Aquacal DIG-220 User manual

1
Model: DIG-220
INSTALLER: THIS DOCUMENT IS PURCHASER’SPROPERTY AND IS TO REMAIN WITH THE EQUIPMENT OWNER
18500-DIG R13
Owner’s
Manual
Salt Chlorine Generator
IMPORTANT !
Swimming Pool & Spa Purification System
Read This Manual Before
Installing or Operating
Installation and Operation
This manual covers the installation and operation of
the DIG-220 Chlorine Generator with associated
manifold assembly.
3/9/17
PoolPilot®
PN: #

2
TABLE OF CONTENTS
CONTACTING THE FACTORY..................................................................................................... 4-5
SAFETY INFORMATION ............................................................................................................... 5-6
OWNER QUICK START & RUN ................................................................................................. 7-10
SPECIFICATIONS............................................................................................................................11
Input Power ......................................................................................................................................... 11
Output Power ...................................................................................................................................... 11
Optional Internal Pump Relay Ratings ................................................................................................. 11
Chlorine Output ................................................................................................................................... 11
Manifold Flow Requirements................................................................................................................ 11
Agency Approvals ................................................................................................................................11
INSTALLATION ...........................................................................................................................11-16
Before Installing: .................................................................................................................................. 11
What is included: ................................................................................................................................ 11
What is not included: .......................................................................................................................... 11
Required Components for a complete system:.................................................................................... 12
Installation Steps: ................................................................................................................................ 12
Plumbing the Manifold Assembly ............................................................................................ 12
Flow Rates Within Normal Range: ................................................................................... 13
Flow Rates Exceeding 100-gpm (379 L/m):...................................................................... 13
Mounting the Control Unit:.............................................................................................................. 13-14
Electrical Connections ................................................................................................................... 14-16
Grounding and Bonding .......................................................................................................... 14
Determine Incoming Voltage Requirements ............................................................................. 14
For incoming voltage of 230 Vac: ................................................................................ 14
For incoming voltage of 115 Vac: ................................................................................ 15
Connecting DIG-220 to External Equipment ........................................................................... 15
Connecting DIG-220 to External Time Clock: ................................................................... 15
Connecting DIG-220 to Control a One-Speed Pump......................................................... 16
Connecting DIG-220 to Control a Two-Speed Pump ......................................................... 16
Cell and Tri-Sensor Cord Connections.............................................................................. 16
PREPARING THE POOL WATER ...................................................................................................17
Steps to Prepare Water: ...................................................................................................................... 17
Calculating Pool Volume: .................................................................................................................... 17
Adding Salt: ........................................................................................................................................ 17
Type of Salt to Add... .............................................................................................................. 17
Determine Amount of Salt Required (and salt level to maintain)... .......................................... 17
How to add the salt (or remove it if too much)... ..................................................................... 17
MENU OVERVIEW ...........................................................................................................................18
ACCESS TO PROGRAMMING................................................................................................. 18-23
Control Panel: ..................................................................................................................................... 18
Operation of Buttons: ..................................................................................................................... 18-19
Menu Button ........................................................................................................................... 18
Select Button ......................................................................................................................... 18
Pump Button ..................................................................................................................... 18-19
Basic Operational Programming: ......................................................................................................... 19
Adjusting the Purifier Output % ... .......................................................................................... 19
Boost or SuperBoost... ........................................................................................................... 19
Purifier Mode .......................................................................................................................... 19
Purifier % Adjustment Procedure: ..................................................................................... 19

3
Menus ............................................................................................................................................ 20-23
Test Pool Pilot ........................................................................................................................ 20
View Setup ............................................................................................................................. 20
Owner Options: ................................................................................................................. 20-21
Select Language: ............................................................................................................. 20
Select Units: .................................................................................................................... 21
Temperature Units ............................................................................................................ 21
12/24 Hour Clock: ............................................................................................................ 21
Set Time of Day: .............................................................................................................. 21
Maintenance Menu: ........................................................................................................... 21-22
Test Pool Pilot: ................................................................................................................21
Set Time of Day: .............................................................................................................. 21
Force Reverse .................................................................................................................. 21
Set Reverse Time: ............................................................................................................ 21
Replace Cell .................................................................................................................... 22
Calibrating Temperature: .................................................................................................. 22
Calibrating Salt: ...............................................................................................................22
Installer Menu: ................................................................................................................... 22-23
Select Language: ............................................................................................................. 22
Select Units: .................................................................................................................... 22
Temperature Units ............................................................................................................ 22
12/24 Hour Clock: ............................................................................................................ 22
Pool Volume .................................................................................................................... 22
Cell Type .......................................................................................................................... 23
Cell Power ....................................................................................................................... 23
Pump Control ................................................................................................................... 23
Set Time of Day ............................................................................................................... 23
Select Remote: ................................................................................................................ 23
Select Minerals: ............................................................................................................... 23
Pump Program 1 and 2: ................................................................................................... 23
Enable Demo: .................................................................................................................. 23
REFERENCE SECTION............................................................................................................ 24-26
Salt Addition Chart: ............................................................................................................................. 24
Basic Water Chemistry: ................................................................................................................. 24-25
Using the Saturation Index (SI):...................................................................................................... 25-26
Part Numbers: ..................................................................................................................................... 26
MAINTENANCE ......................................................................................................................... 27-30
Fuse Location and Ratings:................................................................................................................. 27
Removing \ Inspecting \ Cleaning the Tri-Sensor............................................................................. 27-28
Testing the Flow Switch, Cleaning the Filter Screen,Cleaning the Bypass Valve ............................... 28
Servicing the Pool Pilot Cell .......................................................................................................... 28-29
Visual Inspection of the Pool Pilot Cell.................................................................................. 29
Manual Cleaning of the Pool Pilot Cell... ................................................................................ 29
Installing a Pool Pilot Cell....................................................................................................... 29
Winterizing .......................................................................................................................................... 30
Freeze protection program and its limits ................................................................................. 30
Spring Start-Up .................................................................................................................................... 30
TROUBLESHOOTING.............................................................................................................. 31-32
APPENDIX........................................................................................................................................33
Delaration of Conformity ...................................................................................................................... 33
FCC Compliance ................................................................................................................................. 33
TABLE OF CONTENTS

4
CONTACT INFORMATION
What We Need to Know If You need To Contact Us...
If you should need to call AquaCal AutoPilot, Inc. for questions, service, or parts, please have the following
information ready:
Dear Owner:
Congratulations on your wise decision to make an AquaCal AutoPilot chlorinator a part of your home. Just
add salt, and let your DIG-220 produce the chlorine to sanitize your pool or spa.
A wonderful thing happens to the salt after it is turned into chlorine and
does the work of purifying the water—it turns back into salt and the process
begins all over again.
s,Plus, the salt, being at a much lower level than even contact lens solution
means no “salty” taste to the water for the average bather. And, no
more odors from harsh chlorine products.
No longer experience the discomfort and inconvenience of harsh chemical
reactions like red eyes, green hair, itchy skin, or faded swim wear. Our
product makes it easy to retain a constant level of chlorine, purifying the water while making it soft and silky
to the touch.
“You can rest assured knowing
your new chlorinator is of the
highest quality and effciency, and
is designed and built to provide
years of trouble-free operation.”
INSTALLER - Please record the following information prior to installation:
Control Unit
Date of Installation:
Control Unit
Installer:
Pool Pilot Cell
Serial Number:
Serial Number:Model Type:
Pool Pilot Cell
Model Type:
Pool Volume in Gallons:
DIG-220
1
Use the view set up menu, and test pool pilot menu and write down the results
(see programming on page-20)
3“VIEW SETUP” and “TEST POOL PILOT” information
CHEMISTRY: (from a current water sample)
Salt Level:
Stabilizer (CYA):
pH:
Total Alkalinity:
Calcium Hardness:
Approximate Water Temperature
of pool:
Total Chlorine (TC):
Combined Chlorine (CC):
Free Chlorine (FC):
2NOTE RECOMMENDED LEVELS ON PAGE-24 & 25.

5
Your installer can be one source of service, or AquaCal AutoPilot Customer Support personnel stand
ready to assist you at: (727) 823-5642. For questions concerning installation, operation, service and upkeep,
please contact your installer or AquaCal AutoPilot Customer Support. Warranties may be voided if the
chlorinator has been installed, operated, maintained, or repaired improperly.
In addition to voiding the manufacturer’s warranty... unapproved installation methods, modifications, poor
or incorrect maintenance, service by unqualified personnel, or improper use of the chlorinator may result
in personal injury and/or property damage. For personal safety, and to avoid damage to equipment, follow
all safety instructions displayed on the equipment and within this manual.
SAFETY INFORMATION
Throughout this manual the following two safety signals are placed where particular attention is required.
Please note "WARNING" relates to personal safety, while "NOTICE" signals promote avoiding damage to
equipment.
Safety Signals
If you have questions, please refer to our web site at www.autopilot.com for the latest manual
revisions additional information, and helpful service advice.
You can also call us at: (7) -. We are here to serve you from 8:00 a.m. to 5:00 p.m. Eastern
time, Monday through Friday. If calling after hours, our voice mail system will handle your call. Please
be sure to leave your name, a complete address, and your telephone number
Or, if you prefer, you may FAX us at: (877) 408-8142. Be certain to provide your full address and
a daytime telephone number.
To Contact the Factory...
Used and maintained properly, your chlorine generator will provide year-upon-year of safe and economical
service. However, as with any mechanical or electrical device, to get the most from your equipment— while
insuring personal safety for you and others—certain operational and maintenance factors must be observed.
Likewise, excepting a few minor owner-capable maintenance items (explained later in this manual), repair
and service of your chlorinator must be performed only by experienced service personnel. Should you suspect
your chlorine generator is not performing properly, refer to the section in this manual entitled:
"Troubleshooting," to determine if a call for service is required.
Failure to heed the following may result in equipment damage.
NOTICE idA “Notice” signal appears in this manual where special care is required to avo
equipment damage. ( Specific instructions will appear in this box.)
A “Warning” signal appears in this manual where special attention is required for
personal safety. (Specific instructions will appear in this box.)
Failure to heed the following may result in permanent injury or death.
WARNING
Follow all National Electric Codes (NEC) unless State or Local guidelines supersede. When installing
and using your DIG-220, basic safety precautions must always be followed, including the following:
CONTACT INFORMATION
(CONTINUED)

6
SAFETY INFORMATION
(CONTINUED)
READ AND FOLLOW ALL INSTRUCTIONS
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
All DIG-220 models:
Installation of fixed wiring DIG-220 (115/230Vac, 50/60 Hz):
A disconnect device such as a time clock relay or circuit breaker from the power
source, with a contact separation of at least 0.12” (3mm) in all poles, must be
incorporated in the fixed wiring for permanently wired units.
To avoid personal injury
WARNING
Risk of Electrical Shock.
WARNING Ensure that the electrical panel or filter pump circuit is turned OFF prior to
installation or servicing inside any AutoPilot unit.
Mount the Control Box to ensure the least amount of direct exposure to rain,
garden sprinkler water, direct sunlight, or any corrosive environment.
Risk of Electrical Shock.
WARNING
Install the Control Box at least 10’ (3 m) for 115 Vac Units, from the inside
wall of the pool or spa. Use 5’ (1.5 m) minimum distance for 230 Vac Units.
Risk of Electrical Shock.
WARNING
Do not permit children to use this product unless they are closely supervised
at all times. Children should not use spas, hot tubs, or pools without
permanent adult supervision.
Failure to heed the following may result in permanent injury or death.
WARNING
All field-installed metal components such as rails, ladders, drains, or similar
hardware within 10’(3 m) of the spa or hot tub shall be bonded to the equipment
grounding bus with copper conductors not smaller than No.8 AWG (8.4 mm²).
To avoid personal injury
WARNING
Use the bonding lug provided on the outside of your DIG-220, to connect a min-
imum No. 8 AWG (8.4 mm²) solid copper bonding conductor between the DIG-
220 and any metal equipment, metal enclosures of electrical equipment, metal
water pipe or conduit within 5’ (1.5 m) of the DIG-220.
To avoid personal injury
WARNING
A ground terminal is located on the inside of your DIG-220. To reduce the risk
of electrical shock, this terminal must be connected to the grounding means
provided in the electrical supply panel. A continuous copper wire is to be
used equivalently sized to the circuit conductors supplying your DIG-220.
To avoid personal injury
WARNING
The input voltage to the DIG-220 must match the 115/230Vac jumper
terminals on the Circuit board, marked “TRANSFORMER PRIMARY” (shown
on Page-14 & 15).
To avoid personal injury
WARNING
The proper residual chlorine level and water chemistry must be maintained.
To avoid personal injury
WARNING
The Control Box is provided with (3) knock out holes for electrical conduit con-
nections and has (1) 1/2” Liquidtite fitting already attached. 1/2” nonmetallic flex
conduit is recommended.
To avoid personal injury
WARNING

7
The Pool Pilot DIG-220 is a salt chlorination system designed for pool or spa water purification. Although
the DIG-220 is easy to use, it is important to read through the entire manual before attempting to
operate the system.
How Your Chlorine Generator Works
The system requires a low concentration of dissolved salt (sodium chloride) in the water. The salt concentration
level is normally maintained below the taste threshold. The DIG-220 automatically converts the salt into chlorin
which your pool/spa requires to remain sanitized and algae free. The chlorine reverts back to salt after treating
the water.
Since the salt is constantly recycled, there is minimal loss during a swimming season.
However, salt can be lost due to filter backwashing, rain water over flow, leaks, or bather
splashing/carry out... but not through evaporation.
The amount of chlorine required for proper sanitization will vary based on the pool
size and various factors such as water temperature, bather load, exposure to direct
sunlight, and special water features.
The water circulation pump must be operating for your DIG-220 to produce chlorine,
so run time is one of several key components to maintaining the proper sanitizer levels.
Most installations require a minimum of eight (8) hours-per-day pump run time
to properly filter and sanitize the water.
Control Overview
Following is a brief explanation of owner / operator control options. For full features of the Owner Options
Menu, please see page-20 & 21. The MENU button is pressed to obtain access to the Owner Options Menu.
Please Note: This quick start section assumes the installer has already programmed the system for
specific site parameters, has established proper water balance, and has pretreated water to 1 - 3 ppm
chlorine.
Attention Owner: Should Celsius vs. Fahrenheit, choice of language, or other owner options require
modification, please refer to Operation of Buttons located on page-18 and Owner Options on page-20
& 21.
Use the UP and DOWN arrows to control the purifier output
level, then press the SELECT button to save the value chosen.
With a properly prepared pool, the recommended starting output
level is 50%.
Up and Down Arrows:
Please Note: The optimum output setting will vary based upon pool size, location, exposure to sunlight,
number of users, vegetation around the pool, water balance practices, and pump run time. Your
installer should have already taken these factors into consideration when performing installation
programming. Therefore, your adjustments, at this point, should be relatively minor.
n
After the purifier output level is “tuned in,” the unit will automatically make fine output adjustments as the
water temperature fluctuates. This patented temperature compensation feature will adjust output depending
on water temperature. See page-10 & 30 for more information concerning the temperature compensatio
feature.
OWNER QUICK START & RUN
e,
Upon initial start-up, check sanitizer level every few days
and make small output level adjustments as necessary to
maintain 1-3 ppm free chlorine levels.
Your DIG-220 does not directly measure or regulate the sanitizer
levels in your pool. Rather, the owner / operator will need to
periodically test the water to determine the current chlorine
level, and adjust the output setting as needed. FIG-1
Purifier
12:00 pm 80F
100%

8
OWNER QUICK START & RUN
The Boost Button:
The BOOST button increases output to 100%. Use this feature
when a heavier then normal bather load is anticipated.
Press BOOST once........................= 24-Hour Boost
Press and hold BOOST for 8 seconds= 72-Hour Boost
Press BOOST a second time............= Deactivate Boost
Menu and Select Button:
Allows access to the “Test,” “View Setup,” “Owner Options,”
“Maintenance,” and “Installer” menus. The SELECT button
allows the operator to choose program menu options. The
owner / operator should not normally need to access these
features on a regular basis. Consult “Programming” section
or contact factory customer support for additional information.
The CHECK SYSTEM light will flash to warn the DIG-220
may need attention. A warning message will also be.
displayed. Unless deemed a normal condition, per
below, see troubleshooting section on page 21.
Check System Light:
Flashes if the water flow is insufficient under the
following circumstances:
- When DIG-220 is not set up to control the water
pump (uses an External Timer or Remote Runs
Pump), and DIG-220 is wired to the line side
(hot all the time).
- If the DIG-220 controls the pump (One-speed Pump),
the light will not flash when the pump is off.
Flashes when salt is low
Flashes when water temperature exceeds 125° F, or
drops below 10° F
Flashes when “PUMP OFF FOR SERVICE”
Purifier Output level ................................................. :
Water Temperature .................................................. :
Cell Status ............................................................... :
Check System Light ................................................ :
Normal Display:
In 1% increments, from 0% to 100%
In Fahrenheit or Celsius
ON
OFF
FIG-2
FIG-3
FIG-4
Purifier
12:00 pm 80F
100%
Purifier
12:00 pm 80F
100%
Purifier
12:00 pm 80F
100%
After 30-minutes of inactivity, the display will go to a “walking dot” screen saver model. All functions
such as chlorine generation, reverse, boost, etc., will continue in the background. Pressing any key
will call up the normal informational display.

9
Winterizing
Freeze Protection & Extended Shut Down:
Information Critical to the Survival of Your
DIG- 220 Follows...
In areas where freezing conditions are a rare occurrence, allow the filtration system to run continuously
throughout the freeze period. Typically, during light freeze conditions, circulating (moving) water will not
freeze.
In areas where freezing conditions are prevalent and sustained, the DIG-220 MUST be winterized;
please refer to winterizing instructions on page-30.
OWNER QUICK START & RUN
(CONTINUED)
Proper water balance is critical to the operation of your DIG-220.
Conditions such as high pH levels, low cyanuric acid (stabilizer ) levels, or other factors causing unbalanced
water, will mask the sanitizer production of your DIG-220. Please note the following recommended water
chemistry parameters:
See “Basic Water Chemistry,” on page-24 & 25, and “Using the Saturation Index,” on page-25 & 26 for
further information concerning pool/spa water chemistry maintenance requirements.
PH........................................:
Calcium Hardness....................:
Total Alkalinity.........................:
Salt.......................................:
Cyanuric Acid (stabilizer )..........:
Chlorine.................................:
Should you have additional water balance or chemistry questions, please refer to the Troubleshooting
section in the back of this manual.
Water Balance & Chemistry Recommendations
)
7.2 – 7.8
200 – 400 ppm
80 – 100 ppm
2500 – 4500 ppm (ideal 3000 ppm
60 – 80 ppm
1 – 3 ppm
Failure to heed the following may result in equipment damage.
NOTICE Special measures are required in the event of freezing conditions.
Your DIG-220 may be damaged if measures are not taken in advance of freez-
ing conditions. Equipment damage due to freezing conditions is NOT covered
under the equipment warranty.
Important !!!

10
OWNER QUICK START & RUN
(CONTINUED)
s
The Tri-sensor temperature sensor works in conjunction with the purifier % feature to automatically adjust
chlorine output based upon changes in water temperature. The automatic compensation feature operate
between 55°F and 95°F (13°C - 35°C).
As water temperature falls below 65°F (18°C), the controller will activate a high purifier percent lockout, and
may not allow purifier adjustments up to 100%. This feature prevents the controller from overworking the
cell under colder temperatures, thus preventing premature cell wear.
At 55°F (13°C) or colder water temperatures, the controller will adjust to a fixed 1% output (and will not allow
the percentage to be raised manually), thus preventing over-chlorination and premature cell failure.
As the water temperature rises above set point, the controller will increase output up to 100%, thus preventing
under-chlorination during warmer water temperatures.
Patented Temperature Compensation
Water Manifold Assembly
The DIG-220 may be operated with the Patented (Automatic-Flow Bypass) Manifold using the following
Pool Pilot Cells: PPC1, PPC3, PPC4, or PPC5. Please see Installer section: “Basic System Overview,”
for details and diagrams.
Important Features
Patented temperature compensation for chlorine output control...
Programmable microprocessor control...
Multi-language digital display (English, Spanish, Italian, & French)...
Digitally controlled power to the Pool Pilot Cell..
Tri-sensor circuitry to monitor water flow, water temperature, and salt level. Calculates and provides
recommended salt addition amounts required to maintain the recommended 3000 ppm (3.0 g/l) or
4500 ppm for maximum chlorine production) salt concentration level.
di-
Freeze Protection: allows the water pump, if wired and programmed for One-speed pump, to
override the program cycle and run continually (30-minute minimum) when the water temperature
falls below 40° F (4.4° C). This helps to prevent damage to the plumbing during light freeze con
tions.
Optional Internal relay for controlling an external single-speed or two-speed water pump.
On-board diagnostic and test programs.
Lithium battery back up for saving program settings.
ORP dry contact interface for connection to an external ORP controller.
Opitional Electronic controller interface for Jandy (Versions I,K, and newer), Polaris EOS, or
Pentair IntelliTouch controllers.
®
®
Get the Most from Your Purchase!
To become fully-familiar with all the features, the safe operation, and the care of
your new chlorinator, please read through the entire remainder of this manual.
®

11
SPECIFICATIONS
230 Vac (1.5 AC amps) 50/60 Hz (default from factory)
115 Vac (3 AC amps) (easily converted in the field, refer to page-14 & 15 for instructions
on conversion)
@ Cell Power 3 (8 amps DC) (set at 100% - 24 hour operation)
2.62 lbs/day (1.19 kg/day)
1.92 lbs/day (0.88 kg/day)
1.56 lbs/day (0.71 kg/day)
PPC5
PPC4
PPC3
PPC1 1.28 lbs/day (0.58 kg/day)
Cell Power 1 (5* DC amps)
Cell Power 2 (6.5* DC amps)
Cell Power 3 (8* DC amps)
* Indicates nominal amperage output. The dual axis controller
will slightly vary the amps to optimize the power to the cell.
Input Power: Output Power:
Chlorine Output:
Voltage Input ................... Amps / HP max
115 Vac ............................ 30 amps / 1 HP
230 Vac ............................ 30 amps / 2.5 HP
Optional Internal Pump Relay Ratings:
Maximum Operating Pressure: 50 psi
Maximum Flow Rate: 100 gpm
Minimum Flow Rate: 20 gpm
Manifold Flow Requirements:
A Note Concerning Terminology:
Throughout this manual, the portion of the system which mounts to the wall (and powers the cell) may be referred to as the DIG-220 or unit. In addition, when “pool” is
referred to in the absence of the word “spa,” it should be assumed “spa” is inferred (should a spa be present in the installation).
Agency Approvals:
ETL tested to confirm to UL1081 specification. Standard for Safety for Swimming Pool
Pumps, Filters and Chlorinators.
NSF/ANSI 50 ............................. Circulation System components and related materials
for swimming pools, spas/hot tubs.
CAN/CSA-E335-1 ...................... General Requirements For Safety of Household and
Similar Electrical Appliances.
See appendix on page-33 for CE Declaration of
Conformity
Before Installing:
Installer... Please record the following information on page-4 of this manual:
Date of Installation Pool Pilot Cell Type Control Unit Model
Pool Pilot Cell Serial Number Control Unit Serial Number
For questions concerning installation or operation of this equipment:
Visit www.autopilot.com for latest manual revisions and helpful troubleshooting tips.
You can also contact AquaCal AutoPilot, Inc. customer support as specified on page-5 of this manual.
Determine origination point for control center power feed:
Directly from a circuit breaker...
From an external timer, or
From an electronic controller
Determine everything needed for installation is on hand.
Determine where the Manifold Assembly will be plumbed.
Identify a suitable mounting location for the DIG-220 within proper cord length to the manifold. If possible, avoid location with direct sunlight, sprinklers, etc.
Plan runs for Pool Pilot Cell and Tri-sensor Cables. (Cables are 12’ or 3.65M)
Plan wire runs and wiring connections for source power.
DIG-220 is to be wired to the same location as the circulation pump; the unit is activated only when the
circulation pump is energized.
Circuit breaker is used to power the DIG-220 and circulation pump.
Determine whether the input voltage for the DIG-220 will be 115-Vac or 230-Vac
Determine whether the DIG-220 will be used to control a single speed or a two speed pump. (Optional pump relay must be installed)
Determine whether the DIG-220 will be controlled by an ORP controller.
Determine whether the DIG-220 will be controlled by an Electronic Controller System.
What is included:
Although the manifold assembly may be sold separately, both a manifold and a Digital Control Center are required for a complete installation. The standard cell & manifold assembly
is available with the following cells: PPC1, PPC3, PPC4 and PPC5. Before attempting the installation, verify the following items have been included with the Control Center:
FIG-5
Quantity Item Description
1
4
1
1
DIG-220 Control Center / Power Supply
Screws and Screw Anchors
Drilling Template
Manual
16 amp fuse, and wire jumper kit
1Cell Cable
68mm x 2” metric adaptors (#19059)
* European systems only
*
2
CHECK
SYSTEM
BOOST MENU SELECT PUMP
Screws and Anchors
Power Supply
Cell Cable
What is not included:
Power service electrical wire.
½" liquid tight (nonmetallic flex) conduit.
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this
device must accept any interference received, including interference that may cause undesired operation.

12
When the water flow reaches a minimum flow rate of 20-gpm (76 L/m), the flow paddle magnet closes a micro-
switch monitored by the Control Unit.
The Control Unit uses the Tri-sensor dedicated salt sensor blades to measure the level of salt in the water.
The Control Unit uses the Tri-sensor temperature sensor to determine water temperature. This measurement
is required for the Patented Automatic Temperature Compensation feature to automatically adjust chlorine outpu t
as water temperature varies.
Less chlorine is needed in cold water, so chlorine output is automatically reduced as water temperature drops
(avoiding excess chlorine production). Conversely, more chlorine is needed in warmer water, and production
is automatically adjusted higher as water temperatures increase.
Note: The use of high strength magnet devices in the close proximity of the Tri-sensor can cause the flow switch
to function incorrectly.
The Bypass Valve allows the water flow rate to be slowed and optimized through the Pool Pilot Cell, while
permitting the pump to continue to circulate water to-and from the pool/spa at full flow rates. The slowed water
flow through the Pool Pilot Cell results in a more efficient "Super-Chlorination” effect, resulting in improved
overall sanitization.
The Pool Pilot Cell receives power from the DIG-220 and converts the salt contained in the water to chlorine.
Required Components for a complete system:
Automatic-Flow Bypass Manifold Assembly:
The manifold is connected into the plumbing after all other equipment. Water from the pool/spa is moved though the manifold by the circulation pump. The manifold's four
key components are the: Strainer Screen, Tri-sensor, Pool Pilot Cell, and Bypass Flow Valve (See FIG-7).
The Strainer Screen prevents debris in the water from entering the Tri-sensor or Pool Pilot Cell, and
require periodic inspection and cleaning.
The Tri-sensor provides data (from electronic sensors) to the DIG-220 for monitoring water flow, water temperature,
and salt concentration level. The DIG-220 uses this data to determine if conditions are safe for the Pool Pilot
Cell to operate; the signal read from the temperature sensor allows the automatic temperature compensation
feature to function (See FIG-8).
INSTALLATION
Installation Steps:
Details on each step of the installation process are presented on the following pages:
1. Plumbing the Manifold Assembly (page-12 & 13)
2. Mounting the Control Unit (page-13 & 14)
3. Electrical Connections
a. Grounding and Bonding (page-14)
b. Determine Incoming Voltage Requirements (page-14 & 15)
c. Connecting DIG-220 to External Equipment (page-15 & 16)
d. ORP Connection (page-16)
e. Cell cable (page-16)
f. Tri-sensor cable (page-16)
4. Preparing the Water (page-17)
5. Programming and Setup for Site Parameters. (page-18, 22, & 23 )
FIG-8
FLOW PADDLE
Tri-sensor Assembly
TEMPERATURE
TRI-SENSOR O-RING
DIRECTION OF
FLOW
SALT SENSOR
Plumbing the Manifold Assembly:
The Manifold Assembly is 2" Schedule 40 PVC, and is typically plumbed into the pool return line; and, if applicable, after the heater and spa return diverter valve. Installing the
manifold in the spa return line, will cause an excessive amount of chlorine to be introduced into the spa, while the spa is in use and must be avoided.
STEP-1: Select the location for installing the manifold:
It is recommended the manifold be installed prior to the installation of the Control Unit. The Control Unit must be installed close enough to the Manifold
Assembly to allow the Tri-sensor and Cell cables sufficient slack to enable component service and maintenance. The cables are 12’ long.
The assembly must be installed in a vertical orientation as illustrated in the diagram on page-13 (fig 9). This orientation prevents hazardous gas buildup in the
system, should the flow switch fail to detect insufficient flow. WARNING! Place manifold in vertical position ONLY.
The direction of the water flow through the manifold must be as indicated for the system to operate properly.
For a Pool/Spa combination, the manifod must be located as the last component in the POOL RETURN LINE (to avoid over-sanitization of the spa).
Continued Next Page...
FIG-7
Tri-sensor
Pool Pilot Cell
Strainer Screen
Bypass Flow Valve
(INSIDE)

13
INSTALLATION (CONTINUED)
Note: Insure “proper” flow rates. some two-speed
pumps may provide insufficient flow on low speed.
Flow Rates Within Normal Range:
The manifold can be directly plumbed into the system as shown.
If the flow rate for the system is less than 20-gpm (76 L/m), a larger pump must be installed (or steps taken to improve flow rate).
*One set of 68 mm x 2” metric adapters (#19059) are
included with European Systems.
For other plumbing configurations, please contact the
factory for assistance.
Pump Filter Manifold Assembly
To Pool
Return
FIG-9
Flow Rates Exceeding 100-gpm (379 L/m):
NOTE: 5-lb spring bypass check valve must be plumbed
in parallel with the manifold.
STEP-3: Tighten the unions by hand for a watertight seal. The manifold will accept a PPC1, PPC3, PPC4 or PPC5 cell; use of any other cell may damage the power supply
and the equipment warranty will be voided .
STEP-4: Follow the procedures outlined in the maintenance section on page-28 to verify proper operation of the Tri-sensor Flow Switch protection.
STEP-2: Install the cell into the manifold with the cell cable terminals at the bottom of the manifold as illustrated in picture (fig 10).
NOTICE If the cell is improperly installed upside down, water from rain or other
sources may enter the cable contacts and result in failure of the Pool Pilot
Cell. This would void the warrantly.
Failure to heed the following may result in equipment damage.
NOTICE It is extremely important to verify the safe and proper operation of the
Tri-sensor’s Flow Switch protection device before operating equipment.
Failure to heed the following may result in equipment damage.
NOTICE To avoid over-saturation conditions of your spa, it is suggested to locate the
cell downstream of all other equipment and on the pool return line only. For
applications other than as recommended, contact the factory.
Failure to heed the following may result in equipment damage.
Plumbing the Manifold Assembly:
FROM PUMP TO
WARNING!
MANIFOLD VERTICAL
Mounting the Control Unit:
Your DIG-220 is suitable for indoor or outdoor mounting. If it is connected to 230 Vac, it must be installed at least 5’ (1.5m) horizontal distance from the pool or spa wall (or
more if local codes require). It it is connected to 115 Vac, it must be installed at least 10’ (3m) horizontal distance from the pool or spa.
.The DIG0-220 is designed to mount vertically on a flat surface with the wiring inputs facing downward. The enclosure is designed to allow heat to dissipate from inside the
box It is important not to block the top or bottom of the box. Do NOT mount the unit inside a panel or a tightly enclosed area without proper ventilation.
The cover of the DIG-220 is removed from the sides by four thumbscrews so it is advisable to leave adequate space on the sides for hand access to the thumbscrews.
When selecting a location for installing the DIG-220, please note that the Tri-sensor and Pool Pilot Cell cables are 12’ (3.6m) long.
Failure to heed the following may result in equipment damage.
NOTICE Verify that the selected DIG-220 location is close enough to the Manifold
Assembly so that the Tri-sensor and cell cables will have enough slack
for service or maintenance procedures.
Continued Next Page...
Plumbing the Manifold Assembly Continued:
FIG-10

14
Electrical Connections
The DIG-220 uses both high and low voltage connections. High voltage connections will be made for providing the direct input power. Additional high voltage connections
may be made to the filter pump from the DIG-220. Low voltage connections will be made to the Tri-sensor and Pool Pilot Cell. Additional low voltage connections are provided for
optional equipment such as a pH/ORP or electronic controller.
Grounding and Bonding
Connect a ground wire from the primary electrical input to the grounding lug located inside the box. Also ground any piece of high voltage equipment that is connected to the
DIG-220 relay. The DIG-220 must also be connected to the pool bonding system with an 8 AWG (6 AWG for Canada) wire. A lug is provided on the bottom exterior of the
unit.
AC LINE IN
The DIG-220 is pre-wired from the factory for 230 Vac using a 3-ampere fuse on the AC input. Short test leads are attached to the AC terminal strip and must be removed
prior to installation.
Determine Incoming Voltage Requirements
If 115 Vac input power is required, please follow steps in section entitled ”For incoming voltage of 115 Vac” on pages-15.
For incoming voltage of 230 Vac:
For incoming voltage of 230 Vac, confirm the “TRANSFORMER PRIMARY” is wired as indicated in FIG-11G.
INNER
TAB 7
TAB 9
230VAC
TAB 5
TAB 3
TAB 8
TAB 10
TAB 6
TAB 4
TRANS-
230 Vac
FACTORY
Terminal Strip FIG-11G
Insure the electrical panel or filter pump circuit breaker is turned OFF before wiring the DIG-220. Follow all state, local, NEC,
CEC codes as applicable. AquaCal AutoPilot recommends a licensed electrician or certified electrical contractor perform the
electrical connections.
Failure to heed the following may result in permanent injury or death.
WARNING
Mounting the Control Unit Continued:
Read the following section complety before proceeding (damage to wires and connectors may occur):
1. Level and tape the mounting template to the selected
mounting location. Mark the wall for the four (4)
mounting holes.
2. Plastic anchors and screws have been provided
for concrete or stucco walls. Drill and install
anchors and screws. Leave a 1/4” gap from the
wall when tightening the screws.
3. Loosen, but do not remove the four (4) thumbscrews
on the sides of the unit cover. Carefully slide off the
outer housing cover. Disconnnect the 3 plugs that
connect to the display (mounted inside the cover).
The display circuit board does not need to be removed
from the cover.
4. Safely set the cover aside.
8. See Electrical Connections on page-14, 15,
& 16 for terminal connections.
9. After terminal connections have been made,
reverse steps 3-8 to re-install the metal and external
covers.
Make sure to route and connect the 3 cables
through the side slot in the protective cover properly,
then replace the outer housing cover after first
connecting the 3 plugs (that were disconnected
in step 3).
5. Hang the DIG-220 on the four mounting screws.
Using a long shaft slotted screwdriver, tighten the
screws through the black plastic access holes.
6. For access to the electrical terminal strip, remove
the four screws and lift off the inner metal protective
cover.
7. Safely set the metal protective cover aside.
FIG-11F
FIG-11AFIG-11B
FIG-11CFIG-11D
FIG-11E
DRILL ¼” (6mm) DRILL ¼” (6mm)
TOP
TEMPLATE FOR DRILLING
POOL PI LOT SOF T TOUCH
& POOL PILOT DIGITAL
MOUNTING HOLE S.
DRILL 4 ¼” (6mm) H OLES FOR
WALL ANCHOR S WHERE SHOWN.
P/N 18550
BOTTOM
DRILL ¼” (6mm) DRILL ¼” (6mm)
F1
F2F3
INSTALLATION (CONTINUED)
InsideMetal
Cover

15
Step 1:
Remove the cover to access the inner control panel (see page-14 for more information). Rewire jumper as shown on this page on the circuit board marked
“TRANSFORMER PRIMARY” (using included jumpers).
For incoming voltage of 115 Vac:
For incoming voltage of 115 Vac, re-wire the existing jumper then add the jumper wire provided in the installation kit, as shown on the circuit board marked
“Transformer Primary”. (see fig 12)
INSTALLATION (CONTINUED)
Continued Next Page...
Step 2:
Replace the 3 amp fuse at the lower left corner of the inner control panel with a 6 amp fuse from the installation kit. See fuse location in the reference
section on page-27.
Connecting DIG-220 to External Equipment:
You must provide the appropriate gauge wire for complete installations to External Time Clock, One-Speed Pump, or Two-Speed Pump connections. Select the diagram that
matches your application . (Wiring diagram also located on inside of cover):
Connecting DIG-220 to External Time Clock:
FIG-12
TAB 7
TAB 9
230VAC
TAB 5
TAB 3
TAB 8
TAB 10
TAB 6
TAB 4
TRANSFORMER
PRIMARY
230 Vac
FACTORY SETTING
115 Vac
Converted Setting
TAB 7
TAB 9
115VAC
115VAC
TAB 5
TAB 3
TAB 8
TAB 10
TAB 6
TAB 4
INNER CONTROL PANEL
Terminal Strip
TRANSFORMER
PRIMARY
Terminal Strip
Wire the terminal strip as follows for appropriate equipment
#2
#3
#4
#5
#6
#1
INNER CONTROL PANEL
FIG-13
LINE-IN:
1. Remove and discard factory “test “ wires from terminals 1, 2, and ground.
2. Connect AC wires from Terminals #1, #2, and ground lug of the DIG-220
to the LOAD SIDE of the time clock, or the same location as the circulation
pump wires (pump connected to circuit breaker, time clock or electronic
controller).
#2
#3
#4
#5
#6
#1
Terminal Strip
(LOAD OUT) to
pump
Time Clock, Electronic Controller Relay or Circuit
Breaker
(LINE IN) from
Circuit Breaker
FIG-14

16
Connecting DIG-220 to Control a One-Speed Pump (with optional pump relay installed)
Connecting DIG-220 to Control a Two-Speed Pump (with optional pump relay installed)
1. Remove Factory #6 from the Terminal Strip.
2. Disconnect the other end of the wire from the relay bottom row and reconnect to
the relay top row right terminal. Connect the exposed end to the low speed input
of the pump.
LINE-OUT:
Low Speed Wire Common Wire
1. Remove the factory #4 wire from the relay.
2. Cut the end off and expose 1/2” of wire. Insert this bare end into the #6 terminal
which will create a jumper from #4 to #6.
1. Remove and discard factory “test “ wires from terminals 1, 2, and ground.
2. Cut Factory AC wires to 5”, strip and expose ½” of wire and connect from Terminal #1 to #3, and terminal #2 to #4.
3. Supply new AC LINE-IN wires from circuit breaker to Terminals #3 and #4. Ensure proper gauge wire is used to power the pump.
LINE-IN:
LINE-OUT:
Pump is connected to Terminals #5, #6 and Ground lug.
LINE-IN:
Follow the LINE-IN instructions for the above One-Speed instructions for Two-Speed Pump configuration.
Note: The pump is always powered and will run continuously on low speed when internal time clock program does not have the pump operating on high speed. A safety
shut off (wall switch) between the circuit breaker and control box is recommended when the circuit breaker cannot be accessed easily.
INSTALLATION (CONTINUED)
Cell and Tri-sensor Cord Connections
Failure to heed the following may result in equipment damage.
NOTICE Do not energize the ORP inputs! The ORP connections are dry contact inputs.
FIG-15
#2
#3
#4
#5
#6
#1
(LOAD OUT) to pump
(LINE IN) from GRND
L1/L
L2/N
GRND
L1/L
L2/N
FIG-16
#2
#3
#4
#5
#6
#1
(LINE IN) from
Circuit Breaker Ground
L2/N
L1/L - High speed L1/L Low
Speed
GRND
L1/L
L2/N
AC
Line
Plu
Plu
FIG-17
Cell Cord Connection: (2) banana connectors plug
into the (2) banana jacks on the bottom of the Power
Supply. Red plug provided with PPC1 and
PPC3 cells to cap off one hole. Either
right or left side hole can be plugged.
ORP Connection: When an ORP controller is used, the
purifier output will be automatically controlled. Adjust
the output level to 0% and connect the ORP controller
“dry contact” to the 2-pin connector on the Control Box
Base Plate. Although the output will displaying 0% output,
the DIG-220 will generate purifier as determined by the
ORP controller.
Tri-sensor Cord Connection: 12’ (3.4
m) cord connects to the Power Supply
with a 6 pin connector.
Bonding Lug
Conduit
Pump conduit plugs

17
Determine Amount of Salt Required (and salt level to maintain)...
•The ideal salt range is 3000 - 4500 PPM (2500 minimum) (2.5 - 3.5 g/l).
However, if so desired, the DIG-220 can operate with salt levels in excess of 35,000 PPM (35.0 g/l).
•Salt levels above 6000 PPM are not normally recommended, as corrosion issues may result. Salt levels below 2400 ppm will reduce the efficiency of the DIG-220 and will
result in low chlorine production.
•Extremely low salt levels (below 1900 ppm) will activate the low salt safety cut off, and will halt chlorine production until salt is replenished to proper levels.
•Once the DIG-220 is programmed to the pool water volume, the controller will automatically indicate how much salt is required to attain ideal salt levels. Additionally,
please see the reference table, on page-24 for information on amount of salt to be added relative to the gallons of water to be treated vs existing salt level.
Type of Salt to Add...
•It is important to use Sodium Chloride (NaCl) salt that is greater than 99% pure.
•Acceptable types of salt include granular food grade, water softener pellets, or solar salt flakes; these are usually available in 25-lb (13 kg) to 80-lb (36 kg) bags at local
pool or building supply outlets.
•Water softener and solar salt will have a slower dissolve rate than food grade salt. Rock salt and Granular Salt with Iodine or Rust preventatives should not be used, as
these mixtures contain high levels of impurities and will cause staining.
Note:
While not recommended, granular salt containing anti-caking additives such as YPS (Yellow Prussiate of Soda) or Sodium Ferrocyanide can be used. However, these mixtures—
if not mixed and dissolved immediately— may cause a localized tint to the water or yellow staining of the pool/spa finish.
Adding Salt:
FIRST... Test the water for current salt content !!!
PREPARING THE POOL WATER
Steps to Prepare Water:
1. Calculate Pool Volume:
See next section, below.
2. Adjust Water Chemistry:
(Via saturation index... consider pH, total alkalinity, hardness, and water temperature; also adjust stabilizer level). See Reference section, page-25 & 26.
3. Add Initial Chlorine Dosage:
Use liquid chlorine (sodium hypochlorite), or available types of tablet or granular chlorine as obtained from pool supply, to achieve 1-3 ppm free chlorine.
4. Add salt to water (test the water for salt level, first).
Adjust to 3000 ppm. See salt chart on page-24.
5. Enter pool volume Information into DIG-220:
See “Pool Volume” programming on page-22.
Calculating Pool Volume:
When properly sized to the site, the DIG-220 will meet the sanitizer “maintenance” requirements of the pool/spa. The DIG-220 is not designed to chlorine shock treat, or build
up a chlorine residual, when starting with a zero or very low chlorine level.
Before starting the DIG-220, the water must be properly balanced, and the chlorine level must be adjusted to between 1-to-3 ppm free chlorine. More on adjusting water
balance, and start-up chlorine levels, follows below.
Installer Please Note:
Liters (pool size measured in meters)
= Length x Width x Average Depth x 1000
= Diameter x Diameter x Average Depth x 785
= Length x Width x Average Depth x 785
Rectangular
Round
Oval
Rectangular
Round
Oval
Gallons (pool size measured in feet)
= Length x Width x Average Depth x 7.5
= Diameter x Diameter x Average Depth x 5.9
= Length x Width x Average Depth x 5.9
depth of deep end + depth of shallow end
2
Average Depth =
Calculated pool volume is:
Enter Pool Volume figure in the information section, page-4. FIG-18
How to add the salt (or remove it if too much)...
•The object is to have the salt fully dissolve into the water.
• Add salt directly to pool (or spa, if a spa-only installation), and over the main drain (If main drain is present). If there is no main drain, a vacuum head may be used to
encourage salt circulation. Start the water circulation pump and set to run continuously for 24 hours to properly dissolve salt.
•Distributing the salt through brushing is also helpful; brush the salt toward the main drain (if one is present). Set pump operation to normal run time after salt has fully
dissolved into water.
•If the salt level becomes undesirably high, the only way to remove excess salt is to partially drain the pool/spa and refill it with fresh water.
Add Salt to Pool Water...
NOTICE Do not use a pool cleaner or vacuum head with wheels, as wheels can leave
track marks on newly plastered pools. Do not allow Granular salt to pile up in
one location, without brushing, as staining may occur.
Failure to heed the following may result in equipment damage.

18
Pump Button - One-Speed Pump Control
The DIG-220 must be wired to control the main circulation pump and programmed for a One-Speed pump for this feature to be active (for more information on wiring,
see page-15 & 16, and for pump control programming, see page-23). Note - optional pump relay must be installed.
1. Press Pump.
2. Press - Stop Pump will be displayed. Press
3. “Pump off” will be displayed.
To turn “PUMP OFF” , when pump is on:
1. Press Pump.
2. Press - Stop Pump will be displayed. Press
3. “Pump off for service” will be displayed.
To turn “PUMP OFF FOR SERVICE”, when pump is off:
1. Press Pump.
2. Press - End Maint.
3. “Pump off” will be in the displayed.
To terminate maintenance mode and return to “PUMP OFF” mode:
1. Press Pump.
2. Press - to start pump.
3. The pump will run until the pump program reaches the next scheduled turn off time.
To turn “PUMP ON”, when pump is off:
Pump Button...
(This button is not active if the Pump Configuration is programmed for “External Timer” or “Remote runs pump”. If the Pump button is pressed when programmed for one of
these modes, ”External Time” or ”Remote runs pump” will display, then revert back to the normal display.)
(This mode disables pump operation indefinitely, until manually enabled. Boost and Pump program modes will not enable pump.)
ACCESS TO PROGRAMMING
MENU OVERVIEW
Control Panel:
Operation of Buttons:
The following instructions apply to software versions 4.40 and above. Earlier versions of software will vary slightly.
After 30 minutes of inactivity, the display will go to a walking dot screen saver mode. A ll functions such as chlorine generation, reverse, boost, etc., will continue in the background.
Pressing any key will call up the normal informational displa.y
The First line of the display shows the Purifier Output Level in percent (set to 50% at install), or whether the system is in Boost or Super-Boost mode.
The Second line of the display shows the current TIME in either 12 or 24-hr mode, the TEMPERATURE in either Fahrenheit or Celsius, whether the cell is powered or
not shown as “ON” or “OFF”, and Polarity Direction shown as a “.” or blank.
Select Button...
The SELECT button chooses the displayed menu option. For the Installer Menu, press and hold the SELECT button for approximately 13-seconds to access this feature.
Menu Button...
The MENU button is used to leave the normal operation mode and enter the program and diagnostic modes. Use the UP/DOWN and SELECT buttons to navigate through the
menus and sub-menus.
MAIN MENU:
Test Pool Pilot - displays various operating parameters and diagnostic results
View Setup - displays the programmed setup parameters
Owner Options - programs the primary operating parameters an owner would need to change
Maintenance Menu - tests and programs the primary features a service technician would need to access when servicing the system
Installer Menu - program the initial system setup
Note: to permit quick access to features, some functions are accessed or programmed in several menus.
The DISPLAY –
Press BOOST to start 24-hour boost mode,
or press and hold BOOST for 8-seconds to start
72- hour boost mode. Press BOOST again to
cancel boost.
CHECK SYSTEM – Red
LED flashes when the
circulation pump is off or to
warn attention is required. A
warning message will also
be displayed.See
troubleshooting on page-31
& 32.
Press the UP or
DOWN arrow to:
Set Chlorine Level %*
Scroll through Menus
and sub-Menus
Increase or Decrease
programming values
for menus.
Press MENU to leave normal
operation to access the menus for
programming and diagnostics.
Press the SELECT button
to choose the item currently
displayed.
*Make Initial Setting at
install 50%.
PUMP – over ride the water
pump timer, temporarily
turning the pump on or off
(if wired & programmed to
control the circulation
pump).
Purifier
12:00 pm 80F ON
50%
FIG-19

19
PROGRAMMING (CONTINUED)
Pump Button - Two-Speed Pump Control
The DIG-220 must be wired to control the two-speed main circulation pump and programmed for a Two-Speed pump for this feature to be active (for more
information on wiring, see page-15 & 16, and for pump control programming, see page-23). The DIG-220 cannot turn off the pump, and can only change pump
speeds, between high and low (see “Pump Program 1 and 2” on page-23 for additional information) Note - optional pump relay must be installed.
1. Press Pump.
2. Press Low Speed.
3. Pump will switch to low speed.
To switch to “LOW SPEED” when pump is on high speed:
1. Press Pump.
2. Press High Speed.
3. Pump will switch to high speed.
To switch to “HIGH SPEED” when pump is on low speed:
Basic Operational Programming:
Adjusting the Purifier Output % ...
Press the UP/DOWN arrow buttons to enter the Purifier Adjustment mode. Adjust the purifier output percentage to the desired output: from 0% (off) to 100 % (maximum output);
then, press SELECT to default back to the normal display. At start up of a new system, the standard output setting starting point is 50%.
Typically, once the initial setting is established, very little adjustment is needed. The purifier % setting refers to the amount of time the cell is energized within a 15-minute cycle.
The system cycles on-and-off, as indicated on the display's lower right display.... “ON,” when generating chlorine. Higher settings will generate more chlorine.
Follow the instructions “Purifier % Adjustment Procedure” in the chart on page-19 to determine and correct purifier % settings.
Example:
50% setting = 50% of 15-minutes or 7.5-minutes ON and 7.5-minutes OFF.
25% setting = 3.75-min ON, 11.25-min OFF
Once the percentage is set, the DIG-220 will implement the patented temperature compensation algorithm based on current water temperature.
Pump Button Cotinued...
When Boost is activated, and DIG-220 powered through an external time clock or programmer, the time remaining for the boost cycle is held in memory; Boost will
continue when the pump restarts until the 24 or 72-hr boost period has expired.
If the DIG-220 is controlling the pool pump, the Boost will override the pump program and will run continuously at 100% for either 24 or 72 hours.
To exit Boost or Super-Boost mode and revert to normal operation:
Allow the Boost cycle to expire.
OR press BOOST at anytime to manually deactivate Boost.
Boost or SuperBoost...
The Boost feature is used to increase the purifier % from its normal setting to 100% for a cumulative 24-hour or 72-hour period when the Boost period expires, or is manually
terminated, the Purifier % returns to its previous setting and normal operation.
Boost Purifier Output to 100% for 24-Hours... From the normal operation mode, press and release the BOOST button. The display will flash: "Boost 24-hour,"
then “Boost hh” (with the “hh” actually being the displayed hours remaining in the boost period).
Boost Purifier Output to 100% for 72-Hours... From normal operation mode, press and hold the BOOST button until: "Boost 72 hour ON” is displayed; then release
the BOOST button. Display will then show “Boost hh” with the “hh” actually being the displayed hours remaining in boost period.
For the first two weeks, test the water chemistry parameters every 3-4 days. Adjust chemicals as needed to maintain correct water balance. For the Free Chlorine adjustment,
use the following table for fine-tuning the controller output percentage (%):
2Add the proper amount of salt as indicated by the DIG-220 (or as described on page-24), and run the circulation pump continuously for 24-hours allowing the salt to be fully
mixed and dissolved into the pool. If the salt level is too low, the DIG-220 will provide a warning, and will not generate chlorine until the minimum salt level has been reached.
3 Use the UP and DOWN arrow buttons to set the purifier % to 50%, and then allow the pool to operate normally.
After the optimal output percentage (%) has been determined, this setting will not normally require further adjustment. Rather to compensate for increased bather usage or heavy
rainfalls (which can both quickly consume chlorine), select a Boost Cycle.
FIG-21
Purifier Mode
The DIG-220 will automatically display informative messages about the condition of the chlorinator (Purifier Output %, water temperature, warning messages, etc.), and
responds to manual adjustment of purifier % setting (as described below). After 30 minutes of inactivity, the display will go to a walking dot screen saver mode. All functions
such as chlorine generation, reverse, boost, etc., will continue in the background. Pressing any key will call up the normal informational display.
Purifier % Adjustment Procedure:
1Balance water chemistry according to necessary water chemistry parameters. (See page-24 & 25.) For new start ups, if free clorine level as tested is not at least 1 ppm,
add liquid chlorine to ensure a 1 -3 ppm free chlorine reading.
Purifier % Currently set to: If Free Chlorine is lower than ideal range... If Free Chlorine is higher than ideal range...
0% - 25%
25% - 100%
The purifier % output needs to be increased. The purifier % output needs to be reduced.
The purifier % output needs to be reduced.
The purifier % output needs to be increased. Use the UP
arrow button to increase the purifier output %.- If not done already, set purifier % to lower value.
- Power level may be too high and may need to be adjusted down.
- If not done already, set purifier % to higher value.
- If at 100%, power level may be too low and need to be raised
and/or cell size increased. - Check sizing.
Use the down arrow button to decrease the purifier output %.

20
Owner Options (pg 20)
Select Language
Select Units
Temperature Unit
12/24 Hour Clock
Set time of day
Pump Prog 1 (if active)
Pump Prog 2 (if active)
Exit Menu Mode
Installer Menu (pg 22)
Select Language
Select Units
Temperature Unit
12/24 Hour Clock
Set Pool Volume
Set cell type
Set cell power
Set pump control
Set time of day
Select remote
Select minerals
Pump Program 1 (if One or Two Speed Pump)
Pump Program 2 (if One or Two Speed Pump)
Enable Demo
Exit Menu Mode
Maintenance Menu (pg 21)
Test Pool Pilot
Set time of day
Pump Prog 1 (if active)
Pump Prog 2 (if active)
Force Reverse
Set Reverse Time
Replace Cell
Calibrate Temperature
Calibrate Salt
Exit Menu Mode
View Setup (pg 20)
Software Version
Cell Type
Power Level
Pump Configuration
Pool Size
Reverse Time
Temp Adjust
Salt Adjust
Pump Prog 1 (if active)
Pump Prog 2 (if active)
Freeze Protect
Test Pool Pilot (pg 20)
Salt
Salt Needed
Temperature
Cell V/A
Amp Hrs *
Test Pool Pilot (Diagnostic Menu):
1 Press MENU.
2“Test Pool Pilot” is automatically displayed; then press SELECT.
3 The display will automatically toggle through the following displays ( or allows manual control forward and back. While in this feature, pressing MENU will override
the remaining displays and exit back to normal operation):
“Salt =XXXX ppm (X.x g/l)” (The optimum salt level is 3000 ppm (3.0 g/l). 4500 ppm for maximum chlorine production)
“Add Salt xx Lbs (xx Kg)” (The amount of salt needed to maintain 3000 ppm (3.0 g/l))
“Temperature XX° F (XX° C)” (The temperature of the water flowing through the Tri-sensor)
“Cell = XX V XX.x A” (The measured voltage and current sent to the Pool Pilot Cell)
“Amp-Hrs = xxxxxx” (The amount of amps received by the Pool Pilot Cell per hour) . This is only viewable if "Test Pool Pilot" was selected under the "Maintenance
Menu."
4. The controller will automatically leave the menu and revert to normal operation.
Menus:
* Only available when “Test Pool Pilot” is selected under “Maintenance” menu.
1. Press MENU, press or until “View Setup” is displayed, then press SELECT.
2. allows manual control forward and back. While in this feature, pressing MENUThe display will automatically toggle through the following displays or pressing or
will override the remaining displays and exit back to normal operation):
“Software V X.Xx” (The version number of Digital #DIG-200 software)
“Cell = XX-XX” (cell type: PPC1, PPC3, PPC4, PPC5)
“Power Level” (1-lowest, 2, and 3-highest; factory setting is 1)
PROGRAMMING (CONTINUED)
Main Menu
Test Pool Pilot
View Setup
Owner Options
Maintenance Menu
Installer Menu
Exit Menu Mode
View Setup (Program and parameter menu to view the current programmed settings):
Pump Configuration (External Timer, one-speed pump, two-speed pump, or remote runs pump. Factory setting is External Timer.)
“XX,XXX gallons( liters)” (The pool volume programmed in Installation Menu; 15,000 is the factory setting; page-22)
“Reverse = X hrs” (The reverse rate programmed in Installation Menu: 4-hrs is factory setting)
“Temp. adjust = X” (The temperature adjustment variation of actual Tri-sensor reading; page-22)
“Salt adjust +X %” (The salt calibration adjustment variation of actual Tri-sensor reading; page-22)
“Pump program 1” (Only appears if pump control has been set to one-speed or two-speed)
“Pump program 2” (Only appears if pump control has been set to two-speed or two-speed)
Freeze protect (can only be enabled when the pump control is set to one-speed pump mode)
3. The DIG-220 will automatically leave the menu and revert to normal operation.
Owner Options:
1. Press MENU, press or until “Owner Options” is displayed; then press SELECT.
2. Press or for desired selections, followed by SELECT
3. Once all modifications are complete, press or until “Exit Menu Mode” is displayed; then press SELECT. The menu will also time out after 20 seconds of no key activity.
1. Press or
2. Press or
until “Select Language” is displayed; then press SELECT (English is the factory setting).
until desired language “English,” “Espanol,” “Italiano”, or “Francais,” is displayed; then press SELECT.
Select Language:
(Allows for personal preference language display)
Continued Next Page...
Table of contents
Other Aquacal Water Filtration System manuals
Popular Water Filtration System manuals by other brands

Blodgett
Blodgett B24C-FF owner's manual

Vulcan-Hart
Vulcan-Hart ScaleBlocker SPS600V Specifications

Cuckoo
Cuckoo CP-ADR031UW user guide

amiad
amiad TEQUATIC PLUS F-150 C Series Installation & operation manual

Better Water
Better Water EQASSY60BC-1TNK Service manual

Jesco
Jesco C 2700 Operating and maintenance instructions