Antec Fume Hood Controller Series User manual

MANUAL V110
FHC FIRMWARE V1.6.X, FHI FIRMWARE V3.83.X
FUME HOOD CONTROLLER
FHC Series

Introduction
Product Overview......................................................... 1
Features ....................................................................... 1
Fume Hood Interface (FHI) Features ........................... 2
Sidewall Sensor (SWS) Features .................................. 2
Sash Position Sensor (SPS) Features ........................... 2
Presence Sensor (FPS) Features .................................. 2
Installation and Mounting Instructions
Fume Hood Controller (FHC) Installation & Mounting.. 3
Fume Hood Location Considerations ........................... 4
Sash Position Sensor (SPS) Installation & Mounting.... 5
Sidewall Sensor (SWS) Installation & Mounting........... 7
Presence Sensor (FPS) Installation and Mounting ...... 8
Fume Hood Interface Installation ................................ 9
Wiring Diagram .......................................................... 10
Networking and Setup
Fume Hood Network (FHN) ....................................... 11
BACnet MS/TP Network............................................. 12
Sash, Sidewall & Hybrid Configuration
Control Settings.......................................................... 13
VV Application – Interface And Menus
Fume Hood Interface (FHI) ........................................ 14
FHI - Initial Start Up .................................................... 14
Information Menu....................................................... 15
Service Menu............................................................. 15
Control/Monitor .......................................................... 16
Alarm Points ............................................................... 18
Occupancy ................................................................. 18
Input ........................................................................... 19
Output ........................................................................ 20
Network ..................................................................... 22
FHI Setup ................................................................... 22
Diagnostic .................................................................. 23
VV Application – Setup Wizard
Setup Wizard .............................................................. 24
VV Application – Balance And Verification
Balance and Verification.............................................. 26
Balance and Verification - Airflow ............................... 26
VFX Application
Introduction ................................................................ 27
VFX Application – Interface And Menus
Fume Hood Interface (FHI) ......................................... 28
FHI - Initial Start Up .................................................... 28
Information Menu....................................................... 29
Service Menu............................................................. 29
Control/Monitor .......................................................... 30
Alarm Points ............................................................... 32
Occupancy ................................................................. 32
Input ........................................................................... 33
Output ........................................................................ 34
Network ..................................................................... 36
FHI Setup ................................................................... 36
Diagnostic .................................................................. 37
VFX Application – Setup Wizard
Setup Wizard .............................................................. 38
Sash Menu ................................................................. 38
VFX Application – Balance And Verification
Balance and Verification.............................................. 40
Balance and Verification - Airflow ............................... 40
Maintenance
Troubleshooting.......................................................... 41
Replacement Parts ..................................................... 42
Technical Support ....................................................... 42
FUME HOOD CONTROLLER
TABLE OF CONTENTS
IMPORTANT NOTES
CAUTION
This mark indicates an important point for the proper
function of the fume hood and the FHC. Improper
installation or setup may cause unit failure and
contamination of the laboratory space. Pay close attention
to all caution points throughout this manual.
For local area support, please
contact your local Antec Controls
Representative
For more information visit
AntecControls.com

FUME HOOD CONTROLLER
INTRODUCTION
1
AntecControls.com |FHC - Manual
Product Overview
The Fume Hood Controller (FHC) is an
exceptionally versatile controller for
monitoring and controlling fume hood
face velocity. Designed specifically
to meet the needs of all fume hood
types, the FHC provides assurance
that required fume hood face velocity
is satisfied and the work environment
is safe.
The FHC allows for various fume hood
control configurations including sash
position sensing, sidewall face velocity
sensing or hybrid sensing. When
the FHC is utilizing a venturi valve to
control the fume hood exhaust airflow,
the controller measures pressure
drop across the valve allowing for
duct-system pressure alarms and
simplified balancing. Once installed
and commissioned, the FHC is
maintenance-free allowing for reliable
fume hood control and monitoring.
Features
The Fume Hood Controller (FHC) can ensure a safe working environment by
constantly monitoring and adjusting the exhaust to maintain a safe face velocity.
The main control inputs are sash sensors and sidewall sensors. Sash sensors
use a potentiometer attached to the sash to measure the current height. Face
velocity in feet per minute (FPM) is calculated in real time. Sidewall sensors use an
extremely sensitive, low pressure sensor to measure the negative pressure in the
hood compared to the lab space.
• 16 bit – high speed flash based microprocessor with watch dog timer, brown
out reset
• Multi-stage surge protection against voltage spikes on 24 VAC input
• 2 simple connections to sidewall sensors using RJ-12 jacks
• 3 Sash position inputs (10kΩ)
• 2 binary outputs rated at 0.5 amps each, protected with thermal fuse
(RED LED on trip)
• 1 binary output (dry contact)
• 2 analog outputs (0-10 VDC)
• 2 binary inputs
• Pluggable terminal blocks
• Configurable network port for communication on Mnet (High Speed Fume
Hood Network) or BACnet
• 1 potentiometer input
• 1 pressure port input
CAUTION
A higher face velocity is not
always safer. Turbulence in the
fume hood can be created by high
face velocities causing issues with
spillage/blowback.

FUME HOOD CONTROLLER
INTRODUCTION
2FHC - Manual |AntecControls.com
Fume Hood Interface
(FHI) Features
• Backlit 14x2 LCD Interface with true
character display
• LED side bars offer 180 degree
viewing of current fume hood
status
• Variety of colours displayed to
indicate fume hood status
• Password protected setup menu
• Easy to use MENU system for fast
and simple setup of system
• Included RJ45 plenum rated cable
for fast, error free hookup
• Setup Wizard – walk through setup
of FHC when first powered up
Sidewall Sensor (SWS) Features
• Ultra Low flow digital temperature
compensated pressure transducer
• 25 ft. sensor cable with quick-
connect installation
• Sidewall assembly with easy-to-
mount hardware
Sash Position Sensor
(SPS) Features
• Ultra long life potentiometer (over
250,000 cycles)
• Stainless steel cable for stability
• Metal mounting ring for stable
installation and reliability
• Thick plastic cover for protection
against airborne chemical agents
Presence Sensor (FPS) Features
• Low profile device
• Adjustable coverage pattern
• Sensitive response
FUME HOOD INTERFACE
SIDEWALL SENSOR
SASH POSITION SENSOR
PRESENCE SENSOR

FUME HOOD CONTROLLER
INSTALLATION AND MOUNTING INSTRUCTIONS
3
AntecControls.com |FHC - Manual
Fume Hood Controller (FHC)
Installation & Mounting
• Open the controls enclosure on
the Antec Controls valve that is
installed in the fume hood exhaust
duct.
• Follow the wiring diagram in the
project submittals.
Required items:
1Venturi Valve or Venturi FX
2Fume Hood Controller
3Fume Hood Interface
4RJ-45 Plenum Rated FHI Cable,
by Others
LOW
PRESSURE
PORT
HIGH
PRESSURE
PORT
DUCT
AIRFLOW
DIRECTION
VENTURI
VALVE
RJ-45 PLENUM
RATED FHI CABLE
FUME HOOD
CONTROLLER
1
4
FUME HOOD
INTERFACE
3
2
INSTALLATION AND MOUNTING - VENTURI VALVE APPLICATION
CAUTION
The FHC is factory calibrated and
mounted on the valve with which
it was ordered. Only electrical
installation is required.
Ensure the valve is facing the
correct direction and is mounted in
the correct orientation (vertical or
horizontal).

FUME HOOD CONTROLLER
INSTALLATION AND MOUNTING INSTRUCTIONS
4FHC - Manual |AntecControls.com
Fume Hood Location
Considerations
• Ensure supply/exhaust overhead
diffusers/returns are installed away
from fume hood. Direct airflow
running across the ceiling and then
down the face of the fume hood
will greatly affect the SIDEWALL
SENSOR and general performance
of the hood
• Ensure hood is located away from
pedestrian traffic and doors
• Ensure fume hood has all
components installed properly
– such as air foils and sills. Any
missing components can greatly
affect the commissioning of the
hood. Balancing of the face velocity
should not be done if any of these
components are missing.
CAUTION
The location of the fume hood
and overhead diffusers is critical
to proper safety and performance.
These guidelines will ensure the
effectiveness of the fume hood.
CORRECT FUMEHOOD LOCATION
INCORRECT FUMEHOOD LOCATION

FUME HOOD CONTROLLER
INSTALLATION AND MOUNTING INSTRUCTIONS
5
AntecControls.com |FHC - Manual
Sash Position Sensor (SPS)
Installation & Mounting
The sash sensor can be mounted in
one of four ways. Option A mounts
directly above the sash outside of the
fume hood. Options B and C mount to
the counter weight cable, and Option
D mounts directly in the hood.
Option A) Mount the sash sensor
above the sash.
• Ensure the cable is free from
obstruction along the entire length
of sash movement.
• Ensure that the mounting position
of the end of the cable will not pass
above the sash sensor even at the
maximum sash height.
• Run the sensor cable back to the
FHC mounted on the venturi valve.
Option B) Mount the sash sensor on
the top of the fume hood.
• Ensure the cable is free from
obstruction along the entire length
of sash movement.
• The sensor cable may be attached
directly to the counter weight.
This configuration may be desired
when the sash connects to the
counterweight with a belt and
pulley system.
• Run the sensor cable back to the
FHC mounted on the venturi valve.
Option C) Mount the sash sensor on
the top of the fume hood.
• Ensure the cable clamp does not
pass around a pulley.
• Run the sensor cable back to the
FHC mounted on the venturi valve.
• Ensure the sensor cable travels
parallel to the counter weight cable.
OPTION A
OPTION C
OPTION C
OPTION B

FUME HOOD CONTROLLER
INSTALLATION AND MOUNTING INSTRUCTIONS
6FHC - Manual |AntecControls.com
Option D) Mount the sash sensor on
the inside wall of the fume hood. This
is the least preferable mounting option,
as the sensor is directly in the exhaust
air stream.
• Ensure that the sensor and cable to
not interfere with the mechanical
operation of the fume hood sash.
• Ensure the sensor is as close to the
sash as possible so that the cable
is completely parallel to the sash in
all positions.
• Raise the sash to the fully open
position (not just the working
height). Screw the metal ring into
the sash. Ensure that the sensor is
mounted higher than the fully open
position of the sash.
• Once mounted, raise and lower the
sash several times to ensure that
the cable is clear of all obstructions
and moves freely with the sash.
• Run the sensor cable back to the
FHC mounted on the venturi valve.
OPTION D
CAUTION
The sash position sensor cable must
be mounted as close to parallel as
possible with the direction of the
sash movement. Any angle can
cause improper sash height readings
and result in poor control.
CAUTION
If only one SPS is required, the
SPS must be wired into the Sash
Position Sensor #1 port on the
FHC.

FUME HOOD CONTROLLER
INSTALLATION AND MOUNTING INSTRUCTIONS
7
AntecControls.com |FHC - Manual
Sidewall Sensor (SWS)
Installation & Mounting
• The Sidewall Sensor consists of
multiple components: The Sidewall
Sensor, two hollowed bolts, a
male brass pressure port, and kink
resistant tubing.
• With the sash in the fully open
position, drill a 5/16” hole 5”
above and 5” inward from the
base of the sash. Mount the
Sidewall Sensor behind the fume
hood wall, in the fume hood plenum
using one of the hollow bolts.
• To mount the exterior hollow bolt,
drill a 5/16” hole on the front of
the fume hood, no more than 12”
away from the Sidewall Sensor.
• Attach the provided male brass
pressure port to the exterior hollow
bolt.
• Use the kink-resistant tubing to
attach the brass pressure port from
the SWS to the brass pressure port
on the exterior hollow bolt.
• Attach the sensor cable to the SWS
and run the cable back to the FHC
mounted on the venturi valve.
KINK RESISTANT
TUBING
SENSOR
CABLE
BRASS
PRESSURE
PORT
MALE BRASS
PRESSURE PORT
HOLLOWED
BOLT #2 HOLLOWED
BOLT #1
SIDEWALL
SENSOR
THE SIDEWALL SENSOR IS
MOUNTED BEHIND THE WALL, IN
THE FUME HOOD PLENUM, USING
A HOLLOWED BOLT PROVIDED.
Required items:
1Side Wall Sensor
2Hollowed Bolt x2
3Male Brass Pressure Port
4Sensor Cable
5Kink Resistant Tubing
4
2
3
5
1
CAUTION
Mounting position is critical to
ensure the accuracy of the SWS.
Ensure that there are no sharp
bends or kinks in the tubing during
the installation. Improper installation
will cause failure of the SWS.
CAUTION
If only one SWS is required, the
SWS must be wired into the
Sidewall Sensor #1 port on the
FHC.
INSTALLATION & MOUNTING LOCATION
INSTALLATION & MOUNTING DETAILS

FUME HOOD CONTROLLER
INSTALLATION AND MOUNTING INSTRUCTIONS
8FHC - Manual |AntecControls.com
Presence Sensor (FPS) Installation
and Mounting
1. Remove the cover of the presence
sensor by placing the blade of a
small screwdriver in the notch
in the right side of the cover as
shown (see Figure 1). Always
remove the cover in this manner.
2. Drill two screw pilot holes and
one wire passage according to the
template in Figure 2.
3. Insert mounting screws partially
into holes. Route the wire harness
through the wire passage hole as
shown in Figure 3.
4. Route the wire harness through
the hole in the presence sensor.
Install the presence sensor onto
the mounting screw and tighten.
5. Replace the cover by engaging
the left side first and then gently
snapping the cover into place
POWER CABLE
MOUNTING SCREW
CAUTION
Remember to follow these safety
precautions:
• Shut off power to the FHC before
wiring the sensor.
• Always ensure wiring is located
clear of any moving parts to avoid
damage.
FIGURE 1 - INSERT SMALL SCREWDRIVER AND PRY UPWARDS
FIGURE 2 - MOUNTING TEMPLATE
FIGURE 3 - WIRE HARNESS
FIGURE 4 - MOUNTED PRESENCE SENSOR
FIGURE 5 - PRESENCE SENSOR FACTORY SETTINGS

FUME HOOD CONTROLLER
INSTALLATION AND MOUNTING INSTRUCTIONS
9
AntecControls.com |FHC - Manual
ROOM PRESSURE INTERFACE (RPI) – FRONT VIEW
ROOM PRESSURE INTERFACE (RPI) – REAR VIEW
Fume Hood Interface Installation
The fume hood interface will be the main tool used during
setup. It will also be the main display for the hood user once
the hood has been commissioned.
It is recommended to mount the interface at approximately
5 ½’ to 6’ from the floor. This will allow the interface to be at
an appropriate height for use during setup and during normal
operation.
1. Mark the appropriate mounting location for the interface.
CAUTION
There are often disconnect switches and gas/water lines
running in the fume hood. Make sure that the marked
location for the interface does not conflict with any of the
other components that may be installed on/in the fume
hood.
2. Cut approximately a 2”x2” square hole in the front panel
of the fume hood.
3. Remove the backplate from the fume hood interface.
4. Align the backplate with the square hole in the front
panel. Drill two holes to be used for mounting the
backplate.
5. Once wiring and install has been completed, mount the
interface to the backplate and tighten the set screw on
the bottom of the interface for secure mounting.
See right for interface and backplate dimensions.
Emergency
Enter
Menu
Mute
NORMAL ALARM
Emergency
Enter
Menu
Mute
NORMAL ALARM

FUME HOOD CONTROLLER
INSTALLATION AND MOUNTING INSTRUCTIONS
10 FHC - Manual |AntecControls.com
Wiring Diagram
Ensure proper voltage is available if a transformer is available
in the enclosure. Double check all labels and wiring before
applying high voltage.
1. Ensure disconnect switch is off. Route high voltage line
to L1/L2(N) terminal block using knockout/cable clamp
(by others).
2. Connect an RJ-45 (see Wire Specification section of
Manual for PIN layout) plenum-rated cable to jack labeled
Interface on the FHC. Connect the other end to the back
of the FHI mounted on the side of the fume hood.
3. If using a Sash Position Sensor, connect it to the Sash
1 terminal block. The green LED indicator will light
up when the FHC is powered on and the Sensor is
detected.
4. If using a Sidewall Sensor, connect it to the Sidewall
Sensor 1 jack. The green LED indicator will light up when
the FHC is powered on and the Sensor is detected.
CAUTION
The FHC is a 24 VAC low voltage controller. Do not apply
any voltage above 24 VAC to controller.
TYPICAL WIRING DIAGRAM - FHC

FUME HOOD CONTROLLER
NETWORKING AND SETUP
11
AntecControls.com |FHC - Manual
Fume Hood Network (FHN)
What is the Fume Hood Network?
The Fume Hood Network (FHN) (also referred to as Mnet)
allows each Fume Hood Controller (FHC) to communicate
with Pace™. By transmitting this information at high speeds,
Pace™ can ensure that the lab will remain negatively or
positively pressurized even as the fume hoods are opened
and closed.
A single Pace™ in the room will act as an access point to
FHN. Typically, the room’s exhaust valve will act as this
connection, as shown below.
Network Addressing
When configuring the Fume Hood Controller, ensure to
follow the addressing scheme below.
On any Fume Hood Network:
• Maximum number of fume hoods = 16
• Addressing must begin at 1 and go sequentially up to 16
• No duplicate addresses
Physical Connection
FHN consists of a 3-wire network architecture (+, -, and
NETCOM) using a daisy-chain connection between each
device on the network segment.
While FHN is a 3-wire network, the Fume Hood Controller
does utilize an RJ45 connection. When connecting FHN
to Pace™, the installer is required to terminate the 3-wire
connection from Pace™ into an RJ45 connection. It is crucial
to use the correct wires when crimping the cable to avoid
network communication errors.
FHN will utilize PIN 1, PIN 2, and PIN 8 for the +, -, and
NETCOM signals respectively. Antec Controls recommends
using the T568B Color Convention (shown below) for RJ45
connections to standardize the PINs that are used.
End of line termination can be enabled through the Fume
Hood Controller on the last Fume Hood in the physical
wiring. A 100 ohm resistor must be used for end of line
termination where FHN is connected to Pace™.
Wiring requirements:
• 3-conductor wire (24 - 26 AWG)
• Characteristic impedance: 100 ohms
• Capacitance between conductors: Less than 30pF per
foot (100pF per meter)
CAUTION
The maximum wire length between each device on the
network segment must be limited to 35 feet
TYPICAL FHN WIRING
PIN 1
PIN 3
PIN 5
PIN 7
PIN 2
PIN 4
PIN 6
PIN 8
NOTE: Installer must use an 100 ohm resistor at the FHN end of line termination on Pace™.

FUME HOOD CONTROLLER
NETWORKING AND SETUP
12 FHC - Manual |AntecControls.com
BACnet MS/TP Network
What is BACnet?
If no PACE™ controllers are present in the space, BACnet
MS/TP communication may be used to all the Fume Hood
Controllers to communicate with the building automation
network. BACnet communication allows the end user to
verify fume hoods are operating as expected and allows
them to set up trends to monitor energy consumption,
safety, and any alarms that occur.
BACnet Points
See the FHC - Fume Hood Controller product submittal at
AntecControls.com for the BACnet points list.
Network Addressing
When configuring the Fume Hood Controller, the user needs
to assign the unique identifying address for the room.
On any BACnet MS/TP network:
• MAC Address can be between 0 and 127 and must be
unique to the MS/TP segment
• Device Instance can be between 0 and 4,194,303 and
must be unique to the facility
• Baud Rate can be 9,600, 19,200, 38,400, or 76,800 and
must match that of the Router/System Controller for the
MS/TP segment
Physical Connection
BACnet consists of a 3-wire network architecture. Daisy
chain the +, -, and COM connections of all devices on the
network segment as shown below. The FHC utilizes RJ45
connections for its network connection, see below for the
wire colors required when crimping the RJ45 connection (be
sure to follow the T568B color convention).
When using shielded cable, ground the shield at one end of
the network segment only. Connect the shield of the cable
entering a device to that of the cable exiting the device.
Terminate the MS/TP network segment at each end of
the network segment by connecting a 120 ohm resistor
between the + and - network terminals or by enabling
the EOL Termination function in the FHC. Remove the
termination resistor or disable any network terminations
on all devices when adding devices to an existing network
segment.
Wiring requirements:
• Twisted pair
• Shielded (either foil or braided shields)
• Characteristic impedance: 100 – 130 ohms
• Capacitance between conductors: less than 30pF per
foot (100pF per meter)
TYPICAL BACNET WIRING
CAUTION
When using non-isolated power supplies (i.e. Transformer
secondary common connected to ground), do not reverse
24VAC polarity on any device, as it is critical to the network
health.
For system health and reliability, total MS/TP segment
length should be limited to 1050 ft and a maximum of 32
devices.
NOTE: Ensure End of Line Termination is enabled on the FHC at the physical end of line for the MS/TP segment.

FUME HOOD CONTROLLER
SASH, SIDEWALL & HYBRID CONFIGURATION
13
AntecControls.com |FHC - Manual
Control Type Response
Time Accuracy Face
Velocity
Airflow
Control Stability
Monitor N/A High Measured N/A N/A
Sash
Sensor
Control
Fast Moderate Calculated Ye s Stable
Sidewall
Sensor
Control
Moderate High Measured Ye s Stable
Hybrid
Control Fast High Measured Ye s Stable
Control Settings
No Control - Monitor Only
This choice disables all control.
Sash Sensor Control
This method calculates the face
velocity using the dimensions of the
fume hood opening and the current
CFM. This method will control face
velocity.
Sidewall Sensor Control
This method measures the face
velocity over the sash opening by
measuring the pressure inside the
fume hood. This method will control
face velocity.
Hybrid Control
This method is an optimized
combination of both sidewall sensor
and sash sensor control. It is the most
effective method of fume hood control
and is recommended in all cases.
Hybrid Control is only available if both a
sidewall sensor and a sash sensor are
connected.
CAUTION
The device will now only monitor the
face velocity of the unit, but will not
change the airflow or face velocity of
the unit.
CAUTION
Sash Sensor Control and Hybrid Control methods are only available with Venturi
Valve Applications.

FUME HOOD CONTROLLER
VV APPLICATION – INTERFACE AND MENUS
14 FHC - Manual |AntecControls.com
Mute
NORMAL ALARM
Enter
Menu
Emergency
Up Button
Used for menu selection and adjustment – press
both Up and Down arrows at same time to display
interface Startup screens.
Down Button
Used for menu selection and adjustment – press
both Up and Down arrows at same time to display
interface Startup screens.
Mute
Used to temporarily mute the local alarm for a
certain number of minutes.
Menu/Enter
Used to Enter service menu(s). The setup menu(s)
are password protected.
Emergency
Used to trigger emergency mode. Local Alarm
will sound and BACnet point will change to Alarm
alerting the front end system.
Fume Hood Interface (FHI)
FHI - Initial Start Up
When the FHI is first powered from the FHC, it will display the following information: (When on the default display screen
press both UP/DOWN at same time to show this screen.)
PRICE ELECTRONICS
FHI STANDARD MODEL
FHI VERSION 3.XX
LOADING: 0-100 %
FHC VERSION 1.XX
FACE VELOCITY
PRICE ELECTRONICS Start-up screen
FHI STANDARD MODEL Interface
FHI VERSION 3.XX Fume Hood Interface - Firmware Version V3.xx or
higher
LOADING: 0-100 % Loading Screen – Thermostat pulls in variables
FHC VERSION 1.XX Firmware Version
FUME HOOD
NORMAL
After start up LCD will display default screens
depending on mode of operation
CAUTION
If emergency mode is triggered
it can be disabled by pressing the
Emergency button for 5 seconds.
CAUTION
The FHC comes from the factory with a default
configuration. Field setup is required before the fume
hood will be functional. See Page 24 for Setup Wizard
instructions.

FUME HOOD CONTROLLER
VV APPLICATION – INTERFACE AND MENUS
15
AntecControls.com |FHC - Manual
Service Menu
The service menu contains all setup and configuration parameters. Each FHC ships with factory defaults, but virtually all
settings can be adjusted in the field. All MAIN menus are listed on this page. Use the WIZARD and/or menus shown to setup
the FHC for your application.
NOTE: To access the service menu hold ‘Enter/Menu’ for 5 seconds and enter the passcode. This menu is passcode protected
for safety and is only provided to factory trained technicians.
CTRL/MONITOR
ALARM POINTS
OCCUPANCY
INPUTS
OUTPUTS
NETWORK
FHI SETUP
DIAGNOSTIC
Information Menu
Pressing the Enter/Menu button from the default display screen will open this menu.
VALVEPRESSURE
AIRFLOW
SASH 1 HEIGHT
SASH 2 HEIGHT
SASH 3 HEIGHT
SASH OPEN
VELOCITY TRGT
FACE VELOCITY
CONTROL METHOD
OCCUPANCY
VALVEPRESSURE Displays the current Venturi Valve pressure (in.w.c.) when present.
AIRFLOW Displays the current airflow device airflow rate (CFM).
SASH 1 HEIGHT Displays the current height of Sash Sensor 1 (in.)
SASH 2 HEIGHT Displays the current height of Sash Sensor 2 (in.)
SASH 3 HEIGHT Displays the current height of Sash Sensor 3 (in.)
SASH OPEN Displays the current percentage of open sash area (%)
VELOCITY TRGT Displays the current face velocity target (FPM)
FACE VELOCITY Displays the current face velocity
CONTROL METHOD Displays the current face velocity control method.
OCCUPANCY Displays the current occupancy state of the fume hood
CTRL/MONITOR Manual setup menu for control and monitor methods
ALARM POINTS Manual setup menu for alarm points
OCCUPANCY Configure occupancy and override options
INPUTS Configure the functions of the binary inputs
OUTPUTS Configure the functions of the binary and analog outputs
NETWORK Choose network type (BACnet or Mnet)
FHI SETUP Configure the FHI such as display options, LED color, alarm type, etc.
DIAGNOSTIC Provides manual control and monitoring of variables.

FUME HOOD CONTROLLER
VV APPLICATION – INTERFACE AND MENUS
16 FHC - Manual |AntecControls.com
Control/Monitor
CONTROL METHOD HYBRID
SASH CTRL
SIDEWALL CTRL
NO CONTROL
FALLBACK CTRL SW FALLBACK
NO FALLBACK
MONITOR METHOD SASH MONITOR
SW MONITOR
OCC. SETPOINT
DEADBAND
SETBACKSETPNT
OFFDAMPERPOS.
MIN CFM
MAX CFM
SETBACKMINCFM
OFFREPORT0CFM
CTRL/MONITOR: SIDEWALL SW READ MODE
FREEZE VALVE
SENSOR SCALE
FACE VELOCITY
SENSOR OFFSET
SIDEWALL MENU:ZEROSWSENSOR
SIDEWALLMENU: SIDEWALL PID
CTRL/MONITOR: SASH SASH MENU: CALIBRATE SASH CALIBRATING: SASH # MAX HEIGHT
MIN HEIGHT
FULLY OPEN SASH
CLOSE SASH
SASH WIDTH
SASH MENU: SASH CTRL SASH CTRL METHOD LINEAR CAL.
CAL. FROM SW
CAL. MANUALLY
SASH SCALE
SASH OFFSET
CTRL/MONITOR: VALVE AIRFLOW CAL VALVE
CFM SCALE
CFM OFFSET
CAUTION
When using the FREEZE VALVE setting, all airflow control
aspects of the FHC will be disabled. Remember to disable
FREEZE VALVE to restore control.

FUME HOOD CONTROLLER
VV APPLICATION – INTERFACE AND MENUS
17
AntecControls.com |FHC - Manual
CTRL METHOD: HYBRID A hybrid control method uses both a Sash Position Sensor (SPS) and a Sidewall Sensor (SWS) to control the face velocity.
CTRL METHOD: SASH CTRL A sash control method uses a Sash Position Sensor (SPS) to calculate the required ariflow to maintain face velocity based upon the measured sash
position.
CTRL METHOD: SIDEWALL CTRL A sidewall control method uses a Sidewall Sensor (SWS) to adjust airflow to maintain face velocity based upon the pressure differential between the
fume hood and the space
CTRL METHOD: NO CONTROL Airflow will not be controlled. A sidewall or sash position sensor may still be used to monitor face velocity
FALLBACK CTRL If SW FALLBACK selected, the fallback control method will use the SWS in the event that the primary control method malfunctions. Only an option
when sash control method is selected and there is a SWS detected.
MONITOR METHOD If SASH MONITOR selected, the position of the sash and the current airflow will be used to display the calculated face velocity. If SW MONITOR
selected, the face velocity will be displayed based on the differential pressure measurement provided by the Sidewall Sensor
OCC. SETPOINT Sets the face velocity target of the fume hood in Occupied Mode. The velocity can range from 60 FPM to 150 FPM
DEADBAND The range at which the face velocity target is satisfied. Example: The deadband is set to 10 FPM and the face velocity target is 100 FPM. At any face
velocity between 90 and 110 FPM, the control loop is satisfied and current face velocity will display at 100 FPM. Set the deadband to
CAL MODE for a deadband of 0 FPM.
SETBACKSETPNT Sets the face velocity target when the fume hood is in setback mode. The velocity can be set to 0 FPM or in the range of 60 to 150 FPM. To reach 0
FPM, press and hold the down key.
OFFDAMPERPOS. Off Damper Position sets the actuator position of the airflow device when the fume hood is turned off. Setting this to 0% will be a closed damper
position, setting this to 100% will be a fully open damper position.
MIN CFM Sets the minimum allowable airflow for the fume hood. This is a scheduled value. The airflow can range from 0 to 10000 CFM
MAX CFM Sets the maximum allowable airflow for the fume hood. This is a scheduled value. The airflow can range from 0 to 10000 CFM
SETBACKMINCFM Sets the minimum allowable airflow for the fume hood when in Setback. This is a scheduled value. The airflow can range from 0 to 10000 CFM
OFFREPORT0CFM If set to YES, Airflow will be reported as 0 CFM regardless of current conditions when the Fume Hood is in Off mode.
CTRL/MONITOR: SIDEWALL This menu allows for adjustments to the sidewall sensor (SWS).
SW READ MODE This menu is visible if multiple sidewall sensors are available. Selecting HIGHEST SENSOR will use the highest reading SWS to report face velocity.
LOWEST SENSOR will use the lowest reading SWS to report face velocity. AVG SENSOR will average all SWS readings. SENSOR 1 or 2will provide
only that SWS reading.
FREEZE VALVE Freeze the airflow device at its current position. This setting is used when measuring the face velocity while balancing the fume hood.
SENSOR SCALE Adjust the reading of the SWS by using a multiplying factor. Example: If the SWS is displaying 100 FPM and the balancer’s equipment is displaying 85
FPM, set the sensor scale to 0.850. The range is 0.5 to 2.0.
FACE VELOCITY Read only value displaying the current face velocity that is read by the sidewall sensor including adjustments made by SENSOR SCALE and
SENSOR OFFSET.
SENSOR OFFSET Adjust the reading produced by the sidewall sensor by using an offset. Example, if the SWS is displaying 85 FPM and the blancer’s equipment is reading
100 FPM, set the sensor offset to be 15 FPM. This should be a secondary balancing tool. The range is -20 to 20 FPM
SIDEWALL MENU: ZEROSWSENSOR Zero the SWS. Ensure that both the interior and exterior sensor openings are properly sealed before starting this calibration.
If a SWS is plugged in after initial set-up, it will have to be zeroed before it will be functional.
SIDEWALLMENU: SIDEWALL PID The speed the controller responds to the changes in the SWS reading. PID factors are represented as a single number between 0 and 10 with 0 being
the slowest repsonse and 10 beign the fastest response.
CTRL/MONITOR: SASH This menu allows for adjustments to the sash position sensor (SPS).
MAX HEIGHT Set the maximum height of the sash. This is the fully open position which may be above the working height. The height is the distance measured in the
direction of the SPS movement.
MIN HEIGHT Set the minimum height of the sash in its fully closed position. This position is measured from the bottom of the sash to the work surface. This should
not be measured from the bottom of the sash to the fume hood airfoil.
FULLY OPEN SASH The operator should move the sash to the MAX HEIGHT. Once at the MAX HEIGHT, press OK.
CLOSE SASH The operator should move the sash to the MIN HEIGHT. Once at the MIN HEIGHT, press OK.
SASH WIDTH Set the fixed width of the sash. This is not the width of the fume hood but of the sash.
LINEAR CAL. The airflow provided will be calculated using the sash position and the face velocity target. Flow = Height * Width * Face Velocity
CAL. FROM SW The airflow provided is mapped to the SPS based upon the SWS reading to meet the face velocity target. When selected, the user will be asked to
open the sash to various heights and verify that the face velocity signal is stable at each height. For multiple SPS’s, all sashes need to be moved to the
required position for each stage of the Cal.
CAL. MANUALLY The airflow provided is mapped to the SPS based upon face velocity readings measured by face velocity measuring device to meet the face velocity
target. For multiple SPS’s, all sashes need to be moved to the required position for each stage of the Cal.
SASH SCALE Adjust the airflow provided at a given sash opening position by using a multiplying factor. Example, if the balancer is reading 120 FPM, and the fume
hood is at 100 FPM, set the sash scale to 1.2. The range is 0.5 to 2.0
SASH OFFSET Adjust the airflow provided at a given sash opening position by using an offset. Example, if the sidewall sensor is displaying 85 CFM and the Balancer is
reading 100 FPM, set the Sensor Offset to be 15 FPM. This should be a secondary balancing tool, the sash scale is a more accurate tool. The range is 0
to 20 FPM
CAL VALVE Calibrate the venturi valve. This should be performed any time airflow set points are changed, after an actuator is replaced, after a power failure, or
after clutching and manually moving an actuator
CFM SCALE Adjust the factory calibration of a valve. This function is used when the reported valve airflow does not match a balancers traverse readings when the
valve is operating within design pressure limits. Use the CFM Scale to apply a multiplying factor to the valve airflow. The range is 0.5 to 2.0. NOTE:
Need to Cal Valve after changing this setting.
CFM OFFSET Adjust the factory calibration of a valve. This function is used when the reported airflow valve airflow does not match a balancers traverse readings
when the valve is operating within deign pressure limits. Use the CFM Offset to adjust the airflow by an offset factor. The range is (-10 000) to 10 000
CFM. NOTE: Need to Cal Valve after changing this setting.

FUME HOOD CONTROLLER
VV APPLICATION – INTERFACE AND MENUS
18 FHC - Manual |AntecControls.com
Alarm Points
LOW FPM ALARM
HIGHFPM ALARM
SETBACKLOWFPM
SETBACK HIFPM
FPM ALARMHGHT
SASHHGHTCAUTN
SASHHGHTALARM
SB ALARM HGHT
LOPRESS ALARM
HIPRESS ALARM
LOW CFM ALARM
HIGHCFM ALARM
ALARM POINTS:ALARM DELAYS FACE VELOCITY
VALVEPRESSURE
AIRFLOW
SASHHGHTCAUTN
LOW FPM ALARM Set the Low Face Velocity Alarm. Face Velocity below this value
will activate an alarm in Occupied mode. The value ranges from 1 -
100 FPM or can be disabled.
HIGHFPM ALARM Set the High Face Velocity Alarm. Face Velocity above this value
will activate an alarm in Occupied mode. The value ranges from 100
- 200 FPM or can be disabled.
SETBACKLOWFPM Set the Setback Low Face Velocity Alarm. Face Velocity below this
value will activate an alarm in Setback mode. The value ranges
from 0 - 100 FPM.
SETBACK HIFPM Set the Setback High Face Velocity Alarm. Face Velocity above this
value will activate an alarm in Setback mode. The value ranges
from 60 - 200 FPM or can be disabled.
FPM ALARMHGHT Below the FPM Alarm Height value, High Face Velocity alarms are
disabled. For example setting the FPM Alarm Height to 3 inches
will disable High Velocity Alarm when the sash is less than 3
inches. This value ranges from 0 to 25 inches. This function reduces
nuisance alarms in the closed sash position.
SASHHGHTCAUTN Set the Sash Caution Height. Sash positions greater than this value
will activate a Caution status in Occupied mode. The value ranges
from 0 to 25 in.
SASHHGHTALARM Set the Sash Alarm Height. Sash positions greater than this value
will activate Alarm Mode in Occupied Mode. The value ranges from
0 to 25 in. Sash Alarm Height will override Sash Caution Height.
SB ALARM HGHT Set the Setback Sash Alarm Height. Sash positions greater than
this value will activate Alarm Mode in Setback Mode. The value
ranges from 0 to 25 in.
LOPRESS ALARM Set the Low Valve Pressure Alarm. Venturi Valve static pressure
below this value will activate an Alarm. The value ranges from 0 to
5.0 in.w.c or can be disabled.
HIPRESS ALARM Set the High Valve Pressure Alarm. Venturi Valve static pressure
above this value will activate an Alarm. The value ranges from 0 to
5.0 in.w.c or can be disabled.
LOW CFM ALARM Set the Low Airflow Alarm. Airflow below this value will activate an
Alarm. This value ranges from 0 to 10000 CFM or can be disabled.
HIGHCFM ALARM Set the High Airflow Alarm. Airflow above this value will activate
an Alarm. This value ranges from 0 to 10000 CFM or can be
disabled.
FACE VELOCITY Delay for the Face Velocity Alarm. This delay ranges from 0 and 30
seconds
VALVEPRESSURE Delay for the Valve Pressure Alarm. This delay ranges from 0 and
30 seconds
AIRFLOW Delay for the Airflow Alarm. This delay ranges from 0 and 30
seconds
SASHHGHTCAUTN Delay for the Sash Height Caution. This delay ranges from 0 and
30 seconds
Occupancy
OCC OVERRIDE NO OVERRIDE
FORCE SETBACK
FORCE OCC
FORCE OFF
NO OVERRIDE The occupied status of the Fume Hood is not overridden.
FORCE SETBACK Occupancy is currently forced to setback mode. All Setback options
will now be active
FORCE OCC Occupancy is currently forced to Occupied operation. All Occupied
options will now be active
FORCE OFF Occupancy is currently forced to Off. The FHC is not monitoring
or controlling airflow or face velocity. All alarms and cautions are
inactive
Table of contents
Popular Controllers manuals by other brands

HEXFLY
HEXFLY HEX8 user manual

Acuity Brands
Acuity Brands nLight nPWDMX SNAPSHOT DIN instructions

Dover
Dover DESTACO ROBOHAND DRG Series manual

Salto
Salto BLUEnet CUC1B0 Series installation guide

LOVATO ELECTRIC
LOVATO ELECTRIC ATL600 instruction manual

Extron electronics
Extron electronics MediaLink MLC 104 Plus Series Setup guide

Omron
Omron TJ2-MC64 Hardware reference manual

Mitsubishi Electric
Mitsubishi Electric AJ61BT11 user manual

Aube Technologies
Aube Technologies RC845 installation instructions

iTach
iTach Flex WiFi quick start

Euroterm
Euroterm 2604 Installation and wiring instructions

Flycolor
Flycolor Raptor BLS Series user manual