A: confirm the motor polarity
1: Power on the motherboard normal display: 190, the motor does not move.
2: Manually turn the motor on/off, and automatically detect the open limit/close limit. (The on/off limit needs
to be detected.) When the on/off limit motor is blocked, itwill stop automatically. At this time, the self-test data
will be saved automatically, the buzzer will sound once, and the self-test will open the limit or limit. The bit is
considered complete, and both the open limit and the limit require the same operation to complete the self-test
action, and the board operation will be normal. 3 If the motor and motherboard display data are reversed during
manualdetection(on:displaydata will continue to increase, off: data will continue to decrease), then you need
to enter the motherboard menu LD, change the motor polarity mode until it is correct (standard city state motor
The mode is 001).
B: Debug the horizontal and vertical position of the gate
After the self-test is completed, manually turn on/off the state of the normal operation of the gate, and check
whether the gate opening/closing is normal. If there is a deviation in the on/off position, please go to the main
menu L-6 (offset offset value), and L-9 (open in-position offset value) debugging (according to the field
situation to debug the corresponding parameters, refer to the parameter table parameter description
debugging).
C: Debug the speed and running smooth state of the gate opening/closing.
1: Opening speed L-1: The larger the value, the faster the speed.
2: Closing speed L-2: The larger the value, the faster the speed.
3: Open brake deceleration stroke L-L: The larger the value, the larger the deceleration distance. 4:
Deceleration stroke L-B: The larger the value, the larger the deceleration distance.
5: The largerthe on/off deceleration stroke value will affect the opening/closing speed, and adjust it in real time
according to the on-site operating status.
6: Whether the brake lever is shaking when the on/off gate is in place, adjust the L-3 parameter value (adjust
according to the site conditions). If the parameter is too small, the gate will not move