Armstrong 24-HOUR TIMER User manual

Page 1 of 4
INSTALLATION AND OPERATING INSTRUCTIONS
24-HOUR TIMER and AQUASTAT CONTROL ACCESSORY
FILE NO: 11.87
DATE: Apr. 22, 2004
SUPERSEDES: 11.87
DATE: Feb. 24, 2004
TIMER APPLICATION
The Armstrong 24-hour timers provide On/Off pump control according to preset operating
times in order to increase comfort and improve the overall efficiency of domestic hot water
re-circulation systems. The 24-hour timers are designed only for use with specified
Armstrong Astro series wet rotor circulators installed in indoor hot water re-circulation
applications.
Typical timer applications will cycle the pump at preset times, allowing the user to select
operation of the circulating pump during high peak usage periods in order to decrease the
delivery time to outlet fixtures and reduce wasted water.
The timer control is programmable to ¼ hour intervals within a 24-hour time frame utilizing
a user friendly analog clock timer with hour and minute hands, two directional arrows, and
AM/PM time setting.
AQUASTAT APPLICATION
An optional aquastat is available for constant circulation applications to maintain
temperature between 85ºF and 105ºF (29ºC and 41ºC). The Armstrong aquastat
control accessory is designed for use with Astro Series wet rotor circulators in potable
hot water re-circulation installations.
The aquastat control automatically turns the circulator on when the temperature in the hot
water line falls below approximately 85ºF (ON condition - for example when there is low demand on the hot water
supply). The control turns it off again when the temperature exceeds 105ºF (OFF condition - as in the case of
periods with high demand).
TIMER AND AQUASTAT APPLICATION
The 24-hour timer and aquastat can also be used together giving a comprehensive time and temperature actuated
pump control in a domestic hot water re-circulation system. Typical application of the timer and aquastat combination
will circulate water only when both time and temperature ON conditions are initiated.
TIMER FEATURES
•Easy to install and program
•Time actuated 24-hour on/off pump control
•Hour and minute time setting with AM/PM function
•Manual override switch modes
•Rugged construction - steel enclosure
•Clear plastic cover for dust and moisture protection
of the clock face
•Designed specifically for hot water re-circulation
applications
•UL Listed
AQUASTAT FEATURES
•Easy to install
•Temperature actuated pump control
•Environmentally sealed enclosure
•Surface sensing through snap acting bimetalic disc
•UL Listed

Page 2 of 4
24-HOUR TIMER
TECHNICAL DATA
Description: 24-Hour Timer Power Consumption: 120 V, 0.5 W
Application: Time actuated On/Off pump control Supply Voltage: 110-120 VAC, 60 Hz
Shortest Switching Interval: ¼ hour (15 minutes) Terminals: ¼” spade terminals
Manual Switch Modes: “Timer”, Weight: Approximately 3 oz.
“ON” Override, “OFF” Override
Ambient Temperature Range: -40ºF to 180ºF (-40ºC to 82ºC)
TIMER INSTALLATION
Note: Steps 1 & 3 apply to retrofit installations.
1. Disconnect the electrical supply to the circulator
Note: Numerical component designations included in Steps 2 through 10 refer to circulator and timer
components shown in Fig. 1.
2. Unfasten the mounting screw (4A) and remove the terminal box cover (3).
3. Disconnect motor leads from the power supply.
4. Unfasten the mounting screw (4B) on the timer box cover (10) and detach it from the base (8).
5. Remove the lock nut (5A) from the threaded fitting (6) on the timer box base (8).
6. Attach the timer base (8) to the circulator terminal box (2) by inserting the threaded fitting (6) through the
opening on the side of the terminal box base.
7. Fasten the lock nut (5A) on the end of the threaded fitting (6) to securely attach the timer base (8) to the
terminal box (2).
8. Connect terminal box lead wires (black, white and green) to the timer unit and the power supply (as shown in Fig. 2).
Note: Lead Wiring Specification - Minimum, 6” (152 mm) long, 14 AWG, rated minimum 140ºF (60ºC).
Provided with R/C crimp connectors for attachment to the ground.
9. Re-attach the timer box cover (10) using the mounting screw (4B). Insure that all lead wires are inside the timer assembly.
10. Close the terminal box cover (3) by fastening the mounting screw (4A).
11. Program the timer according to instructions provided on page 4.
12. Connect the unit to electrical supply.
13. Start the circulator.
Fig. 2 Astro Series circulator and 24-Hour Timer wiring diagram
WARNING:
Electrical shock hazard - Verify that the electrical rating of the device matches the values shown on the nameplate of the circulator.
All electrical work should be performed by a qualified electrician in accordance with the latest edition of the National Electric Code,
local codes and regulations. Failure to follow these instructions could result in serious injury, death and/or property damage.
Fig. 1 Astro Series circulator and 24-Hour Timer assembly drawing

Page 3 of 4
AQUASTAT CONTROL ACCESSORY
TECHNICAL DATA
Description: Aquastat (thermostatic) switch
Type: Surface sensing, snap acting bimetallic disc
Enclosure: Environmentally sealed
Switch Modes*: 105 ± 5°F (40 ± 2°C) pump switches OFF
85 ± 6°F (29 ± 3°C) pump switches ON
Contact Position: Normally open
Mounting: 1/2": Clip-on type for 5/8" O.D. system piping size (i.e., 1/2" I.D. copper tubing or 3/8" steel pipe)
3/4": Clip-on type for 7/8" O.D. system piping size (i.e., 3/4" I.D. copper tubing or 1/2" steel pipe)
May be mounted on either the inlet or outlet piping of the circulator.
Lead Length: 14” (356 mm) *Temperatures indicated are at pipe surface
AQUASTAT INSTALLATION
1. Follow Steps 1, 2 and 3 in the Timer Installation section
2. The aquastat control is a surface temperature sensing device that must be in contact
with the system piping to operate properly. Separate models include clip-on mounts
for 3/4" (7/8" O.D.) and 1/2" (5/8" O.D.) copper tubing. (See Fig. 3)
3. Connect the black, green and white lead wires according to the wiring diagram (Fig. 4)
Note: Lead Wiring Specification - Minimum, 6” (152 mm) long, 14 AWG, rated
minimum 140ºF (60ºC). Provided with R/C crimp
connectors for attachment to the ground.
4. Close the terminal box cover and fasten the screw
TIMER and AQUASTAT INSTALLATION
Follow the installation steps in both the Timer and Aquastat installation instructions and refer to Fig. 5 for
the wiring connections.
Fig. 4 Astro Series circulator with Aquastat Control wiring diagram
Fig. 3
Fig. 5 Astro Series circulator with 24-Hour Timer and Aquastat Control wiring diagram

TIMER PROGRAMMING with MANUAL OVERRIDE SWITCH
Automatic Mode
In order to operate the time switch in the automatic mode, the
manual switch must be in the center position. (See Fig. 6)
Manual Mode
With the manual switch selector lever the selected programs can
be overridden. In the lower position, marked "O", terminals 3 and 5
are permanently closed. In the upper position, marked "I",
terminals 3 and 4 are permanently closed. (See Fig. 6)
TIMER PROGRAMMING
1. Set the current time by turning the programming ring clockwise
until the timing arrow points to the current time of day.
2. Restore power to the circulator and set the manual switch on
the timer dial to the "ON" position ("I").
3. Set the required "ON/OFF" times by pushing the programming tabs to the outer position for "ON" time intervals.
For "OFF" ("O") operation keep the programming tabs in the inner position.
4. Set the manual switch to the center position, between the "I" and "O" on the timer dial in order to cycle the pump
according to the programming tab settings. The pump will run continuously when the switch is set to "I" (ON)
position. The "O" (OFF) position of the switch will shut the circulator off at all times.
5. In the event of power outage, the timer must be adjusted for the correct time of day after power is restored.
Note: The 24-hour timer requires manual resetting for daylight savings time.
Fig. 6
Current Time Clock
Timing Arrow
Programming Ring
Manual Switch
Programming Tabs
For Armstrong locations worldwide, please visit www.armstrongpumps.com
SS..AA..AArrmmssttrroonnggLLiimmiitteedd
23 Bertrand Avenue
Toronto, Ontario
Canada, M1L 2P3
TT: (416) 755-2291
FF(Main): (416) 759-9101
AArrmmssttrroonnggPPuummppssIInncc..
93 East Avenue
North Tonawanda, New York
U.S.A., 14120-6594
TT: (716) 693-8813
FF: (716) 693-8970
AArrmmssttrroonnggHHoollddeennBBrrooookkeePPuulllleenn
Wenlock Way
Manchester
United Kingdom, M12 5JL
TT: +44 (0) 161 223 2223
FF: +44 (0) 161 220 9660 © S.A. Armstrong Limited 2004
Table of contents
Popular Timer manuals by other brands

hager
hager EGN100 quick start guide

Denlar
Denlar ClockBox Pro Installation and operation manual

Theben
Theben SYN 169 s operating instructions

TJERNLUND
TJERNLUND 950-1067 RELAY-TIMER KIT 8504053 REV 4 0996 installation instructions

Dewenwils
Dewenwils HODT12A instruction manual

KingShield
KingShield T109-C Installation & operating instructions

RaceAmerica
RaceAmerica 3850C owner's manual

Tamarack Technologies
Tamarack Technologies Airetrak 1A ADVANTAGE Product guide

Intermatic
Intermatic HB31R supplementary guide

RaceAmerica
RaceAmerica Timer MB 3210 Series owner's manual

Conrad Electronic
Conrad Electronic 67 20 08 operating instructions

Intermatic
Intermatic TN311K Installation and user instructions