AP TC5-1N5FAB User manual

REV. 01
M 890-00165 rev. 06
TC5-1N5FAB
Combined Ventilation Controller
USER'SMANUAL
SETTINGS
FUNCTIONS

2TC5-1N5FAB rev.06
TABLE OF CONTENTS
PRECAUTIONS .............................................................. 3
FEATURES..................................................................... 4
LOCATION OF THE CONTROLS................................... 6
ControllerStatusLeds................................................... 7
InternalSwitches ........................................................... 7
INSTALLATION .............................................................. 8
MountingInstructions ..................................................... 8
Connections.................................................................. 8
MotorTypes.................................................................. 9
TemperatureProbes .....................................................10
Stage3Operation.........................................................12
CHANGING THE PARAMETER SETTINGS .................. 13
UsingtheDisplay .......................................................... 13
LockingtheParametersSettings ..................................14
TEMPERATURE SETTINGS .......................................... 15
TemperatureUnits.........................................................15
ViewingTemperatures ..................................................15
TemperatureSetPoint ..................................................18
TemperatureCurve .......................................................19
VENTILATION SETTINGS.............................................. 23
CoolingOperation......................................................... 23
MinimumVentilationCycle ............................................27
HumidityCompensation ................................................29
MinimumSpeedCurve.................................................. 32
DifferentialSettings....................................................... 38
Mist Cooling..................................................................40
NATURAL VENTILATION .............................................. 43
PrincipleofOperation ................................................... 43
CurtainOperatingTimeCompensation .........................46
ManualOperationoftheCurtains ..................................47
HEATER SETTINGS....................................................... 48
ALARM SETTINGS......................................................... 54
TEST MODE.................................................................... 56
TROUBLESHOOTING GUIDE........................................ 57
TECHNICAL SPECIFICATIONS..................................... 61
FACTORY SETTINGS .................................................... 62
FUNCTION SUMMARY................................................... 64
GLOSSARY..................................................................... 68
Page

3
TC5-1N5FAB rev.06
We strongly recommend installing supplementary natural
ventilation as well as a back-up thermostat on at least one
cooling stage (refer to the wiring diagram enclosed with this
user's manual to connect the thermostat).
Although fuses on the outputs of the controller protect its cir-
cuits in case of an overload or overvoltage, we recommend
installing an additional protection device on the controller's
supply circuit.
The room temperature where the controller is located MUST
ALWAYS REMAIN BETWEEN 32°F AND 104°F (0°C TO 40°C).
To avoid exposing the controller to harmful gases or exces-
sive humidity, it is preferable to install it in a corridor.
DO NOT SPRAYWATER ON THE CONTROLLER
PRECAUTIONS
FORCUSTOMERUSE
Enter the serial number located on
the side of the controller below for
future reference.
Model number:
Serial number: TC5-1N5FAB

4TC5-1N5FAB rev.06
The TC5-1N5FAB is an electronic device used for environmental control in
livestock buildings. It allows the user to maintain a specified target tem-
perature by controlling the operation of ventilation and heating equipment.
Onestageofvariablespeed fans, up totwostagesofconstant-speed fans,
as well as curtains, foggers and heaters can be connected to the controller.
Themainfeatures oftheTC5-1N5FAB are as follows:
THREE-DIGITDISPLAY
A three-digit display provides a high level of accuracy, allowing the user to
specify a temperature to within one tenth of a degree (in Fahrenheit or Cel-
sius units).
PILOT LIGHTS
Pilot lights indicating the state of outputs allow the user to monitor the
operation of the system without having to enter the building.
MINIMUMVENTILATION CYCLE
Whenventilationisnot requiredforcooling,the first stagefanscan be oper-
atedeithercontinuouslyor intermittently to reducethelevelof humidity and
supply oxygen to the room.
TEMPERATUREAND MINIMUMVENTILATION SPEEDCURVES
Thecontrollercanbeset to automaticallychangethetemperatureset point
andtheminimum ventilationspeedover agivenperiod oftimeinaccordance
withtheuser'srequirementsby specifying a temperature curveandamini-
mum ventilation speed curve with up to six different points each.
CHOICE OF TEN MOTOR CURVES
Thevariationinmotorspeed resulting from achangeinvoltagewill depend
onthemakeand capacity of themotor. Inorderto achieve a high degreeof
compatibilitybetweencontrollerandmotor, theusercan choosefromamong
tendifferentmotorcurves, thus ensuringthatthecorrect voltage issupplied.
HUMIDITYCOMPENSATION
Thestage1minimumspeed can be adjusted automaticallyasafunctionof
relative humidity. As humidity increases, the minimum speed of stage 1
fans increases proportionally to compensate for the change.
FEATURES
69
TC5-1N5FAB rev.06
TC5-1N5FAB
RAMPING ON STAGE 1: When the temperature rises to the point where
Stage 1 constant-speed fans are needed for cooling, the running time of
the fans is increased gradually from the minimum ventilation settings up
to full operation. Likewise, when the temperature drops below the set
point, the running time is decreased gradually until the minimum ventila-
tion settings are reached.
SET POINT: The set point is the target room temperature. When the
temperature is above the set point, the controller cools the room by
turning on the cooling fans. When the temperature is below the set point,
the controller heats the room by turning on the heaters.
TEMPERATURE CURVE: The controller can be set to automatically
change the temperature set point over a given period of time in accor-
dance with the user's requirements. The set point decreases over time as
theanimalsgrow.
ZONED HEATERS: Whenzonedheaters are used, heaters ineachzone
operateaccordingtotheir own probes ratherthantheaverage temperature
for the entire room. In this way, heaters across zones are independent of
oneanother.

68 TC5-1N5FAB rev.06
GLOSSARY
BANDWIDTH: Thetemperature interval withinwhichthe variable-speed
fans of a given stage increase or decrease in speed proportionally to the
temperature.
CASCADING HEATERS: Heaters operate in a sequence. As the
averageroomtemperaturedrops, additional heatersareturnedon as
needed.
CURTAIN DEAD BAND: Thedeadbandis the temperaturedifference
between the opening and closing temperatures of the curtains. Within
this interval, the curtains are at rest.
DEFAULT VALUE: Atypical parameter setting defined at the factory.
DIFFERENTIAL: Thedifferentialis thetemperaturedifference between
the moment the constant-speed fans or heating units of a given stage
start running and the moment they return to a stop.
HYSTERESIS: A hysteresis is used to smooth the transition from one
state to another. For example, when the temperature drops to the cut-off
point for a stage of constant-speed fans, the fans will actually be cut off at
slightly less than the cut-off point. This way, if the temperature fluctuates
around the cut-off point without dropping significantly below it, the control-
ler will not oscillate between two states. For example, if the hysteresis is
0.3°F and the stage 2 fans are programmed to be cut off at 75°F, the cut-
off will actually occur at 74.7°F.
MINIMUM VENTILATION CYCLE: Whentheroomtemperature is below
the set point, the Stage 1 fans operate intermittently to provide minimum
ventilation to the room.
MINIMUM VENTILATION SPEED CURVE: WhenStage1operates
variable-speed fans, they will run at minimum speed during the minimum
ventilationcycle. Theusercandefinea minimum ventilation speed curve
to adjust the Stage 1 minimum speed automatically over a given time
period. Theminimumspeedincreasesovertime as the animals grow.
OFFSET: An offset is a temperature difference from the set point that
normally defines a cut-off point for a stage operation. For example, a
heater offset of 2°F means the heaters will turn off at 2°F below the set
point.
5
TC5-1N5FAB rev.06
TC5-1N5FAB
HIGH/LOW TEMPERATUREALARM OUTPUT
FULL-SPEED FAN START-UP
In order to overcome the inertia of the ventilation system components and
de-ice the fan blades in cold weather conditions, the controller supplies
maximumvoltagetothevariable speed fansduringthe2seconds immedi-
ately following each start-up.
FOURINDEPENDENT TEMPERATURE PROBE INPUTS
Uptofour temperature probescanbe connected tothecontroller in orderto
obtain a more accurate reading of the average room temperature and a
faster reaction time.
OUTSIDETEMPERATURE COMPENSATION ON CURTAINSPEED
Curtain opening and closing times can be decreased as a function of out-
sidetemperature.
OVERLOADAND OVERVOLTAGEPROTECTION
Fuses and other protection devices are installed on the outputs of the con-
troller to protect its circuitry in the case of an overload or overvoltage.
COMPUTERCONTROL
The controller can be connected to a computer, thus making it possible to
centralizethemanagementofinformation and diversify controlstrategies.
CONTROL OF AIR INLET MOVEMENT
IftheTC5-1N5FABisused incombinationwith aPF-5Bcontroller,themove-
mentoftheair inletscanbecoordinated with theoperationof the fansusing
a potentiometer located on the panel drive. This allows the air inlets to be
adjusted correctly, without the influence of uncontrollable factors such as
windorairfromadjoining rooms.
TEST MODE
Atestmodeallows you to simulatetemperaturechangesand verify control-
lerperformance.

6TC5-1N5FAB rev.06
LOCATIONOFTHECONTROLS
S
E
T
T
I
N
G
S
FUNCTIONS
67
TC5-1N5FAB rev.06
TC5-1N5FAB
POSITION DISPLAY MEANING
MIST
TIMER/
OFFSET/
DIFF.
Oft / StP Mist offset (stop temperature).
diF / Str Mist differential (start temperature).
On Time on for mist cycle.
Off Time off for mist cycle.
StP rH Humidity turn off level.
HEAT 1-2 -
OFFSET/
DIFF.
Ht.1 / Oft / StP Heater 1 offset (stop temperature).
Ht.1 / diF / Str Heater 1 differential (start temperature).
Ht.2 / Oft / StP Heater 2 offset (stop temperature).
Ht.2 / diF / Str Heater 2 differential (start temperature).
Zon DiF Max. Temperature Difference Between Zones.
ALARM OFFSETS
Lo Low alarm offset.
Hi High alarm offset.
Cri. Critical temperature.
OUTSIDE T°
SETTINGS
Steady value / Off Outside temperature / probe deactivated
flashing value Outside set point
ON / OFF On / off state of curtain compensation

66 TC5-1N5FAB rev.06
TC5-1N5FAB
POSITION DISPLAY MEANING
STAGE 2 / 3
St.2 / Str Stage 2 differential (start temperature)
St.3 / Oft Stage 3 offset
St.3 / Str Stage 3 differential (start temperature)
CURTAINS - DEAD
BAND / TIMER
Deb Curtain Dead Band
ON Time on
OFF Time off
Aut /
Off /
OPE /
CLO
Aut - automatic mode
Off - manual off
OPE - manual open
CLO - manual close
CURTAINS -
MANUAL
Aut /
Off /
OPE /
CLO
Aut - automatic mode
Off - manual off
OPE - manual open
CLO - manual close
MIST
TIMER/
OFFSET/
DIFF.
Oft / StP Mist offset (stop temperature).
diF / Str Mist differential (start temperature).
On Time on for mist cycle.
Off Time off for mist cycle.
StP rH Humidity turn off level.
7
TC5-1N5FAB rev.06
TC5-1N5FAB
LED MEANING
STAGE 1TURNS ON WHEN STAGE 1 FANS ARE ON.
STAGE 2 / 3FLASHES WHEN STAGE 2 FANS ARE ON. TURNS ON WHEN STAGE
3 FANS ARE ALSO ON.
CURTAINS FLASHES WHEN CURTAINS ARE CLOSING. TURNS ON WHEN
CURTAINS ARE OPENING.
MIST TURNS ON WHEN MIST UNITS ARE ON.
HEATER 1TURNS ON WHEN HEATER 1 IS ON.
HEATER 2TURNS ON WHEN HEATER 2 IS ON.
DEF. PROBE/
ALARM TURNS ON WHEN AN ALARM IS DETECTED. BLINKS WHEN A
DEFECTIVE PROBE IS DETECTED.
COMPENSATION TURNS ON WHEN THE COMPENSATION ON STAGE 1 MINIMUM
VENTILATION SPEED IS IN EFFECT OR WHEN THE COMPENSATION
ON THE MIST STAGE IS IN EFFECT.
CONTROLLER STATUS LEDS
#OFF ON
1UNLOCKED PARAMETERS LOCKED PARAMETERS
2FAHRENHEIT DEGREES CELSIUS DEGREES
3PROBE 2 DISABLED PROBE 2 ENABLED
4PROBE 3 DISABLED PROBE 3 ENABLED
5PROBE 4 DISABLED PROBE 4 ENABLED
6OUTSIDE PROBE DISABLED OUTSIDE PROBE ENABLED
7STAGE 3 COOLING STAGE 3 HEATING
8CASCADING HEATERS ZONED HEATERS
9NO ACTION CLOSE PF-5B AIR INLET ON
CURTAIN OPENING
10 FLOATING STAGE 3
DISABLED FLOATING STAGE 3
ENABLED
11 RESERVED
12 RESERVED
INTERNAL SWITCHES
Theinternalswitchesare located on theinsideofthe front cover. Whenthe
controller is shipped from the factory, all the switches are set to OFF.
ON
2
134 6 75 8 9 11
10 12

8TC5-1N5FAB rev.06
Toconnectthecontroller,refertothewiringdiagramenclosedwiththisuser's
manual.
nSet the voltage switch to the appropriate voltage.
nUse the electrical knockouts provided at the bottom of the enclosure.
Donotmakeadditionalholes intheenclosure, particularlyontheside
oftheenclosurewhen using acomputercommunicationsmodule.
nIt may be necessary to install a transformer in order to supply the
appropriatevoltagetotheheating unit.
ALARMCONNECTION: Therearetwotypesofalarmsonthemarket. One
typeactivateswhencurrentiscutoffatitsinput,whereastheotheractivates
whencurrentissuppliedatitsinput. Foranalarmofthefirsttype,usetheNO
terminalasshownonthewiringdiagram. Foranalarmofthesecondtype,use
theNCterminal.
ALLWIRINGMUSTBEDONEBYANAUTHORIZEDELECTRICIAN
AND MUST COMPLY WITH APPLICABLE CODES, LAWS AND
REGULATIONS.BESUREPOWERISOFFBEFOREDOINGANY
WIRINGTOAVOIDELECTRICALSHOCKSANDEQUIPMENTDAM-
AGE.
INSTALLATION
MOUNTING INSTRUCTIONS
CONNECTIONS
Openthelatchandliftthecover.Removetheblackcapslocatedoneachof
thefourmountingholes. Mounttheenclosureonthewallusingfourscrews.
Besuretheelectricalknockoutsare at the bottom oftheenclosureinorder
topreventwaterfromenteringthecontroller.Insertthescrewsinthemounting
holesandtighten. Fastenthefourblackcapsprovidedwiththecontrolleronto
the four mounting holes. The enclosure must be mounted in a location that
will allow the cover to be completely opened right up against the wall.
!
WARNING
65
TC5-1N5FAB rev.06
TC5-1N5FAB
POSITION DISPLAY MEANING
STAGE 1 - MIN.
SPEED / CURVE
flashing value User-adjusted minimum speed.
steady value Minimum speed calculated using the minimum
speed curve.
On / OFF Status of minimum speed curve
dAY Day number of the curve point for minimum
speed
SPd Minimum speed of the curve point for minimum
speed
Cur.dAY The current day reference for minimum speed
curve.
STAGE 1 -
BANDWIDTH/
TIMER
flashing value Bandwidth
Ou.C Bandwidth displayed is compensated for
outside temperature
On Time On for minimum ventilation cycle
OFF Time off for minimum ventilation cycle
tYP Motor type for variable speed motors
STAGE 1 -
HUMIDITY
steady value Current relative humidity reading.
Lo / Hi Minimum and maximum humidity levels.
On / OFF Status of humidity compensation.
set rH The relative humidity set point.
SPd Minimum Speed Compensation.
On Time on for Heater 1 timer.
OFF Time off for Heater 1 timer.

64 TC5-1N5FAB rev.06
POSITION DISPLAY MEANING
ROOM
TEMPERATURE
steady value Room temperature
Pr1 - On/OFF
Pr2 - On/OFF
Pr3 - On/OFF
Pr4 - On/OFF
Room temperature and on/off state for probe x
Lo / Hi Minimum / Maximum temperature value.
SET POINT / T°
CURVE
flashing value User-adjusted set point.
steady value Set point calculated using the temperature
curve.
On / OFF Status of temperature curve.
dAY Day number of the current temperature curve
point.
set Set point of the current temperature curve point.
FUNCTIONSUMMARY
9
TC5-1N5FAB rev.06
TC5-1N5FAB
The relationship between the voltage supplied to a motor and its operating
speed is described by a motor curve. This curve varies with the make and
capacityofthemotor. Thevariousmotorsavailableintheindustryhavebeen
dividedintotencategoriesandthe controller has been programmedwitha
different motor curve for each of these categories. To ensure that the
controller supplies the correct voltages, an appropriate curve must be
selected for Stage 1 according to the type of fan motors used.
Selecting a Motor Type for Stage 1
Refertothelistofmotorsenclosedwiththisuser'smanualtodeterminewhich
curve number (1 to 10) is appropriate for the type of motors used.
nSet the selection knob to
STAGE 1 — BANDWIDTH/
TIMER.The Stage1bandwidthis
displayedand flashes.
nPressthepush-buttonthreetimes.
Thecurrentlyselectedtypeisdis-
played,alternatingwiththeletters
"tYP".
nUsetheadjustmentknobtoadjustthemotortypetothedesiredvalue.
nReturn to the Stage1bandwidthdisplay either by pressingthepush-
buttononceagain.
MOTOR TYPES

10 TC5-1N5FAB rev.06
TC5-1N5FAB
1
Connecting the Probes
The controller is supplied with one temperature probe connected to input
# 1. Three additional room probes can be connected to inputs # 2, 3 and 4
and an outside probe can be connected to input # 5 (see wiring diagram
enclosed).
CAUTION: Probes operate at low voltage and are isolated from the
supply. Be sure that probe cables remain insulated from all high voltage
sources. In particular, do not route the probe cables through the same
electricalknockoutasothercables. Donotconnecttheshieldfromtheprobe
cable to a terminal or a ground.
Switchesareusedtoactivateordeactivatetheadditionalprobesconnected
to the controller.
nActivate each additional probe by setting
the appropriate switch toON:
• Switch # 3 activates the probe connected to input # 2.
• Switch # 4 activates the probe connected to input # 3.
• Switch # 5 activates the probe connected to input # 4.
2
Extending the Probes
Eachprobecanbeextendedupto500feet(150meters). Toextendaprobe:
nUseashielded cable ofoutsidediameter between 0.245and0.260 in
(6.22 and 6.60 mm) (the cable dimensions should not be under 18
AWG) to ensure the cable entry is liquid tight. Do not ground the
shielding.
nIt is preferable to solder the cable joint to ensure a proper contact
between the two cables.
TEMPERATURE PROBES
34
ON
5
63
TC5-1N5FAB rev.06
TC5-1N5FAB
NOTES:
i)Theseinitial parameter settingswillnot be retainedinthe controller's
memory. Each new setting will replace the preceding one.
ii) If the power supply is cut off, the last parameter settings will be
retained in memory until the power is restored.
PARAMETER FACTORY
SETTING RANGE OF
VALUES
Mist
Time On 1 minute 0 to 60 minutes,by
increments of 1
minute
Time Off 10 minutes
Offset 14°F (7.8°C) 0.5 to 40 oF
(0.3 to 22.2 oC)
Differential 2oF(1.1oC) 0.5 to 20 oF
(0.3 to 11.1 oC)
Humidity Turn
Off Level 95% 40 to 100% relative
humidity
Heater 1
Differential 2oF(1.1oC) 0.5 to 20 oF
(0.3 to 11.1 oC)
Offset 2.0oF(1.1oC) -10 to 20 oF
(-5.6 to 11.1 oC)
Heater 2
Differential 2oF(1.1oC) 0.5 to 20 oF
(0.3 to 11.1 oC)
Offset 2.0oF(1.1oC) -10 to 20 oF
(-5.6 to 11.1 oC)
Max. Temperature Diff.
Between Zones 7.5°F (4.2°C) 5 to 40°F
(2.8 to 22.2°C)
Alarms
High Offset 12.0oF(6.7oC) 0.5 to 40 oF
(0.3 to 22.2 oC)
Low Offset 10.0oF(5.6oC) 0.5 to 40 oF
(0.3 to 22.2 oC)
Critical High
Temperature 95°F (35°C) -40 to 120.0 oF
(-40 to 48.9 oC)

62 TC5-1N5FAB rev.06
FACTORYSETTINGS
PARAMETER FACTORY
SETTING RANGE OF
VALUES
Temperature Set Point 75oF(23.9oC) -40 to 99.9 oF
(-40 to 37.7 oC)
Stage 1
Minimum Speed 40 %10 % to 100 %
Time On 15 seconds 0 to 900 seconds by
increments of 15
seconds
Time Off 0 seconds
Bandwidth 2oF(1.1oC) 0.5 to 20 oF
(0.3 to 11.1 oC)
Humidity
Control
Humidity
Set Point 65% 40 to 100% relative
humidity
Compensation
Percentage 60% 0 to 100% of stage 1
minimum speed
Stage 2Differential 2oF(1.1oC) 0.5 to 20 oF
(0.3 to 11.1 oC)
Stage 3
Offset 0°F (0°C) 0 to 20°F
(0 to 11.1°C)
Differential 2oF(1.1oC) 0.5 to 20 oF
(0.3 to 11.1 oC)
Curtains
Dead Band 2oF(1.1oC) 0.5 to 20 oF
(0.3 to 11.1 oC)
Time On 20 seconds 0 to 900 seconds, by
increments of 1
second
Time Off 80 seconds
Outside Set
Point 70°F (21°C) -40 to 99.9 oF
(-40 to 37.7 oC)
11
TC5-1N5FAB rev.06
TC5-1N5FAB
CAUTION: Donotrun probecablesnextto otherpowercables. When
crossing over other cables, cross at 90°.
3
Installing the Outside Probe
nRuntheoutsideprobecableonthenorthsideofthebuilding,6ft(2m)
below the eave, inside a pale colored conduit. Avoid installing the
probe in direct sunlight or exposed to the rain.
nBe sure the probe cable is isolated from sheet metal or any other
conductivematerial.
nBe sure no cable joint is exposed to air or water.
4
Defective Probes
Ifadefectiveprobeisdetected,theDefectiveProbePilotLightflashes.The
room temperature shown on the display is then the average temperature
measured by the probes in working condition. The controller will operate
accordingtothistemperature.
Toidentifythedefectiveprobe:
nSettheselectionknob to ROOM
TEMPERATURE.Theroomtem-
peratureisdisplayed.
nPress the push-button. If the
probeconnectedtoinput # 1and
suppliedwiththe controller isnot
defective,theletters"PR1"aredis-
played, alternating with the on/
offstate ofthe probeand thetem-
peraturemeasuredby theprobe.
If the probe is defective, the let-
ters "PR1" are displayed, alter-
natingwiththestate of theprobe
and the letter "P".

12 TC5-1N5FAB rev.06
TC5-1N5FAB
For each additional probe connected to the controller:
nPress the push-button once again. If the probe is not defective, the
letters "PR#" (where #isthenumber of theinputtowhich the probeis
connected)aredisplayed, alternating withtheon/off stateoftheprobe
andthetemperature measured bytheprobe. If theprobeisdefective,
theletters"PR#"aredisplayed,alternatingwiththe on/off state of the
probe and the letter "P".
Outside Probe: Iftheoutsideprobeis
defective, the display shows the letter
"P"whentheparameterselectionknob
is set to OUTSIDE To.
STAGE 3 OPERATION
Stage 3 can operate as a heating or cooling stage.
ðSet switch # 7 toOFF to use Stage 3
forcooling.
ðSet switch # 7 to ON to use Stage 3
forheating. 7
ON
61
TC5-1N5FAB rev.06
TECHNICALSPECIFICATIONS
Supply: -115/230VAC(-18%, +8%), 60Hz,L1 same phasesasStage1,
overloadandovervoltageprotectionfuseF9 fastblow.
-12VDCforACback-upsupply;canactivatestages2-6ifsupplied
withDCback-upvoltage.
Stage 1: Variable output, 60 Hz, 10A FAN (1/2 HP/115 VAC) / (1.5 HP/
230VAC),fuseF1-15Aslow blow.
Stage2: ON-OFFoutput,115/230VAC,60Hz,30VDC,6AFAN,10A RES,
fuseF2-15A slowblow.
Stage3: ON-OFFoutput,115/230VAC,60Hz,30VDC,6AFAN,10A RES,
heating or cooling, fuse F3-15A slow blow.
Curtains: OPEN-CLOSE output, 115/230 VAC, 60 Hz, 30VDC, 5A winch
output, fuse F6-5A slow blow.
Mist: ON-OFFoutput,115/230VAC,60Hz,30VDC,6AFAN,10A RES,fuse
F5-15Aslowblow.
Heater1: ON-OFFoutput,115/230VAC,60Hz,30VDC,6AFAN,10A RES,
heating, fuse F4-15A slow blow.
Alarm: ON-OFFoutput,115/230VAC,60Hz,30VDC,3A,fuseF8-3Aslow
blow.
Probes: Low voltage ( <5V), isolated from the supply. Operating range:
-40.0°to120.0°F(-40.0°to48.9°C).Accuracy:1.8oF(1oC)between41oand
95oF(5oand35oC).
Enclosure: ABS, moisture and dust-tight.
Theroomtemperaturewherethecontrollerislocated MUST
ALWAYSREMAINBETWEEN32oAND104oF(0oAND40oC).

60 TC5-1N5FAB rev.06
TC5-1N5FAB
CAUSE SOLUTION
The Stage's fuse is
open. Replace the fuse.
The display board
interconnect cable is
not plugged into the
power supply board
properly.
Make sure the cable is firmly
plugged in with the tabs in place.
The wiring is incor-
rect. Correct the wiring. In particular,
make sure two different lines
are connected to each motor:
line L1 modulated by the
controller should be combined
with another line (N for 115V or L2
for 230V) to activate the motor or
heating unit. Also, make sure the
Stage COMMON is supplied by
line L1.
Verify if the motor or heating unit
is defective by connecting it to
an alternate power supply.
Replace the motor or heating
unit If it still is not operating.
The fan motor or
heating unit is
defective.
The controller is
defective. Listen to see if there is a clicking
sound when the Stage's pilot
light turns on. If there is no
clicking sound, contact your
distributor to repair the control-
ler.
PROBLEME
One of the
other stages
is not operat-
ing.
13
TC5-1N5FAB rev.06
Flashing Values: The dis-
playwillflashin certain cases
and not in others. The flash-
ing indicates that the value
shown can be adjusted. A
valuethatisnotflashing can-
not be adjusted.
CHANGING THE PARAMETER SETTINGS
USING THE DISPLAY
RelativeandAbsoluteValues: Someparameteradjustmentsaredisplayed
bothasarelativevalueandanabsolutetemperature. Thisappliestoallheating
and cooling differentials, the mist differential and the heater offset. The
parameteris firstdisplayed asarelativevalue. Thecorrespondingabsolute
temperature is displayed after six seconds if no action is taken by the user.
Theabsolutevalueisthetemperatureatwhichthestageturns on(except in
the case of the heater and mist offsets where the value displayed is the
temperature at which the stage turns off). If the user turns the adjustment
knob, the relative value reappears. For example, when the user turns the
selection knob to a differential position, i.e. STAGE 2/3, the sequence is as
follows:
(i) Thecurrentdifferentialforstage2flashes onthedisplay,alternatingwith
"St 2".
78.0
(ii) If, after about 6 seconds, no action is taken by the user, the absolute
temperature value is displayed, alternating with "St 2". In this case, the
absolute value is: Set Point + Bandwidth + Differential 2.
2.0St2

14 TC5-1N5FAB rev.06
TC5-1N5FAB
The parameter settings can be locked to prevent accidentally modifying
them. Whenthesettingsare locked, only thetemperaturesetpoint and the
Stage 1 minimum ventilation speed can be modified (as long as the tem-
perature curve and the minimum ventilation speed curve are deactivated
respectively).
To lock the parameter settings:
nSet internal switch # 1 to ON.
To unlock the parameter settings:
nSet internal switch # 1 to OFF.
LOCKING THE PARAMETER SETTINGS
78.0St2
2.3
(iii) Whentheuserturnsthe adjustment knob tomakeanadjustmentto the
stage2differential,therelativevaluereappearsonthe display.
Inthecaseofthemistandheatingunits,thestartingtemperatureisdisplayed
with the letters "STr" when adjusting the differential and the stopping
temperature is displayed with the letters "STP" when adjusting the offset.
59
TC5-1N5FAB rev.06
TC5-1N5FAB
SOLUTION
PROBLEM CAUSE
Stage 1 fans
runcontinu-
ouslyatfull
speed.
The wiring is incor-
rect.
The ambient tempera-
ture is above the set
point.
Fix the wiring.
Adjust the set point to the
desired value.
Stage 1 fans
run errati-
cally.
The selected motor
curve is inappropri-
ate.
Select an appropriate motor
curve.
The differential is too
small. Adjust the differential to a
higher value.
The time on or time
off is too short. Adjust the time on or time off to
a higher value.
Time off is set to zero. Set time off to a value other than
zero.
Stage 1 fans do
notstop
runningwhen
thecontroller
isoperatingin
minimum
ventilation
cycle.
The wiring is incorrect. Correct the wiring. In particular,
make sure two different lines
are connected to each motor:
line L1 modulated by the
controller should be combined
with another line (N for 115V or
L2 for 230V) to activate the motor.
Also, be sure the stage 1
COMMON is supplied by line L1.
Humidity compensation
is activated and relative
humidity exceeds set
point.
Adjust set point or deactivate
compensation as required.

58 TC5-1N5FAB rev.06
TC5-1N5FAB
SOLUTION
PROBLEM CAUSE
The wiring is incor-
rect. Correct the wiring. In particular,
make sure two different lines are
connected to each motor: line L1
modulated by the controller
should be combined with another
line (N for 115V or L2 for 230V) to
activate the motor. Also, be sure
the Stage 1 COMMON is supplied
by line L1.
The Stage's fuse is
open. Replace the fuse.
Make sure the cable is firmly
plugged in with the tabs in
place.
The display board
interconnect cable is
not plugged into the
power supply board
properly.
The fan motor is
defective. Check if motor is defective by
connecting it to an alternate
power supply. Replace the
motor if it still doesn't operate.
The minimum speed
is too low. Adjust the minimum speed to a
higher value.
Stage 1 fans
are not
running.
15
TC5-1N5FAB rev.06
Temperatures can be displayed in either Celsius or
Fahrenheitunits
nSet internal switch # 2 to the desired position:
• ON to display temperatures in Celsius units.
• OFF to display temperatures inFahrenheit units.
TEMPERATURESETTINGS
TEMPERATURE UNITS
VIEWING TEMPERATURES
ON
2
To display the desired temperature,
settheselectionknobtoROOMTEM-
PERATURE. Thereadoutcandisplay
valuesfrom-40.0oFto120.0oF(-40.0oC
to48.9oC).
1
Viewing Room Temperature
Theroomtemperatureistheaveragevalueofalltemperaturesmeasuredby
activatedprobesinproperoperatingcondition.
nSettheselectionknobto ROOM TEMPERATURE / PROBE To.The
room temperature is displayed.
2
Viewing Probe Temperatures
Thecontrollercandisplayprobetemperaturesindividually. Probescanalso
beturnedonoroff tocontrolthetemperatureindifferentpartsofthebuilding.
nSet selection knob to ROOM TEMPERATURE / PROBE TEMP. The
averageroomtemperature is displayed.

16 TC5-1N5FAB rev.06
TC5-1N5FAB
nPressthepush-button. Thetemperaturereading from probe 1 isdis-
played, alternating with the letters "Pr 1" and the on/off state of probe
1.
nFor each additional probe, press the push-button. The temperature
reading from probe x is displayed, alternating with the letters "Pr x"
and the on/off state of the probe, etc.
Note: Thedisplayreturnsto the average roomtemperatureafterone
minute.
3
Viewing OutsideTemperature
Theoutsidetemperaturecanbeviewedonlyifaprobeisconnectedtoinput
# 5.
nSet the selection knob to OUT-
SIDE To.Theoutsidetemperature
is displayed.
4
Viewing Minimum / Maximum Temperatures
Theminimumandmaximum temperatures are thelowestandhighest tem-
perature values recorded since the last reset. Maximum and minimum
temperaturesvaluesarerecordedfor theaverageroom temperatureaswell
asforindividual probe temperatures.
nSet the selection knob to ROOM TEMPERATURE / PROBE TEMP.
The room temperature is displayed.
nTurn the adjustment knob clockwise by one notch. The minimum
temperature flashes on the display, alternating with the letters "Lo".
nTurntheadjustment knob clockwiseonenotch further. The maximum
temperature flashes on the display, alternating with the letters "Hi".
57
TC5-1N5FAB rev.06
Thedisplay
shows
sudden
variationsin
the room
temperature.
A variation in resist-
ance is induced on a
probe.
There is electrical
noise near an ex-
tended probe cable.
Make sure the probes are dry
and move them away from
drafts and sources of radiant
heating.
Do not run probe cables next to
other power cables. When
crossing other power cables,
cross at 90o.
TROUBLESHOOTINGGUIDE
PROBLEM CAUSE SOLUTION
TheDefective
ProbePilot
Lightison.
One or more probes
are defective. Follow the procedure described
in DEFECTIVE PROBES to
identify and replace the defec-
tive probe.
The display board
interconnect cable is
unplugged from the
power supply board.
The voltage selector
switch is in the wrong
position.
The input fuse is
open.
The circuit breaker on
the service panel is off
or tripped.
Thedisplay
doesn't work. Reset the circuit breaker.
Replace the fuse.
Set the switch to the correct
position.
Plug the cable.
Thedisplay
shows the
letter "P"
Probe # 1 is improp-
erly connected. Fix the probe's connection.
The wiring is incorrect. Fix the wiring.

56 TC5-1N5FAB rev.06
TESTMODE
Atestmodeallows you to simulatetemperaturechangesand verify control-
lerperformance. Intestmode, the temperatureprobeinputsare turned off,
allowing the user to change the temperature used by the controller to oper-
ate the stages. The controller operates as before using the new tempera-
ture settings.
To enter test mode:
nTurn the selector knob to theROOM TEMPERATURE position. The
currentroomtemperatureis displayed.
nPress and hold the push-button for 5 seconds. The letters "TST" are
displayed, alternating with the room temperature.
nTurn the adjustment knob to adjust the room temperature to the de-
sired value. The controller operates the stages according to the new
temperaturesetting.
nTo change the outside temperature, turn the selector knob to OUT-
SIDE T° and turn the adjustment knob to adjust the outside tempera-
ture to the desired value.
To exit test mode:
nTurn the selector knob to theROOM TEMPERATURE position. The
currentroomtemperatureis displayed.
nPress and hold the push-button for 5 seconds.
NOTE: If no user activity is recorded after 5 minutes in test mode, the
controllerresumesnormaloperation.
17
TC5-1N5FAB rev.06
TC5-1N5FAB
nTurntheadjustment knobclockwiseathird notch. Theroomtempera-
ture is displayed again.
nFor each individual probe, press the push-button. The temperature
reading from probe x is displayed, alternating with the letters "Pr x"
and the on/off state of the probe.
nTurn the adjustment knob clockwise by one notch. The minimum
temperature is displayed, alternating with the letters "Lo".
nTurntheadjustment knob clockwiseonenotch further. Themaximum
temperature is displayed, alternating with the letters "Hi".
nTurn the adjustment knob clockwise a third notch. The probe tem-
perature is displayed again.
nPress the push-button to access the other probes, etc.
NOTE:Ifyoulet the displayflashfor more than10seconds,the controller
resetstheminimumandmaximumtemperatures currently in memory (the
display stops flashing to indicate that the reset has been done).

18 TC5-1N5FAB rev.06
TC5-1N5FAB
TEMPERATURE SET POINT
The temperature set point is the tar-
getroomtemperature. Itcan be ad-
justed between -40.0°F and 99.9°F
(-40.0°Cand37.7°C).
Adjusting Temperature Set Point
nSet the selection knob to SET POINT / T° CURVE.The current set
point flashes on the display.
nUsetheadjustmentknobtoadjustthesetpointtothedesiredvalue.
NOTE: Thetemperaturesetpointcanbeadjustedonlyifthetemperature
curveisdeactivated(seefollowingsection).
55
TC5-1N5FAB rev.06
TC5-1N5FAB
nUse the adjustment knob to set the low alarm offset to the desired
value.
nPress the push-button. The current high alarm offset flashes on the
display, alternating with the word "HI".
nUse the adjustment knob to set the high alarm offset to the desired
value.
nPress the push-button. The current critical high temperature is dis-
played, alternating with the letters "Cri".
nUse the adjustment knob to set the critical high temperature to the
desiredvalue.

54 TC5-1N5FAB rev.06
ALARMSETTINGS
The controller sets off an alarm in the case of a power failure, a fault in the
supply circuit or a high or low temperature. Temperature alarms are de-
fined according to the set point as shown in the diagram below.
Room
Temperature
Set Point High Alarm Offset
Time
HighTemperatureAlarm
Low Alarm Offset
Thesituationchangesforhightemperaturealarms,however,whentheoutside
temperature is greater than the set point. In this case, the set point is
replacedbythe outsidetemperatureas thereferencepoint. This meansan
alarmissetoff when theindoortemperature reaches OutsideTemperature
+ High Alarm Offset. Internal switch # 6 must be set to ON to use this
feature. A thirdparameter,calledthe criticalhightemperature,is defined to
continue monitoring the indoor temperature for high temperatures. When
the indoor temperature reaches the critical high temperature (defined as
an absolute value), an alarm is set off.
Adjusting the Alarm Settings
The high and low alarm offsets range from 0.5oF to 40oF. The critical
temperaturerangesfrom-40.0°F to 120.0°F(-40.0°Cto48.9°C).
nSet the selection knob to
ALARM—OFFSETS /CRITI-
CAL. The current low alarm
offset flashes on the display,
alternatingwiththe word"LO".
19
TC5-1N5FAB rev.06
TC5-1N5FAB
Theusercandefineatemperaturecurvetoadjustthesetpointautomatically
overagiventimeperiod.
Acurveisdefinedusingsixpoints. Eachpointspecifiesadaynumberand
aset pointfor thatday. Once thepoints ofthe curveare defined,the curve
mustbeactivated. Thecontrollerwillchangethetemperaturesetpointevery
hourinalinearfashionbetweenconsecutivepointsofthecurve. Whenthe
last point of the curve is reached, the temperature set point for that day is
maintaineduntilthe curve isreactivated.
NOTES :
i)Allsixpointsofthecurvemustbespecified. Ifsixpointsarenotneeded,
repeatthelasttemperaturevalue for each unnecessarypoint.
ii) Certain restrictions apply to reduce the risk of errors:
− The highest possible day number is 99.
−Decreasing day numbers are not allowed.
−Increasingtemperaturesarenotallowed.
−Thetemperaturevariationcannotexceed 3°F(1.6°C)perday.
TEMPERATURE CURVE
Temperature
Days
To1
To2
To3
To4
To5
To6
d4 d25 d35 d50 d70 d80

20 TC5-1N5FAB rev.06
TC5-1N5FAB
1
Specifying the Curve
nSet the selection knob to SET
POINT/ToCURVE.Thecurrent
temperature set point flashes
on the display.
nPressthepush-button. ThewordOFFisdisplayedindicatingthatthe
termperaturecurveisdeactivated. Ifthisisnotthecase,seebelowto
deactivatethecurve.
Repeat the following steps for each of the six points:
nPress the push-button once again. The day number is displayed,
alternating with the word "day".
nUsingtheadjustment knob, settheday number tothedesired value.
nPressthepush-buttononceagain. Thecurrenttemperaturesetpoint
is displayed, alternating with the word "set".
nUsing the adjustment knob, adjust the set point to the desired value.
Oncethesixpointsof the curve havebeenspecified,activate the curve as
explainedbelow.
NOTE: Makesurethetemperature curve isdeactivatedbefore specifying
newpoints(seebelow).
53
TC5-1N5FAB rev.06
TC5-1N5FAB
2
Adjusting Max. Temperature Difference Between
Zones
Whenusingzoned heating,abuilt-inprotection willoperatethe fansaccord-
ing to the probes of the zone with the highest temperature whenever the
temperature difference between zones is greater than this parameter. The
defaultvalueis7.5°F (4.2°C) andvaluesrangefrom 5°F to40.0°F(2.8°Cto
22.2°C).
nSet the selection knob to HEAT 1- 2 — OFFSET/DIFF. The current
heater 1 offset is displayed, alternating with the letters "OFT" and
"Ht.1".
nPress the push-button four times. The maximum temperature differ-
ence between zones is displayed, alternating with the letters "Zon
dif".
nUse the adjustment knob to adjust the temperature difference to the
desiredvalue.
Table of contents
Other AP Controllers manuals