www.pulsar.pl PSDC161214
5
1.4. Specifications:
- electrical specifications (tab.3)
- mechanical specifications (tab.4)
- operation safety (tab.5)
- operating specifications (tab.6)
Electrical specifications (tab. 3).
Supply voltage 176 ÷ 264 V AC
Current consumption 1,36A@230VAC max.
Power frequency 50Hz
PSU power 200 W max.
Efficiency 85%
Output voltage 12 V DC
Output current 16 x 0,8A
Output voltage adjustment range 12 V÷ 15 VDC
Ripple voltage 100mV p-p max.
Short-circuit protection SCP
LB8/AW (A , B) STRIP
16x F 1A (fuse) or PTC 1,1A
PSU MODULE
105% ÷ 150% of PSU power,
electronic current limiting,
Overload protection OLP 105% ÷ 150% of PSU power,
electronic current limiting,
Surge protection of the PSU outputs OVP >16V (varistors)
Technical outputs:
- AW (A, B) outputs indicating fuse failure
(blow), strips LB8/AW A, B (SCP
activation)
OC type, 50mA max,
normal status: L level (0V),
failure: hi-Z level
F1÷ F8 fuses (strips A,B) F 1A/250V or PTC 1,1A (manual selection)
Mechanical specifications (tab. 4).
Enclosure
dimensions 285 x 261 x 58 (280 x 256 x 50) (WxHxD) [mm] (+/- 2)
Fixing 247 x 225 x Φ6 (WxH)
Net/gross weight 2,23/2,40 kg
Enclosure Steel plate, DC01 0,8mm colour: RAL 9003
Closing Cheese-head screw: at the front
Connectors Power supply: 230 V AC: Φ0,63-2,05 (AWG 22-12)
AUX outputs: Φ0,51- 2,05 (AWG 24-12)
LB8/AW: Φ0,51- 2,05 (AWG 24-12)
Notes The enclosure does not adjoin the assembly surface so that cables can be led.
Operation safety (tab.5).
Protection class PN-EN 60950-1:2007 I (first)
Protection grade PN-EN 60529: 2002 (U) IP20
Electrical strength of insulation:
- between input (network) circuit and output circuits of the PSU (I/P-O/P)
- between input circuit and PE protection circuit (I/P-FG)
- between output circuit and PE protection circuit (O/P-FG)
3000 V/AC min.
1500 V/AC min.
500 V/AC min.
Insulation resistance:
- between input circuit and output or protection circuit
100 MΩ, 500V/DC
Operating specifications (tab.6).
Operating temperature -10ºC...+40ºC
Storage temperature -20ºC...+60ºC
Relative humidity 20%...90%, without condensation
Vibrations during operation unacceptable
Impulse waves during operation unacceptable
Direct insolation unacceptable
Vibrations and impulse waves during transport PN-83/T-42106