Ansul AutoPulse Acclimate Plus FAPT-851 User manual

This manual suits for next models

2

Other Ansul Security Sensor manuals

Ansul SharpEye 20/20MI-32-S-F Operating instructions

Ansul

Ansul SharpEye 20/20MI-32-S-F Operating instructions

Ansul CHECKFIRE 210 User manual

Ansul

Ansul CHECKFIRE 210 User manual

Ansul PIRANHA User manual

Ansul

Ansul PIRANHA User manual

Ansul CHECKFIRE 110 Technical manual

Ansul

Ansul CHECKFIRE 110 Technical manual

Popular Security Sensor manuals by other brands

Honeywell Home PROSiXCOCN Installation and setup guide

Honeywell Home

Honeywell Home PROSiXCOCN Installation and setup guide

Duevi SIRPZ-RB-868 Operation

Duevi

Duevi SIRPZ-RB-868 Operation

RKI 65-2483RK Operator's manual

RKI

RKI 65-2483RK Operator's manual

Nortech PD160 Enhanced Series user manual

Nortech

Nortech PD160 Enhanced Series user manual

Omron K8AC-H2 manual

Omron

Omron K8AC-H2 manual

Agilent Technologies G8610 Series Quick reference card

Agilent Technologies

Agilent Technologies G8610 Series Quick reference card

Shinko SE2EA-1-0-0 instruction manual

Shinko

Shinko SE2EA-1-0-0 instruction manual

Det-Tronics X Series instructions

Det-Tronics

Det-Tronics X Series instructions

ACR Electronics COBHAM RCL-300A Product support manual

ACR Electronics

ACR Electronics COBHAM RCL-300A Product support manual

TOOLCRAFT 1712612 operating instructions

TOOLCRAFT

TOOLCRAFT 1712612 operating instructions

Elkron IM600 Installation, programming and functions manual

Elkron

Elkron IM600 Installation, programming and functions manual

Bosch WEU PDO 6 Original instructions

Bosch

Bosch WEU PDO 6 Original instructions

THORLABS PDA10JT user guide

THORLABS

THORLABS PDA10JT user guide

Waeco UV-DETECT operating manual

Waeco

Waeco UV-DETECT operating manual

Intermatic IOS-DSIMF manual

Intermatic

Intermatic IOS-DSIMF manual

Siemens AZL66 Series manual

Siemens

Siemens AZL66 Series manual

BTI Profiline Multi Finder operating instructions

BTI

BTI Profiline Multi Finder operating instructions

Challenger SL01 instruction manual

Challenger

Challenger SL01 instruction manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

Detection and Control Components
FAPT-851 Acclimate Plus™
Multi-Sensor Low-Profile Intelligent Detector
(IQ-318/IQ-636X-2)
Features
• Automatically adjusts sensitivity levels without the need for
operator intervention or programming. Sensitivity increases
with heat.
• Microprocessor-based, combination photo and thermal
technology.
• Compatible with FlashScan®systems
• Sleek, low-profile design.
• Rotary, decimal addressing 1 – 159 on FlashScan
systems.
• Addresses can be viewed and changed without the need
for electronic programmers.
• Dual bi-color LED design provides 360° viewing angle.
• LEDs lock RED when in Alarm. In FlashScan, LEDs flash
GREEN in Standby for normal condition.
• Several base options, including relay, isolator, and
sounder.
• Built-in functional test switch activated by external magnet.
• Listed to UL 268.
• Capable of heat-only alarm mode, enabled by a special
command from the panel. Smoke alarms are ignored.
• Low-temperature signal at 45 °F (7 °C) +/– 10 °F (–12 °C).
Applications
The FAPT-851 Acclimate Plus™ detector is an intelligent,
addressable, multi-sensing, low-profile detector designed for
use on the AUTOPULSE IQ-318 or IQ-636X-2 control panel.
The Acclimate Plus detector uses a combination of photo-
electric and thermal sensing technologies that are designed
to increase immunity to false alarms. Unlike traditional intelli-
gent detectors, the Acclimate Plus detector has a micro-
processor in the detector head that processes alarm data. As
a result, the Acclimate Plus detector adjusts its sensitivity
automatically, without needing operator intervention.
Areas where the Acclimate Plus detector is especially useful
include office complexes, schools, college campuses, manu-
facturing and industrial facilities, and anywhere else the use
of a particular area may change. One day a conference
room, tomorrow a kitchen, the next day a copy machine
room – the Acclimate Plus detector automatically adjusts its
sensitivity to the environment.
Technical Information
Voltage Range: . . . . . . . . . . . 15 to 32 volts DC peak
Standby Current: . . . . . . . . . . . . . 360 μA @ 24 VDC
LED Current: . . . . . . . . . . . 6.5 mA @ 24 VDC (“ON”)
Loop Resistance: . . . . . . . . . . . . 40 ohms maximum
Diameter: . . . . . . . . . . . . . . . . . . 4.0 in. (102 mm)
Height: . . . . . . . . . . . . . . . . . . . 1.69 in. (43 mm)
Weight: . . . . . . . . . . . . . . . . . . . . 5.2 oz (147 g)
Temperature: . . . . . . . . 32 °F to 100 °F (0 °C to 38 °C)
Relative Humidity: . . . . . . . 10% – 93% non-condensing
Thermal Sensor:. . . . . . . . . . . . 135 °F (57 °C) (fixed)
UL Listed Velocity Range . . . 0-4000 ft/min (0-1219 m/min)
FAPT-851 DETECTOR WITH
B210LP, B224RB OR B224BI BASE
006869a
FAPT-851 DETECTOR WITH
B501 BASE
006869b
* ADD 1/4 IN. (6 mm) TO HEIGHT FOR B224RB AND B224BI BASES.
4 1/8 IN.
(104 mm) 6 1/8 IN.
(155 mm)
2 1/8 IN.*
(53 mm)
2 IN.
(51 mm)
FAPT-851 with B210LP Base
006880
3-21
Installation
The FAPT-851 plug-in detector uses a separate base to
simplify installation, service, and maintenance. A special tool
allows maintenance personnel to plug-in and remove detec-
tors without using a ladder. Mount base on a box at least
1.5 in. (38 mm) deep. Suitable mounting base boxes include:
• 3.5 in. (89 mm) or 4.0 in. (102 mm) octagonal box
• Single-gang box (except relay or isolator base)
• With B224RB or B224BI base, use a 3.5 in. (89 mm)
octagonal box, or a 4.0 in. (102 mm) octagonal or square
box
Notes: 1) Because of the inherent supervision provided by
the SLC loop, end-of-line resistors are not required. Wiring
“T-taps” or branches are permitted for Style 4 (Class B)
wiring. 2) When using relay or sounder bases, consult data
sheet F-9587 (ISO-X) for device limitations between isolator
modules and isolator bases.
Application Note: The FAPT-851 detector has the unique
ability to adjust sensitivity according to the environment,
based on heat and smoke levels. Avoid installing these
detectors in locations that are susceptible to rapid and high
temperature changes. An example of an incorrect application
would be near or in line with the output of a self-contained
heater.
Bases:
B210LP: . . . . . . . . . . . . 6.1 in. (155 mm) diameter
B501:. . . . . . . . . . . . . . 4.1 in. (104 mm) diameter
B200SR(A): . . . . . . . . . . . . . . . . Sounder Base
B224RB: . . . . . 6.2 in. dia. x 1.2 in. high (157 x 30 mm)
Relay type: . . . . . . . . . . . . . . . . . . . Form-C
Rating: . . . . . . . . . . . . 2.0 A @ 30 VDC resistive
0.3 A @ 110 VDC inductive
1.0 A @ 30 VDC inductive
Screw terminals: . . . . . . Up to 14 AWG (2.00 mm2)
B224BI Isolator: . . . . . . 6.2 in. x 1.2 in. (157 x 30 mm)
Maximum: . . . . . 25 devices between isolator bases
Listings and Approvals*
UL . . . . . . . . . . . . . . . . . . . . . . . . . . . S1115
ULC . . . . . . . . . . . . . . . . . . . . . . . . . . S911**
Factory Mutual (FM) . . . . . . . . . . . . . . . . Approved
California State Fire Marshal (CSFM) . . . . 7272-0028:206
MEA (NYC). . . . . . . . . . . . . . . . . . . . . 225-02-E
Maryland State Fire Marshal. . . . . . . . . . Permit #2122
UL Listed for In-Duct Applications
*Listings and Approvals are under NOTIFIER.
**System Sensor
Ordering Information
Shipping Weight
Part No. Description lb (kg)
432293 FAPT-851 Low-Profile 0.5 (0.23)
Smoke Detector
437078 FAPT-851A Low Profile 0.5 (0.23)
Smoke Detector (ULC)
438966 B210LP 6 in. (152 mm) Flanged 1 (0.45)
Low Profile Base
417487 B501 European Flangeless Base 1 (0.45)
437438 B200SR Sounder Base 1 (0.45)
437439 B200SRA Sounder Base (ULC) 1 (0.45)
423945 B224RB Intelligent Relay Base 2 (0.9)
426125 B224BI Intelligent Isolator Base 2 (0.9)
417675 M02-04-00 Test Magnet 0.5 (0.23)
AUTO-
PULSE
IQ-318 OR
IQ-636X-2
CONTROL
PANEL
REMOTE ANNUNCIATOR
OPTIONAL RETURN LOOP
Address Dial on Back of Detector
Wiring Diagram (Standard Base)
006868
003582
LED 1
LED 2
MAGNET TEST
MARKER
PAINTED
SURFACE
PAINTED
SURFACE
TEST
MAGNET
TEST
MAGNET
004763
TEST MAGNET POSITIONING
TYCO FIRE PROTECTION PRODUCTS Copyright © 2011 Tyco Fire Protection Products
ONE STANTON STREET All rights reserved.
MARINETTE, WI 54143-2542 715-735-7411 Form No. T-2007121-3
FlashScan® is a registered trademark and Acclimate Plus™ are trademarks of Honeywell International.