AMV OND1000-X-C1 User manual

1KW Pure Sine Wave Power Inverter
User’s Manual
AMV OND1000-X-C1
AMV ELECTRÓNICA SL C/ NAVA Nº7 BAJO 33207 GIJON ASTURIAS
TFNO 985319171 FAX: 985346795 EMAIL amv@amvelectronica.com
www.amvelectronica.com

1
Contents
1. Important Safety Instructions……………………………………………………………………. 2
1-1 General Safety Precaution…………………………………………………………………… 2
1-2 Other Safety Note………………………...…………………………………………………… 2
2. Introduction to Functional Characteristics……………………………………………………. 3
2-1 System...……………………………………………………………………………………….. 3
2-2 Block Diagram.…………………..……………………………………………………………. 4
2-3 Electrical Performance…..……………………………………………………………………. 5
2-4 Mechanical Drawings..………………………………………………………………………... 6
3. Installation and Maintenance….…………………………………………………………………. 7
3-1 Rear Panel……..……………………………………………………………………………. 7
3-2 Front Panel……..……………………………………………………………………………. 12
3-3 Maintenance…….………..……….…………………………………………………………. 12
4. Operation……………………………………………………………………………………………. 12
4-1 Connecting the Input Power………………………………………………………………….. 12
4-2 Connecting the Loads..……………………………………………………………………….. 12
4-3 Inverter Operation...………..…………………………………………………………………. 13
4-4 Protection Features……………………………………………………………………………. 13
5Front LCD Panel Display and Setup……………………………………………………………. 13
5-1 LCD Panel Indications………….……………………………….……………………………. 13
5-2 Startup Sequence and Standby Status…..……….……………..………………………….. 15
5-3 Setup Menu Operation and Instructions……………………………..……………………... 16
6. RS232 Communication and Operation…..…………………………………………………….. 21
6-1 Operation of RS-232 Serial Port..……. ………………………….…………………………. 21
6-2 Interface Command………………………………………………..………………………….. 22
6-3 Example of RS232 Operation……………………………………………………….……….. 22
7. Information………………………………………………………………………………………….. 26
7-1 Troubleshooting……………………………………………………………………………… 26
7-2 Warranty……………………………………………………………………………………... 27

2
AMV OND1000-X-C1
1. Important Safety Instructions
1-1. General Safety Precautions
1-1-1. Do not expose the inverter to rain, snow, spray or dust.
To reduce the risk of fire hazard, do not cover or obstruct the
ventilation openings and. do not install the inverter in a zero-
clearance compartment.
1-1-2. To avoid the risk of fire and electric shock, make sure that the
existing
wiring is in good electrical condition; and that the wire size is not
undersized.
Do not operate the inverter with damaged or substandard wiring.
1-1-3. Depending on the use, the AC output of the inverter may require
user installed breaker or fusing. For telecom use, a GFCI has not
been provided. The inverter incorporates standard AC short circuit
protection.
1-1-4. The following precautions should be taken when working on the
inverter:
▌Remove watches, rings, or other metal objects.
▌Use tools with insulated handles.
▌Wear rubber gloves and boots.
1-2. Other Safety Notes
1-2-1. Upon receipt, examine the shipment box for damage. Notify the
carrier immediately, before opening, if damage is evident.
1-2-2. Do not operate near water or in excessive humidity.
1-2-3. Do not open or disassemble the inverter, warranty may be voided.
1-2-4. The DC side connections should be firm and tight.
1-2-5. Grounding: Reliable grounding of rack-mounted equipment should
be maintained.
1-2-6. Do not drop a metal tool on the battery. The resulting spark or short-
circuit on the battery or on the other electrical part may cause an
explosion.
WARNING!
SAVE THESE INSTRUCTIONS – This manual contains
important instructions that should be followed during
installation and maintenance of the inverter.

3
AMV OND1000-X-C1
1-2-7. Install the inverter in a well-ventilated area. Do not block the front
air vents, or the rear air exhausts of the unit.
1-2-8. Wiring: Adequate input power must be supplied to the inverter for
proper use; correct wiring sizes must be ensured.
1-2-9. Mount the inverter such that the fan axis is horizontal.
1-2-10. Do not operate the inverter close to combustible gas or open fire.
1-2-11. Do not operate appliances that may feed power back into the
inverter.
1-2-12. Temperature: The inverter should be operated in an ambient
temperature range of 0℃to 50 ℃or else the output efficiency
may be affected. Air flow to the inverter must not be restricted.
2. Functional Characteristics Introduction
2-1. System
The unit is a highly reliable DC-AC inverter system, designed with advanced
power electronic and microprocessor technology offering the following features:
▌The inverter is equipped with a self diagnosis microprocessor that is able
to identify and show all failure messages on the LED/LCD display,
with associated visual/audio alarms.
ĭ
1U height x 19” width x 13.6” depth, 19” rack mountable.
▌Pure sine wave output (THD < 2%) to operate higher-end electronic
equipment.
▌Built in 12A rated transfer switch.
▌Speeds up transfer time as a result of synchronized operation with the
AC source at all times that allows the transfer to be interruption-free for
sensitive equipment.
▌Intelligent software for power management.
▌Hard-wire and Dual AC outlets connection model option.
▌Loading and temperature controlled cooling fan.
▌Fan aging, failure, disconnection and blockage alarm.
▌Selectable Bypass/Inverter modes.
▌Local and remote management and control.
▌RS-232 communication.

4
AMV OND1000-X-C1
▌Dry contact terminal.
▌Efficiency >90%. (Full linear load at 220VAC Output)
▌Advanced Protection Features:
Input over/under voltage protection.
Internal over temperature protection.
Input reverse polarity protection (Fuse).
Output overload protection.
Output short circuit protection
AC input short circuit protection: Breaker(6 Amp or 12 Amp)
2-2. Block Diagram
AC GRID
INPUT
DC
INPUT
FILTER
DC
DC AC
DC FILTER
AC
OUTNPUT
BYPASS RELAY
The inverter features IGBT technology which, minimizes weight and dimension,
while enhancing output short circuit reliability and overload capacity.
AC output voltage is provided in one of the two following modes:
1). From DC to AC Inverter Mode: (On-line Mode)
2). From AC Input Bypass Mode: (Off-line Mode)
Either mode is front panel programmable.
In the first option, Off-line mode, AC output power will be supplied through the AC
bypass mode in its normal operation. Upon AC input failure, output power will be
diverted through the DC to AC Inverter Mode. Once AC mains are restored, the unit
will revert from the Inverter Mode to the Bypass Mode.
In the second option, On-line mode, AC output power will be provided directly by
the inverter from the DC source. Should the DC source or inverter fail, the system
will transfer its output power through the bypass mode. Once the DC power source
is restored, the system will revert to the inverter mode.

Note: The specifications are subject to change without 5
notice.
Electrical Performance
Electrical Specification MODEL
Item AMV OND1000-24-C1 AMV OND1000-48-C1
Voltage 24VDC 48 VDC
Input Over-Voltage
Protection 30-34 VDC 60-68 VDC
Input Under-Voltage
Protection 18-22 VDC 36-44 VDC
Voltage Range 18-34 VDC 36-68 VDC
Input
Characteristics
No Load Current 0.6 A 0.35 A
Continuous Output Power 1000 W
Maximum output Power
(3Min) 1150 W
Surge Power 2000 W
Frequency 50 / 60 Hz +/-0.05
Output Voltage 194-246 VAC (User-selectable)
Efficiency (Full Load) 90% 91%
Short-Circuit Protection Yes, Ipk
Output
Characteristics
Output Waveform Pure Sine Wave (THD < 2%)
LCD Panel 2 Lines LCD Panel with keypad for navigation
LED Indicator Red/Orange/Green LED
Dry Contact Terminal By a relay
Signal and Control
Remote Control Terminal Controls the inverter ON / OFF operation
Input Protection Over/Under Voltage, Reverse Polarity (Internal Fuse)
AC Output Protection Short-circuit, Overload
AC Input Protection 6Amp Circuit Breaker
Protection
Temperature protection Shutdown (Internal temperature S65° C)
Relay Specification 12 Amp/250 VAC
Bypass relay On Line/Off Line (Haphazard, Normal, Exacting) selectable
From AC bypass mode(0ff-iine Mode): S9mS
From DC to AC inverter mode(0n-line Mode):g7mS
Transfer Relay
Switching Time
Full Load 0° C -50° C
Operating
Temperature Storage -30° C~70° C
Failure Indication Buzzer alarm and dry contact
Switches On when Temperature = 55° C or Load=30
Fan Operation and
Indicator
Switches Off when Temperature =45° C and Load=20
Size (WXHXD) 19"x1.71"x13.6"(482.6mmX43.5mmX345mm)
Mechanical
Specification Weight 5.8 Kgs (12.7 Lbs)
Safety Standards Meets UL 60950 Meets EN60+950-1
Safety and EMI/ EMC
EMC standards FCC CLASS B EN55022 1998+A1 2000+A2 2003 CLASS B
EN55024: 1997+A1: 2001+a2 :2003
EN61000-3-2: 2006 Class A
EN61000-3-3: 11995+A1:2001

6
AMV OND1000-X-C1
2-4. Mechanical Drawings
GND
ENB
ENB
NC
NO
COM.
INV. FAILURE RS-232
AC
OUTPUT
AC INPUT
BREAKER
CHASSIS
GROUND
WARNING:
POS(+)NEG(-)
REVERSE POLARITY
WILL DAMAGE UNIT
ON
OFF
REMOTE
Inverter Ordering Information
Model
Number
Input
Voltage
Output Voltage
Nominal
Output Voltage
Range
Frequency
Range
AMV OND1000-24-C124 VDC 230VAC 200~240 VAC 47~63 Hz
AMV OND1000-48-C1 48 VDC 230VAC 200~240 VAC 47~63 Hz

7
AMV OND1000-X-C1
3. Installation and Maintenance
3-1. Rear Panel
REAR PANEL VIEW
GND
ENB
ENB
NC
NO
COM.
INV. FAILURE RS-232
AC
OUTPUT
AC INPUT
BREAKER
CHASSIS
GROUND
WARNING:
POS(+)NEG(-)
REVERSE POLARITY
WILL DAMAGE UNIT
3-1-1. AC Input Breaker:
The AC input circuit breaker protects the unit from overload. When an overload
condition occurs, the circuit breaker trips and disconnects the AC grid power
input. To reset it, push the circuit breaker button. The cause of tripping should
be ascertained and corrected before the unit is reset .
3-1-2. Hard-wire Installation (AC wiring connections):
▌AC input and AC output terminal
▌Connect AC output and AC input wiring to the Inverter terminals.
Please use the following information as your reference:

8
AMV OND1000-X-C1
Terminal Wire color Wire length /
gauge
Line (L) Black (120 VAC), Brown (230 VAC)
AC
OUTPUT Neutral (N) White (120 VAC), Blue (230 VAC)
Line (L) Black (120 VAC), Brown (230 VAC)
AC INPUT
Neutral (N) White (120 VAC), Blue (230 VAC)
Chassis Ground or FG Green / Yellow or Bare copper
Within 16 feet /
AWG#
14~16
26~32 feet /
AWG#
12~14
Note. Please double check and review all the connections to ensure that the
wires are connected to the correct terminals and that the connections are tight.
3-1-3. AC output socket:
110VAC
NEMA
230VAC
I.E.C 60320 C13
3-1-4.Chassis Ground: Must be connected to earth ground prior to
making any other connections to the equipment.
3-1-5.RS-232: Serial port monitoring and control through computer interface.
3-1-6.Remote control and Dry contact terminal:
RELAY
ENABLE+
ENABLE -
GROUND
COM.
NO
NC
ENB
ENB
GND

9
AMV OND1000-X-C1
▌Remote Control Terminal:
1). Before installing the inverter, ensure that the main switch “OFF”.
2). Before using the remote function, ensure that the main switch pressed
toward “REMOTE”.
3). Ensure that the remote contacts are off.
4). Use 20 ~ 24 #AWG wire to connect the remote control terminals.
5). Remote control ON/OFF inverter setup status:
ENB
GND
ON:INV. ON
OFF:INV. OFF LOW:INV. OFF
HI:INV. ON
GND
ENB
TR
(TR ON)
(TR OFF)
OFF:INV. OFF
ON:INV. ON
ENB
BAT+
BAT-
GND
ON:INV. ON
OFF:INV. OFF
ENB +
-
DC
POWER
NOTE: At one time, only one remote function should used to control the inverter.
The maximum voltage value is the same as input DC voltage.
▌Dry Contact Terminals:
Dry contact terminals may be connected to a Form C relay for “FAULT”
indication. When “FAULT” occurs, the relay switches.
NOTE: Fault conditions include Input under/over voltage, Output Short Circuit,
Over Temperature, Over-load and, Fan Failure.
Specifications of the Relay
Contact Rating
Maximum
Voltage
Load
N.O. N.C.
Number of
operations
Operating/Storage
Temperature
240 VAC Resistive 16 A 100,000
240 VAC Resistive 8 A
30 VDC Resistive 16 A
30 VDC Resistive 8 A
-30℃~70℃

10
AMV OND1000-X-C1
▌Remote Control Terminal:
Dry Contact Terminal RELAY
COM. Common contact
N.C. Normally closed contact
N.O. Normally open contact
3-1-7.DC Input Connection:
Follow the instructions to connect the battery cables to the DC input
terminals of the inverter. The cables should be as short as possible (less
than 6 feet / 1.8 meters ideally) so that they can handle the required
current in accordance with the Electrical Codes and Regulations. The size
of the cable should be thick enough to limit the voltage drop to less than
2% when carrying the maximum input current to prevent frequent low-input
voltage warnings, and shutdown. UVP (Under Voltage Protection) warning
may result if there is excessive voltage drop across the DC cables between
the batteries and the inverter.
Increasing your DC cable size will help improve the situation.
Batteries are capable of providing very large currents in case of short
circuit. In case there is a short circuit in the cable run between the batteries
and the input terminals of the inverter, it will result in overheating / melting
of the cables and consequent risk of fire and injury, To prevent possibility of
this hazard, use Very Fast Acting DC Fuse in line with the positive cable.
The fuse should be as close to the positive battery terminal as possible.
Use Bussmann ANN series fuses ( will also require Fuse Block 4164) or
equivalent.
The following sizes of cables and fuses are recommended for up to 6 ft.
distance between the batteries and the inverter. (Applies to both 120 VAC
and 230 VAC versions):
Model No Wire AWG Inline Fuse
AMV OND1000-24-C1 # 4 80A
AMV OND1000-48-C1 # 6 40 A
▌Connect DC input terminals to 24V / 48V battery or other DC power source.
[ + ] is positive, [ - ] is negative. Reverse polarity connection can blow the
internal fuse and may damage the inverter permanently.
WARNING!
Make sure that all the DC connections are tight (torque
to 9 – 10 ft-lbs, 11.7 – 13 Nm). Loose connections
could result in overheating and can be a potential
hazard.

11
AMV OND1000-X-C1
RING TERMINAL
PVC WIRE
(AWG#4 - #6)
RING TERMINAL
PVC WIRE
(AWG#4 - #6)
NEGATIVE-
POSITIVE+
b. Also, only use high quality copper wire and keep the cable length
short which is a maximum of 3 - 6 feet.
INLINE FUSE
NEGATIVE-
POSITIVE+
WARNING!
The recommended inline fuse should be installed as
close to the battery positive terminal as possible
Failure to use a fuse on the “+” cable running
Between the inverter and battery may cause
damage to the cable / inverter and will void warranty.

12
AMV OND1000-X-C1
3-2. Front Panel
FRONT PANEL VIEW
ON
OFF
REMOTE
Vi =24.0 Vo=115
FQ=60.0 Io =8.5
3-2-1.Main Switch: These are the 3-stage rocker switches for turning on, turning off
and remote mode.
3-2-2. LED’s Indicators: See details in Section 5-1.
3-2-3. LCD Display Selection Buttons:
Data pertaining to the DC input voltage, AC output voltage, AC output
frequency, AC output current, etc. and system status can be shown
sequentially on the LCD display by pressing these buttons. Please refer to
chapter 5 for more information.
3-2-4. FAN ventilation grille (1)~(3): The fans behind the ventilation grilles provides
cooling. DOT NOT obstruct these vents!
3-3. Maintenance
3-3-1. Make sure that the fan vents are not blocked.
3-3-2. Use a vacuum cleaner to remove any dust from the fan area.
3-3-3. When cleaning the case or front panel, use a soft, dry cloth, only. If the case
or front panel is very dirty, use a neutral, non-abrasive detergent. Do not use
alcohol or ammonia based solutions.
3-3-4. Regular service, and relocation of the inverter, should be performed by a
qualified service technician.
3-3-5. Avoid spilling liquid on the inverter.
4. Operation:
4-1. Connecting the input power
Before making the DC input side connections, the main switch must
be “OFF”.
4-2. Connecting the loads
▌Calculate the total power consumption(W) of the output load. Make sure that
the total power consumption does not exceed the rated load.
▌Should the total load exceed the rated capacity of the inverter, remove the
non-critical. loads until the rated total has been reached.

13
AMV OND1000-X-C1
4-3. Inverter Operation
▌Set the power switch to the “ON” position. The buzzer will sound “beep beep”.
The inverter will carry out self-diagnosis and, the LED’s will also appear various
colors. At the, same time the LCD will display ”SR-1000
INVERTER INITIALIATION..”.
Finally, the buzzer will sound another “beep” and the “INVERTER” and
status LED’s will turn “Green”, The LCD Display will display “Vi, Vo, FQ, Io“.
THE, inverter will start operating normally.
▌Set the power switch to the “OFF” position. THE, inverter stops and all
the lights that are on will, go off.
4-4. Protections Features
DC Input (VDC) Over Temperature Protection
Over Voltage Under Voltage INTERIOR HEAT SINK
Model
Shut-down Restart
Under
Voltage
Alarm Shut-down Restart Shut-
down Restart Shut-
down Restart
24 V 30.1~34.1 28~32 19~23 18.1~22.1 23~27
48 V 60.1~68.1 56~64 38~46 36.1~44.1 46~54 65℃45℃105℃75℃
5. Front LCD Panel – Display & Setup
5-1. LCD Panel Indications
5-1-1. Set the Power Switch to the “ON” position. THE, inverter starts working
normally. The inverter will be operating in normal condition when either
of the following messages are displayed on the LCD screen:
FQ=60.0 Io =8.5
Vi =24.0 Vo=115

14
AMV OND1000-X-C1
5-1-2. LED Indications:
▌AC GRID: Displays AC input status.
AC Input LED Status
AC input and DC-AC Inverter
Output are Synchronous GREEN
AC input ON ORANGE
AC input OFF OFF
Note. Synchronous means that the: grid AC input frequency and DC-AC
inverter output frequency or phase are the same (See details in
Section 5-3-3).
▌INVERTER: Displays DC-AC inverter status.
DC-AC Inverter LED Status
Power OK GREEN
Power not good RED
▌BYPASS: Displays Transfer Switch status.
BYPASS LED Status AC OUTPUT (LOAD)
ORANGE AC INPUT
From DC-AC inverter
(On-line Mode) OFF DC-AC Inverter
GREEN AC INPUT
From AC input bypass
(Off-line Mode) OFF DC-AC Inverter
▌ALARM: Displays status of the Failure Alarm.
ALARM LED Status
Over/Under Alarm
/FAN Alarm ORANGE
Set alarm in the inverter to
operate normally OFF
NOTE. For instructions on setting the alarm, see details in Section 5-3.
5-1-3. LCD Display Selection Buttons:

15
AMV OND1000-X-C1
▌Function of Various Keys :
Function <Up>: You can use the “up” button to scroll through the menus.
or to select the value for set up under setting mode.
Function <Down>: You can use the “Down” button to scroll through the
menus or to select the value for set up under setting mode.
.
Function <Page Up>: You can use the “Page Up” button to scroll through the
menus.
Function <Page Down>: You can use the “Page Down” button to scroll
through the menus.
Function <Enter Setup Menu>: Press the button longer than 2 seconds,
The inverter will change to “Setup Menu Mode” which
appears on the LCD screen for the user to set functions.
Function <Enter>: Confirms a selection or value.
5-1-4. LCD Display: Displays inverter’s operational status.
5-2. Startup Sequence and Standby Status
5-2-1. Once turn on the inverter. The display shows “SR-1000 INVERTER
INITIALIATION..”, then checks the inverter.
Status flow is as follows:

16
AMV OND1000-X-C1
POWER SWITCH
OFF ON
INITIALIATION ..
AMV OND1000 INVERTER
CHECK INVERTER
FAILURE
Vi =XX.X
Vi =XX.X
OR
OR
Vi =XX.X
OR
Vi =XX.X
OK
ALARM
Vi =XX.X Vo=XXX
FQ=XX.X Io =X.X
FQ=XX.X Io =X.X
Vi =XX.X Vo=XXX
Undervoltage!!
Alert:
1Sec 交
換顯示
OR
OR
Alert:
Overload!!
Alert:
Fan Failure!!
5-3. Setup Menu – Operation and Instructions
Entering Setup Menu:
Press Button longer than 2 seconds. The inverter, enters the
Setup Menus consisting of three layers:
(1)Select Menu Heading: (2)Select Menu Item: (3)Setting Value:

17
AMV OND1000-X-C1
Vi =XX.X Vo=XXX
FQ=XX.X Io =X.X
Main Menu:
Select
Menu: User interface
Select Menu:
I/P Parameter
Select Menu:
O/P Parameter
Select Menu:
RST to default
Select Menu:
Select Item:
LCD Contrast
Select
Item:
Select Item:
LCD Auto-off
Select Item:
RS232 Baudrate
Select Item:
Buzzer Setting
Select Item:
Alert Setting
0 1 2 3 4 6 7 8 9 10 11 12 13 14 15
Function
Code:
OVP Setting
Select Item:
OVP Recovery
Select Item:
UVP Setting
Select Item:
UVP Recovery
Select Item:
UV Alarm
Select Item:
O/P Voltage
Select Item:
O/P Frequency
Select Item:
Sync Frequency
Select Item:
Bypass relay
Select Item:
Overload Alarm
Select Item:
50%
LCD Contrast:
Setting
Value:
LCD Auto-off:
120S
RS232 Baudrate:
4800
Buzzer Setting:
MSG , Alert , SHDN
Alert Setting:
Alert , SHDN
OVP Setting:
32.00V
30.00V
OVO Recovery:
20.00V
UVP Setting:
25.00V
UVP Recovery:
21.00V
UV Alarm:
O/P Voltage:
230V
O/P Frequency:
50.00Hz
Sync Frequency:
7.00Hz
Bypass relay:
On-line
Overload Alarm:
100%
5-3-1. User interface (Select Menu):
0). LCD Contrast: Sets LCD screen contrast.
Default=50%
Setting Range= 0%~100%
1). LCD Auto-off: Sets LCD auto off timer.
Default=120 seconds.
Setting Range= Disable~250 seconds.
2). RS232 Baud-rate: Sets standard RS-232 Baud-rate.
Default=4800
Setting Range= 1200/2400/4800/9600
3). Buzzer Setting: Sets the internal buzzer sound ON/OFF.
When setting, the LCD screen display,
Buzzer “ON”, Buzzer “OFF”.
Default=MSG, Alert, SHDN
Setting Range= Disable / Shutdown / Alert
/ Alert, SHDN / Message
/ Message, SHDN / Message, Alert
/ MSG, Alert, SHDN

18
AMV OND1000-X-C1
MENU STATUS BUZZER
Message Power ON or Push Keypad ON
Alert FAN Fail or UV Alarm or Overload Alarm ON
Shutdown OVP or UVP or OLP or OTP ON
Disable Any OFF
4). Alert Setup: When alert occurs, the internal Dry Contact Relay will
open / close. (See details in Section 3-1-6)
Default= Alert, SHDN
Setting Range= Disable / Shutdown / Alert / Alert, SHDN
MENU STATUS RELAY
Alert FAN Fail or UV Alarm or Overload Alarm ON
Shutdown OVP or UVP or OLP or OTP ON
Disable Any OFF
5-3-2. I/P Parameter (Select Menu):
6). OVP Setting: Sets the Over Voltage Protection (OVP) and shutdown.
Default= 32 VDC for 24 V Model, 64 VDC for 48 V Model
Model SETTING VALUE RANGE
24 V 30 VDC ~ 34 VDC
48 V 60 VDC ~ 68 VDC
7). OVP Recovery: When the DC input voltage is higher than the OVP
setting, the inverter shuts-down; Once the input voltage
falls below the set OVP value, the inverter will
automatically restart.
Default= 30 VDC for 24 V Model, 60 VDC for 48 V Model
Model SETTING VALUE RANGE
24 V 28 VDC ~ 32 VDC
48 V 56 VDC ~ 64 VDC
8). UVP Setting: Setting the inverter’s Under Voltage Protection (UVP) and
Shutdown.
Default= 20 VDC for 24 V Model, 40 VDC for 48 V Model
Model SETTING VALUE RANGE
24 V 18 VDC ~ 22 VDC
48 V 36 VDC ~ 44 VDC
9). UVP Recovery:When the DC input voltage is below the set UVP value
the inverter shuts-down; Once the input voltage rises
above the set UVP value, the inverter will automatically
restart.
Default= 25 VDC for 24 V Model, 50 VDC for 48 V Model

19
AMV OND1000-X-C1
Model SETTING VALUE RANGE
24 V 23 VDC ~ 27 VDC
48 V 46 VDC ~ 54 VDC
10). UV Alarm: Sets Under Voltage (UV) alarm. When the input voltage is
lower than the set value, the unit will sound “beep” to remind
that the unit is going to shutdown. At the meantime, the
contact in the internal Dry Contact Relay will open / close
(See details in Section 3-1-6).
Default= 12 VDC for 24 V Model, 42 VDC for 48 V Model
Model SETTING VALUE RANGE
24 V 19 VDC ~ 23 VDC
48 V 38 VDC ~ 46 VDC
NOTE. The value of voltage set for the “UV Alarm” should be equal to or
higher than the value set for “UVP” or else the unit will shutdown
without any audible warning.
5-3-3. O/P Parameters:
11). O/P Voltage: Set the inverter output voltage.
Default= 110 VAC for 110 V Model, 230 VAC for 220 V Model
Model SETTING VALUE RANGE
110 V 97 VAC ~ 123 VAC
220 V 194 VAC ~ 246 VAC
12). O/P Frequency: Set the inverter output frequency.
Default= 60 Hz for 110 V Model, 50 Hz for 220 V Model.
Model SETTING VALUE RANGE
110 V 47 Hz ~ 63 Hz
220 V 47 Hz ~ 63 Hz
13). Sync Frequency: Sets the AC output synchronous frequency.
Example: AC input= 230 VAC / 50Hz
User setting Value= 7Hz
When the DC to AC inverter “Frequency” is within the
Range of 43 Hz~57 Hz, the internal transfer relay will
operate normally. When the “Frequency” is less than
43 Hz or more than 58 Hz, the internal transfer relay
will de-energize (See details in Section 2-2)
Default= 0.1Hz ~ 7Hz.
Model SETTING VALUE RANGE
110 V 0.1 Hz ~ 7 Hz
230 V 0.1 Hz ~ 7 Hz
Table of contents
Popular Inverter manuals by other brands

Analytic Systems
Analytic Systems IPSi305M-20-220ZAS Installation & operation manual

MX-PG
MX-PG 160.100.100 Original instructions

Solectria Renewables
Solectria Renewables PVI 20TL Installation and operation manual

Mitsubishi Electric
Mitsubishi Electric 800 Series instruction manual

AIMS Power
AIMS Power PWRB2500W instruction manual

Portawattz
Portawattz 1750 owner's manual