Apxalarm APX32EN Operating instructions

APX32EN
Security Systems
Programming Guide
K14116-8 11/07 Rev. A

- 2 -
TABLE OF CONTENTS
Data Fields .................................................................................................................................................................................3
✻56 Enhanced Zone Programming ......................................................................................................................................... 11
✻80 Device Programming ........................................................................................................................................................ 13
✻81 Zone Lists ......................................................................................................................................................................... 14
✻83 Enhanced Sequential Mode ............................................................................................................................................ 15
✻84 Assign Zone Voice Descriptors......................................................................................................................................... 16
Vocabulary Index (for ✻84 Assign Zone Voice Descriptors) .................................................................................................... 16
✻85 Record Custom Voice Descriptors ................................................................................................................................... 17
✻56 Enhanced Zone Programming Worksheet ....................................................................................................................... 18
Powerline Carrier Device Worksheet for ✻80 and ✻81............................................................................................................. 20
5800 Series Transmitter Loop Numbers Diagram.................................................................................................................... 22
Special Messages .................................................................................................................................................................... 22
APX32EN Summary of Connections Diagram ......................................................................................................................... 23
Refer to the Installation and Setup Guide for detailed information on programming the APX32EN system. The
Installation and Setup Guide includes full descriptions of all data fields.
ULAPX32EN is not intended for UL985 Household Fire applications unless a 24-hour backup battery
(P/N LYNXRCHKIT-HC or LYNXRCHKIT-SHA) is installed.
TO ENTER PROGRAMMING MODE:
1. Power up, then depress [✻
✻✻
✻] and [#] both at once, within 50 seconds of powering up.
OR
2. For factory defaulted system, enter: Installer Code (4 + 1 + 1 + 2) plus 8 + 0 + 0. OR
If different Installer Code is programmed, enter: New Installer Code + 8 + 0 + 0.
(if ✻98 was used to exit previously, method 1 above must be used to enter the program mode again)
3. Upon entry into Program mode, data field ✻20 will be displayed (the first data field in the system) and
both keypad LEDs will flash.
TO PROGRAM THE DATA FIELDS:
1. Press [✻] followed by the desired field number (e.g., ✻21), then make the required entry.
2. The keypad beeps three times after entering data, then displays the next data field in sequence.
3. For phone number and account number fields, press [✻] to end the entry if less than number maximum
number of digits is entered.
4. To delete an entry, simply press [✻] plus that field number and reenter the correct data. For phone
number and account number fields ✻40-✻44, ✻88 and ✻94, press [✻] + field number + [✻].
INTERACTIVE MENU MODES:
There are six interactive menu modes as listed below. To enter these modes, first enter Program mode. While
in Program mode, press [✻] plus the mode number desired (e.g., ✻56).
✻56 Enhanced Zone Programming............For programming zone characteristics, report codes, etc.
✻80 Device Programming...........................For programming Powerline Carrier Devices
✻81 Zone List Programming.......................For programming zone lists for use with Powerline Carrier Devices
✻83 Enhanced Sequential Mode ................For entering transmitter serial numbers
✻84 Assign Zone Voice Descriptors ...........For assigning voice descriptors to zones
✻85 Record Custom Voice Descriptors......For recording custom voice descriptors
TO LOAD A DEFAULT SET:
While in Program mode, press ✻97, and then enter number 1. See the Installation Instructions for the default
tables. Enter 0 if you are not selecting a default table.

- 3 -
TO EXIT PROGRAMMING MODE:
✻98 Exits programming mode and prevents re-entry by: Installer Code + 8+ 0 + 0. If ✻98 is used to exit
programming mode, system must be powered down, then press [✻] and [#] within 50 seconds of power
up to re-enter programming mode.
✻99 Exits programming mode and allows re-entry by: Installer Code + 8 + 0 + 0 or: Power-up, then press
[✻] and [#] within 50 seconds of power up.
DATA FIELDS
Field Function Programmed Values [ ] = Table 1 Default Values
SYSTEM SETUP (✱20– ✱ 30)
✱20 INSTALLER CODE [4112]
Enter 4 digits, 0–9
✱21 QUICK ARM ENABLE †[1]
0 = no; 1 = yes
✱22 KEYPAD BACKLIGHT TIMEOUT [0]
0 = none (backlighting always on); 1 = backlight off after 10secs
✱23 FORCED BYPASS †[0]
0 = none; 1 = bypass open zones
UL installations = 0
✱24 RF HOUSE ID CODE | [00]
00 = disable all wireless keypad usage;
01–31 = 5804BD/5804BDV house ID
✱25 POWERLINE CARRIER DEVICE
HOUSE CODE [0]
0 = A; 1 = B, 2 = C, 3 = D, 4 = E, 5 = F, 6 = G, 7 = H, 8 = I,
9 = J, #10 = K, #11 = L, #12 = M, #13 = N, #14 = O, #15 = P
✱26 CHIME BY ZONE †[0]
0 = no; 1 = yes (program zones to chime on zone list 3)
✱27 REAL TIME CLOCK DISPLAY †[1]
0 = no; 1 = yes, display time on keypad
✱29 DAYLIGHT SAVING TIME
START/END MONTH [3, 11]
Start End
1-9, #+10,#+11,#+12. Enter 0,0 if no daylight savings time used.
✱30 DAYLIGHT SAVING TIME
START/END WEEKEND [2,1]
Start End
0=disable; 1=first; 2=second; 3=third; 4=fourth;
5=last; 6=next to last; 7=third from last
ZONE SOUNDS AND TIMING (✱
✱✱
✱31– ✱
✱ ✱
✱ 39)
✱31 SINGLE ALARM SOUNDING/ZONE † [0]
0 = Alarm Sounding Per Zone will be the same as the Swinger
Shutdown” set in field *92;
1 = yes, limit once per arming period (also applies to long range
radio output if “0” is selected in ✻91 field)
UL installations = 0
† Entering a number other than the one specified may give unpredictable results.

- 4 -
Field Function Programmed Values [ ] = Table 1 Default Values
✱32 FIRE SOUNDER TIMEOUT †[0]
0=timeout; 1=no timeout
✱33 ALARM BELL TIMEOUT †[1]
0 = none; 1=4 min; 2=8 min; 3=12 min; 4 = 16 min
UL installations = 1 (4 min) minimum
✱34 EXIT DELAY | †[70]
00-99 = exit delay time (in seconds).
UL installations = 60 seconds max.
✱35 ENTRY DELAY 1 (zone type 01) | †[30]
00-99 = entry delay time (in seconds);
UL installations = 45 seconds max.
✱36 ENTRY DELAY 2 (zone type 02) | †[60]
00-99 = entry delay 2 time (in seconds);
UL installations = 45 seconds max.
✱37 AUDIBLE EXIT WARNING /
QUICK EXIT † [1, 1]
Exit Warn Quick Exit
0 = no; 1 = yes
✱38 CONFIRMATION OF ARMING DING
Note: If LYNX is armed by RF button (key fob),
a confirmation ding occurs immediately after
arming regardless of field *38 settings. If LYNX
is disarmed by RF button (key fob), additional
disarming confirmation ding is provided. The
ding occurs immediately after disarming and is
longer than arming confirmation ding.
† [0]
0 = no arming confirmation ding after arming system by APX32EN keypad or
RF keypad; 1 = arming confirmation ding after arming system by APX32EN
keypad or RF keypad; 2 = arming confirmation ding after arming from RF
keypad only
If Option 1 is selected, confirmation of arming is provided by a 1/2 second
sounder “ding” that sounds when closing report is sent, or at the end of exit
delay. If Option 2 is selected the external sounder “ding” occurs immediately
after arming from an RF keypad.
Note: Confirmation ding only sounds when LYNX is Armed Away or disarmed
after being Armed Away.
✱39 POWER UP IN PREVIOUS STATE † [1]
0 = no; 1 = yes; UL installations = 1
DIALER PROGRAMMING (✱40– ✱ 53)
In fields ✱40, ✱41, ✱42, enter up to the number of digits shown. Enter 0–9; #+11 for '✻'; #+12 for '#'; #+13 for
a pause.
✱40 PABX ACCESS CODE
Enter 6 digits. If fewer than 6 digits are entered, pressing ✻
advances to the next field. To clear entries from field, press ✻40✻
✱41 PRIMARY PHONE NUMBER
Enter up to 20 digits; Do not fill unused spaces. If fewer than 20 digits
entered, pressing ✻advances to the next field. To clear entries from
field, press ✻41✻.
† Entering a number other than the one specified may give unpredictable results.

- 5 -
Field Function Programmed Values [ ] = Table 1 Default Values
✱42 SECONDARY PHONE NUMBER
Enter up to 24 digits; Do not fill unused spaces. If fewer than 24 digits
entered, pressing ✻advances to the next field. To clear entries from
field, press ✻41✻.
!
All four digits of the subscriber account number must be entered in Fields ✻
✻✻
✻43 and ✻
✻✻
✻44. If ten digit format is
selected in ✻
✻✻
✻48 (option 5), all ten digits of the Subscriber Account number must be entered.
For fields ✻43, ✻44:
Enter 4 to 10 digits. Enter 0–9; #+11 for B; #+12 for C; #+13 for D; #+14 for E; [#+15 for F]. Enter ✻ as 4th digit, if 3+1
dialer reporting is to be used. If only 3 digits used, pressing ✻advances to the next field. Enter [✻] as the fifth digit if a 4-
digit account number (for 3+1, CID®) is used.
To clear entries from field, press ✻43✻ or ✻44✻. Examples:
For Acct. 1234, enter: 1 | 2 | 3 | 4 ; For Acct. B234, enter: #+11| 2 | 3 | 4 For Acct. 1234567890, enter:
1| 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 0 ; For Acct. 123, enter: 1 | 2 | 3 | ✻
✱43 PRIMARY SUBS ACCT # See note above.
✱44 SECONDARY SUBS ACCT # See note above.
For field ✻46
Enter up to 24 digits. Enter 0-9, #+11 for ‘✻’; #+12 for ‘#’; #+13 for a pause (two seconds).
✱46 “FOLLOW ME” REMINDER
PHONE NUMBER
Enter up to 24 digits; Do not fill unused spaces. If fewer than 24 digits
entered, pressing ✻advances to the next field. To clear entries from
field, press ✻46✻.
✱47 PHONE SYSTEM SELECT † [5]
Central Dialing Mode
Station Pulse Tone Pulse Tone
No WATS 0 = No Speaker
Phone
1 = No
Speaker Phone
4 = With
Speaker Phone
5 = With
Speaker Phone
WATS 2 = No Speaker
Phone
3 = No
Speaker Phone
6 = With
Speaker Phone
7 = With
Speaker Phone
✱48 REPORT FORMAT for PRIM./SEC [7, 7]
Primary Secondary
0 = 3+1, 4+1 ADEMCO L/S STANDARD
1 = 3+1, 4+1 RADIONICS STANDARD
2 = 4+2 ADEMCO L/S STANDARD
3 = 4+2 RADIONICS STANDARD
5 = ADEMCO CONTACT ID® REPORTING WITH 10-DIGIT SUBS ACCT NO.
6 or undefined = 4+2 ADEMCO EXPRESS
7 = ADEMCO CONTACT ID® REPORTING WITH 4-DIGIT SUBS ACCT NO.
8 = 3+1, 4+1 ADEMCO L/S EXPANDED
9 = 3+1, 4+1 RADIONICS EXPANDED
† Entering a number other than the one specified may give unpredictable results.
Note: If you are using Pulse (rotary) Dialing, you must
enter the numbers slowly to allow the pulse dialer
time to o
p
erate.
Note: Option 5 or 7 (ADEMCO Contact ID®)
must be selected for AAV.

- 6 -
Field Function Programmed Values [ ] = Table 1 Default Value
✱49 SPLIT/DUAL REPORTING [0]
0 = Disable (None, unless primary fails)
TO PRIMARY PHONE No. TO SECONDARY PHONE No.
1 = Alarms, Restore, Cancel Others
2 = All except Open/Close, Test Open/Close, Test
3 = Alarms, Restore, Cancel All
4 = All except Open/Close, Test All
5 = All All
** Pager Message
A 7-digit code (plus optional 16-digit prefix) is
sent to the pager consisting of a 3-digit event code,
followed by 0 and a 3-digit user or zone number.
See Installation Instructions for an explanation of
the pager code, which takes the following form:
AAAAAAAAAAAAAAAA-EEE-0NNN
TO PRIMARY PHONE No.
6 = All except Open/Close
7 = All reports
8 = All reports
9 = All except Open/Close
TO PAGING** No. (Secondary)
Alarms, Open/Close‡, Troubles
Alarms, Troubles
Alarms, Open/Close‡, Troubles
Open/Close‡
‡Will report users 0, 5-8 or wireless
arm/disarm button zones 26-33; all other
zones and users do not report
AAA… = optional 16-digits (see field ✻88)
EEE = 3-digit event code: 911 (alarm), 101 (open), 102 (close),
811 (trouble)
0 = always displayed
NNN = 3-digit user number or zone number, depending on the
type of event (EEE) that occurred.
TO PRIMARY PHONE No.
10 = All except Open/Close
11 = All reports
12 = All reports
13 = All except Open/Close
TO SECONDARY (“FOLLOW
ME”) SYSTEM PHONE No.
Alarms, Open/Close‡, Troubles
Alarms, Troubles
Alarms, Open/Close‡, Troubles
Open/Close‡
‡Will report users 0, 5-8 or wireless
arm/disarm button zones 26-33; all other
zones and users do not report
✱50 15 SEC DIALER DELAY (BURG) †[0]
0 = no; 1 = yes; UL installations = 0
✱51 PERIODIC TEST REPORT †[0]
0 = none; 1 = 24 hours; 2 = weekly; 3 = 30 days
(enter Test Code in field ✻64)
✱52 FIRST TEST REPORT OFFSET †[2]
0 = 24 hour; 1 = 6 hours; 2 = 12 hours; 3 = 18 hours
(Time to 1st report from power up/programming or downloading).
✱53 SESCOA/RADIONICS SELECT [0]
0 = Radionics (0–9, B–F reporting); 1 = SESCOA (0–9 only reporting).
Select 0 for all other formats.
✱54 LACK OF USAGE NOTIFICATION [0]
0 = Disabled 4 = 90 days
1 = 1 day 5 = 180 days
2 = 7 days 6 = 365 days
3 = 27 days
✱55 REPORTING CHANNELS
[0]
0 = Telco Line (no Radio)
1 = LRR/IP(Digital Communication only) and Telco Line
3 = LRR/IP (Digital Communication only) (no Telco Line)
5 = LRR/IP (Digital Communication with AAV) (no Telco Line)
7 = LRR/IP (Digital Communication with AAV) and Telco Line
✱56 ENHANCED ZONE PROGRAMMING See procedure in this guide and refer to the Installation Guide.
✱58 RF JAM DETECT [0]
0 = no RF Jam Detection; 1 = RF Jam Detect on, no CS report;
2 = RF Jam Detect on with CS report
(if trouble/restore report is enabled in fields ✻60, ✻71)
Note: For event logging option 2 must be selected.
† Entering a number other than the one specified may give unpredictable results.

- 7 -
Field Function Programmed Values [ ] = Table 1 Default Value
TO PROGRAM SYSTEM STATUS, & RESTORE REPORT CODES (✱59–✱76, & ✱89):
With a 3+1 or 4+1 Standard Format: Enter a code in the first box: 1–9, 0, B, C, D, E, or F. Enter "#+10" for 0, "#+11" for
B, "#+12" for C, "#+13" for D, "#+14" for E, "#+15" for F.
A "0" (not "#+10") in the first box will disable a report.
A "0" (not "#+10") in the second box will result in automatic advance to the next field when programming.
With an Expanded or 4+2 Format: Enter codes in both boxes (1st and 2nd digits) for 1–9, 0, or B–F, as described above.
A "0" (not "#+10") in the second box will eliminate the expanded message for that report.
A "0" (not "#+10") in both boxes will disable the report.
With Ademco Contact ID Reporting: Enter any digit (other than "0") in the first box, to enable zone to report (entries in the
second boxes will be ignored).
A "0" (not "#+10") in the first box will disable the report.
Examples: For Code 3(single digit), enter: 3 | 0
For Code 3 2 (two digits), enter: 3 | 2
For Code B 2 (Hexadecimal), enter: #+11 | 2
SYSTEM STATUS REPORT CODES (✱59–✱68)
✱59 EXIT ERROR REPORT CODE [1]
✱60 TROUBLE REPORT CODE | [1,0]
✱61 BYPASS REPORT CODE | [0,0]
✱62 AC LOSS REPORT CODE | [0,0]
✱63 LOW BATTERY REPORT CODE | [1,0]
✱64 TEST REPORT CODE | [1,0]
✱65 OPEN REPORT CODE †† [0]
✱66 ARM AWAY/STAY RPT CODE †† [0,0]
AWAY STAY
✱67 RF XMTR LOW BAT REPORT CODE | [1,0]
✱68 CANCEL REPORT CODE | [1,0]
RESTORE REPORT CODES (✱70–✱76)
✱70 ALARM RESTORE RPT CODE [1]
✱71 TROUBLE RESTORE RPT CODE | [1,0]
✱72 BYPASS RESTORE RPT CODE | [0,0]
✱73 AC RESTORE RPT CODE | [0,0]
✱74 LOW BAT RESTORE RPT CODE | [1,0]
✱75 RF XMTR LO BAT RST RPT CODE | [1,0]
✱76 TEST RESTORE RPT CODE | [0,0]
2nd digit is automatically sent as 2nd digit of the zone alarm report code
p
ro
g
rammed in ✻56
,
if ex
p
anded or 4+2 re
p
ortin
g
is selected.
(
††
2nd digit is automatically sent as the user number
if ex
p
anded or 4+2 re
p
ortin
g
is selected.
)
2nd digit is automatically sent as 2nd digit of the zone alarm report
code programmed in ✻56, if expanded or 4+2 reporting is selected.

- 8 -
Field Function Programmed Values[ ] = Table 1 Default Value
DYNAMIC SIGNALING FIELD ✻
✻✻
✻77
✱77 DYNAMIC SIGNALING DELAY/
DYNAMIC SIGNALING PRIORITY
| [0, 0]
1st Entry (delay before switch CS reporting path)
0 = Redundant reporting
on dialer and LRR/IP
device
7 = 105 seconds
8 = 120 seconds
9 = 135 seconds
1 = 15 seconds #10 = 150 seconds
2 = 30 seconds #11 = 165 seconds
3 = 45 seconds #12 = 180 seconds
4 = 60 seconds #13 = 195 seconds
5 = 75 seconds #14 = 210 seconds
6 = 90 seconds #15 = 225 seconds
2nd Entry
0 = Primary Dialer Preferred Channel
1 = LRR/IP Preferred Channel
2 = LRR/IP reporting only
✱78 PROGRAMMABLE TONE
GENERATION TIME | [0, 0]
00 = Disabled
01-09 = 100-900 ms
10-99 = 1.0 – 9.9 secs.
OUTPUT AND SYSTEM SETUP (✱80–✱92)
✱80
✱81
DEVICE PROGRAMMING MENU
MODE
ZONE LISTS MENU MODE
Program ✻80 and ✻81 only if Powerline Carrier Devices or chime by
zone are to be used. See procedure later in this manual.
✱83 ENHANCED SEQUENTIAL MODE See procedure later in this manual.
✱84 ASSIGN ZONE VOICE DESCRIPTOR
See procedure later in this manual.
✱85 RECORD CUSTOM VOICE
DESCRIPTOR
See procedure later in this manual.
✱86 MULTI-MODE (E-MAIL
NOTIFICATION) [0]
0 = Disable multi-mode devices
1 = Enable multi-mode device address #6 only
2 = Enable multi-mode device address #7 only
3 = Enable multi-mode addresses
✱87 AUX FUNCTION/ 1-BUTTON PAGING [0]
0 = Aux key performs defined function (macro);
1 = Aux key sends message to pager or voice message to
follow me system phone number.
If 1, you must also select an option 6-9 in field ✻49 for the
pager or 10-13 for the follow me system announcement.

- 9 -
Field Function Programmed Values[ ] = Table 1 Default Value
✱88 PAGER CHARACTERS
Up to 16 digits can be entered that will appear in front of the 7-digit
pager message sent by the control (either upon system event or upon
pressing AUX key [if programmed for paging]; see field ✻87 and ✻49
for other options regarding the paging feature). See the Installation
Instructions (fields ✻87, ✻88 and ✻49) for full descriptions of the
paging feature. You do not need to fill all 16 digits (press [✻] to
advance to next field). To clear entries, enter ✻88✻.
To enter “✻” = [#] + [11]; To enter “#” = [#] + 12]
To enter 2-second pause = [#] + [13] (some pagers require an
additional delay [pause] in order to receive the entire message)
✱89 EVENT LOG 80% FULL RPT CODE | [0,0]
✱90 EVENT LOGGING [3]
0 = None; 1 = Alarm/Alarm Restore; 2 = Trouble/Trouble Restore; 4
= Bypass/Bypass Restore; 8 = Open/Close.
Example: To select “Alarm/Alarm Restore”, and “Open/Close”, enter 9
(1 + 8); To select all, enter #15.
Note: System messages are logged when any non-zero selection is
made.
✱91 ALARM AUDIO VERIFICATION
(AAV)/REMOTE PHONE CONTROL [2]
0 = None
1 = AAV and remote phone control
2 = remote phone control only
4 = AAV only
Notes: (1) In order to activate the Remote Phone Control feature and defeat
an answering machine, ensure that the correct ring detection
count (“15”) has been programmed in field ✻95.
(2) Remote phone session will be terminated if a report must be
sent.
(3) Alarm Audio Verification will only function when Contact ID® is
selected. AAV cannot be used for UL installations.
(4) If an alarm will be reported to primary and secondary phone
numbers, AAV can only function via the secondary number.
(5) If an alarm will be reported to a pager (6-8 in field ✻49), or to
follow me phone number (10-12 in field ✻49) AAV cannot be
used.
(6) If AAV is selected and LRR/IP communications device is
enabled, you must enter "0" (primary dialer preferred channel) as
the second entry in Field *77.
✱92 NUMBER OF REPORTS IN ARMED
PERIOD [0]
0 = 10 Alarm/Alarm Restore Reports;
1 = Unlimited (UL installations = 0)
DOWNLOAD INFORMATION (✱93, ✱94, ✱95)
✱93 FLEXIBLE CALLBACK [0]
0 = No flexible callback; 1 = Last digit flexible; 2 = Last 2 digits
flexible;
3 = Last 3 digits flexible

- 10 -
Field Function Programmed Values [ ] = Table 1 Default Value
✱94 DOWNLOAD PHONE NUMBER
Enter up to 20 digits, 0–9; #+11 for '✻'; #+12 for '#'; #+13 for a
pause. Do not fill unused spaces. If fewer than 20 digits entered,
pressing ✻advances to the next field. To clear entries from field,
press ✻94✻.
Note: In UL installations, downloading may only be performed if a technician
is at the site.
✱95 RING DETECT COUNT FOR
DOWNLOADING/REMOTE PHONE
CONTROL MODE
[15]
0 = Disable Station Initiated Download; 1–14 = number of rings (1–9,
[#]+10 =10, [#] +11 =11, [#] +12 =12, [#] +13 =13, [#] +14
=14); 15 = answering machine defeat ([#] +15 =15)
✱96 INITIALIZE DOWNLOAD ID &
SUBSCRIBER ACCOUNT
No entry required
✱97 SET ALL PROGRAM FIELDS TO
DEFAULT VALUES
Enter 1 to select default table
Enter 0 to abort.
✱98 EXITS PROGRAMMING MODE
(PREVENTS RE-ENTRY)
If ✻98 is used to exit programming mode, you cannot enter the
Installer Code + 8+ 0 + 0 for re-entry. You must press "✻" and "#"
within 50 seconds of power up or from exiting Programming mode to
re-enter Programming mode.
Note: After exiting Program mode, the system takes up to 1 minute to reset. To
bypass the reset delay, press [#] + [0].
✱99 EXITS PROGRAMMING MODE
(ALLOWS RE-ENTRY)
Installer Code + 8 + 0 + 0
or:
Power-up, then press "✻" and "#" within 50 seconds of power up or
from exiting Programming mode.
Note: After exiting Program mode, the system takes up to 1 minute to reset.
To bypass the reset delay, press [#] + [0].

- 11 -
✻
✻✻
✻56 ENHANCED ZONE PROGRAMMING PROCEDURE
Use this mode to program zone information. Press ✻56 while in programming mode.
Notes: (1) Entering a number other than the one specified may give unpredictable results.
(2) You may find it convenient to adjust the volume setting before entering the Programming Mode. This will allow
you to clearly hear feedback announcements or system beeps.
A 02
ZONE NUMBER
Enter the 2-digit zone number to be programmed. The system will announce the Voice Descriptor for
the selected zone, if it is programmed.
[✻] = Continue •Zones 2-25 = RF transmitter zones (only)
00 = exit zone programming mode; •Zone 26-41 = RF button zones (only)
upon exiting, the prompt “56” blinks; press •Zone 92 = Duress
[✻] + any field number to go to that field. •Zone 95, 96, 99 = Panic zones
bzt ZONE TYPE
Enter the 2-digit zone type (zt) for this zone (see table of zone types on worksheet).
[✻] = Continue [if 00 is entered the system will skip to DELETE ZONE PARAMETERS prompt (F)].
[#] = Return to previous prompt
Crc
REPORT CODE
Enter the report code (rc) for this zone.
Report consists of 2 hexadecimal digits, each composed of 2 numerical digits (A = 10, B = 11, C = 12,
D = 13, E = 14, F = 15; see Report Code description for explanation of codes). [✻] = Continue; If this is
zone 95, 96 or 99, the system skips to the VOICE DESCRIPTOR prompt (1C)
[#] = Return to previous prompt
diINPUT TYPE
Enter the input type (i) for the transmitter assigned to this zone as follows:
3 = Supervised RF (RF) [✻] = Continue
4 = Unsupervised RF (UR) [#] = Return to previous prompt
5 = Button type (BR)
El
LOOP NUMBER or LOOP AND SERIAL NUMBER (if using RF Learning)
Note: It is not necessary to manually enter a Loop Number if using the RF Learning Mode.
RF Learning - Two (2) transmissions (two key depressions at least five seconds apart) will be required
for BR type devices (device type 5). Two beeps will sound after the second transmission, confirming that
the loop number and serial number have been learned.
For all other device types, four (4) transmissions are required (fault, restore and fault, restore). A single
beep will sound after the second transmission confirming that the loop and serial number have been
captured. Following the fourth transmission the system will confirm that the loop and serial number have
been learned by announcing the Voice Descriptor for the zone, if it is programmed, followed by two
beeps.
Note: BR type devices cannot be enrolled by using UR or RF type. Likewise, UR or RF type devices cannot be
enrolled by using a BR type device. There is a 52-second time-out for RF enrolling. At the end of the time-out,
the system returns to the INPUT TYPE prompt (d). If enrolled, loop number and “L” are displayed.
Manual Entry - Enter the desired loop number and press [✻] to continue (see the transmitter’s
Installation Instructions for specific loop designations). If “L” is displayed the zone’s serial number has
already been enrolled.
Note: The loop number can be changed even if the zone has already been entered. Care should be taken when using
this feature as it has the capability to make zones inoperable by creating a mismatch of a working serial
number/loop number combination. This should be re-confirmed if the loop number is changed.
0 + [✻] = to Delete Serial Number prompt (F)
[✻] = Continue to the ENROLL MODE prompt (1A) if not enrolled, or VOICE DESCRIPTOR prompt (1C) if
already enrolled.
[#] = Return to previous prompt
1-4 = Loop number for the zone of the transmitter being entered or learned
Note
Zones 2-25 should be assigned
as Input Type 3 or 4 and Zones
26-41 should be assigned as
Type 5 only.

- 12 -
✻
✻✻
✻56 ENHANCED ZONE PROGRAMMING PROCEDURE
F
DELETE ZONE PARAMETERS
0 = Discard the delete request.
1 = Confirm the requested delete.
If 00 is entered in the zone type, confirmation of the delete request will delete all information associated
with zone currently being programmed.
If 0 is entered in the loop number, confirmation of the delete request will delete the serial number
associated with zone currently being programmed.
Note: 00 was entered as a zone type in prompt (b), 00 will be retained and system will advance to prompt (1C).
IA LC ENROLL MODE
0 = Skip to the VOICE DESCRIPTOR prompt (1C). If zone type is “00,” then skips to DELETE SERIAL
NUMBER prompt instead.
1 = Enroll now and proceed to SERIAL NUMBER prompt (1b) (If “L” is not displayed).
2 = Copy the last serial number from the local memory buffer (If “L” is not displayed).
3 = View existing serial number. (Only if “L” is displayed).
9 = Delete existing serial number. (Only if “L” is displayed).
[✻] = Advance to the VOICE DESCRIPTOR prompt (1C). This will save all zone parameters.
[#] = Return to the loop number prompt (E).
Notes: (1) “L” will be displayed only if transmitter was already learned.
(2) The system will announce the Voice Descriptor for the selected zone, if it is programmed, followed by
three beeps and “C” will be displayed only after confirmation.
Ib
SERIAL NUMBER
Manually enter the transmitter’s 7-digit serial number (printed on the transmitter). If an incorrect digit is
entered, press the [#] key to return to prompt (1A).
Note: In order for all parameters to be accepted, you must advance to prompt (1C).
When all 7 digits are entered, press the [✻] key. The serial number will be copied into EEROM and the
local memory buffer and the system will return to the (1A) prompt and “L” will be displayed. If 52
seconds pass and no entry is been made, the system will return to prompt (1A).
IC
VOICE DESCRIPTOR
0 = Skip to next zone (A)
1 = Enter descriptor mode (existing zone descriptor will be announced, then descriptor 1 will be
repeated)
Idvi
DESCRIPTOR 1
Enter [#] + 2-digit vocabulary index†number (vi) of first descriptor word for this zone.
To change the entered index number, press [#] + desired index number.
6 = accept word and advance to descriptor 2 (descriptor 2 will be announced)
8 = accept word and advance to next zone (prompt A) – zone descriptor will be announced
Press any other key to repeat the selected word
IE vi
DESCRIPTOR 2
Enter [#] + 2-digit vocabulary index†number (vi) of second descriptor word for this zone.
To change the entered index number, press [#] + desired index number.
6 = accept word and advance to descriptor 3 (descriptor 3 will be announced)
8 = accept word and advance to next zone (prompt A) – zone descriptor will be announced
Press any other key to repeat the selected word
IF vi
DESCRIPTOR 3
Enter [#] + 2-digit vocabulary index†number (vi) of third descriptor word for this zone.
To change the entered index number, press [#] + desired index number.
6 or 8 = accept word and advance to next zone (prompt A) – zone descriptor will be announced
Press any other key to repeat the selected word
†See ✻84 ASSIGN ZONE VOICE DESCRIPTORS section for Vocabulary Index.

- 13 -
✻
✻✻
✻80 DEVICE PROGRAMMING
Use this mode to program Powerline Carrier Devices or zone lists for Chime by Zone feature. It is also used to
program the Remote Services Multi-mode (e-mail) event triggers. Press ✻80 while in programming mode.
Note: Entering a number other than the one specified may give unpredictable results.
80 Device Programming
0 = Exit mode, upon which this prompt blinks.
1 = Enter mode
A 0 I
DEVICE NUMBER
Enter the 2-digit device number to be programmed
01-08 = X10 device number
09-16 = Multi-mode (e-mail) event triggers
[✻] = Continue
00 = Exit Device Programming mode (displays blinking 80; enter ✻+ desired data field or menu mode number)
baa
DEVICE ACTION
Enter the 1-digit action, 0-3, for the device being programmed (current action is displayed).
0 = No response 3 = Pulse on and off
1 = Close for 2 seconds [✻] = Continue
2 = Close and stay closed [#] = Return to previous prompt
C et
START EVENT TYPE (if applicable)
Enter the 1-digit start event type, 0-3, for the device being programmed.
0 = Not used 3 = Trouble
1 = Alarm [✻] = Continue
2 = Fault [#] = Return to previous prompt
dzl START ZONE LIST (if applicable)
Enter the 1-digit zone list number, 1-3, or 0 if not used, for the device being programmed.
[✻] = Continue
[#] = Return to previous prompt
E zt
START ZONE TYPE (if applicable)
Enter the 2-digit start zone type for the device being programmed (see Powerline Carrier Device
Worksheet for zone type/system operation codes later in this manual).
[✻] = Continue
[#] = Return to previous prompt
F zl
STOP ZONE LIST (if applicable)
Enter the 1-digit zone list number, 1-3, or 0 if not used, for the device being programmed.
[✻] = Continue
[#] = Return to previous prompt
IA zt
STOP ZONE TYPE (if applicable)
Enter the 2-digit stop zone type for the device being programmed (see Powerline Carrier Device
Worksheet for zone type/system operation codes later in this manual).
[✻] = Return to Device Number prompt (A)
[#] = Return to previous prompt

- 14 -
✻
✻✻
✻81 ZONE LISTS
Use this mode to define zone lists for Powerline Carrier Devices and/or for the chime by zone feature. Press ✻81
while in programming mode.
Notes: (1) Entering a number other than one specified will give unpredictable results.
(2) Do not assign zones with zone types 20, 21 or 22 to a zone list.
8 I ZONE LIST PROGRAMMING
0 = Exit mode, upon which this prompt blinks.
1 = Enter mode
A 0 I
ZONE LIST NUMBER
Enter the 2-digit zone list number (01-03) to be programmed (use zone list 03 for chime by zone feature).
[✻] = Continue
00 = Exit mode (displays blinking 81; enter ✻+ desired data field or menu mode number)
bzz ZONE ENTRY TO LIST
Enter the 2-digit zone number (zz) to be added to this zone list. The system will announce the Voice
Descriptor for the selected zone, if it is programmed.
[✻] = Accept zone number and enter the next zone number
00 = Accept zone number and continue to next prompt
C
DELETE ENTIRE ZONE LIST?
0 = Don’t delete; continue to next prompt
1 = Delete the current zone list
d
DELETE SPECIFIC ZONES FROM LIST?
0 = Don’t delete; continue to next zone list number (prompt A 01)
1 = Continue to delete zones prompt
E
DELETE ZONES
Enter the 2-digit zone number to be deleted from the current zone list. When deleting a zone(s) from the
zone list, if the selected zone has a Voice Descriptor programmed, upon deletion it will be announced as
a confirmation that it has been deleted.
[✻] = Delete zone and enter next zone to be deleted
00 = Return to next zone list number (prompt A 01)

- 15 -
✻
✻✻
✻83 ENHANCED SEQUENTIAL MODE
Use this mode to enter transmitter serial numbers. Press ✻83 while in programming mode.
A 02
ZONE NUMBER
Enter the 2-digit zone number of the first transmitter to have its serial number entered. The system will
announce the Voice Descriptor for the selected zone if it has been programmed.
[✻] = Continue; system searches for zones not yet entered, (for zones 2 to 25 a zone type must be
entered) then advances to ENROLL SERIAL NUMBER prompt (1b).
00 = Exit Sequential mode, upon which the prompt “83” blinks.
IA zz
IA LC
ENROLL MODE
0 = Advance to next unlearned zone.
1 = Enter now and proceed to SERIAL NUMER prompt (1b). For 4-button keys (zones 26-29, 30-33, 34-
37 and 38-41) the serial number will be learned to all four buttons.
2 = copy the previous serial number entry from the buffer.
Note: Before you can copy a serial number you must first enter a serial number. If no serial is stored in the buffer and
a copy is attempted the panel will emit a long beep indicating an invalid operation.
3 = View existing serial number. (Only if “L” is displayed. If “L” is not displayed, panel will emit a long
beep. Each digit will be displayed and the keypad will beep once for digits 1-6 and three times for last
digit.
4 = Copy the 4-button key template set for zones 26 - 29 (includes all zone parameters except serial
numbers). Only valid on 4-button key zones 30-33, 34-37 and 38-41 that do not have serial numbers
learned. (Template acceptance is indicated by two beeps after copying. A single long beep emitted
when copying templates indicates the template is not valid.)
9 = Delete existing serial number. Go to the (1A) prompt. (For 4-button key zones 26-29, 30-33, 34-37
and 38-41, deletes all four at once.)
[✻] = Advance to the next unlearned zone.
[#] = Return to previous prompt (1A).
Ibzz
Ib
SERIAL NUMBER
This prompt can be used to enroll the transmitter serial number via RF transmission or manually.
RF Learning - Two (2) transmissions (two key depressions at least five second apart) will be required for
BR type or four (4) transmissions (fault, restore and fault, restore) for UR or RF type. BR type devices can
be enrolled only by transmission from BR devices. Likewise, UR and RF devices can only be enrolled by
transmission from a UR or RF device.
If the learned serial number has a different loop number than that entered in ✻56 the system will
announce the Voice Descriptor, if it is programmed, followed by two beeps and will return to Prompt
(1A) and “L” will be displayed.
If the loop number captured by RF transmission and that entered in ✻56 mode match, the system will
announce the Voice Descriptor, if it is programmed, followed by three beeps and return to Prompt (1A)
and “LC” will be displayed. No additional transmissions are needed for confirmation.
Manual Entry - Enter the 7-digit serial number printed on the transmitter. If you enter an incorrect digit,
press the [#] key to backup to prompt (1A) and start over. When all 7 digits are entered, press the [✻]
key. If less than 7 digits are entered, the keypad will emit a single long beep and return to the (1A)
prompt without displaying the “L”. If more than 7 digits have been entered, the first 6 digits will be saved
along with the last digit that was entered (entering 123456789 yields the serial number 1234569).
Note: If 52 seconds passes and no entry has been made, the system returns to prompt (1A).
F
DELETE ZONE PARAMETERS CONFIRMATION
0 = Discard the delete request.
1 = Confirm requested delete.

- 16 -
✻
✻✻
✻84 ASSIGN ZONE VOICE DESCRIPTORS
Use this mode to assign voice descriptors for each zone. These are the descriptors that are announced when the
system announces any event involving a zone number. Press ✻84 while in programming mode.
Note: Entering a number other than the one specified may give unpredictable results.
84
ASSIGN ZONE VOICE DESCRIPTORS
0 = Exit mode, upon which this prompt blinks.
1 = Enter mode
A zz
ZONE NUMBER
Enter the 2-digit zone number (zz) for which this descriptor is being assigned. The Voice Descriptor
for the selected zone will be announced, if it is programmed.
[✻] = Continue to next prompt (existing descriptors will be announced, then descriptor 1 will be
repeated.)
00 = Exit Zone Voice Descriptor mode (displays blinking 84; enter ✻+ desired data field or menu
mode number)
bvv DESCRIPTOR 1
Enter [#] + 2-digit vocabulary index number of first descriptor word for this zone.
To change the entered index number, press [#] + desired index number.
6 = accept word and advance to descriptor 2 (descriptor 2 will be announced)
8 = accept word and advance to next zone (prompt A….zz) – zone descriptor will be announced
Press any other key to repeat the selected word
Cvv
DESCRIPTOR 2
Enter [#] + 2-digit vocabulary index number of second descriptor word for this zone.
To change the entered index number, press [#] + desired index number.
6 = accept word and advance to descriptor 3 (descriptor 3 will be announced)
8 = accept word and advance to next zone (prompt A….zz) – zone descriptor will be announced
Press any other key to repeat the selected word
dvv DESCRIPTOR 3
Enter [#] + 2-digit vocabulary index number of third descriptor word for this zone.
To change the entered index number, press [#] + desired index number.
6 or 8 = accept word and advance to next zone (prompt A….zz) – zone descriptor will be announced
Press any other key to repeat the selected word
VOCABULARY INDEX
00 ½ sec pause
A
82 ALARM
32 ATTIC
B
01 BABY
33 BACK
34 BASEMENT
35 BATHROOM
36 BEDROOM
C
83 CHECK
D
37 DELAY DOOR
38 DEN
02 DETECTOR
03 DINING
39 DINING ROOM
04 DOOR
40 DOWNSTAIRS
05 DRIVEWAY
E
06 EAST
41 EIGHT
42 EMERGENCY
F
43 FAMILY ROOM
87 FIRE
44 FIRE DETECTION
07 FIRST FLOOR
45 FIVE
08 FLOOR
46 FOUR
47 FRONT
G
48 GARAGE
49 GUEST ROOM
09 GUN
H
50 HALL
I
10 INSIDE
K
51 KITCHEN
L
11 LAUNDRY
52 LAUNDRY ROOM
12 LIBRARY
13 LIVING
53 LIVING ROOM
M
14 MAIN
15 MASTER
54 MASTER
BEDROOM
55 MEDICAL
84 MESSAGE
56 MOTION DETECTOR
N
57 NINE
16 NORTH
58 NURSERY
O
59 OFFICE
60 ONE
17 OUTSIDE
P
61 PATIO
62 POLICE
18 POOL
R
63 REAR
19 ROOM
S
64 SECOND FLOOR
65 SEVEN
20 SHED
21 SHOP
66 SIDE
67 SILENT POLICE
68 SIX
69 SLIDING
22 SMOKE
23 SOUTH
24 STORAGE
85 SYSTEM
T
25 THIRD FLOOR
75 THREE
76 TRANSMITTER
77 TWO
U
78 UPSTAIRS
26 UTILITY
79 UTILITY ROOM
W
27 WEST
80 WINDOW
Y
28 YARD
Z
81 ZERO
86 ZONES
29 1ST
30 2ND
31 3RD
70 Custom Word #1
71 Custom Word #2
72 Custom Word #3
73 Custom Word #4
74 Custom Word #5
99 Blank (to erase
previously
programmed word)
SYSTEM WORDS
(Announced by system –
not programmable)
AC LOSS
ARMED
AWAY
BYPASSED
CARBON MONOXIDE
CHIME
DISARMED
DISARM SYSTEM
NOW
EXIT NOW
FAULT
INSTANT
LOW BATTERY
NOT
READY TO ARM
STAY
Note: If a Wireless Keypad is being installed along with this system, not all the voice descriptors shown on this list can be
announced by keypad. (Refer to the Wireless Keypad documentation for further information).

-17-
✻
✻✻
✻85 RECORD CUSTOM VOICE DESCRIPTORS
Use this mode to record up to 5 custom voice descriptors for use with zone announcements. Press ✻85 while in
programming mode.
NOTE: Entry of a number other than one specified will give unpredictable results.
85
RECORD CUSTOM VOICE DESCRIPTORS
0 = Exit mode, upon which this prompt blinks.
1 = Enter mode
A 7d
CUSTOM DESCRIPTOR NUMBER
Enter 7 + d + [✻]
where d= 0-4, each representing custom word 70, 71, 72, 73 or 74 respectively. Existing descriptor will
be announced.
Press [#] to start recorder. Begin speaking immediately after the third beep.
Speak the desired word clearly near the keypad microphone. Recording stops after 1.5 seconds.
6 = Accept word and ready to record next descriptor (prompt A….7d)
[#] = Re-record descriptor
00 = Exit Record mode after pressing 6 (displays blinking 85; enter ✻+ desired data field or menu
mode number)
Press any other key to repeat the recorded word.

- 18 -
✻
✻✻
✻56 ENHANCED ZONE PROGRAMMING WORKSHEET
Fill in the required data on this worksheet, then follow the programming procedure in the Installation and Setup
Guide.
ZONES ON CONTROL: See explanation of headings
Zone Zone Zone Alarm rpt code Vocabulary
Description No. (a 02) Type (zt) (hex) (rc) Index
Zone No. Zone Alarm Report Input Loop Transmitter Vocabulary
(A 02) Type (zt) Code in hex (rc) Type (i) No. (l) Serial Number Index
0|2 | [01] | | [01 00] [3] [2] | | [47-04-99]
0|3 | [01] | | [01 00] [3] [2] | | [33-04-99]
0|4 | [03] | | [01 00] [3] [2] | | [80-99-99]
0|5 | [10] | | [01 00] [3] [1] | | [56-99-99]
0|6 | | | | |
0|7 | | | | |
0|8 | | | | |
0|9 | | | | |
1|0 | | | | |
1|1 | | | | |
1|2 | | | | |
1|3 | | | | |
1|4 | | | | |
1|5 | | | | |
1|6 | | | | |
1|7 | | | | |
1|8 | | | | |
1|9 | | | | |
2|0 | | | | |
2|1 | | | | |
2|2 | | | | |
2|3 | | | | |
2|4 | | | | |
2|5 | | | | |
Duress 92[00 00] I I
Keypad Panic (1 & ✻)95
[00] [00 00] I I
Keypad Panic (3 & #) 96
[00] [00 00] I I
Keypad Panic (✻& #) 99
[06] [01 00] I I

- 19 -
Zone No. Zone Alarm Report Input Loop Transmitter Vocabulary
(A 02) Type (zt) Code in hex (rc) Type (i) No. (l) Serial Number Index
Button Zones
2|6 | [21] | | [01 00] [5] [3 | |
2|7 | [22] | | [01 00] [5] [2] | |
2|8 | [20] | | [01 00] [5] [4] | |
2|9 | [23] | | [00 00] [5] [1] | |
3|0 | [21] | | [01 00] [5] [3] | |
3|1 | [22] | | [01 00] [5] [2] | |
3|2 | [20] | | [01 00] [5] [4] | |
3|3 | [23] | | [00 00] [5] [1] | |
3|4 | | | | |
3|5 | | | | |
3|6 | | | | |
3|7 | | | | |
3|8 | | | | |
3|9 | | | | |
4|0 | | | | |
4|1 | | | | |
EXPLANATION OF ZONE ASSIGNMENT TABLE HEADINGS
A 02 = ZONE No. Zone Numbers are 2-25 (RF) only, 26-41 (Button) only, 92 (duress), 95, 96, 99 (panic)
zt = ZONE TYPE
00 = Not Used
01 = Entry/Exit #1
02 = Entry/Exit #2
03 = Perimeter
04 = Interior Follower
05 = Trouble Day/Alarm Night
06 = 24 Hr Silent
07 = 24 Hr Audible
08 = 24 Hr Aux
09 = Fire without Verification
10 = Interior with Delay
14 = Carbon Monoxide
20 = Arm–Stay
21 = Arm–Away
22 = Disarm
23 = No Alarm Response
24 = Silent Burglary
rc = ALARM REPORT CODE Two Hex Digits. For each Hex Digit, enter: 00–09 for 0–9, 10 for A, 11 for B,12 for C, 13 for D,
14 for E, 15 for F. If "00" is entered as the first digit, there will be no report for that zone.
For Contact ID reporting, this is enabling code only. Enter any hex digit (other than 00) in the
first pair of boxes. The second pair of boxes is ignored.
i = INPUT TYPE Enter 3 for RF: Supervised RF
Enter 4 for UR: Unsupervised RF
Enter 5 for BR: Button Type RF
l = LOOP NUMBER Used with 5800 RF Loop Input Devices. Record transmitter loop number. Entries are 1-4,
depending on device being used. Refer to the transmitter’s instructions for appropriate loop
numbers.
Zones 2-25 should be assigned as Input Type 3 or 4 and
Zones 26-41 should be assigned as Type 5 only.

- 20 -
POWERLINE CARRIER DEVICES WORKSHEET FOR ✻
✻✻
✻80, and ✻
✻✻
✻81.
Applicable only if Powerline Carrier Devices are to be used, or chime-by-zone feature is used.
ULPowerline Carrier Devices have not been evaluated by UL.
✱80 OUTPUT DEVICES
Fill in the required data on the worksheet on below and follow the programming procedure in the Installation
Instructions as you enter the data during the displays and prompts that appear in sequence.
Note:Field ✱25 must be programmed with a House Code.
START
either or both
STOP
either or both
DEVICE
NUMBER
ACTION
(aa)
EVENT ZONE
TYPE (et) LIST (zl)
ZONE TYPE
SYS OPERATION (zt)
RESTORE
ZONE LIST (zl)
ZONE TYPE/
SYS OPERATION (zt)
P.L.C.D.*† 01
P.L.C.D.*† 02
P.L.C.D.*† 03
P.L.C.D.* 04
P.L.C.D.* †05
P.L.C.D.*† 06
SYS. P.L.C.D.*† 07
SYS. P.L.C.D.*† 08 [2] [33] [36]
E-mail Event Trigger 09
E-mail Event Trigger 10
E-mail Event Trigger 11
E-mail Event Trigger 12
E-mail Event Trigger 13
E-mail Event Trigger 14
E-mail Event Trigger 15
E-mail Event Trigger 16 [2] [33] [36]
* P.L.C.D. = Powerline Carrier Device (X10).
Where: A = DEVICE ACTION 0 = No Response; 1 = Close for 2 sec; 2 = Close and stay closed; 3 = Pulse on and off.
ET = EVENT TYPE 0 = Not used; 1 = Alarm; 2 = Fault; 3 = Trouble.
Z L = ZONE LIST 1, 2, or 3 (from Field ✱81) or 0 = Not Used.
"START" ZONE LIST: Upon alarm, fault, or trouble of ANY zone on this list, device action will START.
"STOP" RESTORE of ZONE LIST: Upon restore of ALL zones on this list, device action will STOP.
It need not be same list as used for START.
Note: Do not assign zones with types 20, 21, or 22 to a zone list.3
ZT = ZONE TYPE/
SYSTEM OPERATION Choices for Zone Types are:
00 = Not Used 07 = 24 Hour Audible
01 = Entry/Exit#1 08 = 24 Hour Aux
02 = Entry/Exit#2 09 = Fire Zone without Verification
03 = Perimeter 10 = Interior with Delay
04 = Interior Follower 14 = Carbon Monoxide
05 = Trouble Day/Alarm Night 24= Silent Burglary
06 = 24 Hour Silent
Choices for System Operation are:
20 = Arming–Stay 33 = Any Alarm* 42 = System Battery Low
21 = Arming–Away 36 = At Bell Timeout** 43 = Communication Failure
22 = Disarming (Code + OFF) 38 = Chime 52 = Kissoff
31 = End of Exit Time 39 = Any Fire Alarm 58 = Duress
32 = Start of Entry Time 40 = Bypassing
* Except ZT=08, 09, 14 or 16.
** Or at Disarming, whichever occurs earlier.
Note: In normal operation mode:
For Devices 1-6: For Devices 7 and 8: N = device (unit) number
Function + Lights On + N Code + Function + 4 + N (Entry starts Device N)
Function + Lights Off + N Code + Function + 7 + N (Entry stops Device N)
Note: Any zone in "ZT" going into alarm, fault, or trouble will activate device with the
exception of 01, 02 when the system is in alarm. Any zone that restores will
sto
p
device action.
Other manuals for APX32EN
2
Table of contents
Other Apxalarm Security System manuals