Ansul AUTOPULSE IQ-636X User manual

A
P/N 52181:A ECN 05-034
Document 52181
04/28/2005 Rev:

2 IQ-636X Operations Manual P/N 52181:A 04/28/2005
Fire Alarm System Limitations
While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!
An automatic fire alarm system—typically made up of
smoke detectors, heat detectors, manual pull stations, audible
warning devices, and a fire alarm control panel with remote
notification capability—can provide early warning of a develop-
ing fire. Such a system, however, does not assure protection
against property damage or loss of life resulting from a fire.
The Manufacturer recommends that smoke and/or heat detec-
tors be located throughout a protected premise following the
recommendations of the current edition of the National Fire
Protection Association Standard 72 (NFPA 72), manufacturer's
recommendations, State and local codes, and the recommen-
dations contained in the Guide for Proper Use of System
Smoke Detectors, which is made available at no charge to all
installing dealers. A study by the Federal Emergency Man-
agement Agency (an agency of the United States government)
indicated that smoke detectors may not go off in as many as
35% of all fires. While fire alarm systems are designed to pro-
vide early warning against fire, they do not guarantee warning
or protection against fire. A fire alarm system may not provide
timely or adequate warning, or simply may not function, for a
variety of reasons:
Smoke detectors may not sense fire where smoke cannot
reach the detectors such as in chimneys, in or behind walls, on
roofs, or on the other side of closed doors. Smoke detectors
also may not sense a fire on another level or floor of a building.
A second-floor detector, for example, may not sense a first-
floor or basement fire.
Particles of combustion or “smoke” from a developing fire
may not reach the sensing chambers of smoke detectors
because:
• Barriers such as closed or partially closed doors, walls, or
chimneys may inhibit particle or smoke flow.
• Smoke particles may become “cold,” stratify, and not reach
the ceiling or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air
outlets.
• Smoke particles may be drawn into air returns before
reaching the detector.
The amount of “smoke” present may be insufficient to alarm
smoke detectors. Smoke detectors are designed to alarm at
various levels of smoke density. If such density levels are not
created by a developing fire at the location of detectors, the
detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing
limitations. Detectors that have photoelectronic sensing
chambers tend to detect smoldering fires better than flaming
fires, which have little visible smoke. Detectors that have ion-
izing-type sensing chambers tend to detect fast-flaming fires
better than smoldering fires. Because fires develop in different
ways and are often unpredictable in their growth, neither type
of detector is necessarily best and a given type of detector
may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate
warning of fires caused by arson, children playing with
matches (especially in bedrooms), smoking in bed, and violent
explosions (caused by escaping gas, improper storage of
flammable materials, etc.).
Heat detectors do not sense particles of combustion and
alarm only when heat on their sensors increases at a predeter-
mined rate or reaches a predetermined level. Rate-of-rise
heat detectors may be subject to reduced sensitivity over time.
For this reason, the rate-of-rise feature of each detector
should be tested at least once per year by a qualified fire pro-
tection specialist. Heat detectors are designed to protect
property, not life.
IMPORTANT! Smoke detectors must be installed in the
same room as the control panel and in rooms used by the sys-
tem for the connection of alarm transmission wiring, communi-
cations, signaling, and/or power. If detectors are not so
located, a developing fire may damage the alarm system, crip-
pling its ability to report a fire.
Audible warning devices such as bells may not alert people
if these devices are located on the other side of closed or
partly open doors or are located on another floor of a building.
Any warning device may fail to alert people with a disability or
those who have recently consumed drugs, alcohol or medica-
tion. Please note that:
• Strobes can, under certain circumstances, cause seizures
in people with conditions such as epilepsy.
• Studies have shown that certain people, even when they
hear a fire alarm signal, do not respond or comprehend the
meaning of the signal. It is the property owner's responsi-
bility to conduct fire drills and other training exercise to
make people aware of fire alarm signals and instruct them
on the proper reaction to alarm signals.
• In rare instances, the sounding of a warning device can
cause temporary or permanent hearing loss.
A fire alarm system will not operate without any electrical
power. If AC power fails, the system will operate from standby
batteries only for a specified time and only if the batteries have
been properly maintained and replaced regularly.
Equipment used in the system may not be technically com-
patible with the control panel. It is essential to use only equip-
ment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a
premise to a central monitoring station may be out of service
or temporarily disabled. For added protection against tele-
phone line failure, backup radio transmission systems are rec-
ommended.
The most common cause of fire alarm malfunction is inade-
quate maintenance. To keep the entire fire alarm system in
excellent working order, ongoing maintenance is required per
the manufacturer's recommendations, and UL and NFPA stan-
dards. At a minimum, the requirements of NFPA 72 shall be
followed. Environments with large amounts of dust, dirt or
high air velocity require more frequent maintenance. A main-
tenance agreement should be arranged through the local man-
ufacturer's representative. Maintenance should be scheduled
monthly or as required by National and/or local fire codes and
should be performed by authorized professional fire alarm
installers only. Adequate written records of all inspections
should be kept.
Precau-L-1-2005.fm

IQ-636X Operations Manual P/N 52181:A 04/28/2005 3
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be
connected to the fire alarm control panel. Disconnect all
sources of power before servicing. The control unit and asso-
ciated equipment may be damaged by removing and/or insert-
ing cards, modules, or interconnecting cables while the unit is
energized. Do not attempt to install, service, or operate this
unit until this manual is read and understood.
CAUTION - System Reacceptance Test after Software
Changes. To ensure proper system operation, this product
must be tested in accordance with NFPA 72 after any pro-
gramming operation or change in site-specific software. Reac-
ceptance testing is required after any change, addition or
deletion of system components, or after any modification,
repair or adjustment to system hardware or wiring.
All components, circuits, system operations, or software func-
tions known to be affected by a change must be 100% tested.
In addition, to ensure that other operations are not inadvert-
ently affected, at least 10% of initiating devices that are not
directly affected by the change, up to a maximum of 50
devices, must also be tested and proper system operation ver-
ified.
This system meets NFPA requirements for operation at 0°C
to 49°C (32°F to 120°F) and at a relative humidity (non con-
densing) of 85% at 30°C (86°F) per NFPA, and 93% ± 2% at
32°C ± 2°C (89.6°F ± 1.1°F) per ULC. However, the useful life
of the system's standby batteries and the electronic compo-
nents may be adversely affected by extreme temperature
ranges and humidity. Therefore, it is recommended that this
system and all peripherals be installed in an environment with
a nominal room temperature of 15-27° C/60-80° F.
Verify that wire sizes are adequate for all initiating and indi-
cating device loops. Most devices cannot tolerate more than a
10% I.R. drop from the specified device voltage.
Like all solid state electronic devices, this system may
operate erratically or can be damaged when subjected to light-
ning-induced transients. Although no system is completely
immune from lightning transients and interferences, proper
grounding will reduce susceptibility. Overhead or outside
aerial wiring is not recommended, due to an increased sus-
ceptibility to nearby lightning strikes. Consult with the Techni-
cal Services Department if any problems are anticipated or
encountered.
Disconnect AC power and batteries prior to removing or
inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing,
reaming, or punching of the enclosure. When possible, make
all cable entries from the sides or rear. Before making modifi-
cations, verify that they will not interfere with battery, trans-
former, and printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs.
Over-tightening may damage threads, resulting in reduced ter-
minal contact pressure and difficulty with screw terminal
removal.
Though designed to last many years, system components
can fail at any time. This system contains static-sensitive
components. Always ground yourself with a proper wrist strap
before handling any circuits so that static charges are removed
from the body. Use static-suppressive packaging to protect
electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and pro-
gramming manuals. These instructions must be followed to
avoid damage to the control panel and associated equipment.
FACP operation and reliability depend upon proper installation
by authorized personnel.
Precau-L-1-2005.fm
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and
used in accordance with the instruction manual, may
cause interference to radio communications. It has been
tested and found to comply with the limits for class A
computing device pursuant to Subpart B of Part 15 of
FCC Rules, which is designed to provide reasonable
protection against such interference when operated in a
commercial environment. Operation of this equipment in
a residential area is likely to cause interference, in which
case the user will be required to correct the interference
at his own expense.
Canadian Requirements
This digital apparatus does not exceed the Class A limits
for radiation noise emissions from digital apparatus set
out in the Radio Interference Regulations of the Cana-
dian Department of Communications.
Le present appareil numerique n'emet pas de bruits radi-
oelectriques depassant les limites applicables aux appa-
reils numeriques de la classe A prescrites dans le
Reglement sur le brouillage radioelectrique edicte par le
ministere des Communications du Canada.
HARSH™, NIS™, Notifier Integrated Systems™,and ONYXWorks™ are all trademarks; and Acclimate®, FlashScan®, NION®, NOTIFIER®, ONYX®,
UniNet®, VeriFire®, and VIEW® are all registered trademarks of Honeywell International Inc. Echelon® is a registered trademark and LonWorks™ is a
trademark of Echelon Corporation. ARCNET® is a registered trademark of Datapoint Corporation. Microsoft® and Windows® are registered trademarks of
the Microsoft Corporation. LEXAN® is a registered trademark of GE Plastics, a subsidiary of General Electric Company.
©2005 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.

4 IQ-636X Operations Manual P/N 52181:A 04/28/2005
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any com-
ments or suggestions about our online Help or printed manuals, you can email us.
Please include the following information:
• Product name and version number (if applicable)
• Printed manual or online Help
• Topic Title (for online Help)
• Page number (for printed manual)
• Brief description of content you think should be improved or corrected
• Your suggestion for how to correct/improve documentation
Send email messages to:
TechPubs_Fir[email protected]
Please note this email address is for documentation feedback only. If you have any technical
issues, please contact Technical Services.

IQ-636X Operations Manual P/N 52181:A 04/28/2005 5
Contents
About This Manual
Cautions and Warnings .............................................................................................. 9
Typographic Conventions........................................................................................... 9
Supplemental Information.......................................................................................... 9
Shortcuts to Operating Functions ............................................................................ 11
1. Introduction
Product Description................................................................................................... 13
Operating Features.................................................................................................... 13
2. Use of the Controls
Introduction ............................................................................................................... 15
System Status Indicator LEDs ................................................................................. 16
Descriptions: .......................................................................................................... 16
Control Keys .............................................................................................................. 17
Acknowledge/Scroll Display .................................................................................. 17
Signal Silence.......................................................................................................... 17
Drill ......................................................................................................................... 17
System Reset ........................................................................................................... 18
Lamp Test................................................................................................................ 18
Programming Keypad............................................................................................... 19
3. Operation of the Control Panel
Overview..................................................................................................................... 21
Normal Mode of Operation ...................................................................................... 22
Fire Alarm Mode of Operation ................................................................................ 23
How the Control Panel Indicates a Fire Alarm ....................................................... 23
How to Respond to a Fire Alarm ............................................................................ 23
Interpreting Fire Alarm Type Codes ....................................................................... 24
System Trouble Mode of Operation ........................................................................ 25
How the Control Panel Indicates a System Trouble ............................................... 25
How to Respond to a System Trouble..................................................................... 25
Security Alarm Mode of Operation ......................................................................... 27
How the Control Panel Indicates a Security Alarm ................................................ 27
How to Respond to a Security Alarm ..................................................................... 27
Interpreting Security Type Codes ........................................................................... 28
Active Supervisory Signal Mode of Operation ....................................................... 29
How the Control Panel Indicates an Active Supervisory........................................ 29
How to Respond to an Active Supervisory ............................................................. 29
If a Latching Supervisory Type Code Displays.................................................. 29
If Non-latching Type Code Displays .................................................................. 30
How to Interpret Supervisory Type Codes.............................................................. 30
Pre-Alarm Warning Mode of Operation................................................................. 31
How the Control Panel Indicates a Pre-Alarm Warning ......................................... 31
How to Respond to a Pre-Alarm Warning .............................................................. 31
Pre-Alarm Alert and Action Levels .................................................................... 31
Responding to a Pre-Alarm Warning.................................................................. 31
Interpreting Pre-Alarm Type Codes.................................................................... 31
Disabled Points Mode of Operation......................................................................... 32
Non-Alarm Mode of Operation................................................................................ 33
Purpose of Non-Alarm Points ................................................................................. 33
How the Control Panel Indicates an Active Fire Control ....................................... 33

6 IQ-636X Operations Manual P/N 52181:A 04/28/2005
How the Control Panel Indicates an Active Non-Fire Point ................................... 33
Active Trouble Monitor Mode of Operation........................................................... 34
How the Control Panel Indicates an Active Trouble Monitor ................................ 34
How to Respond to an Active Trouble Monitor...................................................... 34
Output Circuit Trouble Mode of Operation ........................................................... 35
Overview ................................................................................................................. 35
How the Control Panel Indicates a NAC Trouble................................................... 36
How the Control Panel Indicates a Panel Circuit Trouble ...................................... 36
How the Control Panel Indicates a Control/Relay Trouble .................................... 36
How to Respond to a NAC, Panel Circuit or Control/Relay Trouble ..................... 37
Operation of Special System Timers........................................................................ 38
What are System Timers? ....................................................................................... 38
How to View System Timer Selections .................................................................. 38
How System Timers Work...................................................................................... 38
Auto Silence Timer............................................................................................. 38
Alarm Verification Timer ................................................................................... 38
Silence Inhibit Timer .......................................................................................... 39
Waterflow Circuit Operation ................................................................................... 39
Style 6 and Style 7 Operation ................................................................................... 39
4. Read Status Operation
Introduction ............................................................................................................... 41
What is Read Status? ................................................................................................ 41
Quick Reference Key Sequences ............................................................................ 41
Entering Read Status ................................................................................................ 41
Viewing and Printing a Read Status........................................................................ 42
How to View Read Status of Devices, Zones, and System Settings....................... 43
Overview............................................................................................................. 43
How to Display the Total of Installed Devices................................................... 43
How to Display a Point or Zone for Read Status................................................ 43
How to View Read Status for a Detector............................................................ 44
How to View Read Status for a Control/Relay or Monitor Module ................... 45
How to View Read Status for a NAC or Panel Circuit....................................... 46
How to View Read Status for a Software Zone (Z01-Z99)................................ 47
How to View Read Status for a Special Zone (F0-F9) ....................................... 47
How to View Read Status for a Releasing Zone (R0-R9) .................................. 47
How to Read Status for System Functions ......................................................... 48
How to Read Status for Annunciator Selections................................................. 49
How to Read Status for Battery Levels............................................................... 50
How to View Read Status for Event and Alarm History ........................................ 51
Overview............................................................................................................. 51
How to View Read Status for Event History ...................................................... 51
How to View Read Status for Alarm History ..................................................... 52
How to Print Points, Event and Alarm History....................................................... 53
Overview............................................................................................................. 53
How to Print Points............................................................................................. 53
How to Print Event History ................................................................................ 53
How to Print Alarm History................................................................................ 53
How to View and Print Hidden Event and Alarm History...................................... 54
Appendix A: Special Zone Operation
Overview..................................................................................................................... 55
Releasing Zones (R0-R9)........................................................................................... 56
Purpose of Releasing Zones ................................................................................. 56
How to View Releasing Zone Selections................................................................ 56
How Releasing Zones Operate................................................................................ 57

IQ-636X Operations Manual P/N 52181:A 04/28/2005 7
Time, Date, and Holiday Functions ......................................................................... 59
Overview ................................................................................................................. 59
How to View Time Control Selections ................................................................... 59
How to View Holiday Function Selections............................................................. 60
How Time Control and Holiday Functions Work................................................... 60
NAC and Panel Circuit Coding................................................................................ 61
Overview of Coding................................................................................................ 61
How to View Coding (F8) Selections ..................................................................... 61
How to Respond to an Alarm with Coding............................................................. 61
Presignal and Positive Alarm Sequence (PAS) Operation .................................... 62
Overview ................................................................................................................. 62
What is Presignal and PAS?.................................................................................... 62
How to View Presignal and PAS Selections........................................................... 63
How to Respond to an Alarm with a Presignal Delay Timer (no PAS).................. 63
How to Respond to an Alarm with a Presignal Delay Timer (PAS selected)......... 64
Appendix B: Intelligent Detector Functions
Descriptions for Intelligent Detector Functions ..................................................... 65
Appendix C: Remote Terminal Access
General Description................................................................................................... 67
Operating Modes ....................................................................................................... 67
Local Terminal Mode (LocT) ................................................................................. 68
Local Monitor Mode (LocM).................................................................................. 69
Remote Terminal Mode (RemT)............................................................................. 70
Using the CRT-2 for Read Status............................................................................. 71
Overview ................................................................................................................. 71
Accessing Read Status Options............................................................................... 71
Read Point ............................................................................................................... 72
Display Devices in Alarm or Trouble ..................................................................... 72
Display the Status of all Programmed Points.......................................................... 73
View the History Buffer.......................................................................................... 73
Send the History Buffer to the CRT-2 .................................................................... 73
View the Alarm History Buffer............................................................................... 73
Send the Alarm History Buffer to the CRT-2 ......................................................... 74
Using the CRT-2 for Alter Status............................................................................. 75
Overview ................................................................................................................. 75
Accessing Alter Status Options............................................................................... 75
Enable or Disable Detectors, Modules, or Panel Circuits ....................................... 76
Change Alarm and Pre-Alarm levels ...................................................................... 77
Clear the Verification Counter ................................................................................ 77
Clear the Entire History Buffer ............................................................................... 77
Set the Pre-Alarm for Alert or Action..................................................................... 78
Appendix D: Point and System Troubles Lists
Point (Device) Troubles............................................................................................. 79
System Troubles......................................................................................................... 80

8 IQ-636X Operations Manual P/N 52181:A 04/28/2005
Notes

IQ-636X Operations Manual P/N 52181:A 04/28/2005 9
About This Manual
Cautions and Warnings
This manual contains cautions and warnings to alert the reader as follows:
Typographic Conventions
This manual uses the following typographic conventions as listed in below:
Supplemental Information
The table below provides a list of documents referenced in this manual, as well as documents for
selected other compatible devices. The document series chart (DOC-ANS) provides the current
document revision. A copy of this document is included in every shipment.
!
CAUTION: Information about procedures that could cause programming errors, runtime errors,
or equipment damage.
!
WARNING: Indicates information about procedures that could cause irreversible damage to the
control panel, irreversible loss of programming data or personal injury.
When you see Specifies Example
text in small caps the text as it appears in the LCD
display or on the control panel
MARCH TIME is a selection that appears in the
LCD display; or Press the ENTER key
text in quotes a reference to a section or a
LCD menu screen
“Read Status”; specifies the Read Status
section or menu screen
bold text In body text, a number or
character that you enter
Press 1; means to press the number “1” on the
keypad
italic text a specific document IQ-636X Installation Manual
a graphic of the key In a graphic, a key as it appears
on the control panel Press means to press the Escape key
Table 1 Typographic Conventions in this Manual
Compatible Conventional Devices (Non-addressable)
Document Number
(Ansul part no. if
applicable)
Device Compatibility Document 50054
Fire Alarm Control Panel (FACP) and Main Power Supply Installation
Document Number
(Ansul part no. if
applicable)
IQ-636X Installation, Operations, and Programming Manuals 52180 (432779),
52181 (432778),
52182 (432777)
Ansul SLC Wiring Manual 52184
Note: For individual SLC Devices, refer to the SLC Wiring Manual
Off-line Programming Utility
Document Number
(Ansul part no. if
applicable)
VeriFire™ Tools CD help file ANSUL-TCD
Table 2 Supplemental Documentation (Sheet 1 of 2)

About This Manual Supplemental Information
10 IQ-636X Operations Manual P/N 52181:A 04/28/2005
Cabinets & Chassis
Document Number
(Ansul part no. if
applicable)
CAB-3/CAB-4 Series Cabinet Installation Document 15330
Battery/Peripherals Enclosure Installation Document 50295
Power Supplies, Auxiliary Power Supplies & Battery Chargers
Document Number
(Ansul part no. if
applicable)
ACPS-2406 Installation Manual 51304
APS-6R Instruction Manual 50702
CHG-120 Battery Charger Manual 50641
FCPS-24 Field Charger/Power Supply Manual 50059
System Components
Document Number
(Ansul part no. if
applicable)
Annunciator Control System Manual 15842
Annunciator Fixed Module Manual 15048
AFM-16A Annunciator Fixed Module Manual 15207
ACM-8R Annunciator Control Module Manual 15342
Ansul LCD-80 Manual 50028
LCD-80TM Manual 51082
LDM Series Lamp Driver Annunciator Manual 15885
ANSUL-NCA Network Control Annunciator Manual 52185
SCS Smoke Control Manual (Smoke and HVAC Control Station) 15712
RPT-485W/RPT-485WF EIA-485 Annunciator Loop Repeater Manual 15640
DPI-232 Direct Panel Interface Manual 51499
TM-4 Installation Document (Reverse Polarity Transmitter) 51490
UDACT Manual (Universal Digital Alarm Communicator/Transmitter) 50050
ACT-2 Installation Document 51118
VEC 25/50 Manual 50686
RA400Z Remote LED Annunciator Installation Document I56-508
UZC-256 Universal Zone Coder Manual 15216
UZC-256 Programming Manual 15976
XP Transponder Manual 15888
XP10-M Installation Document I56-1803
XP5 Series Manual 50786
XP6-C Installation Document I56-1805
XP6-MA Installation Document I56-1806
XP6-R Installation Document I56-1804
Table 2 Supplemental Documentation (Sheet 2 of 2)

Shortcuts to Operating Functions About This Manual
IQ-636X Operations Manual P/N 52181:A 04/28/2005 11
Shortcuts to Operating Functions
To the left of each program function, you’ll find a keypad shortcut, which contains a
series of keypad entries required to access the program function. All shortcuts start with
the control panel in normal operation.
For example, the keypad shortcut to the left, shows how to enter the Read Status
function with the control panel in normal operation, as well as how to exit the function.

12 IQ-636X Operations Manual P/N 52181:A 04/28/2005
Notes

IQ-636X Operations Manual P/N 52181:A 04/28/2005 13
1. Introduction
Product Description
The IQ-636X is a modular, intelligent Fire Alarm Control Panel (FACP) with an extensive list of
powerful features suitable for most applications.
Operating Features
• Alarm Verification selection, to reduce unwanted alarms, for intelligent detector points
• Positive Alarm Sequence (PAS) and Presignal per NFPA 72
• Silence Inhibit timer and Auto Silence timer for Notification Appliance Circuits (NACs)
• March time/temporal code for Notification Appliance Circuits (NACs) and Panel Circuit
modules
• Programmable Signal Silence, System Reset, and Alarm Activate functions through monitor
modules
• Automatic time-of-day and day-of-week control functions, with holiday option
• AWACS™ (Advanced Warning Addressable Combustion Sensing) with nine field-adjustable
Pre-Alarm levels with programmable Control-By-Event (CBE)
• Operate automatic smoke or heat detector sounder base on action Pre-Alarm level, with
general evacuation on alarm level
• Security alarm point option with separate audible signal code
• Audible alarm signaling options
• Programmable Control-By-Event control of outputs from individual alarm or supervisory
addressable devices

14 IQ-636X Operations Manual P/N 52181:A 04/28/2005
Notes

IQ-636X Operations Manual P/N 52181:A 04/28/2005 15
2. Use of the Controls
Introduction
Listing of the controls and indicators and where to find information on their use:
Figure 1 Control Panel Keys and Indicators
Operating Components Covered in
Eight System Status Indicator LEDs “System Status Indicator LEDs” on page 16
Five Control Keys “Control Keys” on page 17
Programming Keypad “Programming Keypad” on page 19
Z X C V B N M
A S D F G H J K L
Q W E R T Y U I O P
*
#
&
/
+
–
(
)
1234567890
!@=,%: . ?
NEXT
SELECTION
PREVIOUS
SELECTION
DETECTOR
MODULE
OUTPUT
RECALL
LAST
ENTRY
INCREMENT
NUMBER
BATTERY
LEVELS
SPACE
FIRE
ALARM
ACKNOWLEDGE
SCROLL DISPLAY
SIGNAL
SILENCE
PRE-ALARM SECURITY SUPERVISORY SYSTEM
TROUBLE
POINT
DISABLED
SIGNALS
SILENCED
POWER
DRILL
HOLD 2 SECONDS
SYSTEM
RESET
LAMP
TEST
Esc
Enter
Control Keys
Status
Indicator
LEDs
Programming Keypad
Function
keys
Cursor movement (arrow) keys,
ESC key, and ENTER key
NFS640keypad.cdr
80-character (2 x 40) Liquid Crystal
Display.(LCD)

2. Use of the Controls System Status Indicator LEDs
16 IQ-636X Operations Manual P/N 52181:A 04/28/2005
System Status Indicator LEDs
The control panel contains eight LEDs with labels as shown below:
Figure 2 System Status Indicator LEDs
Descriptions:
Table 3 Descriptions of System Status Indicator LEDs
Indicator Color When Active To Turn Off
POWER Green Lights when the proper primary AC
power is applied. Remains lit while
power is applied.
Always lit with AC power applied.
FIRE ALARM Red Flashes when a non-acknowledged fire
alarm exists. Lights steadily after you
acknowledge the fire alarm.
Clear the alarm condition and reset
the system.
PRE-ALARM Red Flashes when a non-acknowledged fire
Pre-Alarm exists. Lights steadily after
you acknowledge the Pre-Alarm.
Clear the pre-alarm condition. (An
Action Pre-Alarm requires a
system reset.)
SECURITY Blue Flashes when a non-acknowledged
Security alarm exists. Lights steadily
after you acknowledge the alarm.
Clear the Security alarm condition
and reset the system.
SUPERVISORY Yellow Flashes when a non-acknowledged
Supervisory condition exists. Lights
steadily after you acknowledge the event.
Clear the condition (Supervisory
inputs require a system reset if they
are latching. Refer to Table 6 page
30 for latching information.).
SYSTEM
TROUBLE
Yellow Flashes when a non-acknowledged
system trouble exists. Lights steadily
after you acknowledge the trouble.
Clear the trouble condition.
SIGNALS
SILENCED
Yellow Lights after a fire alarm condition occurs
and after you press SIGNAL SILENCE.
Press SYSTEM RESET. DRILL will
also turn off the LED.
POINT
DISABLED
Yellow Lights when one or more system devices
are disabled.
Enable the device or remove the
disabled device from the system
program.
FIRE
ALARM
PRE-ALARM SECURITY SUPERVISORY SYSTEM
TROUBLE
POINT
DISABLE
D
SIGNALS
SILENCE
D
POWER
NFS640-keypad1.cdr

Control Keys 2. Use of the Controls
IQ-636X Operations Manual P/N 52181:A 04/28/2005 17
Control Keys
The control panel provides five Control Keys as shown below:
Figure 3 Control Keys
Acknowledge/Scroll Display
Use the ACKNOWLEDGE/SCROLL DISPLAY key to respond to new alarm or trouble signals. When pressed, the
control panel does the following:
• Silences the panel sounder
• Changes all active LED indicators from flashing to steady
• Sends an Acknowledge message to the History buffer and installed printers, CRT-2 terminals,
and terminal mode LCD-80s
• Sends a signal to silence the sounders on the LCD-80 and ACS annunciators
You can also press this key to display multiple alarms or troubles. If more than one alarm or trouble
exists, the control panel displays the next alarm or trouble for 3 seconds (or until you press the
ACKNOWLEDGE/SCROLL DISPLAY key), then displays the next alarm or trouble.
Note: Set Local Control to “YES” when used with IQ-646X.
Signal Silence
Use the SIGNAL SILENCE key to silence the panel sounder and turn off all audio and visual devices
connected to Notification Appliance Circuits. When pressed, the control panel does the following:
• Turns off the panel sounder
• Turns off all silenceable output circuits
•LightstheSIGNALS SILENCED LED
• Sends a SIGNALS SILENCED message to the History buffer and installed printers, CRT-2 terminals,
and terminal mode LCD-80s
Note: Set Local Control to “YES” when used with IQ-646X.
Drill
Use the DRILL key to manually activate all silenceable outputs and Notification Appliance Circuits. To
prevent accidental activation, you must press the DRILL key for 2 seconds. When pressed, the control
panel does the following:
• Turns on all silenceable NACs
• Turns off the SIGNALS SILENCED LED
• Sends a Manual Evacuate message to the History buffer and installed printers, CRT-2
terminals, and terminal mode LCD-80s
Note: Set Local Control to “YES” when used with IQ-646X.
ACKNOWLEDGE
SCROLL DISPLAY
SIGNAL
SILENCE
DRILL
HOLD 2 SECONDS
SYSTEM
RESET
LAMP
TEST
NFS640-keypad2.cdr

2. Use of the Controls Control Keys
18 IQ-636X Operations Manual P/N 52181:A 04/28/2005
System Reset
Use the SYSTEM RESET key to reset the control panel. When pressed, the control panel does the
following:
• Clears ALL active inputs
• Interrupts resettable power
• Sends a “System Reset” message to the History buffer, and installed printers, CRT-2 terminals,
and terminal mode LCD-80s
If any alarm or trouble exists after you press the SYSTEM RESET key, all NACs, control outputs, and
panel audio and visual indicators will reactivate.
Note: Trouble conditions will not clear and re-report upon RESET.
Note: Set Local Control to “YES” when used with IQ-646X.
Lamp Test
Use the LAMP TEST key to test the control panel LEDs, all installed panel circuits, and the panel sounder.
When pressed and held, the control panel does the following:
• Lights all control panel LEDs
• Turns on the panel sounder
• Lights all segments of the LCD display. When the LAMP TEST key is held for longer than five
seconds, the LCD will display the Software Revisions.
• Lights all panel circuit LEDs

Programming Keypad 2. Use of the Controls
IQ-636X Operations Manual P/N 52181:A 04/28/2005 19
Programming Keypad
The programming keypad includes:
• Function keys: DETECTOR, MODULE, OUTPUT, BATTERY LEVELS, NEXT SELECTION, PREVIOUS
SELECTION, RECALL LAST ENTRY, AND INCREMENT NUMBER
•ENTER key
• Cursor movement keys: ESC/left arrow key, up key, right key, down key
• Alphabetic and numeric keys, with LOWER CASE selection key
Shown below is the Programming Keypad, with descriptions for the keys.
Figure 4 Programming Keypad
Z X C V B N M
A S D F G H J K L
Q W E R T Y U I O P
*
#
&
/
+
–
(
)
1234567890
!@=,%: . ?
NEXT
SELECTION
PREVIOUS
SELECTION
RECALL
LAST
ENTRY
INCREMENT
NUMBER
SPACE
Esc
Enter
DETECTOR
MODULE
OUTPUT
BATTERY
LEVELS
LOWER CASE key – press
with an alphabetic key to
enter lower case characters
DETECTOR key – press
to select a detector
OUTPUT key – press to select
a NAC or Panel Circuit
MODULE key – press to select a
control/relay or monitor module
NEXT SELECTION key – press to display the next item in a list
or display the device at the next highest address
PREVIOUS SELECTION key – press to display the previous item
in a list or display the device at the next lowest address
Arrow keys – press to move the cursor
one place in the direction of the arrow
ESC key – press to exit a selection or
move the cursor one place to the left
ENTER key – press to complete
or save an entry. Also press to
enter Programming
Numeric keys – press to enter
numeric characters. Press with
Lower Case key for symbols.
Alphabetic keys – press to enter
alphabetic characters
SPACE – press to enter a space
NFS640-keypad3.cdr
BATTERY LEVELS key – press to
check the voltage and
charging status of the
batteries.

20 IQ-636X Operations Manual P/N 52181:A 04/28/2005
Notes
This manual suits for next models
1
Table of contents
Other Ansul Control Panel manuals
Popular Control Panel manuals by other brands

MOOSE
MOOSE MPI-712a installation instructions

Leprecon
Leprecon LP612 user manual

Kentec Electronics
Kentec Electronics Sigma ZXT installation manual

Indel Webasto
Indel Webasto isotherm 101N0510 instruction manual

BLAUBERG Ventilatoren
BLAUBERG Ventilatoren S11 user manual

Sony
Sony BKS-R6010 Maintenance manual