INSTALLATION AND MAINTENANCE INSTRUCTIONS
P152 BASIC
SERIES
P152
Table of Contents
1 Notifications .......................................................................................................................................... 2
1.1 Technical Support Contact ..........................................................................................................................................2
1.2 Disclaimer ...................................................................................................................................................................
1. Symbols and Conventions ...........................................................................................................................................
1.4 Safety ..........................................................................................................................................................................4
1.5 Associated Documentation .........................................................................................................................................5
2Introduction ......................................................................................................................................... 5
2.1 P152 BASIC Overview .................................................................................................................................................5
2.2 Components ...............................................................................................................................................................7
2. Technical Data ............................................................................................................................................................8
2.4 Model Configuration ...................................................................................................................................................9
3Installation .......................................................................................................................................... 11
.1 Location ....................................................................................................................................................................11
.2 Process Mounts ........................................................................................................................................................14
. Sensor Mounting ......................................................................................................................................................15
.4 Test Port....................................................................................................................................................................16
4Wiring ................................................................................................................................................. 17
4.1 Terminal Connections ...............................................................................................................................................19
5Operation ............................................................................................................................................ 21
5.1 User Interface ...........................................................................................................................................................21
5.2 Settings .....................................................................................................................................................................22
6Commissioning ................................................................................................................................... 25
6.1 Signal Smoothing ......................................................................................................................................................25
6.2 Alarms (P152E)..........................................................................................................................................................25
6. Analog Output (P152D) .............................................................................................................................................26
7Alarm Setpoint Guidance ................................................................................................................... 27
Functional Verification ....................................................................................................................... 2
8.1 Power-Up Check .......................................................................................................................................................28
8.2 System-Zero Check ...................................................................................................................................................28
8. Response Testing ......................................................................................................................................................29
8.4 Factory Testing .........................................................................................................................................................29
9Troubleshooting ................................................................................................................................. 30
10 Maintenance ....................................................................................................................................... 31
11 Spare Parts .......................................................................................................................................... 32
11.1 Electronics Module Replacement ............................................................................................................................. 2
ASCO Valves® All Rights Reserved. I&M V_10025_AA
E406787 - 11/2023 www.emerson.com/ASCO Page 1 of 32

INSTALLATION AND MAINTENANCE INSTRUCTIONS
P152 BASIC
SERIES
P152
1 Notifications
1.1 Technical Support Contact
Emerson provides industry leading Engineering and Technical Support for all product lines. The Technical Support
department is staffed with a team of engineering professionals. Areas of assistance provided by the Technical Support
department include:
•Pre-Installation Site Analysis
•Product Installation
•eneral Operation
•Application-Specific Review
•Routine Calibration
•EPA Compliance
•Performance Upgrades and Add-On Features
To assure the best and most efficient technical support, please be prepared with the following information prior to
contacting Emerson. If it is determined that the component be returned for evaluation/repair, a Return Material
Authorization (RMA) number will be issued. You must include the RMA number on the packing slip and mark the outside of
the shipping container.
•Company Name
•Product Model Number
•Product Serial Number
•Date of Installation
•Reason for Return
Contact egional Sales for Technical Support.
Notes:
•Any control unit or particulate sensor that was exposed to hazardous materials in a process must be properly
cleaned in accordance with OSHA standards and a Material Safety Data Sheet (MSDS) must be completed before it
is returned to the factory.
•All shipments returned to the factory must be sent by prepaid transportation.
•All shipments will be returned F.O.B. factory.
•Returns will not be accepted without an RMA number.
Page 2 of 32I&M V_10025_AA
www.emerson.com

INSTALLATION AND MAINTENANCE INSTRUCTIONS
P152 BASIC
SERIES
P152
1.2 Disclaimer
This document contains important information necessary for proper operation of the product. It is strongly urged
that all users of the product read this manual in its entirety. All instructions should be followed properly and any
questions that arise should be discussed with Emerson.
Any use or distribution of this document without the express consent of Emerson is strictly prohibited. Any
reproduction is prohibited without written permission.
In no event will Emerson be liable for any mistake, including lost profits, lost savings, environmental compliance
costs, or other incidental or consequential damages or injury arising out of the use or inability to use this manual,
even if advised of the possibility of such damages, or any claim by any other party. Terms and conditions supplied
with each order contain additional liability limitations related to this product.
1.3 Symbols and Conventions
Identifies information about practices or circumstances that can lead to personal injury or
death, property damage, or economic loss.
Warning statements help you to:
•Identify a hazard.
•Avoid a hazard.
•Recognize the consequences.
Identifie les informations sur les pratiques ou les circonstances qui peuvent entraîner des
blessures corporelles ou la mort, des dommages matériels ou des pertes économiques.
Les avertissements vous aident à:
•Identifier un danger
•Évitez un danger
•Reconnaître les conséquences
Identifies information that is critical for successful application and understanding of the
product.
Identifies information, sections or statements in this manual that apply to approved
hazardous area systems, regulations, or installation.
Identifie les informations, sections ou déclarations de ce manuel qui s'appliquent aux
systèmes, réglementations ou installations approuvés pour zones dangereuses.
Page 3 of 32I&M V_10025_AA
www.emerson.com

INSTALLATION AND MAINTENANCE INSTRUCTIONS
P152 BASIC
SERIES
P152
1.4 Safety
A EA CLASSIFICATION (CLASSIFICATION DE ZONE)
Before installing any device, confirm area classification requirements as specified on the
product label. Do not install any device that is not tagged as suitable for the required area
classification.
Avant d'installer un appareil, confirmez les exigences de classification de zone telles que
spécifiées sur l'étiquette du produit. N'installez aucun appareil qui n'est pas étiqueté comme
adapté à la classification de zone requise.
ENVI ONMENT (ENVI ONNEMENT)
Before installing any device, confirm ambient temperature, process temperature, and process
pressure requirements. Do not install any device that is not tagged as suitable for the
required temperatures and pressures.
Avant d'installer un appareil, vérifiez les exigences de température ambiante, de température
de processus et de pression de processus. N'installez aucun appareil qui n'est pas étiqueté
comme adapté aux températures et pressions requises.
NOT A SAFETY ATED DEVICE (PAS UN DISPOSITIF DE SÉCU ITÉ ÉVALUÉ)
This model must not be used independently for safety or as a critical input signal to a safety
system. This model is designated for general process control, diagnostics, and environmental
monitoring. Safety must be addressed with the detailed engineering, redundancy, and safety
certified components where applicable. Consult factory for critical safety applications.
Ce modèle ne doit pas être utilisé indépendamment pour la sécurité ou comme signal
d'entrée critique vers un système de sécurité. Ce modèle est conçu pour le contrôle général
des processus, les diagnostics et la surveillance environnementale. La sécurité doit être
abordée avec l'ingénierie détaillée, la redondance et les composants certifiés de sécurité, le
cas échéant. Consultez l'usine pour les applications de sécurité critiques.
G OUNDING (MISE À LA TE E)
Before turning on the instrument, you must connect the protective earth terminal of the
instrument to a proper earth ground. rounding to the neutral conductor of a single-phase
circuit is not sufficient protection.
Avant de mettre l'instrument sous tension, vous devez connecter la borne de terre de
protection de l'instrument à une prise de terre appropriée. La mise à la terre du conducteur
neutre d'un circuit monophasé ne constitue pas une protection suffisante.
INSTALLATION AND SE VICE PE SONNEL (PE SONNEL D'INSTALLATION ET DE
SE VICE)
Only appropriately licensed professionals should install this product. Always disconnect
power before servicing.
Personnel must be familiar with operational hazards, such as those caused by hot,
pressurized, or toxic gases, liquids, or particulates.
Service of individual electronics is limited to replacement of the electronics module. Do not
attempt to disassemble electronics. Any components that are not operating properly should
be returned to Emerson for service.
Seuls les professionnels agréés doivent installer ce produit. Débranchez toujours
l'alimentation avant de procéder à l'entretien.
Le personnel doit être familiarisé avec les dangers opérationnels, tels que ceux causés par
des gaz, des liquides ou des particules chauds, sous pression ou toxiques.
L'entretien de l'électronique individuelle est limité au remplacement du module
électronique. N'essayez pas de démonter l'électronique. Tous les composants qui ne
fonctionnent pas correctement doivent être renvoyés à Auburn FilterSense pour réparation.
Page 4 of 32I&M V_10025_AA
www.emerson.com

INSTALLATION AND MAINTENANCE INSTRUCTIONS
P152 BASIC
SERIES
P152
1.5 Associated Documentation
This manual is to be referenced in conjunction with the following Emerson documentation:
Product Information
Publication Number Title
564942 P152F/ /H Hazardous Area Wiring with P152 Electronics
564943 P152A/D Intrinsically Safety Wiring
EXXXX Project Specific Drawings if Applicable
Specific Conditions of Use:
1. When the manufacturer of the equipment has not identified the type of protection to be used for installation
on the label, the user shall, on installation, mark the label with the type of protection used. Once the type of
protection has been marked it shall not be changed.
2. The P152D shall be used with the EATON MTL5541/S-T when installed in the hazardous area according to
56494 (I.S. Barrier not required for Hazardous Location, Class II, Division 2).
3. NEMA 4X and IP66 ratings only apply to the probe assembly when installed per drawing 564942.
4. The maximum permitted ambient temperature of the P152 BASIC Transmitter is 71 °C. To avoid the effects of
process temperature and other thermal effects care shall be taken to ensure the surrounding ambient and
the ambient inside the transmitter housing does not exceed 71°C.
5. To prevent the risk of electrostatic sparking the painted surface of the enclosure should only be cleaned with
a damp cloth.
Conditions particulières d'utilisation:
1. Lorsque le fabricant de l'équipement n'a pas identifié le type de protection à utiliser pour l'installation sur
l'étiquette, l'utilisateur doit, lors de l'installation, marquer l'étiquette avec le type de protection utilisé. Une
fois que le type de protection a été marqué, il ne doit pas être modifié.
2. Le P152D doit être utilisé avec l'EATON MTL5541/S-T lorsqu'il est installé dans la zone dangereuse
conformément à 56494 (barrière I.S. non requise pour les emplacements Atmosphere Explosif Classe II
Division 2)..
3. Les indices NEMA 4X et IP66 s'appliquent uniquement à l'ensemble de sonde lorsqu'il est installé
conformément au schéma 564942.
4. La température ambiante maximale autorisée du transmetteur P152 BASIC est de 71 °C. Pour éviter les
effets de la température du processus et d'autres effets thermiques, il faut veiller à ce que la température
ambiante et la température ambiante à l'intérieur du boîtier du transmetteur ne dépassent pas 71 °C.
5. Pour éviter le risque d'étincelles électrostatiques, la surface peinte du boîtier ne doit être nettoyée qu'avec
un chiffon humide.
2 Introduction
2.1 P152 BASIC Overview
The P152 BASIC is a single point/basic functionality particulate monitor employing charge induction sensing for reliable
continuous monitoring of particulate in stacks, ducts, and pipes. Applications include filter leak detection, cyclone
overflow, and powder flow/no flow. The P152 BASIC is available in two versions.
P152 BASIC
Page 5 of 32I&M V_10025_AA
www.emerson.com

INSTALLATION AND MAINTENANCE INSTRUCTIONS
P152 BASIC
SERIES
P152
•P152E
oBasic Particulate Monitor with Alarm
Relay Outputs
oIntegral Electronics Only
•P152D
oBasic Particulate 4-20mA Transmitter
oIntegral Electronics Only
The P152 BASIC is also available in a PLUS for demanding process control and EPA compliance applications. Refer to separate
manual for the P152A/B/C.
P152A PLUS
•P152B
oAdvanced, High-Performance Particulate
Monitor with Alarm Relay Output
oIntegral or Remote Electronics
oraphical Display/Keypad
•P152C
oAdvanced, High-Performance Particulate
Monitor with Alarm Relay Outputs and
Analog Output
oIntegral or Remote Electronics
oraphical Display/Keypad
•P152A
oAdvanced, High-Performance Particulate
4-20mA Transmitter
oIntegral or Remote Electronics
oraphical Display/Keypad
•Refer to the P152 PLUS manual or contact
Regional Sales for more information.
Page 6 of 32I&M V_10025_AA
www.emerson.com

INSTALLATION AND MAINTENANCE INSTRUCTIONS
P152 BASIC
SERIES
P152
Principle of Operation
As particles flow near or around the electrically
isolated sensing probe, minute charge is continuously
induced into the probe. The charge flows through a
measurement circuit to ground.
The induced charge signal is digitally analyzed and
processed to provide an output that is reasonably
linear to mass. The unit of measure is picoamperes
(pA). For highest accuracy and linearity to mass, refer
to model P150B/C.
For best understanding of particulate levels, 4-20 mA
analog outputs should be converted to pA at remote
recording devices or remote displays.
2.2 Components
The P152 BASIC consists of the following main elements:
①
Electronics Module
②
Electronics Enclosure
③Process Mount
④Sensing Probe
Page 7 of 32I&M V_10025_AA
www.emerson.com

INSTALLATION AND MAINTENANCE INSTRUCTIONS
P152 BASIC
SERIES
P152
2.3 Technical Data
Product Code Example
P152D 0 S A A B 0 C F 1 C
Electronics Module
Parameter Model Code Specifications Notes
Measurement Technology Charge Induction
8
th
digit: Electronic
Resolution, Range
A
B
C
0.5pA, Range 0 to 5,000pA
5.0pA, Range 0 to 5,000pA
10.0pA, Range 0 to 100,000pA
The “C” is
recommended for
Powder Flow
Applications
Minimum Particle Size 0.3 Micron
7
th
digit: Temperature
Ambient
S
W
-13 °F to 140 °F (-25 °C to 60 °C))
-40 °F to 160 °F (-40 °C to 71 °C)
-40F to +185F (-40C to +85C)
Operating
Storage
5
th
digit: Relay Outputs E Form A (SPST)
250 VAC / 1A (Resistive), 1A (Inductive)
30 VDC / 1A (Resistive), 1A (Inductive)
Type
Max Rating
5
th
digit: 4-20mA Output D 500Ω Max. Loop Impedance @ 24 VDC Loop
Power
Adjustable via Keypad
Rating
Span
9
th
digit: Area
Classification & Enclosure
A
B
C
D
Ordinary/ eneral Purpose, (UL, CSA, CE)
& NEMA 4/IP 66 Aluminum, Powder Coated
Hazardous Location, Class I, II, Division 2 roups
A- , T4; Zone 21,21 (tb,tc). & NEMA 4/IP 66
Aluminum, Powder Coated Ordinary/ eneral
Purpose, (UL, CSA, CE)
& NEMA 4/IP 66 Aluminum, Powder Coated
with window
Hazardous Location, Class I, II, Division 2 roups
A- , T4; Zone 21,21 (tb,tc). & Type 4/IP66
Aluminum (Powder Coated) with Window
Sensor Probe
Parameter Detail/Code Specifications Notes
10
th
digit: Mounting A
B
C
NPT Male, 0.5 in., 316L
BSPP ( thread) Male, 0.5 in., 316L
BSPT (R thread) Male, 0.5 in., 316L Quick
Clamp, 1.5 in., 316L
Page 8 of 32I&M V_10025_AA
www.emerson.com

INSTALLATION AND MAINTENANCE INSTRUCTIONS
P152 BASIC
SERIES
P152
14digit: Probe Type 1
2
Bare 316L Stainless Steel
Fully Insulated, Teflon Coated, 316L
The Fully insulated
probe CANNOT be
used with Hazardous
Location (“B” & “D”
at 9
th
digit);
12
th
digit: Process
Temperature Operating
Range & Process Pressure
Operating Range
A
B
-13 °F to 250 °F (-25 °C to 121 °C) & Full
Vacuum to 10PSI (0.69 Bar) Max.
-13 °F to 450 °F (-25 °C to 232 °C) & Full
Vacuum to 10PSI (0.69 Bar) Max.
"B” CANNOT be used
with Hazardous
Location (“B” & “D”
at 9
th
digit)
For Higher Pressures
efer to P152A/B/C
2.4 Model Configuration
P152 BASIC Particulate Monitor Order
Code
Base Unit (1~5
th
digit)
Transmitter (4-20 mA), 2-Wire Loop Power P152D
Alarm (2 Relays) P152E
esolution and ange (8
th
digit)
Resolution: 0.5 pA, Range: 0 to 5,000 pA A
Resolution: 5.0 pA, Range: 0 to 5,000 pA B
Resolution: 10.0 pA, Range: 0 to 100,000 pA C
Probe Length (13
th
digit)
Length - 1.5 in (3.8 cm) A
Length - 3.0 in (7.6 cm) B
Length - 6.0 in (15.2 cm) C
Length - 12 in (30.5 cm) D
Length - 18 in (45.7 cm) E
Length - 24 in (60.9 cm) F
Length - 30 in (76.2 cm)
Length - 36 in (91.4 cm) H
Process Mount (10
th
digit)
NPT Male 0.5 in (1.3 cm) with Mounting Coupling, 316L A
BSPP ( thread) Male, 0.5 in., 316L B
BSPT (R thread) Male, 0.5 in., 316L C
Quick Clamp, 1.5 in., 316L
Process Temperature & Process Pressure (12
th
digit)
-13 °F to 250 °F (-25 °C to 121 °C) & Full Vacuum to 10 PSI (0.69 Bar) Max. A
-13 °F to 450 °F (-25 °C to 232 °C) & Full Vacuum to 10 PSI (0.69 Bar) Max. B
Probe Type (14
th
digit)
Bare 316L Stainless Steel 1
Fully Insulated, Teflon Coated, 316L (Coated CANNOT be used with Hazardous Location, Class
II, Division 2 Groups A-G, T4-“B” or “D” at 9
th
digit) 2
Page 9 of 32I&M V_10025_AA
www.emerson.com

INSTALLATION AND MAINTENANCE INSTRUCTIONS
P152 BASIC
SERIES
P152
Area Classification & Enclosure (9
th
digit)
Ordinary/ eneral Purpose, (UL, CSA, CE) & NEMA 4/IP 66 Aluminum, Powder Coated A
Hazardous Location, Class I, II, Division 2 roups A- , T4; Zone 21,21 (tb,tc). UL, CSA, ATEX, IECEx. &
NEMA 4/IP 66 Aluminum, Powder Coated B
Ordinary/ eneral Purpose, (UL, CSA, CE) & NEMA 4/IP 66 Aluminum, Powder Coated with window C
Hazardous Location, Class I, II, Division 2 Groups A-G, T4; Zone 21,21 (tb,tc). UL, CSA, ATEX, IECEx. &
Type 4/IP66 Aluminum (Powder Coated) with Window D
Note: unless specified, the rest digits are kept “0” as default.
Page 10 of 32I&M V_10025_AA
www.emerson.com

INSTALLATION AND MAINTENANCE INSTRUCTIONS
P152 BASIC
SERIES
P152
3 Installation
•Only trained professionals should install/maintain this product.
•Shutdown processes that include high temperatures, high pressures, toxic gases,
hazardous particulate, or explosion risks prior to installing or removing equipment.
•Seuls des professionnels qualifiés doivent installer / entretenir ce produit.
•Arrêtez les processus qui incluent des températures élevées, des pressions élevées,
des gaz toxiques, des particules dangereuses ou des risques d'explosion avant
d'installer ou de retirer l'équipement.
3.1 Location
Area Classification
•
Do not install any device that is not tagged as
suitable for the required area classification.
•Check label for the following:
oArea classification
oCertification numbers as required.
•FM23NUS0011
•FM23NCA0008
•FM23ATEX0035X
•FM23ATEX0034X
•FM23US0070X
•FM23CA0052X
•IECEx FM 23.0017X
Hazardous Area Label Example
Temperature and Pressure
o`
Hazardous Area Side Label Examples
Page 11 of 32I&M V_10025_AA
www.emerson.com

INSTALLATION AND MAINTENANCE INSTRUCTIONS
P152 BASIC
SERIES
P152
The following factors should be considered:
•Confirm compatibility of all sensor ratings with process and installation area.
•Check label for the following:
oWetted materials
oEnclosure rating
•Installation must be in grounded metal duct/pipe. Consult factory for non-metallic duct/pipe solutions.
•High levels of vibration should be avoided.
Filter Outlet Locations
①
Ensure good access.
②
Avoid locating within one pipe diameter or 36
inches of vertical stack exit to protect against
weather. Horizontal exits allow for closer
placement to open weather.
③Straight runs and laminar flow best for
measurement.
④Short straight runs are acceptable for basic leak
detection.
⑤Accessible negative pressure locations may be
preferred to prevent exposure to toxic gases
and particulate.
④
③
⑤
①
⑤
③
②
Intrinsically Safe Side Label Examples
Page 12 of 32I&M V_10025_AA
www.emerson.com

INSTALLATION AND MAINTENANCE INSTRUCTIONS
P152 BASIC
SERIES
P152
Straight un Considerations
•Install in straight run if possible (not required).
•Three (3) duct diameters upstream.
•Two (2) duct diameters downstream.
•Straight run can be horizontal or vertical.
Powder Flow Locations
①
Best installed in pneumatic section (positive
or negative pressure).
②For gravity feed, consult factory.
•rounded metal duct required.
oConsult factory for nonmetallic duct/
pipe solutions.
•Follow straight run considerations.
Horizontal Pipes/Ducts
•Side or top mount recommended.
•Bottom mount not recommended.
•Proper mount and installation location will
prevent buildup.
•For further installation advice please contact
regional sales.
①
②
Page 13 of 32I&M V_10025_AA
www.emerson.com

INSTALLATION AND MAINTENANCE INSTRUCTIONS
P152 BASIC
SERIES
P152
3.2 Process Mounts
The following types of process mounts are available:
Threaded
•NPT Standard
•BSPP ( ) / BSPT (R) Optional
①Threaded Nipple
②Threaded Half-Coupling Process Mount
Quick-Clamp
•1.5” Tri-Clamp
•Allows quick and easy removal from process
•Allows rotation to easily align
①Quick-Clamp Nipple
②Quick-Clamp Process Mount Kit
•Ferrule
•Tri-Clamp
•asket
①
②
①
②
Page 14 of 32I&M V_10025_AA
www.emerson.com

INSTALLATION AND MAINTENANCE INSTRUCTIONS
P152 BASIC
SERIES
P152
3.3 Sensor Mounting
Sensor Mounting Considerations
①
Process mount should protrude into process
0.125 in (3.175 mm) to 0.5 in (12.7 mm).
②Sensor probe should extend approximately
1/2 of the duct diameter for filter outlet
applications and 1/4 to 1/2 of the pipe
diameter for powder flow applications.
•In smaller pipes, the probe should be 1 in
(25.4 mm) minimum from the opposing side.
•High levels of vibration should be avoided.
Welding and Clearance
①
“Through weld” half coupling or quick-clamp
mount to ensure proper clearance and to prevent
particulate buildup in mount. Process
mount should protrude into process 0.125 in
(3.175 mm) to 0.5 in (12.7 mm).
②Do not face weld.
•Weld in center of the duct/pipe, perpendicular to
the flow.
•Air and watertight seal.
②
②
①
①
Quick-Clamp
Threaded
①
①
②
②
Page 15 of 32I&M V_10025_AA
www.emerson.com

INSTALLATION AND MAINTENANCE INSTRUCTIONS
P152 BASIC
SERIES
P152
Improper Extensions
①
Do not use an extended or improper mount.
②
Longer mounts can cause the nipple not to
protrude into the process.
③Extended mounts can cause particulate
buildup on the insulator and sensing probe.
•Contact the factory for custom sensor nipple
extensions for proper installation in an
existing port.
•Do not use non-stainless steel mounts that
may corrode and cause corrosive residue to
drip on the sensor.
3.4 Test Port
Installation of a sensor test port is for introducing particulate upstream of the sensor as a method for checking the
response to an increase in particulate. Some applications are required by EPA regulations to include a sensor test port for
esponse Testing.
Location and Mounting
•Non-hazardous areas only.
•Negative pressure location.
•Install at least 3 ft upstream of the particulate
sensor.
•In line with sensor on the same side of the
duct.
•If possible, locate the test port at ground level
and/or a location with easy access.
•If the test port must be located at an
inaccessible location, a length of tubing can
be used to improve access.
•Typical test port is a 1/8” NPT x 3” long nipple
with a cap or shutoff valve.
①
②
③
Page 16 of 32I&M V_10025_AA
www.emerson.com

INSTALLATION AND MAINTENANCE INSTRUCTIONS
P152 BASIC
SERIES
P152
4 Wiring
Conduit Entries
•One (1) ¾” and two (2) ½” NPT entries
provided.
•Conduit fittings should be tight.
•Conduit should be routed downward to
prevent moisture from entering enclosure.
•The three plastic shipping thread protectors
must be removed and replaced during
installation to prevent water entry into the
housing.
ecommended Service Loop
•Flex conduit or instrument cabling and
ground cable should be sufficient length to
allow removal of the sensor.
•Recommended service loop is 1 to 2 times the
sensor probe length.
•Service loop should extend downward to
prevent moisture from entering enclosure.
Page 17 of 32I&M V_10025_AA
www.emerson.com

INSTALLATION AND MAINTENANCE INSTRUCTIONS
P152 BASIC
SERIES
P152
Grounding
•Required for reliable operation and safety.
•P152D: Earth ground connection is made
through the process mount (for threaded
mounts do not use Teflon tape, use
conductive pipe dope or conductive grease).
rounding to the enclosure ground studs is
not required.
•P152E: Earth ground connection should be
made to one of the three ground locations:
oExternal enclosure ground screw.
oInternal enclosure ground screw.
oElectronics module earth ground
terminal.
•Analog wiring cable shield should be
terminated to earth ground in PLC/DCS
cabinet or at panel meter (terminate at one
end only).
•round wire should not impede service loop.
G OUNDING IN HAZA DOUS A EAS (MISE À LA TE E DANS LES ZONES
DANGE EUSES)
•For hazardous area applications, an external sensor earth ground cable is required to
maintain sensor grounding during installation and maintenance.
•The ground cable must remain attached when the sensor is temporarily removed
from the process. Do not disconnect the ground cable.
•Hazardous area installation of the P152D must be performed using drawing 56494
“P152A/D Intrinsically Safety Wiring”. The P152D unit must be marked for correct
hazardous area installation and required ratings.
•Pour les applications en zone dangereuse, un câble de mise à la terre du capteur
externe est nécessaire pour maintenir la mise à la terre du capteur pendant
l'installation et la maintenance.
•Le câble de masse doit rester attaché lorsque le capteur est temporairement retiré
du processus. Ne déconnectez pas le câble de masse.
•L'installation en zone dangereuse du P152D doit être effectuée à l'aide du dessin
56494 , « Câblage de sécurité intrinsèque P152A/D ». L'unité P152D doit être
marquée pour une installation en zone dangereuse correcte et les classifications
requises.
Page 18 of 32I&M V_10025_AA
www.emerson.com

INSTALLATION AND MAINTENANCE INSTRUCTIONS
P152 BASIC
SERIES
P152
4.1 Terminal Connections
P152E
•Terminal connections for power and two alarm
relays.
•All wiring must be rated for 250V minimum.
•Always disconnect power before connecting/
removing wiring from the terminal
connectors.
Page 19 of 32I&M V_10025_AA
www.emerson.com

INSTALLATION AND MAINTENANCE INSTRUCTIONS
P152 BASIC
SERIES
P152
P152D
•Terminal connection for loop powered analog
output.
•All wiring must be rated for 250V minimum.
•Always disconnect power before connecting/
removing wiring from the terminal connectors.
•Analog 4-20mA wire should be 22 AW stranded
shielded twisted pair, Belden 88761 or equivalent.
•Analog wiring cable shield should be terminated
to earth ground in PLC/DCS panel/cabinet
(terminate one end only).
Page 20 of 32I&M V_10025_AA
www.emerson.com
Other manuals for P152 Series
1
This manual suits for next models