DAM-3028D User’s Manual V6.13
5
Default Setting
If the module’s address or baud rate is wrong, or forget the last modified value, the module can be reverted to default
settings. Steps: Short-circuit the “INIT*” and “GND” when there is no power; power-on for 3 seconds, power off,
disconnect “INIT*” and “GND”. The module is reverted to the default settings.
Address: 00
Baud Rate :9600bps
Noparity
The serial port default work mode: parity bit: none
data bits: 8
stop bit: 1
Code Configuration Table
Baud Rate Configuration Code Table
Code 00 01 02 03 04 05 06 07
Rate 1200 2400 4800 9600 19200 38400 57600 115200
Pin Definition
Pin Name Function
1 IN0 Digital input 0-ch
2 IN1 Digital input 1-ch
3 IN2 Digital input 2-ch
4 IN3 Digital input 3-ch
5 IN4 Digital input 4-ch
6 IN5 Digital input 5-ch
7 IN6 Digital input 6-ch
8 IN7 Digital input 7-ch
9 INIT* reset pin, connect with(B)GND, then power-on to reset
10 (Y)DATA+ RS-485 positive
11 (G)DATA- RS-485 negative
12 (R)+Vs DC Power Supply (+),+10~+30VDC
13 (B)GND DC Power Supply (-)
14 OUT0 Digital output 0-ch
15 OUT1 Digital output 1-ch
16 OUT2 Digital output 2-ch
17 OUT3 Digital output 3-ch
18 OUT4 Digital output 4-ch
19 OUT5 Digital output 5-ch
20 OUT6 Digital output 6-ch
21 OUT7 Digital output 7-ch
22 EXT.PWR External power (+)
23 OUT.COM External power (-)
24~26 NC