manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Ampac
  6. •
  7. Fire Alarm
  8. •
  9. Ampac 4210-0050 User manual

Ampac 4210-0050 User manual

MAN3052-2
Input Output Device Range Item Number: 4210-0050, 4210-0057
Installation guide
1
Description
The Input Output Device range comprises of the
following eight variants:
4210-0050
Single Input Output Device DIN Mount
4210-0051
Single Input Output Device Enclosed
4210-0052
Single Input Device DIN Mount
4210-0053
Single Input Device Enclosed
4210-0054
Three Input Output Device DIN Mount
4210-0055
Three Input Output Device Enclosed
4210-0056
Three Input Device DIN Mount
4210-0057
Three Input Device Enclosed
The DIN-Rail Mounted Devices are designed to be
mounted in an enclosure, clipped onto a standard
35mm DIN Rail (DIN46277) and secured using the built
in fixing. End stops can also be used to provide
additional security. Alternatively, the Devices can be
mounted direct to an enclosure back panel using the
internal preformed fixing holes.
The Enclosed variant Devices are each supplied within
a backbox and are suitable for surface mounting.
Note: the Devices are not intended for outdoor use
unless mounted in a suitable weatherproof enclosure.
The installation must conform to applicable local codes
and be carried out such that the Devices are not
subjected to exposure to temperatures exceeding the
maximum ambient, exposure to moisture, dust and
foreign bodies or exposure to a risk of mechanical
damage.
The Devices are all loop powered and are controlled by
the main fire control panel. The address is set using the
onboard DIL switch.
Each Device incorporates a bi-directional short circuit
isolator between the loop input and loop output
terminals which will protect the external Input
monitoring circuit against a single loop short circuit on
either side of the device.
Installation
DIN Rail
Clip the Input/Output Device to the standard 35mm
DIN rail using the Red locking clip located in the front of
the device. Alternatively, fix direct to the enclosure back
panel using appropriate M4 nuts and bolts.
Enclosed
Remove the clear ABS cover and securely mount the
backbox to a wall or suitable structure using the
integral fixing positions then install all external cables
using the knock outs and/or cable tray entry points as
required.
1. Connect the cables from the detection loop and the
conventional detector zone into the device. Ensure
that the earth continuity is maintained.
2. Set the Device address using switches 1-7 on the
DIL switch in accordance with the address Table 2
and record the location description of the device
itself together with the address setting on the
device fascia label.
3. For commissioning purposes, set the LED
Indications to On using switch 8 of the DIL switch.
This can be disabled upon completion of testing &
commissioning.
4. Following commissioning ensure that the device is
securely fastened and replace the ABS clear cover.
Schematic Diagram (4210-0054)
LED Indications
The Device has several onboard LEDs which provide
indication for Input Active (Alarm), Output Active, Loop
Polling/Short Circuit Isolation and Fault conditions.
Function
Colour
Mode
Description
Input
Yellow
On
Input is active
Input
Yellow
Flashing
Input is in fault
Output
Red
On
Output is active
S/C Poll
Green
Flashing
Device is being
polled
S/C Poll
Green
On
Loop Short
MAN3052-2
Input Output Device Range Item Number: 4210-0050, 4210-0057
Installation guide
2
Maximum Loop Current Consumption
4210-0050/1 (LEDs disabled)
Quiescent Current
1.3mA
Input On
1.5mA
Output On
1.3mA
Total (All On)
1.58mA
Refer PDS for remaining range of devices.
Commissioning
It is important that the Device is tested thoroughly after installation by initiating an alarm condition at Input circuit.
Initiation of both an open and short circuit fault condition at a suitable location on the circuit will also prove the integrity
and reliability of the system.
Troubleshooting
Before investigating individual device faults, it is important to check that the system wiring is fault free. Earth faults on
the data loops or zone input conventional detector circuits may cause communications errors to occur.
Many fault conditions are the result of simple wiring errors. Check all terminal connections to the device and make sure
that the correct value EOL devices/resistors are fitted where necessary.
Fault Finding
Symptom
Possible Cause
No response
Incorrect address setting
Incorrect loop wiring
Fault condition reported
Incorrect input wiring
Incorrect EOL resistor fitted
Analogue value unstable
Dual address
Loop data fault
Data corruption
Constant alarm
Incorrect input wiring
Incorrect EOL fitted
Incorrect control panel software
MAN3052-2
Input Output Device Range Item Number: 4210-0050, 4210-0057
Installation guide
3
Table 2 –Address DIL Switch Settings
The address is set using the first seven switches of the 8 way DIL switch (marked address). Switch 8 enables and
disables the on-board LED indications.
DIL switch setting
DIL switch setting
DIL switch setting
DIL switch setting
DIL switch setting
Address
1234567
Address
1234567
Address
1234567
Address
1234567
Address
1234567
1
1000000
26
0101100
51
1100110
76
0011001
101
1010011
2
0100000
27
1101100
52
0010110
77
1011001
102
0110011
3
1100000
28
0011100
53
1010110
78
0111001
103
1110011
4
0010000
29
1011100
54
0110110
79
1111001
104
0001011
5
1010000
30
0111100
55
1110110
80
0000101
105
1001011
6
0110000
31
1111100
56
0001110
81
1000101
106
0101011
7
1110000
32
0000010
57
1001110
82
0100101
107
1101011
8
0001000
33
1000010
58
0101110
83
1100101
108
0011011
9
1001000
34
0100010
59
1101110
84
0010101
109
1011011
10
0101000
35
1100010
60
0011110
85
1010101
110
0111011
11
1101000
36
0010010
61
1011110
86
0110101
111
1111011
12
0011000
37
1010010
62
0111110
87
1110101
112
0000111
13
1011000
38
0110010
63
1111110
88
0001101
113
1000111
14
0111000
39
1110010
64
0000001
89
1001101
114
0100111
15
1111000
40
0001010
65
1000001
90
0101101
115
1100111
16
0000100
41
1001010
66
0100001
91
1101101
116
0010111
17
1000100
42
0101010
67
1100001
92
0011101
117
1010111
18
0100100
43
1101010
68
0010001
93
1011101
118
0110111
19
1100100
44
0011010
69
1010001
94
0111101
119
1110111
20
0010100
45
1011010
70
0110001
95
1111101
120
0001111
21
1010100
46
0111010
71
1110001
96
0000011
121
1001111
22
0110100
47
1111010
72
0001001
97
1000011
122
0101111
23
1110100
48
0000110
73
1001001
98
0100011
123
1101111
24
0001100
49
1000110
74
0101001
99
1100011
124
0011111
25
1001100
50
0100110
75
1101001
100
0010011
125
1011111
126
0111111

This manual suits for next models

7

Other Ampac Fire Alarm manuals

Ampac Apartment Module User manual

Ampac

Ampac Apartment Module User manual

Ampac FireFinder II Series User manual

Ampac

Ampac FireFinder II Series User manual

Ampac FireFinder PLUS Guide

Ampac

Ampac FireFinder PLUS Guide

Ampac Warning Sign 4210-011 User manual

Ampac

Ampac Warning Sign 4210-011 User manual

Ampac ZoneSense Plus Guide

Ampac

Ampac ZoneSense Plus Guide

Ampac ACP-02 User manual

Ampac

Ampac ACP-02 User manual

Ampac MAN 3038 User manual

Ampac

Ampac MAN 3038 User manual

Ampac NZ 100 User manual

Ampac

Ampac NZ 100 User manual

Ampac ACP05 User manual

Ampac

Ampac ACP05 User manual

Ampac 4310-0086 User manual

Ampac

Ampac 4310-0086 User manual

Ampac FireFinder PLUS Guide

Ampac

Ampac FireFinder PLUS Guide

Ampac 4310-0082 User manual

Ampac

Ampac 4310-0082 User manual

Ampac ZoneSenseDH4 Guide

Ampac

Ampac ZoneSenseDH4 Guide

Ampac ZoneSense PLUS Agent Release Guide

Ampac

Ampac ZoneSense PLUS Agent Release Guide

Ampac ZoneSense Plus Guide

Ampac

Ampac ZoneSense Plus Guide

Ampac FireFinder NZS 4512 User manual

Ampac

Ampac FireFinder NZS 4512 User manual

Ampac ZoneSense User manual

Ampac

Ampac ZoneSense User manual

Ampac ACP-02 User manual

Ampac

Ampac ACP-02 User manual

Ampac XP95 User manual

Ampac

Ampac XP95 User manual

Ampac SmartTerminal Guide

Ampac

Ampac SmartTerminal Guide

Ampac XP95 User manual

Ampac

Ampac XP95 User manual

Popular Fire Alarm manuals by other brands

FireClass FC420CP quick guide

FireClass

FireClass FC420CP quick guide

Comelit 48CMI000 Technical manual

Comelit

Comelit 48CMI000 Technical manual

Texecom Ricochet INS742-2 installation manual

Texecom

Texecom Ricochet INS742-2 installation manual

Interlogix ESL installation instructions

Interlogix

Interlogix ESL installation instructions

AJAX ManualCallPoint Jeweller user manual

AJAX

AJAX ManualCallPoint Jeweller user manual

Simplex TrueAlarm 4008-9101 Installation, Programming and Operating Instructions

Simplex

Simplex TrueAlarm 4008-9101 Installation, Programming and Operating Instructions

Simplex 49SVC-CWFIRE installation instructions

Simplex

Simplex 49SVC-CWFIRE installation instructions

Consilium Salwico CS4000 installation manual

Consilium

Consilium Salwico CS4000 installation manual

Silent Call Communications FA41-MC Installation and operating instructions

Silent Call Communications

Silent Call Communications FA41-MC Installation and operating instructions

Tyco RC-1 manual

Tyco

Tyco RC-1 manual

Fireboy- Xintex FR-1000 installation manual

Fireboy- Xintex

Fireboy- Xintex FR-1000 installation manual

Fiberplex FAK-2981 user manual

Fiberplex

Fiberplex FAK-2981 user manual

Simplex 4100-1265 installation instructions

Simplex

Simplex 4100-1265 installation instructions

Notifier AVL-1 Operation and installation manual

Notifier

Notifier AVL-1 Operation and installation manual

Teletek electronics IRIS Installation and programming manual

Teletek electronics

Teletek electronics IRIS Installation and programming manual

Simplex 4098 Applications manual

Simplex

Simplex 4098 Applications manual

Honeywell ESSER 761694 Installation instructions manual

Honeywell

Honeywell ESSER 761694 Installation instructions manual

Honeywell NOTIFIER NFX-SMT3 Installation and maintenance instructions

Honeywell

Honeywell NOTIFIER NFX-SMT3 Installation and maintenance instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.