any misuse of the controller may
lead to damage and may affect your warranty coverage. Consult with the manufacturer prior to any non-standard use
of this equipment.
➢Do not carry out system cleaning and/or maintenance in an explosive atmosphere.
Installation
General
➢Install the controller according to the detailed installation instructions provided in this manual or in the Quick Guide
provided with the filter or controller.
➢Make sure to leave enough side and top clearance to enable easy access for safe maintenance operations.
➢Make sure to have suitable lighting at the filter’s location to enable good visibility and safe maintenance.
➢Arrange suitable platforms and safety barriers to enable easy and safe access to the controller without needing to climb
on pipes and other equipment. Verify that any platform, barrier, ladder or other such equipment is built, installed and
used in accordance with the relevant local authorized standards.
➢Use only appropriate standard tools and equipment operated by qualified operators when installing, operating and
maintaining the controller.
➢When installation is required in hazardous environment sites, underground or high above ground, make sure that the
site design and the auxiliary equipment are appropriate and that installation procedures are carried out in accordance
with the relevant standards and regulations.
➢Ensure walking areas around the installation are slip resistant when wet.
Shipment and transporting
➢Shipping and transporting the controller must be done in a safe and stable manner and in accordance with the relevant
standards and regulations.

ADI-P 910101-000992 / 05.20 02 Page 5 of 21
Electricity
➢Electric wiring must be performed by an authorized electrician only, using standardized and approved components.
➢The filter should be installed in a manner in which the controller’s electrical components are protected from direct
contact with water.
➢When using external power a 1A external fuse and minimum 22AWG wires are required.
Commissioning
➢Carefully read this manual prior to operating the controller.
➢In order to achieve maximum performance and smooth operation of the controller, performing the start-up and first
operation procedures exactly as described in this manual is crucial.
Operation and Control
➢Do not operate the controller before carefully reading and becoming familiar with its operation instructions.
➢Observe the safety stickers on the controller and do not perform any operation other than those given in this manual.
➢Do not operate or use the controller for purposes other than its original design.
➢The system is for use for non-hazardous liquids only!
➢Do not carry out system cleaning and/or maintenance in an explosive atmosphere.
Before any maintenance or non-standard operation
➢Servicing the controller should be done only by technicians authorized by the manufacturer.
➢Do not carry out system cleaning and/or maintenance in an explosive atmosphere.
➢Disconnect the controller and the filter from the power supply and lock the main power switch.
Preventing damage due to frost
➢Non-operating periods:
To avoid damage or breakage when temperatures drop, command tubes must be disconnected and drained prior to
non-operating periods.
➢Operating season:
Your ADI-P controller is equipped with a built-in feature that detects low temperatures and increases the number of
flushes to avoid freezing of water. You can activate and adjust the settings of this feature in your Settings menu.

ADI-P 910101-000992 / 05.20 02 Page 6 of 21
Introduction
Thank you for purchasing the ADI-P controller - a smartphone operated controller for filtration systems of up to
two filters. The system consists of two major components, the ADI-P Controller and the ADI-P Mobile Application.
The ADI-P Controller can be supplied in two different configurations: as an integral component already connected
to the filter(s) and configured for that specific filter model or as a standalone unit to be connected and configured
for an existing installed filter(s).
This document covers both product configurations.
ADI-P Controller Quick Guide
(for detailed information see Understanding the application's screens data items on page 10)
Take few moments to familiarize yourself with the ADI-P Controller components:
1. ADI-P panel for manual flushing button and indication LEDs
2. 3-Way 12VDC solenoid #1 –latch
3. 3-Way 12VDC solenoid #2 –latch
4. Solenoids' manual operation handles
5. ADI-P cover
Dual solenoid controller
Single solenoid controller

ADI-P 910101-000992 / 05.20 02 Page 7 of 21
Initial operation of the ADI-P Controller:
Open the cover of the ADI-P Controller by turning it counterclockwise [1] and insert four alkaline 1.5V AA batteries
[2]. The Power LED turns on and the ADI-P Controller starts operating according to its pre-defined default flushing
program; flushing at 0.5 bar DP signal or 4-hour time intervals.
Downloading the Mobile Application:
The free ADI-P application by Amiad Water Systems is available for download on Google Play (Android
version 5 and up) or the App Store (iOS version 9 and up).
Pairing the controller with your mobile phone:
1. Activate your phone’s Bluetooth®discovery mode and start the ADI-P application.
2. Select the applicable SYSTEM UNITS.
3. REGISTER your filter to create an account.
4. Click CONNECT. The application scans for controllers within Bluetooth® range.
5. Select your controller from the list of controllers in range. Verify the that the blue/green LED on your controller
is blinking before clicking YES to initiate the paring process.
1
2

ADI-P 910101-000992 / 05.20 02 Page 8 of 21
6. Confirm the paring process.
7. Complete the SITE ID form.
a. Controller supplied with filter: Name your site and then select "Predefined". The application reads the
filter model and controller's serial number automatically.
b. Controller purchased separately: Name your site, select the filter model and enter your controller's serial
number.
You may add a site photo by clicking on
8. Enter the SITE INFO details (optional).
9. Once done, click SUBMIT to add your new filter to the SITE LIST.
10. In order to view data from your controller, select the active controller from the SITE LIST, marked by the active
Bluetooth®icon.
11. The ONLINE STATUS screen appears and relevant data regarding your filter’s performance can be viewed.

ADI-P 910101-000992 / 05.20 02 Page 9 of 21
Getting to know the ADI-P Application:
Take a few moments to familiarize yourself with the ADI-P mobile application interface:
Once running and controlling the filter, the application has 5 main screens. Scroll through these screens by sliding
to the right or to the left.
You may also reach the desired screen by clicking on the designated icons that appear at the bottom of the screen.

ADI-P 910101-000992 / 05.20 02 Page 10 of 21
Screens Details
The Online Status screen:
The upper red line
Displays the name of the currently connected controller and the communication status.
Time from last flush
The time since the end of the last flush cycle.
Last flush cause
The trigger that initiated the last flush.
Pressures - Inlet
The current reading of the filter's inlet pressure.
Pressure - Outlet
The current reading of the filter's outlet pressure.
Pressure - DP
The pressure differential across the filter; calculated by subtracting the outlet pressure from the
inlet pressure.
Manual Flushing
Press this icon to start a manual flush cycle.
The Counters screen:
The upper red line
Displays the name of the currently connected controller and the communication status.
Last reset at:
The date of the last resetting of the counters.
DP Cycles
The number of flush cycles started due to a DP signal.
Interval Cycles
The number of flush cycles started due to the time intervals program. Also count the Antifreeze
Protection Intervals Flushes
Preset
The number of flush cycles started due to the preset daily start time and the current status of this
program.
Manual Cycles
The number of flush cycles started due to a manual start command issued by the user.
Total Flushing Cycles
The total number of flush cycles started for any reason.
Reset Button
Press this button to reset the counters to zero.
Alerts screen:
The upper red line
Displays the name of the currently connected controller and the communication status.
The second line
Enables sorting alerts between two dates and resetting an alert.
The alerts list (see
below)
Display the alert messages according to their occurrence time and date.
Alarms and faults list:
Alert
Possible cause
Recommended Action
Low battery
Low battery voltage
Replace all 4 controller batteries
Low battery pause
Controller paused due to low battery voltage
Replace all 4 controller batteries
High DP alarm
DP value is >= HDA threshold (units: bar/100)
Alert only
High DP fault
DP value is >= HDF threshold (units: bar/100)
Alert only
Continuous mode alert
Controller exceeded number of consecutive
flushes for alerts
Check configuration/check DP: If high, perform
manual flush with downstream valve closed,
open the filter for inspection
DFU failed
Firmware update fail
Validate cellular reception and try again
Out of range app
connection
Controller out of range during connection
session
Get closer to the controller with the
smartphone (within Bluetooth® range)
Sensor pressure read
failed
The number of the sensor that failed to read.
Inlet(0), Outlet(1), Piston(2)
If continues - contact support
Capacitor charger start
failed
Unable to charge capacitor
Contact support
Load capacitor timeout
Capacitor charge timeout
Check battery voltage level, contact support
Low downstream
pressure
The outlet pressure is less than 1.5 bar
Check the filter and the water system
High upstream pressure
The inlet pressure is greater than maximum
allowed pressure for the filter
Adjust the water system inlet pressure

ADI-P 910101-000992 / 05.20 02 Page 11 of 21
Anti Freeze Active
Freezing Protection start, as a result of Low
Temperature Threshold
Anti Freeze Exit
Stop Freezing Protection procedure
Reports screen:
The upper red line
Displays the name of the currently connected controller and the communication status.
The second line
Displays icons of the different flush types. Select the desired icons to be displayed on the chart.
The chart window
Displays the number of flush cycles according to the selected icons.
Total Flushing Cycles
The total number of flush cycles currently displayed in the chart window.
The lower black line
Enables the user to select the chart’s time span (day, week, month).
History screen:
The upper red line
Displays the name of the currently connected controller and the communication status.
The second line
Enables sorting events between two dates and deleting an event.
The black line
Enables filtering events according to the four flush types (DP, Interval, Manual, Preset, Anti Freeze).
The events list
Display the events messages according to their occurring time and date.
The Menu screens:
Enter the menu screens by tapping on the Menu icon in the upper left corner of the SITE LIST screen:
System Units
Select the system engineering units: Metric or US.
Language
Select the application user interface language: English, French, German, Hebrew, Italian,
Portuguese, Russian or Turkish.
Account
Displays the registration details of the system: User name, User e-mail, User country, User company
and User job description.
User Manual
This screen shows the user manual.
Support
Contact Us screen.
App Version
Displays the current version of the ADI-P Application.
Messages
Messages from the Amiad system
The Settings screens:
Enter the setup screens by tapping on the Settings icon in the upper right corner of any of the 5 main screens:
The upper red line
Displays the name of the currently connected controller and the communication status.
Controller State
Displays the current controller state and allows the user to switch the controller ON and OFF
DP Set Point
Displays the DP level for starting a flush cycle and allows the user to enable or disable the DP
operation.
The recommended setting is displayed at the bottom of the screen.
Interval
Allows the user to set the time intervals for flushing and enable or disable the flushing according to
time intervals.
The recommended setting is displayed at the bottom of the screen.
Daily Preset Flush
Allows the user to set specific flushing start times. Start time can be set as daily start times or
single-time start times. The user can set up to 8 start times.
Flush Time
Allows the user to set the duration of the flush operation.
The recommended setting is displayed at the bottom of the screen.
Dwell Time
In case the system operates two filters, this parameter allows the operator to set the time delay
between the flush cycles of the first and second filters.
Battery
Displays the current charge level of the controller’s batteries.
ID
Enables the user to set the site’s picture, name and ID parameters such as: filter model, controller’s
serial number and filter serial number.
The second screen allows the user to select the type of the water source, flow-rate, the working

ADI-P 910101-000992 / 05.20 02 Page 12 of 21
pressure and the filtration degree of the filter.
Press SUBMIT to submit the data.
Technician Settings
See the following table.
About
Displays the current device ID, App version, Firmware version, Hardware version, Bootloader
version, controller installation date. If updated firmware is available this screen prompts the user to
update the system by pressing the Update Now button.
Technician Settings screens:
This section of the application contains the system’s basic and fundamental settings. Do not change any of these settings if you
are not totally familiar with the specific filtration system, filters and controller. Incorrect settings may cause the system to
become nonoperational.
Access to the Technician Settings screens requires a password. Please contact your dealer to obtain a password.
The upper black line
Allows the technician to search for a specific data item.
Filter Type
Select the specific filter(s) model controlled by the current controller.
Operation Mode
Select the operation mode of this controller;
Controller = Primary
Primary = the first controller in a chain of controllers or a stand-alone controller.
Secondary = a member of a chain of controllers which is controlled by a Primary controller.
DP Sensor = set this controller as the source of DP signal for the controller chain.
Pause Interval flush if DP
is less than
Set a DP value to serve as a minimal DP level for starting a flush cycle by the time intervals
parameter. If the DP reading is lower than this value the flush cycle by time interval will not start.
Interval Flush Pause
Enable or disable the operation of the Time Operation Mode Threshold parameter.
DP Delay
Set the time that the DP signal should be ON before starting flushing according to a DP signal. This
parameter is used to eliminate unnecessary flushing due to a momentary high differential pressure.
High DP Alarm Set Point
Set the DP level for issuing a High DP Alarm Message (System Log).
Repeated Flushes to
Start Fault Mode
Set the number of continuous flush cycles so the ADI-P controller enter to Fault Mode .
Cycle Time for
Continuous
Set the cycle time for counting a flush cycle as continuous flushing. If the time between two flush
cycles is shorter than “Minimum Cycle Time for Continuous Status” – then it’s counted as
continuous flushing.
Action in Continuous
Select the Action to Take when Continuous Fault Mode is detected: Ignore: Ignore the alert and
continue flushing according to DP Set Point. Time only: Stop flushing according to DP measurement
and flush according to Time Interval only.
Ignore DP After Flush
Set the time duration after the end of a flush cycle during which the DP reading is ignored.
End of Cycle
Set the time for the end of cycle signal to be ON after the flush cycle ends.
Relay Output
Set the operation of the Output relay to EOC (end of cycle ON), Alarm (set this output as an Alarm
output) or Disable (the relay is not active).
Valve 2 Mode
It is possible to connect a second solenoid to the system that can operate as a second filter or a
downstream valve.
Set the task for the second solenoid: Disable, 2nd filter or Downstream.
When a downstream valve is selected a new entry field is added to the Technician Screens List for
setting the delay time for the downstream valve.
IO Screen
This screen displays the status of the system's I/Os according to the currently designated filter
model:
Digital Input 1 type, Digital Input 3 type, the maximal reading of the Inlet pressure, the minimal
reading of the Outlet pressure, the Piston pressure and the current Battery Voltage.
This screen also allows the technician to test the operation of the system outputs:
Solenoid 1, Solenoid 2 and the Output Relay. Select ON or OFF.
Freezing Protection
Freezing Protection - This function is come to prevent from the filter to freeze in low temperature
while it connected to water source. Default: Enable

ADI-P 910101-000992 / 05.20 02 Page 13 of 21
Low Temperature
Threshold
Freezing Protection - Temperature setpoint to start filter flushing. Default: 4°c
Protecting Flushing
Interval
Freezing Protection - Flushing Interval while freezing protection Is activated. Default: 60 min
Important note: make sure to press SAVE after changing any of the above technician settings.
Additional Settings screens:
Export Data
This screen allows the user to export the controller’s data (as an Excel file). The screen displays a
list of supported applications for exporting the data (depending on the applications already
installed on the user’s smartphone.
Restore to Filter Type
Settings
Allows the user to reset the controller’s data and restore the default parameters for the current
filter type which is controlled by this controller.
Restore to Factory
Settings
Allows the user to delete all of the controller’s data and restore the factory default settings; The
default filter model will be according to the filter provided with the controller, or according to the
customer's initial settings.
Delete
Allows the user to delete a site from the smartphone.
Download and Export Reports
In addition to the on-screen reports, the ADI-P is capable of logging, storing, downloading and exporting status and
operation data through the user's smartphone.
1. Enter the "Export Data" section of the Settings Screen; In order to make sure that the system exports the
latest data, refresh the screen (slide your finger along the screen from top to bottom).
2. Depending on the general communication applications installed on your smartphone, the ADI-P application
displays the various options for sending the reports.
3. Select the preferred application, the recipient and send the reports.
4. ADI-P sends 5 reports in CVS file format (Excel): system-id, parameters-setup, flush-events, alarm-events
and params-setup-audit.

ADI-P 910101-000992 / 05.20 02 Page 14 of 21
Specifications Table
Item
Description
Remarks
Ideal Working Pressure
0-10 bar
0-150 psi
Burst pressure (Peak)
20 bar
300 psi
Power
Internal
4x1.5V AA batteries
External
7-14 VDC
1A external fuse, min 22 AWG wires
Temperature range
(-)10C to (+)60C
(+)14F to (+)140F
Weight
0.5 kg
1.1 lb
DP sensor
Internal
Internal Piston Pressure
Sensor
Optimized flush time
duration
IP Rating
IP65
User Interface
Via Smartphone
Application
Filter models
Sigma Pro , Mini Sigma , M104LPN , M104XLP ,
M106LP , M106XLP , M108LP , M110P , M102C ,
M103C , M103CL , M104C , M104CL , MG-110 , MG-
112-M , MG-112-S , MG-114-M , MG-114-S , SK
Compact 2"
Digital Inputs
DP Switch, Pause
Chain Controller Options
Onboard End of Cycle
Pulse
NO, NC
Standards
FCC 47CFR part 15: 2017, subpart B, Class B
ICES-003: 2016 Issue 6, Class b
AS/NZS CISPAR 32 :2015 Class B
EN 61326-1: 2013, basic immunity requirements, Class B
JEC 61010-1

ADI-P 910101-000992 / 05.20 02 Page 15 of 21
ADI-P Terminal Blocks Connections
Connecting NO or NC solenoids to the controller
Connecting NO or NC solenoids to the ADI-P Controller is possible depending on the filter type.
NO versus NC solenoids
a. Please note that NO solenoids have black manual overriding handles while NC solenoids have red manual
overriding handles.
b. For both solenoid types do not change the wires connection at the controller’s terminal strip; the black
wire should be connected to the black solenoid connector and the red wire should be connected to the red
solenoid connector.

ADI-P 910101-000992 / 05.20 02 Page 16 of 21
Annex A. Chaining ADI-P Controllers:
General:
It is possible to daisy-chain several ADI-P Controllers in order to operate a battery of filters’flushing according to a
single DP switch (either internal or external).
The DP switch that reads the pressure drop across the battery is the internal DP switch of the first controller in the
chain (the Primary) or an external DP switch connected to the Primary Controller. The End of Cycle output of the
Primary Controller is connected to the external DP input of the second controller in the chain (the first Secondary)
and this controller’s EC output is connected to the DP input of the rest. This type of connection can be spanned
over as many controllers as needed. (See page 17 –Stage 1: Wires Connection).
When the actual DP switch sends a signal, the Primary Controller starts a flush cycle. Once this cycle is completed
the Primary Controller sends a signal through its EC output to the second controller to start its flush cycle, and so
on to the last controller in the chain, as illustrated in the following:
Important Note: Please make sure that the DP delay in the chained controllers (Secondary controllers) is set to no
more than 5 seconds. This ensures proper transition from the last filter in the first controller to the first filter in the
next controller.
Optional
External DP
Switch
DP
Input
EC
Output
DP
Input
EC
Output
DP
Input
EC
Output
Primary Controller
Secondary 1 Controller
Secondary N Controller

ADI-P 910101-000992 / 05.20 02 Page 17 of 21
Connection Instructions:
The connecting process has two stages; Stage 1: wires connection. Stage 2: setting the ADI-P App for chained
operation.
Stage 1: Wires Connection
1. Connect between the Primary controller’s NO relay output and the Secondary controller’s external DP
input. Important: For your safety and in order to avoid damaging the controller, remove the batteries
before starting the wiring process.
2. Make sure that the wires’gauge (the diameter of the cable) used is similar to the solenoid wires’gauge
(~4 mm). This is critical for maintaining the IP65 rating of the controller (dust tight and protected against
water projected from a nozzle).

ADI-P 910101-000992 / 05.20 02 Page 18 of 21
Stage 2: Setting the Application
To connect the Adi-P App to the Primary controller, perform the following:
A. Click the Settings icon on the top right of the home screen.
B. Scroll down through the Settings screen.
C. Select Technician Settings.
D. Enter the password.
E. Select Mode of Operation.
F. Click on the current status of the controller (generally set to "Controller")
G. Under Choose Mode, select Primary mode for the current controller.
To change from Primary controller to Secondary controller, perform Steps A-F as above, and under Step G, select
Secondary mode.
Check the controller’s operation by starting a flush cycle through the application or by the controller's MANUAL
FLUSHING button.

ADI-P 910101-000992 / 05.20 02 Page 19 of 21
Annex B.
Connecting the ADI-P Controller to a DC external power source:
General:
The ADI-P system is powered by 4X1.5V AA consumer alkaline batteries (non-rechargeable, safety approved)
and/or by external safety approved external DC power supply 7-14VDC, max 1A (not provided with equipment).
Safety First:
When connecting the external power supply
•Make sure to comply with all the general and local regulations and standards required for connecting an
indoor / outdoor external power source.
•All external connections must be done by an authorized electrician with qualifications to perform this type
of work.
Type of Adaptor (Not supplied by Amiad)
•The adaptor should be a standard DC adaptor that supplies 7-14 VDC at its output connection.
•The system must be protected by a max 1A external fuse and it must use a minimum of 22 AWG wires.
Connections and Connection Drawing
•The DC output of the adaptor should be connected to the J1 terminal strip of the controller to the:
Power In (+) and Power In (–) connectors.
•For backup during power outages, the batteries may be left in place within the controller.
DO NOT USE RECHARGEABLE BATTERIES!
J2
1
1
8
8
J1

ADI-P 910101-000992 / 05.20 02 Page 20 of 21
Amiad Limited Warranty
1. This certificate applies to Amiad Water Systems Ltd. ("Amiad") products purchased by you (the "Buyer") from Amiad unless
specifically agreed otherwise in writing by Amiad. This Warranty extends only to the original purchaser, and is not transferable to
anyone who subsequently purchases, leases, or otherwise obtains the product from the original purchaser.
2. Amiad hereby warrants that the products are and will be free from defects in material and workmanship under normal use and
service. Amiad warrants that it will correct manufacturing defects in the products, in accordance with the conditions set out in this
Warranty.
3. This Warranty is enforceable for a period of 12 months after the date upon which the products were delivered (the “Warranty
Period”).
4. In the event that during the Warranty Period the Buyer discovers a defect in material and/or workmanship in any product or part (the
“Defective Product”), it shall submit a written complaint to Amiad using Amiad's standard Buyer Complaint Form. For the receipt of
the Buyer Complaint Form, the submission of the complaint or any questions please contact your service representative.
5. Upon written demand by Amiad the Buyer shall return the Defective Product - or a sample thereof - to Amiad, at Amiad's cost. If the
Buyer ships any such Defective Product, Amiad suggests the Buyer package it securely and insure it for value, as Amiad assumes no
liability for any loss or damage occurring during shipment. Provided however that in the event Amiad determines that this Warranty
does not apply to such product, Buyer shall promptly reimburse Amiad for such cost (including freight and customs). Any returned
product or part must be accompanied by the Warranty certificate and the purchase invoice. It is clarified that the Buyer may not
return the Defective Product unless such return was coordinated and approved by Amiad in advance.
6. Amiad's obligation under this Warranty shall be limited to, at Amiad's option, the repair or exchange, free of charge, of the product
or any part which may prove defective under normal use and service during the Warranty Period. The provision of a repair or
replacement of a product during the Warranty Period will result in an extension of the Warranty Period by an additional period of 12
months, provided that the total accumulated Warranty Period shall in any event be no more than 18 months from the date upon
which the products were delivered.
7. This Warranty is valid on the condition that the products are installed according to Amiad's instructions as expressed in Amiad's
instruction manuals and according to the technical limitations as stipulated in Amiad's literature or as stated by a representative of
Amiad.
8. This Warranty will not apply to damaged or defective products resulting from or related to:
(i) Fire, flood, power surges or failures or any other catastrophe and/or unforeseen occurrence, such as but not limited to those
for which the Buyer is customarily insured for, or any force majeure events;
(ii) Fault, abuse or negligence of the Buyer;
(iii) Intake water not meeting the agreed standards, as set forth in a written document, approved by Amiad, or improper storage;
(iv) Improper or unauthorized use of the product or related parts by the Buyer, including Buyer’s failure to operate the product in
conformity with the recommendations and instructions of Amiad, as set forth in Amiad's manuals and other written materials,
the operation of the product other than by a trained and qualified operator, or improper installation of the product by a third
party not authorized by Amiad;
(v) Performance by the Buyer of maintenance or operation other than in conformity with the recommendations and instructions of
Amiad, or other than in accordance with procedures defined in the literature supplied for products (including the timely
replacement of requisite parts), and for services provided other than by a trained and qualified advanced operator; or
(vi) Any alteration, modification, foreign attachment to or repair of the products, other than by Amiad or its authorized technical
representatives.
9. In no event shall Amiad be liable to the Buyer or any third party for any damages to property, or for any intangible or economic loss,
including loss of profits, loss of customers or damage to reputation, for any damages, including indirect, special, consequential
damages, or punitive damage arising out of or in connection with this Warranty, or arising out of or in connection with the product's
performance or failure to perform, even if it has been advised of the possibility of such damages.
10. Amiad will be excused for failure to perform or for delay in performance hereunder if such failure or delay is due to causes beyond its
reasonable control or force majeure preventing or hindering performance.
11. This Warranty set forth herein is the only contractual warranty given by Amiad and is provided in lieu of any other warranties created
by any documentation, packaging or otherwise.
12. Amiad makes no warranty whatsoever in respect to accessories or parts not supplied by Amiad. In the event that Amiad is required to
correct a Defective Product or product not covered by this Warranty, it will do so solely in consideration for additional fees.
13. The parties will actively endeavor to amicably settle any dispute arising between them. In the event that the parties are unable to
reach an equitable settlement of such dispute, any claim or lawsuit related to the Warranty, its validity execution, its performance be
brought before only the courts of Tel-Aviv, Israel. Israeli law will govern the Warranty, to the exclusion of any conflict of law rules.
Other manuals for ADI-P
1
Table of contents
Other amiad Controllers manuals
Popular Controllers manuals by other brands

CBE
CBE PRS300 user manual

RKI Instruments
RKI Instruments Beacon 110 Operator's manual

Motrona
Motrona CT 701.04 operating instructions

Texas Instruments
Texas Instruments TMDSHVMTRPFCKIT quick start guide

NotaTech
NotaTech 8000SeriesI/O product catalog

Bosch
Bosch WORCESTER Sense II installation instructions