Ampac NZ100 Series Guide

MAN2336 June 2006
N
N
NZ
Z
Z1
1
10
0
00
0
0
S
S
Se
e
er
r
ri
i
ie
e
es
s
s
F
F
Fi
i
ir
r
re
e
e
A
A
Al
l
la
a
ar
r
rm
m
m
C
C
Co
o
on
n
nt
t
tr
r
ro
o
ol
l
l
P
P
Pa
a
an
n
ne
e
el
l
l
N
N
NZ
Z
ZS
S
S4
4
45
5
51
1
12
2
2
2
2
20
0
00
0
03
3
3
“Our aim is to provide ‘ Consistently Excellent Service ’in the eyes of our customers ”
INSTALLATION
COMMISSIONING
&
OPERATION
FIRE
DEFECT
NORMAL
FIRE ALARM PANEL
NZ100
SILENCE ALARMS
BIGADE USE ONLY EVACUATION
AMPAC

NZ100 Installation Commissioning & Operation
Page 1

NZ100 Installation Commissioning & Operation
CONTENTS PAGE NO.
1. INTRODUCTION................................................................................................................1
1.1 Unpacking and Inspection................................................................................................. 1
1.2 Anti Static Precautions .................................................................................................... 1
2. SPECIFICATIONS.............................................................................................................1
2.1 Power Supply/Battery Charger.......................................................................................... 1
2.2 Outputs .......................................................................................................................... 1
2.3 Detector Circuit ............................................................................................................... 1
3. SYSTEM DESCRIPTION..................................................................................................2
3.1 General Description ......................................................................................................... 2
3.2 Front Panel Layout .......................................................................................................... 2
3.3 Internal Layout................................................................................................................. 3
3.4 Detector Circuits.............................................................................................................. 3
3.5 Bell Circuits .................................................................................................................... 4
3.6 Auxiliary Output............................................................................................................... 4
3.7 Walk Test....................................................................................................................... 4
3.8 Buzzer............................................................................................................................ 4
3.9 Buzzer Mute................................................................................................................... 4
3.10 Defect Indicators.............................................................................................................. 4
3.11 Power Supply.................................................................................................................. 5
3.12 Mains On Indicator........................................................................................................... 5
3.13 Fusing............................................................................................................................ 5
3.14 Batteries......................................................................................................................... 5
4. CONNECTING DEVICES.................................................................................................6
4.1 Detectors........................................................................................................................ 6
4.2 Detector Limitations......................................................................................................... 6
4.3 Manual Call Points........................................................................................................... 6
4.4Bells and Sounders.......................................................................................................... 8
4.5 Auxiliary Relay ................................................................................................................ 8
5. SETTINGS...........................................................................................................................9
5.1 Gating ............................................................................................................................ 9
5.2 No Brigade Board ............................................................................................................ 9
6. INSTALLATION AND INITIAL OPERATION..............................................................10
6.1 Installing the NZ100 ........................................................................................................10
6.2 Initial operation...............................................................................................................10
7. INSTALLING THE BRIGADE BOARD (SGD TYPE II ).............................................11
8. ASPI RELAY BOARD.....................................................................................................13
9. SYSTEM OPERATION....................................................................................................14
9.1 Resetting the system......................................................................................................14
9.2 Using the Walk Test facility.............................................................................................14
9.3 Evacuation. ....................................................................................................................14
10. TROUBLESHOOTING....................................................................................................15
11. APPENDIX........................................................................................................................16


NZ100 Installation Commissioning & Operation
Page 1
1. INTRODUCTION
1.1 Unpacking and Inspection
Carefully check packing before unpacking goods for any transit damage. Unpack the goods and check
both externally and internally for any loose or damaged components that may affect the appearance,
installation or operation of the goods.
1.2 Anti Static Precautions
To prevent damage to panel components please ensure before touching or handling any of the wiring or
printed circuit boards within the panel that you are correctly earthed.
2. SPECIFICATIONS
Size 220mmH x 290mmW x 80mmD
2.1 Power Supply/Battery Charger
Mains Supply 230V AC ± 10% @ 0.5A
Charger Output Voltage 13.5V DC
Output Current 0.5A
Battery (one of only) 12V 7AH
System Quiescent Current 22mA
(After 10 minutes battery operation)
2.2 Outputs
Bell Circuits (2 total)
Voltage 12V DC
Maximum current 3A max for both circuits
End of line resistor 10kOhm 1/4W 2%
Auxiliary output
Voltage 12V
Current 50mA max
2.3 Detector Circuit
Line voltage (open circuit) 22V
Short circuit current 22mA
Maximum Cable Length Impedance 100 ohm
End of line resistor 6.8kohm 1/4W 2%
Devices Smoke detectors 24V
Electronic heat detectors 24V
Contact heat detectors
Manual call points

NZ100 Installation Commissioning & Operation
Page 2
3. SYSTEM DESCRIPTION
3.1 General Description
The NZ100 is an automatic fire alarm system. The NZ100 has one fire detection circuit able to
accommodate heat detectors, smoke detectors, manual call points or a combination of these devices.
The NZ100 has a monitored bell output to alert personnel in the event of a fire.
All circuitry except for the front panel LED’s is on a single printed circuit board.
3.2 Front Panel Layout
EVACUATIONSILENCE ALARMS
BRIGADE USE ONLY
DEFECT
NORMAL
Fire Alarm Panel
NZ100
FIRE
Figure 1: Front Panel Layout
MODEL:
S/No:
REG No :
TESTED BY :
DATE :
NZ100
AC/102
LINK SETTINGS
LINK
K1-1
SMOKE
ONLY
K1-2
GATING
FUSE RATINGS
FUSE
MAINS TERMINATON
BELL, F1
BATTERY, F2
SECONDARY AC, F3
FITTED
SMOKE
DETECTORS
ONLY
GATING ON
NOT FITTED
MIXED ZONE
MANUAL CALL POINTS
HEAT DETECTORS
AND SMOKE DETECTORS
GATING OFF
RATING AND TYPE
0.5A M205
3A M205
0.8AM205
0.8A M205
L003 CAMLOCK
8 Way Ribbon Cable
Cabled to CN2 of the
Main System Board
PCB
LED
M3 NUT
M3 NUT
API 595 MOUNTING
M3 STUD
5 - 5.5mm
LED3 LED1LED2
R3
TB1
R2
D3
R1
D2 D1
API
+VE 123
595A
Red
YellowGreen
+ve
1
23
Lamp Test
Label
Silence Alarms
Brigade Use
Only Keyswitch
Trial
Evacuation
Keyswitch
Front Door
Chassis
Earth
Terminal
To Mains Earth Door Hinge
Figure 2: Internal Front Panel Layout

NZ100 Installation Commissioning & Operation
Page 3
3.3 Internal Layout
Mains Transformer
Mains Termination
Reset Switch
Buzzer Mute Switch
Walk Test Switch
3A
0V
DS1232
U4
UA78S40P
U2
ST6265
U3
CN4
TB2
U1 L1
RL1
TB1
TB3
RN5
CN2
CN3
K3
SW1 SW2 SW3
CN1
MC74HC595A
U5
K1
TX CONNECTION
BELL
+
-
-
+
-
+
-
WALK TEST BUZZER
MUTE
NORMAL
BELL
SYS.
DEFECTS
SMOKE ONLY
+
AUX
1
2
SECONDARY
FUSE
BELL
BATT
MAINS ON
30V C.T
15V A.C.
TX
302 665B
1
2
3
BATTERY
BELL
DET
BRIGADE
ASPI
GATING
3
RESET
+
Fuse
Battery
12 Volt
7 AH
ZONE
BATT.
Shows
Panel
Mounting
Keyholes
Black
Red
Knockouts
To Battery
Bell
Bell
Detectors
Mains Earth
to Front
Panel
Front Panel
+
BZ1
U6
F1
0.8A
F2
0.8A F1
AC IN
Brigade Board
( If Fitted )
Relay Board
( If Fitted )
Link Pins 5,6 if
Board NOT Fitted
Figure 3: Internal Layout
3.4 Detector Circuits
The detector circuit acceptssmoke detectors, heat detectors or manual call points that will cause the
panel to go into alarm within one second. Detector types used are subject to the compatibility
limitations as described in section 4.
Devices such as smoke detectors, which signal by increasing line current, can, when signalling, go
through “gating” or Alarm Verification. As such, when a detector goes into alarm, it is reset and not
monitored for two to three seconds, if an alarm is still present after this time, the system will then latch
into alarm. This function may be de-selected if not required by removing link K1-2 (GATING). See
section 5 for details.
Important:
Detector line voltage is 22V (open circuit). Current signalling detectors ( smoke or electronic
heat ) must be rated for 24V operation.

NZ100 Installation Commissioning & Operation
Page 4
3.5 Bell Circuits
The NZ100 provides a monitored bell circuit split to drive up to three (3) Amps of alarm load. The circuit
is split into two parallel lines, which must be less than three (3) Amps total. Each line requires a 10K
EOL resistor to give a system normal indication. If either output line is open or shorted, a defect signal
is generated and the “BELLS” defect LED is illuminated.
See section 4 for connection details.
3.6 Auxiliary Output
The NZ100 system provides an auxiliary output, marked AUX (CN1) on the PCB, designed to drive a
relay which can provide 12V ( nominal ) @ 50ma for the control of ancillary devices.
This output is;
âswitched off during an alarm;
ânormally powered, when a relay is connected which increases the quiescent system
current and reduces the battery backup time.
3.7 Walk Test
This function is initiated by pressing the walk test button on the 302-665B. When pressed;
âa LED directly above the switch will indicate the test is active;
âthe test will remain active for ten minutes ( automatically cancelling itself after this time);
âdetectors can be operated in the field ( reset by the panel after four seconds ).
To restore the panel to normal operation, repress the switch and the walk test indicator will turn off.
3.8 Buzzer
The NZ100 has an internal buzzer that will sound;
âcontinuously should any defect occur; and
âin short bursts to confirm any key switch operation.
3.9 Buzzer Mute
Pressing this switch will cause the buzzer to stop sounding though should another defect occur after
this time the buzzer will sound again.
3.10 Defect Indicators
Defect indicators are provided on the NZ100 for the following.
(a) Battery Fault. This indicates one of the following:
âBattery voltage is below 12.2 Volts during discharge (mains failure).
âBattery voltage is below 12.6 Volts whilst charging.
âBattery voltage is above 14 Volts.
âBattery is not connected.
âBattery failed automatic test.
(b) Bell Fault. This indicates an open or short circuit on bell line/s.

NZ100 Installation Commissioning & Operation
Page 5
(c) System Fault. This indicates one of the following system faults
âMains not present, indicates after ten minutes.
âDoor closed with switches on brigade board not in normal position.
âBrigade board disconnected.
âMicroprocessor fault.
(d) Zone fault.This indicates a fault on the zone wiring. This can either be a short circuit or
open circuit.
3.11 Power Supply
The 302-665B has an onboard power supply providing 13.5VDC at 0.5A for system power and charging
the system batteries. The system incorporates atest function, controlled by the CPU,that decreases
the power supply output voltage to approximately 10V for 1 hour each dayto check the condition of the
system battery. If the battery voltage falls below 12.2V during the test period a defect signal is
generated and the battery fault LED is illuminated.
3.12 Mains On Indicator
This LED is illuminated when the mains supply is connected and operational.
3.13 Fusing
The NZ100 has four fuses:
Designator Function Rating
F1 Bell circuit fuse 3 Amp M205
F2 Battery circuit fuse 0.8 Amp M205
F3 Power supply fuse 0.8 Amp M205
F4 Mains fuse 0.5 Amp M205
3.14 Batteries
The NZ100 system is designed to accept one 12V, 7 AH sealed lead acid battery. This should provide
more than 240 hours of backup capacity leaving sufficient capacity to drive the alarm load for the
required 30 minutes.

NZ100 Installation Commissioning & Operation
Page 6
4. CONNECTING DEVICES
4.1 Detectors
A sample of the detectors approved for use with the NZ100 are listed below. ( See Appendix )
Detector Type Iq Circuit Limit Order Code
Apollo Series 65 Ionisation Smoke Detector 45µA35 55000-217
Apollo Series 65 Photoelectric Smoke Detector 45µA35 55000-317
Apollo Orbis Photoelectric Smoke Detector with
Flashing LED 65µA24 201-0501
Thermal Detector Blue Indicating 40µA40 4255-0300
Thermal Detector Yellow Indicating 40µA40 4255-0400
Ampac Fireray Beam 2000 8mA N/A 220-0004
Ampac Fireray Beam 50R 4N/A 220-0005
Ampac Fireray Beam 100R 4N/A 220-0006
Note: Iq = Quiescent Current Draw
The maximum current on the Detector Circuit is 1.6mA, or 1600µΑ
Rate of Rise Heat Detectors are also available.
FACP
+
-
6K8
EOL
1
2
SCREW
CAPS
MOUNTING
HOLES
WIRE IN WIRE OUT
WIRE IN
TERMINATING METHOD
AMPAC
27.0
LED
MEASURE LINE VOLTAGE
WIRE OUT
UP TO 40 DETECTORS CAN BE
CONNECTED TO EACH CIRCUIT
NOTE:
TB5
AMPAC
MANUAL CALL POINT
IN + + OUT
IN - - OUT
SERIES
65 DETECTOR
L1 In -R
L2
Earth
L1 Out
AMPAC HEAT
DETECTOR
Figure 4: Example of Detector & MCP Wiring
The zone circuit must be terminated with an end of line resistor with a value of 6.8K (2%
tolerance or better, power rating 1/4W)
4.2 Detector Limitations
1. Most detectors, with the exception of thermostatic heat detectors, draw a small
monitoring current and this limits the number detectors that can be connected to a
given zone circuit. The total quiescent current of all devices on a zone circuit must be
less than 1.6mA @ 24V to ensure correct operation.
2. Detectors are not intended for use in areas subject to higher than normal corrosive
environments or where hydrogen sulphide or other corrosive gasses may be present.
4.3 Manual Call Points
Type Quiescent Current Circuit Limit Order Code
Ampac Manual Call Point 40µA40 4255-0700

NZ100 Installation Commissioning & Operation
Page 7
Connect as shown above.

NZ100 Installation Commissioning & Operation
Page 8
4.4 Bells and Sounders
Two bell/sounder circuits are provided, capable of driving a combined load of three (3)Amps. Theselines
are monitored using a small current in reverse polarity to normal operation. For this reason it is
necessary to observe bell/sounder polarity and connect bells via diodes, 1N4004 diodes are
recommended, as shown below.
EOL
10K RESISTOR BELLS
1N4004
DIODES
TB2
ZD1
BELL
+
-
-
+
-
+
BELL
DET
Figure 5:Bell/Sounder Connections
Compatible Devices
Order Code Description
206-0002 * Bell 12VDC Red 150 mm.
205-0006 * Horn Siren 12VDC 200mA Red.
205-0002 * AS2W Flush sounder White 12/24V 15mA .
205-0001 * AS2R Flush sounder Red 12/24V 15mA.
205-0009 Vara Sounder white AS2220 Evac Tones
205-0011 Vector Sounder white AS2220 Evac Tones
205-0062 Vantage Sounder AS2220 Evac Tones ( Red )
205-0063 Vantage Sounder AS2220 Evac Tones ( White
205-0066 Vantage Combi Sounder AS2220 Evac Tones ( Red )
205-0067 Vantage Combi Sounder AS2220 Evac Tones ( White )
* Note: these devices do not comply with NZS4512 2003
4.5 Auxiliary Relay
An auxiliary relay can be fitted ifrequired to signal ancillary devices. Connect the coil of the relay to the
AUX output connector as shown below and ensure a fly back diode is fitted across auxiliary relay.
302 3171
+
-
C6
C5
TB2
M3
M1 M4
ZD1
C2
CN1
BELL
+
-
-
+
-
+
AUX
1
2
BELL
DET
The Output of CN1 is:
Pin1 = Coil Positive ( + )
Pin2 = Coil Negative ( - )
Figure 6: Auxiliary Wiring

NZ100 Installation Commissioning & Operation
Page 9
5. SETTINGS
The NZ100 system has two (2) link options. K1/2 sets the “Gating” function, K1/1 and K1/3 arenot used
and a link fitted pins 5 and 6 of CN3 identifies the absence of a Brigade Board.
If removing a jumper link, it is a good idea to refit it to one of the header pins. This will avoid losing the
jumper, which may be required at a later date.
Important: Link K3 is for use during factory testing only, this must not be fitted.
5.1 Gating
“GATING” is an automatic verification facility to reduce nuisance alarms caused by a transient condition.
When the “GATING” link (K1-2) has been fitted, the signal from smoke detectors and electronic heat
detectors is verified before an alarm is recognised.
K1
DEFECTS
NOT USED
GATING
3
BATT.
LINK
1
2
Figure 7: K1 Linking Set to GATING and Link Storage to a Single Header Pin
5.2 No Brigade Board
If a brigade board is not fitted it is necessary to fit a jumper link from pin 5 to pin 6 of CN3 (BRIGADE).
This link is fitted at the factory to systems without the brigade board. Failing to have the link fitted will
cause a system fault.
Pin 1
Link Fitted to
Pins 5 & 6
U4 U6
U7
C26
C25
R33
CN4
RN4
R32
C22C18
R24
CN2
CN3
R26
D8
C15
C20
X1
C19
R30
R31
D22
K3
D16
D18 D21
BRIGADEASPI
++
+ +
U3
ST6265
74HC132
Cabling To
Front Panel
Figure 8: Link Location When a Brigade Board is NOT Fitted

NZ100 Installation Commissioning & Operation
Page 10
6. INSTALLATION AND INITIAL OPERATION
6.1 Installing the NZ100
Do not apply power or connect batteries during this procedure.
1. Unpack NZ100.
2. Check for transit damage.
3. Drill all cable access and mounting holes.
4. Provide insulation grommet for mains entry hole
3. Mount the unit into position.
4. Feed cables into the unit.
5. Connect mains cabling to the mains terminal block.
6. Anchor incoming Mains cable with cable tie provided, through chassis holes provided.
5. Connect detector cabling.
6. Connect ancillary cabling.
7. Set links as required. See section 5.
12. Ensure all swarf is removed from panel before applying power.
6.2 Initial Operation
1. Switch on Mains power to the unit.
2. Battery defect LED should illuminate after 10 seconds.
2. Connect batteries. Press ‘RESET’, Battery defect LED should extinguish.
4. The unit is ready for operation.

NZ100 Installation Commissioning & Operation
Page 11
7. INSTALLING THE BRIGADE BOARD (SGD type II )
The Brigade Board interfaces to a Line Transmitter to facilitate monitoring by a Fire Brigade or
monitoring service. It can be supplied installed or in fast fit kit form which contains all the necessary
parts for installation. Fitting the board is a simple procedure as detailed and illustrated below.
1. Turn off power and disconnect the battery.
2. Fit door switch bracket assembly to top right corner of cabinet with M3 screws supplied.
2. Fit four nylon standoffs onto 302 -665B.
4. Remove the jumper link from CN3 and fit the six-way cable.
5. Remove the left bottom screw of 302 -665B and install the earth cable as shown below.
6. Fit 302 -678 onto nylon standoffs as shown below.
6. Connect the six-way cable to CN2 of 302 -678 and the two-way cable to CN1.
8. Terminate Line Transmitter ( LTX ) cables to 302 -678.
9. Set the K1 links to the assigned address.
10. Switch power on to NZ100 and connect battery.
11. Test the monitoring in accordance with the LTX SDG Input Interface Specifications.
Note: When the SGD is ordered with the panel, the SGD will be fitted and programmed prior to delivery.
Fit25mmnylon
standoffs into
302 665B board.
Then fit 302 678
board to standoffs.
Fit door switch bracket
with M3 screws.
Fit 6 way cable from CN3 of the
302 - 665B to CN2 302 - 6780
Fit 2 Way cable to door switch.
Fitearthwire
from 302 678
to under screw
of 302 665B.
3A
F1
0V F3
0.8A
F2
C14
TB2
BZ1
D6
SW1 SW2 SW3
CN1
BELL
+
-
-
+
-
WALK
TEST BUZZER
MUTE
NORMAL
BELL
SYS.
ZONE
BATT.
+
AUX
1
2
SECONDARY FUSE
BELL BATT
MAINS ON
15V A.C.
302 665B
BELL
DET
RESET
+
AMPAC
SGD
Type
II
A
+
-
B
NORMAL
NORMAL
ISOLATE TEST
NORMAL
FIRE
DEFECT
ISOLATE
POLL
DOOR
SWITCH
302 678
U7
+
BZ1
CN1
U3
U4
TB1
U2
R12
U6
U5
SW2
SW1
Cable
to LTX
Interface
& 12 volt
Supply
+
CN2
FIRE
SYSTEM
K2
K1
F1
250mA
SDG
ADDRESS
AllLinks
Off = 16
1
2
3
4

NZ100 Installation Commissioning & Operation
Page 12
Figure 9:Brigade Board Installation

NZ100 Installation Commissioning & Operation
Page 13
8. ASPI RELAY BOARD
The ASPI (AMPAC Serial Peripheral Interface) relay board will provide the NZ100 system with a 5-amp
relay contact for use by ancillary devices.
The relay is normally de activated and can be selected to be activated by the fire zone ALARM,
DEFECT or a system NORMAL condition. The type of condition is set by the SELECT OUTPUT links
(LK3).1 = ALARM
2 = DEFECT
3 = NORMAL
The ASPI board has to be addressed for correct operation in the NZ100 panel. This is set by the
ADDRESS links LK1 pin 3 as shown below.
To install the 302-5930:
1. Power system down.
2. Mount the board on standoffs and mount within the NZ100 cabinet, as the Serial Interface
Standard does not allow for long runs.
3. Use the 8 way Ribbon supplied to connect CN1 (302-5930) to CN4 (302-665B).
4. Connect the ancillary devices to TB1
The panel is now ready to power up and the relay checked for desired outputs.
TO CN4 OF THE MAIN SYSTEM BOARD 302 593
N/O
COM
N/C
N/C=NORMALLY CLOSED
COM=COMMON
N/O=NORMALLY OPEN
C5
+
C4
+
RN1
C3
R7
R1
R6
R5
K3
SELECT
R4
U3
LM78L05
K1
ADDRESS
CN2CN1
TB1
C2
C1
K2
RTN
RL1
JS1-12V
Q1
BD139
U2
74HC595
U1
74HC138
D11
D10
D9
D8
D7
D6
D5
D4
D3
D2
D1
R3
R2
D12
OF SELECT JUMPERS 1 to 3
FIT ANY COMBINATION ADDRESS JUMPER 3
K1 FIT ONLY ONE
7
8
6
5
4
3
2
17
6
5
4
3
2
1
N/O
COM
N/C
302 5930
ASPI
K1
1
K3
1
2
3
4
5
6
7
8
NOT USED
Example: Relay set
to operate on Alarm
Figure 10: ASPI Relay Board Layout with “SELECT” Set to Activate on Alarm
+Note:Should there be a need to extend a panels control functions this board can be supplied in kit form
( order Kit 155 –0015 ).

NZ100 Installation Commissioning & Operation
Page 14
9. SYSTEM OPERATION
9.1 Resetting the System
To reset the system after a fire, press the ‘RESET’ button on the 302-665B. This will return the system
back to its normal state. The buzzer will sound for confirmation.
9.2 Using the Walk Test Facility.
To start the walk test facility, press the ‘Walk Test’ switch on the 302-665B. The buzzer will beep once
and the LED above the switch will illuminate.
The detectors can now be tested. When a detector is set into alarm the system will operate as normal
for approximately four seconds. After this time the detectors on the circuit in alarm will be reset.When
testing is complete, press the ‘Walk Test’ switch to return to normal.
The walk test facility has an internal time out and will be de-selected automatically after ten (10)
minutes of operation.
9.3 Evacuation.
On the door of the NZ100 a key switch is provided for Evacuation, operating this key switch will cause
the system to operate the bells /sounders. This will override any other bell isolate or silence condition.

NZ100 Installation Commissioning & Operation
Page 15
10. TROUBLESHOOTING
Problem Possible cause/s Suggested remedy/ action
Mains LED is off Mains supply is not operational.
AC Fuse on 302-665B or Mains
Fuse is blown.
Check mains supply.
Check and replace if necessary
F3 on 302-665B, and Mains
Fuse F4.
Bell circuits in defect. Diodes not fitted in series with
bell.
End of line not fitted.
Fuse blown.
Fit diodes to bells as shown in
section 4.
Fit end of line resistor
Check fuse F1 on PCB.
Replace if necessary.
Zone always in defect.
Line is shorted.
Line is open.
End of line not fitted.
Check and remove short.
Check line and rectify.
Fit 6K8 resistor to end of line.
System fault light is on.
(Mains is on). Brigade board is disconnected.
No brigade board.
Connect brigade board.
Make sure link is fitted to CN3,
pins 5 and 6.
Defect occurs when door is
closed. Isolate or Test switches on
brigade board not in normal
position
Return switches to normal
position.

NZ100 Installation Commissioning & Operation
Page 16
11. APPENDIX A
QI= Quiescent Current Draw
Cct Max = The maximum number of devices that can exist on any one circuit ( IE 1.6mA max/cct ).
Heat Detectors
Order Code Description Q I Cct Max
4255-0300 Heat Detector blue Indicating 57°C 40µA40
4255-0400 Heat Detector yellow Indicating 77°C 40µA40
Note: Rate of Rise Heat Detectors are also available.
Smoke Detectors
Order Code Description
55000-217 Apollo Series 65Ionisation (LPC) 45µA35
55000-317 Apollo Series 65 Optical (LPC) 45µA35
55000-220 Apollo Series 65Integrating Ionisation (LPC) 45µA35
45681-200 Apollo Series 60/65 universal base N/A
201-0501 Apollo Orbis Optical with Flashing LED 65µA 24
201-0505 Apollo Orbis MultiSensor 65µA 24
201-0528 Apollo Orbis universal base N/A
Beam Detectors
Order Code Description
220 0004 Fireray 2000 Beam Detector Tx/Rx/controller 8mA N/A
220 0005 Fireray 50R Beam Detector 4mA N/A
220 0006 Fireray 100R Beam Detector 4mA N/A
Manual Call Points
Order Code Description
213 0042 Ampac Manual Call Point 40µA40
Table of contents
Other Ampac Control Panel manuals

Ampac
Ampac ZoneSense Plus Guide

Ampac
Ampac ZoneSense Plus Guide

Ampac
Ampac FireFinder Series II AS442 User manual

Ampac
Ampac EV3000 4210-0030 Guide

Ampac
Ampac ZoneSense Product guide

Ampac
Ampac ZoneSense Plus Owner's manual

Ampac
Ampac LoopSense MAN 1572-4 User manual

Ampac
Ampac Fire Finder EN54-2 Guide

Ampac
Ampac LoopSense User manual

Ampac
Ampac FireFinder II Series Instruction Manual
Popular Control Panel manuals by other brands

Danfoss
Danfoss VLT LCP 32 installation guide

Erreka
Erreka SMART-D201 Quick installation and programming guide

Digital Monitoring Products
Digital Monitoring Products XTLplus 9000 Series user guide

Mircom
Mircom FX-2000 series Operation

Gemini
Gemini GEM-P816 installation instructions

DSE
DSE 7220 installation instructions