11
MAIN OUTPUT CONFIGURATION (P1/SSR1) – submenu out1 - chapter 12 (12.2)
17: coS1 control signal for
output 1 (assignment of
input)
inP1 = measurement from input 1, inP2 = measurement from input 2, Subt
= difference between measurements (1-2), Addi = sum of measurements
(1+2), AvrG = average value of measurements (sum of measurements from
two inputs divided by 2 )
inP1
18: Fto1 failure status of
output 1 (3)
output status in the case of
lack of or damage to the measurement sensor (signal):
noCh = no change, oFF = switched off, on = switched on, hAnd = manual mode
with set output signal level (parameter 26: HSEt , chapter 12.8)
noCh
19: Fun1 function of
output 1
oFF = off, hAnd = manual mode, inv = heating, dir = cooling inv
20: SEt1 set value 1 applies to output 1, changes in scope 6: Lo1 ÷ 7: Hi1 or 13: Lo2 ÷ 14: Hi2
(only when 17: coS1 = inP2 ) 100.0 °C
21: H1 hysteresis of output
1 or PID tuning one
hysteresis or insensitivity one of PID tuning in mode Auto , chapter 12.5
0.0 ÷ 999.9 °C or 0 ÷ 9999 units (2) 1.0 °C
CONFIGURATION OF AUXILIARY OUTPUTS (P2/SSR2 and P3/SSR3) – submenu out2 for output 2 and analogously
out3 for output 3 - chapter 12 - the parameters for output 2 are shown below
22: coS1 control signal for
output 2 (assignment of
input)
inP1 = measurement from input 1, inP2 = measurement from input 2,
Subt = difference between measurements (1-2), Addi = sum of
measurements (1+2), AvrG = average value of measurements (sum of
measurements from two inputs divided by 2 )
inP2
( inP1 for
output 3 )
23: Fto2 failure status of
output 2 (3)
output status in the case of lack of or damage to the measurement sensor (signal):
noCh = no change, oFF = switched off, on = switched on, hAnd = manual mode
with set output signal level (parameter 26: HSEt , chapter 12.8)
noCh
24: Fun2
function of output 2
(chapter 12.2)
oFF = off, hAnd = manual mode, inv = heating, dir = cooling,
bAon or bAoF = band 2* SEt2 ( SEt3 for output 3) around SEt1 ,
dEoF or dEon = deviation from SEt1 ,
rEon , rEoF , rEP3 = controlled by the process controller (ramping),
chapter 12.7
inv
( oFF for
output 3 )
25: SEt2 set value 2 applies to output 2, changes in scope 13: Lo2 ÷ 14: Hi2 or 6: Lo1 ÷ 7: Hi1
(only when 22: coS2 = inP1 ) 100.0 °C
26: H2 hysteresis of output
2 0.0 ÷ 999.9 °C or 0 ÷ 9999 units (2) 1.0 °C
ANALOG OUTPUT CONFIGURATION – submenu outA - (chapter 12.3)
32: coSA signal for the
function of retransmission
of measurement for the
analog output (assignment
of input)
inP1 = measurement from input 1, inP2 = measurement from input 2,
Subt = difference between measurements (1-2),
Addi = sum of measurements (1+2), AvrG = average value of measurements
(sum of measurements from two inputs divided by 2 )
inP1
33: AtYP type of analog
output
depending on the order code: for current output 0-20 or 4-20 mA,
for voltage output 0-10 or 2-10 V
0-20 mA
(0-10 V)
34: FunA function of analog
output
oFF = off, hAnd = manual mode, rEtr = retransmission of measurement,
cont = control output, a detailed description is provided in chapter 12.3 oFF
35: A-Lo lower indication
for retransmission
start of the output scale
for output signal value 0/4 mA or 0/2 V (the
parameter is active only for measurement retransmission
when 34: FunA = rEtr )
0.0 °C
36: A-Hi upper indication
for retransmission
for output signal value 20 mA or 10 V (the parameter
is active only for measurement retransmission when 34: FunA = rEtr )
100.0 °C