Arcticpro AP025miniR3 Troubleshooting guide

4"
"
"
Mini"Heater" "
User"and"Service"manual"
"

Regulation"(EU)"n°"517/2014"of"16/04/14"on"fluorinated"greenhouse"gases"and"repealing"Regulation"(EC)"n°"
842/2006"
Leak"checks"
1. Operators+of+equipment+that+contains+fluorinated+greenhouses+gases+in+quantities+of+5+tons+of+CO2,+equivalent+or+more+
and+not+contained+in+foams+shall+ensure+that+the+equipment+is+checked+for+leaks.+
2.+For+equipment+that+contains+fluorinated+greenhouse+gases+in+quantities+of+5+tons+of+CO2+equivalent+or+more,+but+of+less+
than+50+tons+of+CO2+equivalent:+at+least+every+12+months.+
Picture"of"the"equivalence"CO2"
1."Load+in+kg+and+Tons+amounting+CO2.+
Load"and"Tons"amounting"CO2"
Frequency"of"test"
From+2+at+30+kg+load+=+from+5+at+50+Tons+
Each+year+
Concerning"the"Gaz"R32,"7.41kg"amounting"at"5"tons"of"CO2,"commitment"to"check"each"year."
Do"no"release"R32"coolant"liquid"into"the"atmosphere."This"is"a"fluoride"greenhouse"effect"gas"covered"by"the"Kyoto"
agreement" with" a" global" warming" potencial" (GWP)" =" 675-(see" the" European" Community" regulations" on" fluoride"
greenhouse"effect"gases"Regulation"(EU)"No"517/2014)."
Training"and"certification"
1." The+ operator+ of+ the+ relevant+ application+ shall+ ensure+ that+ the+ relevant+ personnel+ have+ obtained+ the+ necessary+
certification,+which+implies+appropriate+knowledge+of+the+applicable+regulations+and+standards+as+well+as+the+necessary+
competence+in+emission+prevention+and+recovery+of+fluorinated+greenhouse+gases+and+handling+safety+the+relevant+type+
and+size+of+equipment.+
Record"keeping"
1."Operators+of+equipment+which+is+required+to+be+checked+for+leaks,+shall+establish+and+maintain+records+for+each+piece+of+
such+equipment+specifying+the+following+information:+
a)+The+quantity+and+type+of+fluorinated+greenhouse+gases+installed;+
b)+The+quantities+of+fluorinated+greenhouse+gases+added+during+installation,+maintenance+or+servicing+or+due+to+leakage;+
c)+Whether+the+quantities+of+installed+fluorinated+greenhouse+gases+have+been+recycled+or+reclaimed,+including+the+name+
and+address+of+the+recycling+or+reclamation+facility+and,+where+applicable,+the+certificate+number;+
d)+The+quantity+of+fluorinated+greenhouse+gases+recovered+
e)The+identity+of+the+undertaking+which+installed,+serviced,+maintained+and+where+applicable+repaired+or+decommissioned+
the+equipment,+including,+where+applicable,+the+number+of+its+certificate;+
f)+The+dates+and+results+of+the+checks+carried+out;+
g)+If+the+equipment+was+decommissioned,+the+measures+taken+to+recover+and+dispose+of+the+fluorinated+greenhouse+gases.+
2.+The+operator+shall+keep+the+records+for+at+least+five+years,+undertakings+carrying+out+the+activities+for+operators+shall+
keep+copies+of+the+records+for+at+least+five+years."
MINI"HEATER"

User"and"Service"manual"
"
"
INDEX"
1. Specifications+
2. Dimension+
3. Installation+and+connection+
4. Electrical+wiring+
5. Display+controller+operation+
6. Trouble+shooting+
7. Exploded+diagram+ +
8. Maintenance+
+
Thank+ you+ for+ using+ Mini+ Heater+ for+ your+ pool+ heating,+ it+ will+ heat+ your+ pool+ water+ and+ keep+ the+ constant+
temperature+when+the+air+ambient+temperature+is+above+12+℃+
+
"ATTENTION:+This"manual"includes"all"the"necessary"information"with"the"use"and"the"installation"of"your"
heat"pump."
The+installer+must+read+the+manual+and+attentively+follow+the+instructions+in+implementation+and+maintenance.+
The+installer+ is+responsible+for+the+installation+of+the+product+ and+should+ follow+ all+ the+instructions+of+the+
manufacturer+and+the+regulations+in+application.+Incorrect+installation+against+the+manual+implies+the+exclusion+
of+the+entire+guarantee.+
The+manufacturer+declines+any+responsibility+for+the+damage+caused+with+the+people,+objects+and+of+the+errors+
due+to+the+installation+that+disobey+the+manual+guideline.+Any+use+that+is+without+conformity+at+the+origin+of+its+
manufacturing+will+be+regarded+as+dangerous."
"
"
"
"WARNING"
-+Please"always"keep"the"heat"pump"in"the"ventilation"place"and"away"from"anything"which"could"cause"fire."

-"Don’t"weld"the"pipe"if"there"is"refrigerant"inside"machine."Please"keep"the"machine"out"of"the"confined"space"
when"make"gas"filling."
-"Please"always"empty"the"water"in"heat"pump"during"winter"time"or"when"the"ambient"temperature"drops"
below" 0
℃
," or" else" the" Titanium" exchanger" will" be" damaged" because" of" being" frozen," in" such" case," your"
warranty"will"be"lost."
-"Please"always"cut"the"power"supply"if"you"want"to"open"the"cabinet"to"reach"inside"the"heat"pump,"because"
there"is"high"voltage"electricity"inside." "
-"Please"well"keep"the"display"controller"in"a"dry"area"to"protect"the"display"controller"from"being"damaged"
by"humidity."
-"Action"of"filling"gas"must"be"conducted"by"professional"with"R32"operating"license."
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
1. Specifications"
1.1 Technical"data"pool"heat"pumps"
CE+Standard,+gas+R32.+

Model+
+
AP025miniR3+
AP045miniR3+
AP060miniR3+
*Heating"Capacity"at"Air"28
℃
,"Water"28
℃
,Humidity"80%"
Heat+Output+(kW)+
kW+
2.5+
4.2+
5.5+
Power+Consumption+
(kW)+
kW+
0.59+ +
1.00+ +
1.31+ +
COP+
+
4.2+ +
4.2+ +
4.2+
*Heating"Capacity"at"Air"15
℃
,"Water"26
℃
,Humidity"70%"
+
Heat+Output+(kW)+
kW+
1.9+
3.2+
4.2+
Power+Consumption+
(kW)+
kW+
0.56+ +
0.91+ +
1.2+
COP+
+
3.4+ +
3.5+ +
3.5+
*"General"data"
"
+
Voltage+
+
+
+
Rated+Current+ +
A+
2.6+ +
4.4+ +
5.8+
Fuse+Current+
A+
7.5+
13+
16+
Advised+pool+volume+
(with+pool+cover)+
m³+
0-10+ +
5-16+
10-20+
Advised+water+flux+
m3/h+
2+
2+
2.5-3.2+
Water+Pressure+Drop+
KPa+
4+
2.5+
3+
Condenser+
+
Titanium+exchanger+in+PVC+
Water+pipe+in-out+
mm+
32+or+38mm+
Fan+Speed+
RPM+
2100+
1100+
1100+
Noise+level(10m)+
dB(A)+
48+
46+
46+
Noise+level(1m)+
dB(A)+
57+
55+
55+
Refrigerant+type+ +
+
R32+
R32+
R32+
Refrigerant+amount+ +
g+
150+
290+
450+
CO2+quota+
tonne+
0.11+
0.2+
0.31+
*"Dimension/"Weight"
"
"
+
Net+Weight+
kg+
18+
26+
28+
Gross+Weight+
kg+
20+
30+
32+
Net+Dimension+
mm+
310*364*375+
434*433*460+
Packing+Dimension+
mm+
375*450*450+
495*520*530+
*Above+data+is+subject+to+modification+without+prior+notice.+
+
+
2. Dimension" "
"

+
+
+
+
+
+
+
+
+
+
+
3. Installation"and"connection"
Attention:"
Item"/"(mm)"
A"
B"
C"
D"
E"
F"
G"
AP025miniR3+
90.4+
130+
50+
375+
310+
300+
363.5+
AP045miniR3/+
AP060miniR3+
116.5+
200+
50+
460+
434+
365+
432.5+

Please+observe+the+following+rules+when+installing+the+heat+pump:+
1. Any+addition+of+chemicals+must+take+place+in+the+piping+located+downstream+from+the+heat+pump.+
2. Always+hold+the+heat+pump+upright.+If+the+unit+has+been+held+at+an+angle,+wait+at+least+24+hours+before+
starting+the+heat+pump.+
3.1"Heat"pump"location"
The+unit+will+work+properly+in+any+desired+location+as+long+as+the+following+three+items+are+present:+
"
"""""""""""1."Fresh"air" " " –"""2."Electricity" " " –""""3."Swimming"pool"filters"
"
"
The+unit+may+be+installed+in+virtually+any+outdoor+location+as+long+as+the+specified+minimum+distances+to+other+
objects+are+maintained+(see+drawing+below).+Please+consult+your+installer+for+installation+with+an+indoor+pool.+
Installation+ in+ a+ windy+ location+ does+ not+ present+ any+ problem+ at+ all,+ unlike+ the+ situation+ with+ a+ gas+ heater+
(including+pilot+flame+problems).+
+
"
ATTENTION:"Never+install+the+unit+in+a+closed+room+with+a+limited+air+volume+in+which+the+air+expelled+from+the+
unit+will+be+reused,+or+close+to+shrubbery+that+could+block+the+air+inlet.+Such+locations+impair+the+continuous+
supply+of+fresh+air,+resulting+in+reduced+efficiency+and+possibly+preventing+sufficient+heat+output.+
3.2"Initial"operation"
Note:"In"order"to"heat"the"water"in"the"pool"(or"hot"tub),"the"filter"pump"must"be"running"to"cause"the"water"
to"circulate"through"the"heat"pump."The"heat"pump"will"not"start"up"if"the"water"is"not"circulating.+
+
+
3.3"Hose"connection"

"
"
"
"
"
"
"
"
"
"
"
"
"
Note:"
The+factory+supplies+only+the+heat+pump.+All+other+components,+including+two+hoses+&+clamp+will+be+provided+
by+the+user+or+the+installer.+
"
3.4"Electrical"connection"
Before+connecting+the+unit,+verify+that+the+supply+voltage+matches+the+operating+voltage+of+the+heat+pump.+
+
The+RCD+plug+has+been+included+with+power+cable,+which+can+offer+electrical+protection.+ +
+
+
+
+
Attention:"

Ensure"the"power"plug"is"secure"
If+the+plug+is+not+secure,+it+may+cause+
an+electric+shock,+over-heating+or+
fire+
+
Never"pull"out"the"power"plug"during"
operation"
Otherwise,+it+may+cause+an+electric+
shock+or+a+fire+due+to+over-heating.+
+
+
Never"use"damaged"electric"wires"
or"unspecified"electric"wires."
Otherwise+it+may+cause+an+electric+
shock+or+a+fire.+
+
"
+
After+all+connections+have+been+made+and+checked,+carry+out+the+following+procedure:+
1. Switch+on+the+filter+pump.+Check+for+leaks+and+verify+that+water+is+flowing+from+and+to+the+swimming+pool.+
2. Connect+power+to+the+heat+pump+and+press+the+On/Off+button+ +on+the+electronic+control+panel.+The+unit+
will+start+up+after+the+time+delay+expires+(see+below).+
3. After+a+few+minutes,+check+whether+the+air+blowing+out+of+the+unit+is+cooler.+
4. When+turn+off+the+filter+pump,+the+unit+should+also+turn+off+automatically.+
Depending+on+the+initial+temperature+of+the+water+in+the+swimming+pool+and+the+air+temperature,+it+may+take+
several+days+to+heat+the+water+to+the+desired+temperature.+A+good+swimming+pool+cover+can+dramatically+reduce+
the+required+length+of+time.+
+
Time"delay"-" The+heat+pump+has+a+built-in+3-minute+start-up+delay+to+protect+the+circuitry+and+avoid+excessive+
contact+wear.+The+unit+will+restart+automatically+after+this+time+delay+expires.+ +
If+first+power+on+or+additional+power+interruptions,+the+heat+pump+starts+10s+later+after+pressing+‘ON/OFF’+button.+
3.5"Condensation"
The+air+drawn+into+the+heat+pump+is+strongly+cooled+by+the+operation+of+the+heat+pump+for+heating+the+pool+
water,+which+may+cause+condensation+on+the+fins+of+the+evaporator.+The+amount+of+condensation+may+be+as+
much+as+several+litters+per+hour+at+high+relative+humidity.+This+is+sometimes+mistakenly+regarded+as+a+water+leak.+
+
+
4.Electrical"wiring"

4.1"Swimming"pool"heat"pump"wiring"diagram"
+AP025miniR3+
+
"
"
"
"
"
"
4.2"Swimming"pool"heat"pump"wiring"diagram"
AP045miniR3/+AP060miniR3+

+
+
NOTE:" "
(1)+Above+electrical+wiring+diagram+only+for+your+reference,+please+subject+machine+posted+the+wiring+diagram.+
(2)+The+swimming+pool+heat+pump+must+be+connected+ground+wire+well,+although+the+unit+heat+exchanger+is+
electrically+isolated+from+the+rest+of+the+unit.+Grounding+the+unit+is+still+required+to+protect+you+against+short+
circuits+inside+the+unit.+Bonding+is+also+required.+
+
Disconnect:"A+disconnect+means+(circuit+breaker,+fused+or+un-fused+switch)+should+be+located+within+sight+of+and+
readily+accessible+from+the+unit.+This+is+common+practice+on+commercial+and+residential+heat+pumps.+It+prevents+
remotely-energizing+unattended+equipment+and+permits+turning+off+power+at+the+unit+while+the+unit+is+being+
serviced.+
+
+
5. Display"controller"operation"
5.1"The"buttons"of"LED"wire"controller"

+
+
When"the"heat"pump"is"running,"the"LED"display"shows"the"water"inlet"temperature."
LED+1+is+on+when+compressor+is+running.+
LED+2+is+on+when+failure+occurs.+
5.2"Turn"on/off"the"heat"pump"
Press+ +to+turn+on+the+heat+pump,+the+LED+display+shows+the+water+setting+temperature+for+5s,+then+show+
water+inlet+temperature.+ + +
press+ +again+to+turn+off+the+heat+pump.+
5.3"Set"the"water"temperature"
Press+ +or+ + directly+to+adjust+water+temperature+(range:.10—42℃)+
Press+ +to+save+the+setting+then+exit.+
"
5.4"Parameter"checking+
Press+ ,it+will+enter+the+parameter+checking,+Press+ +or+ +to+choose+the+code+d0/d1,press+ +
again,+it+will+show+the+measured+value.+Lastly+press+ +to+exit."
+
"
"
"
Notice:"It"can’t"set"the"Parameter"data"by"end-users."
6. Trouble"shooting"
6.1"Error"code"on"the"LED"controller"
NOTE:+the+heat+pump+can+run+only+if+the+water+circle/filtration+system+is+running.+
Code+
Parameter+
d0+
Ambient+temperature+
d1+
Water+in+temperature+

Malfunction"
Code"
Reason"
Solution"
Too+low+or+too+high+
ambient+temperature+
protection+ +
P0+
1. Ambient+temperature+is+out+
of+operating+range:+
12℃-+42℃.+
2. Controller+failure.+
1. Wait+the+ambient+temperature+
rising+to+13℃+or+cooling+down+to+
40℃+to+res-start.+
2. Replace+the+new+controller.+
Water+temperature+sensor+
failure+
P1+
Water+temperature+sensor+
open+circuit+or+short+circuit.+
Replace+the+new+water+
temperature+sensor.+
Ambient+temperature+
sensor+failure+
P2+
Ambient+temperature+sensor+
open+circuit+or+short+circuit.+
Replace+the+new+ambient+
temperature+sensor.+
Low+pressure+protection+
EL+
1. Low+pressure+switch+
disconnected+or+failure.+
2. Gas+leakage.+
It+must+be+repaired+by+the+
professional+technicians.+
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
6.2"Other"Malfunctions"and"Solutions"(No"display"on"LED"wire"controller)"
Malfunctions" "
Observing"
Reason"
Solution"

"
"
"
"
"
"
"
7. Exploded"diagram"
AP025miniR3+
Heat+pump+is+ +
not+running+
LED+wire+controller+
no+display.+
No+power+supply.+
+
+
Check+cable+and+circuit+breaker+if+
it+is+connected.+
LED+wire+controller+
displays+the+actual+
water+temperature.+
1.+Water+temperature+is+
reaching+to+setting+value,+HP+
under+constant+temperature+
status.+
2.+Heat+pump+just+starts+to+run.+
1.+Verify+water+temperature+
setting.+
2.+Startup+heat+pump+after+a+few+
minutes.+
Short+running+
LED+displays+actual+
water+temperature,+no+
error+code+displays.+
1.+Fan+NO+running.+
2.+Air+ventilation+is+not+enough.+
3.+Refrigerant+is+not+enough.+
1.+Check+the+cable+connections+
between+the+motor+and+fan,+if+
necessary,+it+should+be+replaced.+
2.+Check+the+location+of+heat+
pump+unit+and+eliminate+all+
obstacles+to+make+good+air+
ventilation.+
3.+Replace+or+repair+the+heat+
pump+unit.+
Water+stains+
Water+stains+on+heat+
pump+unit.+
1.+Concreting.+
2.+Water+leakage.+
1.+No+action.+
2.+Check+the+titanium+heat+
exchanger+carefully+if+it+is+any+
defect.+

"
"
No."
Spare"parts"
No."
Spare"parts"
1+
Top+cover+
13+
Power+cord+buckle+
2+
Pillar+
14+
Fan+and+fan+motor+assembly+
3+
Ambient+temp.+sensor+
15+
Front+panel+
4+
Transition+tube+
16+
Base+
5+
Gas+collecting+pipe+
17+
Titanium+heat+exchanger+
6+
Capillary+
18+
Coupling+tube+ +
7+
Electric+box+
19+
Water+in+temp.+sensor+ + +
8+
Cilp+
20+
Gas+collecting+pipe+
9+
Compressor+capacitance+
21+
Gas+return+piping+
10+
Fan+motor+top+plate+
22+
Low+pressure+switch+
11+
Controller+
23+
Compressor+
12+
Front+grill+
24+
Evaporator+
"
"
AP045miniR3/+AP060miniR3+

"
No."
Spare"parts"
No."
Spare"parts"
1+
Pillar+
14+
Fan+blade+
Fan+blade+
+
2+
Top+cover+
15+
Front+grill+
3+
Exhaust+pipe+
16+
Power+cord+buckle+
4+
Ambient+temp.+sensor+ +
17+
Base+
5+
Electric+box+
18+
Titanium+heat+exchanger+
6+
Fan+capacitor+ +
19+
Water+in+temp.+sensor+ + +
7+
Capillary+
20+
Gas+collecting+pipe+
8+
Controller+
21+
Low+pressure+switch+
Low+pressure+switch+
9+
Copper+pipe+
22+
Compressor+
10+
Compressor+capacitance+clip+
23+
Gas+return+piping+
11+
Compressor+capacitance+
24+
Copper+pipe+
12+
Front+panel+assemble+
25+
Evaporator+
13+
Fan+motor+
+
Fan+blade+

8. Maintenance" " " "
(1)+You+should+check+the+water+supply+system+regularly+to+avoid+the+air+entering+the+system+and+occurrence+of+
low+water+flow,+because+it+would+reduce+the+performance+and+reliability+of+HP+unit.+
+
(2)+Clean+your+pools+and+filtration+system+regularly+to+avoid+the+damage+of+the+unit+as+a+result+of+the+dirty+of+
clogged+filter.+
+
(3)+You+should+discharge+the+water+from+heat+pump+if+it+will+stop+running+for+a+long+time+(especially+during+the+
winter+season).+ +
+
(4)+In+another+way,+you+should+check+the+unit+is+water+fully+before+the+unit+start+to+run+again.+
+ +
(5)When+the+unit+is+running,+there+is+all+the+time+a+little+water+discharge+under+the+unit.+
+
"
+
+
+
+
+
+
+
+

+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++A0162MHS01+
This manual suits for next models
2
Table of contents