manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Armstrong
  6. •
  7. Fan
  8. •
  9. Armstrong Legacy AG Series User manual

Armstrong Legacy AG Series User manual

Page 1 of 2
This installation guide gives basic instructions which are to be observed
during installation, operation and maintenance of the circulator. It is therefore
imperative that this manual is read by the responsible operator prior to the
installation and should always be kept available at the site.
It is not only the general safety instructions under the ”Safety” section that
are to be observed but also the specific information provided throughout this
guide.
APPLICATION
The AGE SERIES circulators are used in all types of heating systems. By
use of the advanced internal speed control, the electronic automatic
adjustment the circulator performance according to system needs. This
feature gives both great electrical and thermal savings together with reduced
noise level in the installation.
CIRCULATOR MEDIUM
Clean, non aggressive and non explosive fluids without any solids or fibres.
Kinematic viscosity: Max. 10mm2/s. Higher viscosity will cause circulator to
regulate improperly. Capacities shown on the data sheets are measured
with water v =1mm2/s at 20ºC.
Suitable for water impurity up to 5mg/dm3.
Please note: If any liquid other than water is being circulated, we
recommend that you contact our representative as the circulator
characteristics may change.
SAFETY
- The surface temperature might be hot.
- When venting the circulator (fig. 6), it could result in a slight
escape of hot water or steam!
- Circulator should be wired according to the existing regulations
- The circulator must always be earthed..
- All the wires must be disconnected before any work is
carried out on the circulator.
Personnel qualification and training
Personnel responsible for operation, maintenance, inspection and
installation of the circulator must be adequatelyqualified.
The person responsible for the complete installation must ensure that the
contents of this manual are fully understood by any personnel working on
the system.
INSTALLATION
1. The circulator should always be installed with the circulator shaft
horizontal (See fig. 1). Direction of flow through the circulator casing is
indicated by an arrow located on the casing.
2. If terminal box is to be repositioned by rotating the motor, care must be
taken to ensure the casing 0-ring is correctly positioned.
3. Ensure pipework alignment and adequately supported to both the
circulator and pipework. Sharp bends should be avoided nearby the
circulator.
4. If the circulator is mounted in vertical pipework, flow should be
upwards. If flow is downwards, an air-vent must be fitted at the highest
point before circulator suction.
5. Circulator should never be allowed to operate against a closed valve
for more then a few minutes at the time.
6. To avoid accumulation of impurities in the circulator, make sure that it is
not mounted at the lowest point in a system.
7. It is recommended that isolating valves be fitted either side of the
circulator.
8. Before installing a new pump the system should be thoroughly flushed
AGE Series Water temp. max. [C°] Ambient temp. max. [C°]
32-07, 32-10, 42-
10 & 52-11 110 30
90 40
90 30
70 40
62-09 & 82-12
Fig.1
Fig.6
VENTING
Before start up of the circulator, fill the system
and vent the circulator thoroughly. Venting can
be achieved by loosening the plug positioned in
centre of nameplate (See fig. 6). This process
should be repeated periodically untilall air within
the system has been removed. Venting is best
done in manual speed 4.
ELECTRICAL CONNECTION
Electrical data is shown on the nameplate. The
circulator needs no external protection but must
be earthed.How to connect the wires can be
Electrical data: See nameplate
Serial no: See nameplate
Max. working pressure: 10 bar
Min. static head at 80°C: 0,5 bar (62-09 & 82-12- 0,8 bar)
Min. static head at 95°C 1,5 bar
Sound pressure level
32-10 up to 42-10: Max. 35 dB(A)
52-11 up to 82-12: Max. 50 dB(A)
Technical data
According to EN 12639
32-07 Max. 40 dB(A)
DUTY CONTROL
There are two modes for controlling the circulators.
• Controlled to follow a specific defined differential pressure at different
flows (auto).
• Controlled to follow constant speed for systems with constant demand (1-4).
Setting is done via the rotating button on the top of the terminal box.
Fig.2
Electronic controlled settings
Normal setting, to
cover app. 90 % of
all installations.
Factory-setting Auto controlled
performance for
power savings
and extra comfort
where flow demands
are changing.
Reduced differential
pressure. For systems
with little resistance.
Increased differential
pressure. For systems
with high resistance
as radiant floor
heating systems.
INSTALLATION AND OPERATING INSTRUCTIONS
FILE NO: 10. 823IN
DATE: Apr. 12, 2010
SUPERSEDES: New
DATE: New
AGE SERIES
Fixed speed settings
1-4 speeds1. For
small systems and 4.
for large systems or
venting
Fixed speed for
systems with constant
resistance and radi-
ant floor heating
systems.
GENERAL
In all AGE circulators, Pressure Loss Compensation (P.L.C.) is included in
the control, which means that the circulator does not follow a constant differ-
ential pressure but takes into account the decreasing pressure needs at
decreasing flow. This setting isin the auto controlling mode. See fig. 4.
Signal LED
No light Main supply switched off
Green light Normal operation – power on
Red light Error detected by the electronics
Description
ERROR SIGNALS
The red light on the back of the terminal box will, in case of an error, indicate
the type of error detected by the electronic. Approximately every minute the
light will blink a number of times, except 31-07, which is permanently illumi-
nated in the event of a fault.
Number of blinks
1 Under voltage from the power supply
2 Over voltage from the power supply
3 Instantaneous over current
Error
4 Internal power failure
5 Continues power overload
6 Overheating of the electronic
7 Memory failure
8 Motor overheated
9 Program failure
ERROR RELAY
With the exception of the 32-07, the AGE
has a fault relay. The relay has both a NC
and a NO connecting. See fig. 3.
Fault Cause Action
The circulator is not
running. See under heading
”Signals” Reset fault indication.
Check main supply and fuses.
Circulator will not start /
is running irregularly. Impurities in the
circulator. See under heading
“Service/ Maintenance”.
The circulatoris running
but no flow. Air in the system.
Closed valve Vent circulator and
system.Open valve.
Circulator noisy. Circulator speed too
high. Static head too
low. Air in system
Decrease set point of
control. Increase inlet
pressure. Vent circulator
and system.
SERVICE / MAINTENANCE
Armstrong’s AGE Series range of glandless circulators is virtually
maintenance free and in a well designed system should give many years of
trouble free operation.
If motor shaft is seized as a result of a long period without use or due to
accumulation of impurities, it should be freed. Insert a screwdriver through
the venting plughole and into the slot in the end of the shaft and rotate.
Please note: Any repairs required to the internal electrical parts of the circu-
lator, are to be carried out by an Armstrong approved service organisation.
Transport, Handling and Storage Instructions
a. Transport.
i . AGE circulators are despatched fully assembled. AGE
circulators are packed for transport by mornal road, sea and air
carriers.
b. Handling
i. Crushing Hazard.
Ii. When lifting an AGE circulator above a weight of 25 kg,
use lifting equipment haveing a safe working load rating
suitable for the load specified. Use suitable slings for lifting any
circulator..
c. Storage
i. Short term Storage (six weeks). If the AGE circulator is not to be
installed immediately after unpacking, then it is to be be stored in
a cool dry dust free location.
Ii. Long term storage. If the AGE circulator is not to be installed for
period of longer than six weeks after receipt on site, then it is to
be retained in its packing case. If the casing case is disposed of,
then the inlet and outlet connections are to be blanked off with
suitable clean covers to prevent ingress of damaging solids.
DECLARATION OF CONFORMITY
Armstrong hereby declares that this unit complies with the following
relevant provisions
i. EC Machinery Directives 89/392/EEC, 91/368/EEC, 93/44/EEC,
93/68/EEC
Ii. Electromagnatic compatability standard 89/336/EEC, 02/31/EEC,
93/68/EEC
iii. Applied harmonisation of standards EN809, EN50 081-1,
EN50 082-1, EN50-081-2, EN50-082-2.
Fig.3
SIGNALS
AGE circulators have two LED’s on the terminal box for status indication.
Power to the circulator is indicated with the green LED. The red LED will
be on if the circulator detect a fault. Reset is carried out by switching the
mains supply off for 5 sec. and then on again. See fig.5.
1
1
2
2
3
3
4
4
Auto max.
Auto min.
Fig.4 Fig.5
FAULT FINDING
Red = Alam
Green = Power on
For Armstrong locations worldwide, please visit www.armstrongintegrated.com
S. A. Armstrong Limited
23 Bertrand Avenue
Toronto, Ontario
Canada, M1L 2P3
T: (416) 755-2291
F(Main): (416) 759-9101
Armstrong Holden Brooke Pullen
Wenlock Way
Manchester
United Kingdom, M12 5JL
T: +44 (0) 1612 232223
F: +44 (0) 1612 209660
Armstrong Design Private Ltd.
(Unit 1- Armstrong Manufacturing Center)
490-L, 4th Phase, Peenya Industrial Area,
Bangalore, India 650 058
T: +91 (80) 4149 2832
F: +91 (80) 4117 9783 © S.A. Armstrong Limited 2010

This manual suits for next models

7

Other Armstrong Fan manuals

Armstrong AV-11 User manual

Armstrong

Armstrong AV-11 User manual

Armstrong HLAR Series User manual

Armstrong

Armstrong HLAR Series User manual

Armstrong 21-AR User manual

Armstrong

Armstrong 21-AR User manual

Armstrong TT Series User manual

Armstrong

Armstrong TT Series User manual

Armstrong 11-AV User manual

Armstrong

Armstrong 11-AV User manual

Armstrong 21-AR User manual

Armstrong

Armstrong 21-AR User manual

Armstrong 21AR Instruction Manual

Armstrong

Armstrong 21AR Instruction Manual

Popular Fan manuals by other brands

Central Machinery 47755 Owner's manual & safety instructions

Central Machinery

Central Machinery 47755 Owner's manual & safety instructions

Craftmade DCF52 5C1W Series installation guide

Craftmade

Craftmade DCF52 5C1W Series installation guide

Excelsior E46PFO instruction manual

Excelsior

Excelsior E46PFO instruction manual

Hunter Aerodyne installation manual

Hunter

Hunter Aerodyne installation manual

Siemens 8MR64 LV Series operating instructions

Siemens

Siemens 8MR64 LV Series operating instructions

Swegon CDHb Installation, commissioning maintenance

Swegon

Swegon CDHb Installation, commissioning maintenance

Klarstein 10021738 manual

Klarstein

Klarstein 10021738 manual

ACME BreezeMaster BDR36 W/WSS Installation & maintenance instructions

ACME

ACME BreezeMaster BDR36 W/WSS Installation & maintenance instructions

Kair KHRV150/12RH Installation & maintenance instructions

Kair

Kair KHRV150/12RH Installation & maintenance instructions

NuTone 710 Specification sheet

NuTone

NuTone 710 Specification sheet

TJERNLUND AIRESHARE AS2 manual

TJERNLUND

TJERNLUND AIRESHARE AS2 manual

Milwaukee M18 AF Operator's manual

Milwaukee

Milwaukee M18 AF Operator's manual

Spirax Sarco AE36 Installation and maintenance instructions

Spirax Sarco

Spirax Sarco AE36 Installation and maintenance instructions

S&P TDM-100 User instruction

S&P

S&P TDM-100 User instruction

iLiving ILG8MF72-430 owner's manual

iLiving

iLiving ILG8MF72-430 owner's manual

Jata VC3000 Instructions of use

Jata

Jata VC3000 Instructions of use

Hunter Highbury Owner's guide and installation manual

Hunter

Hunter Highbury Owner's guide and installation manual

HOMCOM 824-043V70 Assembly & instruction manual

HOMCOM

HOMCOM 824-043V70 Assembly & instruction manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.