Aplab VSP1060 User manual

MODELS
VSP1060, VSP2030, VSP3020,VSP4015,
VSP6010, VSP1205, VSP2060, VSP3040,
VSP4030, VSP6020, VSP12010, VSP8015,
VSP3080, VSP4060,VSP6040, VSP8030,
VSP12020, VSP20180, VSP30120, VSP4090,
VSP6060, VSP12030, VSP8045, VSP30240,
VSP40180,VSP60120, VSP8090, VSP12060
High Power Switching DC Power Supplies
Instruction Manual

TABLE OF CONTENTS
SECTION DESCRIPTION PAGE NO.
1 TEST INSTRUMENT SAFETY 1
2 GENERAL INFORMATION 2
3 INSTALLATION 6
4 OPERATING INSTRUCTION 10
5 MAINTENANCE 19
6 REMOTE INTERFACE 21
7 CUSTOMER SUPPORT 63
8 WARRENTY INFORMATION 64
9 SERVICE INFORMATION 65

Section 1
Test Instrument Safety
WARNING
Normal use of test equipment exposes you to a certain amount of danger from electrical
shock because testing must sometimes be performed where exposed voltage is present.
An electrical shock causing 10milliamps of current to pass through the heart will stop most
human heartbeats. A Voltage as low as 35 volts dc or ac (rms.) should be considered
dangerous and hazardous since it can produce a lethal current under certain conditions.
Higher voltages pose an even greater threat because such voltage can more easily produce
a lethal current. Your normal work habits should include all accepted practices to prevent
contact with exposed high voltage and to steer current away from your heart in case of
accidental contact with high voltage. You will significantly reduce the risk factor if you know
and observe the following safety precaution.
1. Don’t expose high voltage needlessly. Remove housings and covers only when necessary.
Turn off equipment while making test connections in high voltage circuits. Discharge high
voltage capacitors after removing power.
2. If possible, familiarize yourself with the equipment being tested and the location of its high
voltage points. However, remember that high voltage may appear at unexpected points in
defective equipment.
3. Use an insulated floor material or a large, insulated floor to stand on and an insulated work
surface on which to place equipment and make certain such surfaces are not damp or wet.
4. Use the time proven “one hand in the pocket” technique while handling an instrument probe.
Be particularly careful to avoid contacting a nearby metal object that could provide a good
ground return path.
5. When testing ac powered equipment, remember that ac line voltage is usually present on
some power input circuits such as the on-off switch, fuses, power transformer etc. any time
the equipment is connected to an ac outlet, even if the equipment is turned off.
6. Some equipment with a two-wire ac power cord, including some with polarized power plugs,
is the “hot chassis” type. This includes most recent television receivers and audio equip-
ment. A plastic wooden cabinet insulates the chassis to protect the customer. When the
cabinet is removed for servicing, a serious shock hazard exists if the chassis is touched. Not
only does this present a dangerous shock hazard, but damage to test equipment. Always
connect an isolation transformer between the ac outlet and the equipment under test. To be
on the safe side, treat all two-wire ac equipment as “hot chassis” unless you are sure it is
isolated chassis or an earth ground chassis.
7. On test instruments or any equipment with a 3-wire ac power plug, use only a 3-wire outlet.
This is a safety feature to keep the housing or other exposed elements at earth ground.
8. Aplab products are not authorized for use in any application involving direct contact between
our product and the human body or for use as a critical component in a life support device or
system. Here “direct contact” refers to any connection from or to our equipment via any
cabling or switching means. A “critical component” is any component of a life support device
or system whose failure to perform can be reasonably expected to cause failure of that
device or system or to affect its safety or effectiveness.
Never work all alone. Someone should be nearby to render aid if necessary. Training
in CPR (cardiopulmonary resuscitation) first aid is highly recommended.
1

Section 2
General information
2.1 INTRODUCTION
2.2 FEATURE
2.3 MARKINGS
2.4 INTERFACE
2.5 SPECIFICATION
2.6 ORDERING INFORMATION
2.1 INTRODUCTION
The VSP SERIES power supplies are designed to deliver power in constant
voltage and constant current mode by switch mode conversion in sleek 1U high
cabinet and in a 19’’ rack construction.
This series comprises the two device soft switching technology that yields
very high efficiency of conversion for dc-to-dc converter part. Also it comprises
power factor correction circuity, which shapes the input current to follow the voltage
to maintain almost unity power factor at full load, and limits the current harmonics in
the input line.
It provides the user the option of isolated analog voltage, current and resis-
tance programming with built-in isolation amplifiers. It gives the option to monitor the
isolated signals with the option to change either from 0 to 5 Volts or from 0 to 10
Volts, for output voltage and current from 0 to full-scale level. It provides the display of
the output voltage, over voltage set level and current with 3-digit LED displays.
Piggyback series pass device ensures the ripple and noise levels to very low values.
Current sharing facility in the module gives the advantage to increase the power with
ease and the vents in the front and the rear enables it with absolutely zero stacking.
The module can be switched on/off through the front panel ON/OFF switch or re-
mote switch on rear panel.
VSP series provides digital interface options for remote programming from
PC. The digital interface provides 12-bit resolution for control as well as monitoring
the output.
2

Some of the features of the power supply are listed below:
2.2 FEATURES
MAINS OPERATED, WITH WIDE INPUT RANGE.
POWER FACTOR CORRECTED INPUT.
ISOLATED D.C. OUTPUT.
CONSTANT VOLTAGE OPERATION FROM 0 TO FULL-SCALE LEVEL.
CONSTANT CURRENT OPERATION FROM 0 TO FULL-SCALE LEVEL.
OVER VOLTAGE CONTROL FACILITY.
REMOTE SENSING FACILITY.
PARALLELABLE CURRENT SHARING OUTPUT.
HIGH OVERALL EFFICIENCY – 80% TYPICAL.
VERY LOW OUTPUT RIPPLE AND NOISE.
INPUT EMI FILTERING TO MEET EN55022 CLASS A.
20 MILLISECOND HOLD-UP TIME.
TWO FRONT PANEL DPMS. FOR V / O.V AND I.
MULTI TURN POTENTIOMETERS FOR V, O.V AND I SET.
FRONT PANEL OUTPUT TERMINALS FOR MONITORING.
SLEEK, 1U HIGH, 19 INCH RACK CONSTRUCTION.
INTERNAL FORCED AIR COOLING WITH ZERO STACKING.
ISOLATED ANALOG VOLTAGE, CURRENT AND RESISTANCE PROGRAM
MING AND MONITORING.
REMOTE ON/OFF FACILITY.
RS232/ GPIB/ INTERFACE.
2.3 MARKINGS
The unit has the name PROGRAMMABLE PFC DC SUPPLY written clearly
on the top of the front panel. The Model Number and ratings are also clearly written
on the front panel. The ratings are clearly written on the rear panel, just near the
output terminals.
2.4 INTERFACE
The unit has both local as well as remote controls. For Remote operation, the
series offers analog as well as digital interface or both. Both RS 232 or GPIB digital
interfaces can be provided.
3

4
2.5 SPECIFICATIONS
Output Specification
Model VSP1060* VSP2030* VSP3020* VSP4015*
Power 0.6KW 0.6KW 0.6KW 0.6KW
Output Voltage 0–10V 0–20V 0–30V 0–40V
Output Current 0–60A 0–30A 0–20A 0–15A
Noise (10Hz to 20MHz) <45mVpp <45mVpp <45mVpp <45mVpp
Model VSP6010 VSP1205 VSP2060 VSP3040
Power 0.6KW 0.6KW 1.2KW 1.2KW
Output Voltage 0–60V 0–120V 0–20V 0–30V
Output Current 0–10A 0–5A 0–60A 0–40A
Noise (10Hz to 20MHz) <45mVpp <45mVpp <45mVpp <45mVpp
Model VSP4030 VSP6020 VSP12010 VSP8015
Power 1.2KW 1.2KW 1.2KW 1.2KW
Output Voltage 0–40V 0–60V 0–120V 0–80V
Output Current 0–30A 0–20A 0–10A 0–15A
Noise (10Hz to 20MHz) <45mVpp <45mVpp <45mVpp <45mVpp
Model VSP3080 VSP4060 VSP6040 VSP8030
Power 2.4KW 2.4KW 2.4KW 2.4KW
Output Voltage 0–30V 0–40V 0–60V 0–80V
Output Current 0–80A 0–60A 0–40A 0–30A
Noise (10Hz to 20MHz) <45mVpp <45mVpp <45mVpp <45mVpp
Model VSP12020 VSP20180 VSP30120 VSP4090
Power 2.4KW 3.6KW 3.6KW 3.6KW
Output Voltage 0–120V 0–20V 0–30V 0–40V
Output Current 0–20A 0–180A 0–120A 0–90A
Noise (10Hz to 20MHz) <45mVpp <45mVpp <45mVpp <45mVpp
Model VSP6060 VSP12030 VSP8045 VSP30240
Power 3.6KW 3.6KW 3.6KW 7.2KW
Output Voltage 0–60V 0–120V 0–80V 0–30V
Output Current 0–60A 0–30A 0–45A 0–240A
Noise (10Hz to 20MHz) <45mVpp <45mVpp <45mVpp <45mVpp
Model VSP40180 VSP60120 VSP8090 VSP12060
Power 7.2KW 7.2KW 7.2KKW 7.2KW
Output Voltage 0–40V 0–60V 0–80V 0–120V
Output Current 0–180A 0–120A 0–90A 0–60A
Noise (10Hz to 20MHz) <45mVpp <45mVpp <45mVpp <45mVpp

Programming Resolution (Digital Interface), LSB (not LED displays)
Voltage 20 mV 10 mV 10 mV 100 mV
Current 10 mA 20 mA 10 mA 10 mA
Output Programming Accuracy (Analog Programming 0 To 5V & 0 To 10V)
Voltage 0.5 % of F. S. ± 1 Digit (spec. for all VSP models)
Current 0.5 % of F. S. ± 1 Digit (spec. for all VSP models)
Meter Accuracy
Voltage +/- 0.2% of F.S. +/- 3 Digit. (spec. for all VSP models)
Current +/- 0.2% of F.S. +/- 3 Digit. (spec. for all VSP models)
Regulation
CV Line Regulation (mV) 0.1 % of F.S (spec. for all VSP models)
CC Line Regulation (mV) 0.1 % of F.S (spec. for all VSP models)
CV Load Regulation (mA) 0.1 % of F.S (spec. for all VSP models)
CC Load Regulation (mA) 0.1 % of F.S (spec. for all VSP models)
Output Specification
Stability 0.05%
Efficiency< 80% Minimum
Transient Response 250 microseconds for load change from 40% to 90%
Mode Of Operation
Local Mode Through front panel potentiometer for voltage, current
and
over voltage and Push switch for Output ON/ OFF control.
Remote Mode Interface Analog programming of voltage
and current.Voltage: 0 - 5 volts or 0 – 10 volts for output
voltage and current, selection through DIP-switch.
Resistance: 0 – 4.85k ohms from 0 to full-scale level.
* = Specification also apply to corresponding GPIB model
F.S = Full Scale. Full scale will be different for each model. Example: If you have a VSP2030
and you are measuring the voltage meter accuracy, the meter can not offer more than 0.3V
(20V + 0.2% +3 digit). Note: 3 digits refferes to the power supply displays least significant
digit.
Digital Interface RS-232 / GPIB
Over voltage protection Programmable through POT in local mode and through
digital interface in remote mode.
Over temperature protection Through 90 °C. thermal switch on heat sink.
Input specifications
Mains Input Range 95Vac to 264Vac.
Input Frequency 47 To 63 Hz
Input Power Factor 0.99 On Full Load At Nominal Input.
Inrush Current Limited By NTC

Operating Environment
Temperature 0 - 50°C
Relative Humidity < 80% rh – non condensing
Storage Temperature - 20°C. to + 70°C.
Warm-up Time 15 minutes.
Safety Standards
EMI Filtering EN55022 Class-A
Safety Class EN60950
Mechanical Specifications
Weight (appox.) 13.7lbs. (6.2 KG.)
Dimensions (WxHxD) 19 x 1.75 x 18” (483 x 44.5 x 457mm)
Dimensions with rubber feet 19 x 2.13 x 20” (483 x 54 x 457mm)
5

Section 3
Installation
3.1 INTRODUCTION
3.2 UNPACKING
3.3 INPUT POWER REQUIREMENTS
3.4 SYSTEM CONFIGURATION
3.5 INSTALLATION
3.6 TEST EQUIPMENT REQUIREMENTS
3.1 Introduction
VSP series power supply is configured, calibrated and tested prior to shipment.
This unit is therefore ready for immediate use upon receipt. The initial physical inspec-
tions should be made to ensure that no damage has been sustained during shipment.
3.2 Unpacking
Inspect the shipping container before accepting it from the carrier. If damage to
the container is evident, remove the instrument from the container and visually inspect
it for damage to the instrument case and parts.
If damage to the instrument is evident, a description of the damage should be
noted on the carrier’s receipt and signed by the driver or carrier agent. Save all shipping
containers and material for inspection.
Forward a report of any damage to the factory or the agent through which the unit
is procured.
Retain the original packing container if subsequent repackaging for return to the
factory were required. Repackaging is straightforward and is essentially the reverse of
the unpacking. Only subassemblies need to be repackaged for reshipment, use the
original containers.
Remove the Source module from its shipping container and inspect for any dam-
age to the front panel and display module. Also check for any optional parts which may
have been ordered by you. If the switch or display is heavily damaged or is broken then
DO NOT switch-ON the instrument.
Check the rear of the instrument for damage to Sockets or Fuse Holders. In-
spect also the POWER-ON switch on the front panel.
6

3.3 Input Power Requirements
The Model VSP power supply is configured at the factory to operate from 95-264
VAC at 47-63 Hz power line.
3.4 System Configuration
The Model VSP series power supply comes in ready to use fashion and does not
require any configuration in the field for operation in the local mode. For analog interface
refer to the connector details for the connections.
3.5 Installation
1. AC Input Power Connection
Connect a 3-pin power mains cord to the available line supply. Before connect-
ing line ensure the following:
a) The available line supply is compatible to your unit.
b) The available line supply point is capable of supplying the maximum peak current
and power.
2. Load Connections
Refer fig.3.1A for load connection in local and remote sensing mode, the unit has
5mm brass studs on the rear panel for load connections for model up to 30A. The bus
bar is provided from 30A onwards.
For remote sensing and the current sharing option it is provided with separate 6
way terminal block. This is required if your load is far away & regulation needs to be
maintained at load terminals.
An output cable should be able to handle the full load current and maximum
voltage and power under worst case conditions of temperature, humidity, mechani-
cal abuse, and effects of long term aging.
3. Analog Interface Connections
A 25 pin D type connector & DIP switch is provided for remote analog interface
to the unit. There is 8 pin DIP switch associated with the function of analog interface.
Refer to section 4.3.5 of chapter 4 for switch settings.
4. Turn-On
Switch the POWER ON switch to the ON position. Soon the DPM will be turned
on & the output voltage & current are displayed, if output on-off switch is in ON position.
Voltmeter should display the voltage set by voltage control.
Check the current meter. It must show zero (very low) current under no load. If
not then please switch off the unit and call the service personnel.
For details of TURN ON CHECK refer section 4.5 of CHAPTER 4.
7

3.6 Test Equipment Requirements
The following instruments will be required to test the complete installation of the
unit.
1). A four and half digit or better digital multimeter for verifying the voltage and current
output of the unit.
2). A 20 MHz dual channel oscilloscope for verifying the Ripple in Output of the Source.
3). A Resistive load or an Electronic Load to take an input to suit the maximum
output from the unit depending on the model and capacity of the channel of the
Source.
8

9
NC 2
VPROGI 3
VPIN 4
VPROGR 5
AGND3 6
NC 7
NC 8
IPIN 9
IPROGI 10
IPROGR 11
NC 12
NC 13
NC 14
+12V 15
AGND3 16
REMOTE ON/OFF 17
AMX 18
VMX 19
AGND3 20
NC 21
VPSET 22
VMSET 23
IPSET 24
IMSET 25
+S 1
+2
-3
-S 4
NC 5
CS BUS 6
+S 1
+2
-3
-S 4
NC 5
CS BUS 6
Output +VE
Output -VE
LOAD
REMOTE SENSING
Output +VE
Output -VE
LOAD
LOCAL SENSING
SWITCH CONFIGURATION
(ON REAR PANEL)
Fig 3.1a : CONNECTION DETAILS IN LOCAL & REMOTE INTERFACE
LOCAL MODE
NC 1
87654321
O
N

Section 4
Operating instruction
4.1 INTRODUCTION
4.2 FRONT PANEL DESCRIPTION
4.3 REAR PANEL DESCRIPTION
4.4 POWER ON CHECK
4.5 OPERATING INSTRUCTIONS IN LOCAL MODE
4.6 OPERATING INSTRUCTIONS IN ANALOG REMOTE INTERFACE
4.7 OPERATING INSTRUCTIONS IN DIGITAL INTERFACE
4.8 TRIP INDICATIONS
4.1 INTRODUCTION
The VSP series Model is a variable switch mode power supply to provide wide
range of DC supply from 0 to full-scale specified voltage. This chapter explains the
operating procedure of the unit. The operation is very simple by providing POT control
for voltage, current limit and over voltage protection limit and 8 way DIP switch along
with 25 Pin D type connector for the remote programming interface.
Optional RS232 interface or GPIB interface can be provided as per the order
placed. In case of RS232 interface, a slide switch no. 7 on 8 pin DIP switch array on the
rear panel facilitates either LOCAL/ RS232 communication interface or Analog pro-
gramming.
The unit is internally fan cooled. The air inlet vents are provided on the front panel.
The air outlet is a rectangular slotted area on the 1U high rear panel, and is located
between the A.C. input and D.C.output connectors.
The instrument front panel and rear panel are described first in detail, explain-
ing the layout, identification, function and usage of each item on the panel. The Turn-
on sequence and the procedure to use the major functions and operation of unit in
digital interface are also explained. At the end all the ALARM indications, errors and
warning signals are explained. In the same section procedures to clear the TRIP and
ALARM conditions are discussed.
10

4.2 FRONT PANEL DESCRIPTION
Figure 4.1 shows layout of front panel. On the front panel following controls and
indicators are provided.
1. Main ON/OFF switch with neon indication.
2. 3 digit display for Voltage/ Set Voltage/ Set Over Voltage indication
3. 3 digit display for Current/ Set Current indication.
4. 10 turn POT for voltage control.
5. 10 turn POT for current control.
6. 10 turn POT for over voltage protection control.
7. Push switch to view set parameters in SET mode.
8. Latch type Push switch for Output ON/OFF control.
9. LED indications for CV, CC, Output ON, Trip, Remote, V set, I set, O/V set and
Set mode.
- The display shows 3 digit value for voltage and current parameters. The resolution of
indication is 0.1 volt and 0.1 amp for voltage and current parameters. The display is
used to show actual output voltage and current or to show set values of voltage, over
voltage and set current limit in the set mode. The set mode is activated using Set key
during output OFF condition.
- CV LED indicates the constant voltage operation of power supply.
- CC LED indicates constant current operation of power supply.
- TRIP LED becomes ON either for over voltage trip condition or for over temperature
trip condition.
- Output ON/OFF can be controlled by push button switch (latch type) and LED turns
ON if output is available.
- Remote LED is provided for the digital interface option. It lights up when the power
supply is controlled by external digital interface.
- To view the set values of POT on the display press the SET key. Also LED’s for
each POT and common SET MODE Led is provided.
- Also monitoring terminals of output are provided on front panel so that user can verify
the output with calibrated meter. Additional earth terminal is also provided on front
panel.
4.3 REAR PANEL DESCRIPTION
The rear panel of the unit is shown in fig 4.2. The mains input connection is
made through a mains cord and is located on the right side of the unit at the rear.
A 20A fuse of type ’F’ is used for line input range 95Vac to 264Vac,) provided at input.
At the center are the oval shaped ventilation slots for air exhaust, for D.C. output 5mm
brass studs or bus bars (as per the current specifications) are provided, next to
it is 6 way terminal block for remote sensing and current share bus. Further is the 25
pin D-type connector for analog interfacing & the associated 8 pin DIP switch for
selection of analog mode operation and it’s associated modes of operation. Above the
25 pin D-type connector the provision is made for digital interface connection, which
can be either GPIB or RS232.
11

12

1
2
3
4
5
6
7
8
9
11
12
13 14 15 16
17 17
17
18
19
20
22
23
24
26
25
26
21
10
Sr. No. Description Sr. No. Description
1 Input Line Cable 14 Output Sense Terminals
2 Input Fuse 15 Analog Interface Connector
3 Input R. F. Filter 16 DIP switches for Analog Interface
selection
4 VSP-PFC-1.2KW-1103D, PCB 17 Cooling Fans
5 Input ON/OFF Switch 18 SBC-IEB-0504A, PCB (For GPIB)
6 Heat Sinks 19 VSP-POT-IMON-0604A, PCB
7 PFC Choke 20 VSP-FPDAC CONV-0604A, PCB
8 DC DC Converter Transformer 21 Voltage Monitoring Terminals
9 VSP-DPM-CONT-1204D, PCB 22 VSP-DPM-1UFP-0604D, PCB
10 VSP-FAN-CNT-1103C, PCB 23 Potentiometers for control
11 VSPDDC-1.2KW-0704E, PCB 24 SET, ON/OFF switch Assembly
12 Digital Interface PCB 25 Earth Terminal
13 Output Power Terminals 26 Handles
GENERAL ASSEMBLYDRAWING OF VSP SERIES POWER SUPPLY
13

4.3.1 LINE INPUT
The mains input range is clearly indicated on rear panel. The unit comes stan-
dard with a U.S. standard plug and a mains input rating of 95VAC to 265VAC, 50/60Hz.
4.3.2 INPUT FUSE
This fuse protects the unit against short circuits and over loading. The 20A
fuse of type ’F’ is used for line input range 95Vac to 264Vac.
4.3.3 DC OUTPUT TERMINALS
VSP models with upto 30 amp output ratings have a pair of 5mm brass studs is
provided on the rear panel. Models above 30 amps have bus bars are provided. Output
polarity is shown near the terminal.
4.3.4 REMOTE SENSE CONNECTOR
6 Way terminals block is provided for remote sensing and current
share option.
1. +S: - Positive Sense terminal for remote sensing.
2. +Output: - Positive DC output terminal.
3. -Output: - Negative DC output terminal.
4. -S: - Negative Sense terminal for remote sensing.
5. NC
6. CS Bus: - Current share bus for parallel operation.
4.3.5 ANALOG INTERFACE CONNECTOR (Reference Fig. 4.1a and 4.1b in back of
manual)
25 Pin D type connector is provided for remote analog interface, it is factory set
to operate through the front panel controls.
Pin no. 1: N.C.
Pin no. 2: N.C.
Pin no. 3: VPROGI-1 mA (typical) Current source for voltage programming.
Pin no. 4: VPIN - Input for voltage programming.
Pin no. 5: VPROGR - Resistance programming (0 to 4.85KOhms for full-scale volt-
age)
Pin no. 6: AGND3 - Common terminal for remote programming.
Pin no. 7: N.C.
Pin no. 8: N.C.
Pin no. 9: IPIN - Input for Current programming.
Pin no.10: IPROGI- 1mA (typical) Current source for Current programming.
Pin no.11: IPROGR - Resistance programming (0 to 4.85KOhms for full-scale cur-
rent)
Pin no.12: N.C.
Pin no.13: N.C.
14

Pin no.14: N.C.
Pin no.15: +12 V- Remote on/off relay supply +ve.
Pin no.16: AGND3 - Common terminal for remote programming.
Pin no.17: Remote On/Off - Remote on/off relay.
Pin no.18: AMX- Output Current monitoring. (Factory set to 0 to 5 volts for full scale)
Pin no.19: VMX - Output Voltage monitoring. (Factory set to 0 to 5 volts for full scale)
Pin no. 20: AGND3 - Common terminal for remote monitoring.
Pin no. 21: N.C.
Pin no. 22: VPSET - External programming option set for output voltage.
Pin no. 23: VMSET -External-monitoring option set for monitoring the output voltage.
Pin no. 24: IPSET - External programming option set for output current.
Pin no. 25: IMSET - External monitoring option set for current.
4.3.6 DIP SWITCH DETAILS.
DIP Switch is provided on the rear panel to facilitates remote analog interface as
well as local mode interface in the power supply by just changing the switch positions
Switch no. 1 & 2 are associated with voltage programming
Switch no. 3 & 4 are associated with current programming
Switch no. 5 is associated with 0-5V & 0-10V programming
Switch no. 6 is associated 0-5V & 0-10V monitoring
Switch no. 7 is Local/RS232 and Analog interface selection
Switch no. 8 is associated with remote ON-OFF.
4.3.7 DIGITAL COMMUNICATION INTERFACE (optional)
Digital communication interface either GPIB or RS-232 interface can be incor-
porated with the system as per the order placed. As per the ordered digital communi-
cation interface, the slots are available on the rear panel
The slide switch no. 7 on 8 pin DIP switch array selects the LOCAL/RS232 or Analog
interface & 9 pin D-Type connector is provided on rear panel to connect the unit to PC.
NOTE: Refer Chapter 5 For Details Of Digital Communication Interface.
4.4 POWER ON CHECK
Keep the DIP switch settings for local mode operation. (Refer to 4.5)
After switching ON the unit, the display will show the actual voltage and current at the
output if output ON/OFF switch is in pressed position. If the switch is in OFF position
then the output voltage goes to 0V & displays zero. Also LED associated with key
shows the condition of output. If TRIP LED is ON then display show zero values and
LED associated with ON/OFF key remains off.
15

4.5 OPERATING INSTRUCTIONS IN LOCAL MODE
These are the instructions for operating the source in local mode. Initially after
Power ON Unit work in local mode.In local mode the power supply can be controlled
through front panel potantion meters.
Also Refer to the settings of 8Way DIP Switch provided on rear panel to operate in
Local mode.
Switch No. 12345678
Position On On On On On OFF On On
Refer fig. 3.1a for connection details in local & remote interface
Normally user can vary the V SET POT to change the output voltage while working
in constant voltage mode operation. I SET POT is used to set the output current
while working in constant current mode operation.
4.5.1 SET MODE OPERATION IN LOCAL MODE
User can view the set parameters using set mode operation before
turning the output ON. To enter the SET mode, switch off the ON/OFF switch.
When SET key is pressed for the first time then SET LED turns ON and display
shows OVP value and OVP POT LED keeps on flashing. In this mode the OVP POT
can be used to change the over voltage limit. On pressing the SET key again the
display shows the set voltage and VSET POT LED keeps on flashing. In this mode
the VSET POT can be used to change the output voltage. On pressing the SET key
again the display shows the set current and ISET POT LED keeps on flashing. In this
mode the ISET POT can be used to change the output current.
Set mode operation ends after pressing SET key fourth time & displays zero if the
output on / off switch is off. At any instant, while in set mode, if output on / off switch
is pressed the display displays the output voltage & current.
16

4.6 OPERATING INSTRUCTIONS IN ANALOG REMOTE INTERFACE
The Remote analog interface is Provided to control the power supply with
external analog signals.Before using the interface check the type of digital interface
provided with the system.
A slide switch no. 7 on 8 pin DIP switch array is provided at the rear panel to bypass
digital and front panel pot controls. Ensure the position of slide switch is in off
position when operating with external analog controls.
When GPIB interface is used then internal adjustment is required to bypass the GPIB
interface. Refer to GPIB section of Chapter 6.
Following are the positions of switches for the operating the source in remote mode
by external analog voltage and resistance.
4.6.1 Voltage Programming
Apply the input programming voltage of 0 to 5Volts or 0 to10 Volts between pin 4
& common control pin 6 of 25 pin D type connector for voltage programming & for
current programming between 9 & 6 (common control pin) of 25 pin D-Type connector.
8 pin DIP switch on rear panel:
Switch No. 1 2345678
Position Off Off Off Off off On
5 = ON for 0-5V programming
5 = OFF for 0-10V programming
6 = OFF for 0-5V monitoring
6 = ON for 0-10V monitoring
Refer fig. 4.1a for remote voltage and current programming and monitoring
It also explains load connections required in this mode.
Note: Factory set for 0 to 5 volts for full scale output programming and moni-
toring.
4.6.2 Resistance Programming
For resistance programming standard resistor used is 4.85KOhms.
Following shows the DIP switch configuration required in this mode & explains the
connection of the resistor to the 25 pin D-type connector.
8 pin DIP switch on rear panel:
Switch No. 1 2345678
Position Off On Off On On off On
6 = OFF for 0-5V monitoring
6 = ON for 0-10V monitoring
17
This manual suits for next models
24
Table of contents