Asco POSIMATIC 606 Series User manual

IM165-2-X.R0
(383 45 96)
Installation manual
Manuel d'installation
Electropneumatic positioner
series 606
Positionneur électropneumatique
série 606
POSIMATIC
F
GB

2
POSIMATIC
INSTALLATION
Contents
1. Safety instructions ......................................................................................................................................... 3
1.1 General .................................................................................................................................................. 3
1.2 Description of symbols .......................................................................................................................... 3
1.3 Electrical and pneumatic safety instructions .......................................................................................... 4
1.4 Proper use ............................................................................................................................................. 4
1.5 Tools required for installation and connection ......................................................................................... 4
2. Manufacturer’s specifications ......................................................................................................................... 4
2.1 Scope of delivery ................................................................................................................................... 4
3. Mechanical assembly .................................................................................................................................... 5
3.1 Assembly to linear actuators ................................................................................................................. 5
3.2 Assembly to a rotary actuator ................................................................................................................ 5
3.3 External assembly ................................................................................................................................. 5
4. Pneumatic connections.................................................................................................................................. 6
5. Electrical connections .................................................................................................................................... 7
6. Operation ...................................................................................................................................................... 7
6.1 Controls and indicators .................................................................................................................................. 7
6.2 Access levels ........................................................................................................................................ 8
7. Startup ...................................................................................................................................................... 8
7.1 General operating instructions................................................................................................................ 8
7.2 Initialisation ........................................................................................................................................... 8
7.2.1Settings ......................................................................................................................................... 8
7.2.2Factory settings (positioner assembled to valve) ..........................................................................10
8. Operating modes...........................................................................................................................................10
8.1 Automatic mode (A: AUTO) ...................................................................................................................10
8.2 Manual mode (B: MANUAL) ..................................................................................................................10
8.3 Configuration (C: CONFIG) .................................................................................................................... 10
9. Integration of options ....................................................................................................................................11
9.1 Plug-in module for analog position feedback .........................................................................................11
10. List of parameters ......................................................................................................................................... 12
10.1 Description of parameters .....................................................................................................................13
11. Error messages ............................................................................................................................................ 18
12. Technical characteristics ...............................................................................................................................19
13. Assembly options .........................................................................................................................................20
14. Dimensions ...................................................................................................................................................21
Index.....................................................................................................................................................................22
NOTICE
The information in this manual is subject to change without notice.
In no event shall ASCO/JOUCOMATIC be liable for technical or editorial errors or omissions. Neither is any
liability assumed for accidental or consequential damages arising out of or in connection with the supply or
use of the information contained herein.
THIS MANUAL CONTAINS INFORMATION PROTECTED BY COPYRIGHT. NO PART OF THIS DOCUMENT
MAY BE PHOTOCOPIED OR REPRODUCED IN ANY FORM OR MANNER WHATSOEVER WITHOUT
PRIOR WRITTEN PERMISSION FROM ASCO/JOUCOMATIC.
COPYRIGHT ©2000/2001 - ASCO/JOUCOMATIC - All rights reserved.

3
INSTALLATION
POSIMATIC
!
i
!
Warning
1. Safety instructions
Please read and observe the following safety precautions:
1.1 General
To ensure proper functioning of the positioner please provide for the following:
- Ensure proper transport and storage.
- Installation and start-up must be carried out by trained and qualified personnel only.
- The positioner must be operated in accordance with the instructions contained in this installation manual.
- Ensure proper maintenance and care.
Please follow:
- the instructions contained in this installation manual;
- all safety regulations related to the installation and operation of electrical equipment.
- This product must not be operated in potentially explosive atmospheres.
The regulations, standards and directives mentioned in this installation manual are applicable for the member states of the
European Union only. If the
POSIMATIC
positioner is used outside the European Union, please adhere to local rules and
regulations.
1.2 Description of symbols
Throughout this manual, the following symbols refer to important information:
Warning. Non-observance of the instructions contained in this manual may result in danger to life
and health and/or substantial damage to property.
Caution.Non-observance of the safety precautions marked by this symbol may cause slight personal
injury and/or damage to property.
Note.This symbol refers to important information on the
POSIMATIC
positioner.
ThisproductcomplieswiththeessentialrequirementsoftheEMC-Directive89/336/EECandamendments.
CertifiedCE.A
separate Declaration of Conformity is available on request.
A separate Declaration of Incorporation relating to EEC-Directive 89/392/EEC Annex II B is available on
request. Please provide acknowledgement number and serial numbers of products concerned.

4
POSIMATIC
INSTALLATION
!
Warning
1.3 Electrical and pneumatic safety instructions
The assembly, electrical and pneumatic connection as well as startup of the ASCO/JOUCOMATIC
positioner must be carried out by trained, qualified personnel only.
The electrical safety of all power supplying equipment must be ensured.
Please provide for the following equipment:
- 24 VDC power supply unit.
- 1 analog output of 0/4-20mA for current setpoint (terminal Iw+, Iw-),
- or 1 analog output of 0-10V (terminal Uw+, Uw-).
All electrical specifications must be observed.
All safety measures for the installation and startup of pneumatic actuators must be adhered to.
The high forces generated by the positioning actuators may cause injury.
1.4 Proper use
The
POSIMATIC
is a smart electropneumatic positioner to be mounted to pneumatically operated linear or rotary actuators.
The positioner can be mounted directly on the actuator with a corresponding assembly kit containing the mounting bracket
or adapter, the position sensor and the appropriate fastening screws.
The positioner can also be assembled externally. No mounting bracket or adapter is required for this purpose.
1.5 Tools required for assembly and connection
- Open-end wrench –dimensions across flats: 8, 10, 27
- Allen keys: 3 mm and 4 mm
- Screw driver: 3.5 mm
2. Manufacturer’s specifications
2.1 Scope of delivery
Please check the delivery immediately on receipt for completeness and intactness.The scope of delivery is detailed in the
shipping documents.
Check the products delivered and the ordering codes to see whether the construction and quantity comply with your order.
If you have ordered a complete unit consisting of positioner and valve, these devices and the pertinent accessories are
fully preassembled and factory-set at delivery. ASCO/JOUCOMATIC’s positioner is ready for immediate use.

5
INSTALLATION
POSIMATIC
3. Mechanical assembly
3.1 Assembly to linear actuators
- The actuator must be in its initial position (actuator exhausted).
- Insert the mounting bracket (1) between the actuator’s head (2) and the
position sensor (3) and fasten it by tightening the position sensor at the
hexagon (4).
- Screw the positioner to the mounting bracket (1) with two M6 screws (5).
- Unscrew and open the bonnet of the positioner.
- Introduce the cable of the linear position sensor into the M12 gland (6) of
the positioner and connect it to the terminal board according to the
assignment plan (see chapter 5).
- Then screw the M12 gland tight. The cable must fit tightly.
3.2 Assembly to rotary actuators
- The actuator must be in its initial position.
- Screw the rotary position sensor (3) with the mounting bracket (1)
to the actuator.
- Mount the positioner with the NAMUR adapter (4)
directly to the rotary actuator (2).
- Unscrew and open the bonnet of the positioner.
- Introduce the cable of the linear position sensor into
the M12 gland (6) of the positioner and connect it to
the terminal board according to the assignment plan
(see chapter 5).
- Then screw the M12 gland tight.The cable must be
fit tightly.
- Observe the correct mounting position of the rotating position sensor to the “pivot with cheeks”.
3.3. External assembly
- The actuator must be in its initial position (actuator exhausted).
- Mount the position sensor as described in chapter 3.1 and/or 3.2.
Fig. 1: Assembly to linear actuator
Fig. 2: Assembly to rotary actuator
Positioning of the rotary potentiometer on a rotary
actuator (top view)
Rotary potentiometer
Actuator
Gate closed
Gate open
Adapter marking
Pneumatic connection
Potentiometer spindle
marking
Drive shaft (top view)
Rotary potentiometer spindle
Adapter
Rotary potentiometer
connection
Gate disk closed
i
1
5
6
3
42
24
6
3
1

6
POSIMATIC
INSTALLATION
4. Pneumatic connections
- Establish the connection between the pneumatic outlet A1 (single acting) or outlets A1 and A2 (double acting) of the
positioner and the pneumatic pilot pressure inlet of the actuator.
- Connect the pressure supply to port P (max. 6 bar or 90 psi).
Caution: Observe the max. pilot pressure of the actuators !
!
Fig. 2: Pneumatic connections
Legend:
A1: pneumatic outlet A1 (single and double acting actuators)
A2: pneumatic outlet A2 (double acting actuators)
P: Pressure supply
R: Exhaust
Actuator functions:
„Control function 1“: single acting device with spring in retracted position
„Control function 2“: single acting device with spring in extended position
„Control function 3“: double acting device
Rear view Side view (from left)

7
INSTALLATION
POSIMATIC
- Shut the bonnet and screw it tight.
Make sure not to damage the seal and cable.
6. Operation
6.1 Controls and indicators
Legend
10 V gn Connection of
X br external displacement
measuring system
Iw+ Setpoint input
Iw- 0/4-20 mA
Uw+ Setpoint input
Uw- 0-10 V
X+
Feedback value output 0-10V
X- 4-20 mA (optional)
GND Supply voltage
24 V 24 V DC
Protection earth
A1 Alarm1
A2 Alarm2
ERR Error output
⊥GND out
External earth terminal:
Grounding for personal protection
Fig. 3: Terminal assignment
!
5. Electrical connections
- Connect the position sensor.
- Connect the setpoint signal 0/4-20 mA or 0-10 V to the corresponding terminals.
- Connect the 24 VDC power supply cable.
!
1 Two-line display of 16 characters each
2 Return key (yellow)
3 Jump key (green)
4 Up key (red)
5 Down key (black)
Fig. 4: Controls and indicators
2345
yellow green red black
⇐⇐
⇐⇐
⇐⇒⇒
⇒⇒
⇒+-
1
or orange
gn green
bl blue
gr grey

8
POSIMATIC
INSTALLATION
i
i
i
6.2 Access levels
The following two access levels are provided for operation of the positioner:
Control level (A: AUTO, B: MANUAL)
This level is automatically set each time the positioner is switched on.You can toggle between the AUTO and MANUAL
operating modes at this level.
In the MANUAL mode, the valve can be operated with the +key and -key.The specified value is activated only when the
→→
→→
→key is pressed. This allows you to test the reactions to jumps.
In the AUTO operating mode, the valve is controlled by a setpoint signal.
Configuration level (C: CONFIG)
Different parameters can be set at this level (see list of parameters on page 12).
This allows for optimal adaptation to your specific application.
7. Startup
- Activate the pneumatic pressure supply (observe max. pilot pressure !).
- Switch on the 24 VDC power supply [terminal 24V (+) and ⊥ (-)].
- Specify the analog setpoint 0/4-20 mA or 0-10 V.
7.1 General operating instructions
The two screws on the keyboard cover must be loosened to change the settings and parameters of
the positioner. Pull the cover slightly to remove it.
The different operating levels and parameters can be accessed with the ←←
←←
←key and →→
→→
→key.The parameters can be changed
with the +key and the –key. Pressing the ←←
←←
←or →→
→→
→key automatically stores the new values.
Fast return: Press ← ←
← ←
← and →→
→→
→to return to A: AUTO.
Memory function: Enter the menu item C:CONFIG to return to the previously selected menu.
7.2 Initialisation (C: CONFIG, D: NO INIT)
7.2.1 Settings
After the assembly and electrical and pneumatic connection has been completed, the positioner must be initialised.Without
initialisation, the positioner is in the operating mode „D: NO INIT“.This operating mode can also be obtained by selecting
„DEFAULT“in the menu „3:DEFAULT STATE“.
In the operating mode „D: NO INIT“, you can OPEN and CLOSE the valve manually by pressing
the +and –keys.
Press + and – to OPEN the actuator at high speed.
Press – and + to CLOSE the actuator at high speed.

9
INSTALLATION
POSIMATIC
- Press ←←
←←
←once to call „C: CONFIG“.
- Press →→
→→
→for approx. 3 secs. until the upper readout disappears. „1: SETPOINT“ is displayed. Use the +and –keys to
select the setpoint input in the upper readout (0-20 mA, 4-20 mA or 0-10 V).
- Press →→
→→
→to call „2: INIT ALL“:
„NO INIT“ is displayed in the upper readout.
- Press + or – and then →→
→→
→for 3 seconds.
The automatic initialisation steps run1 ... run5 are started.
This process can take up a few minutes.
- During run3, the actual positioning time for OPEN (up) and CLOSE (down) is displayed for 5 seconds. The positioning
time can be changed by pressing →→
→→
→during these 5 seconds.
-„ADJUST NOZZLE(S) THEN PRESS <-“is displayed.
- You can then adjust the integrated flow restrictors D1 and D2 (D2 only available for double acting actuators) (turn
clockwise for longer positioning times).
(Minimum valve positioning time > 1 s)
- Check the setting by pressing the ←←
←←
←key.The newly set positioning time is displayed. If no key is pressed in the following
5 seconds, the initialisation routine is automatically continued.
After the initialisation has been successfully completed, „INIT OK“ is displayed in the upper readout.
- Press the ←←
←←
←key three times until „A: AUTO“ is displayed.
The positioner is ready for use. (Note: An external setpoint signal is required.)
If you operate an actuator in „control function 2“(spring in extended position) we recommend
integrating an external flow restrictor into the air inlet (port P).
Adjustment: - Open internal flow restrictor D.
- Adjust external flow restrictor so that a positioning speed > 1 sec is reached.
- Adjust the OPEN/CLOSE positioning times with the internal flow restrictor
(if necessary).
- Set parameter 24: SETP DIRECTN to INVERS.
i
After switch-on

10
POSIMATIC
INSTALLATION
„A: AUTO“ is displayed. The positioner is ready for use.
If you wish to drive the valve by hand, press the →→
→→
→key once.
„B: MANUAL“ is displayed.
The value can be adjusted with the + and – keys and the valve can be driven into the desired position with the →→
→→
→key.
The positioner must be newly initialised after each replacement of valve or diaphragm. For this purpose call the menu
„2: INIT ALL“ and proceed as described under 7.2.1.
For „control function 2“set the parameter 24:SETP DIRECTN to INVERS.
8. Operating modes
8.1 Automatic mode (A: AUTO)
The automatic mode is the standard operating mode. The initialised positioner reacts automatically to setpoint changes
and sets the valve into motion accordingly .
The + and –keys do not have any function in this operating mode.
The actual position (x) is displayed in percent together with a bar graph in the upper readout.
In the lower readout, the current operating mode is displayed on the left and the current setpoint (w) is displayed in percent
on the right.
8.2 Manual mode (B: MANUAL)
Press the →→
→→
→key to access menu item „B: MANUAL“.
The valve can be driven by hand in the manual operation mode.The value can be adjusted with the + and – keys and the
valve is driven into the desired position with the →→
→→
→key.
8.3 Configuration (C: CONFIG)
Press the →→
→→
→key to access the configuration settings (C: CONFIG).
7.2.2 Factory settings (positioner assembled to valve)

11
INSTALLATION
POSIMATIC
The parameters of the positioner can be changed in the configuration menu.The parameter value is displayed in the upper
readout; the parameter number and parameter name are displayed in the lower readout. Settings are made as shown
above. See chapter 10.1 for a description of the parameters.
9. Integration of options
All options ordered together with the positioner are preassembled at delivered and ready for use.
If you wish to add options at a later date, please consult us.

12
POSIMATIC
INSTALLATION
10. List of parameters
Electropneumatic positioner: List of parameters
Display Function Parameter values Unit Factory settings
1: SETPOINT Current range of setpoint 0..10 V V 4..20 mA
0..20 mA mA
4..20 mA
2: INIT ALL Initialisation of actuator NO INIT - NO INIT
and positioner INIT OK
3: DEFAULT STATE Recovery NO DEFAULT - DEFAULT
of factory settings DEFAULT
11: X-DIRECTION Direction of X display RISE RISE
and of feedback value output FALL
12: ALARM FUNCTN Alarm function OFF OFF
Binary outputs min/max
(Alarm1, Alarm2) min/min
max/max
13: LEVEL ALARM1 Response threshold Alarm1 0.0...10 % 10.0
14: LEVEL ALARM2 Response threshold Alarm2 0.0...100 % 90.0
15: ERROR FUNCTN Triggering of ERROR ERROR + RANGE
error output ERROR + INACTIVE
RANGE
ERROR + RANGE
ERR+RANGE+INAC
16: ERROR TIME
Monitoring of valve positioning time
auto s auto
(Error output) 0...100
17: ERROR LEVEL Max. deviation auto % auto
(Error output) 0.0...100
18: RANGE FUNCTN Monitoring of < 4mA mA <4mA or > 20 mA
setpoint input/ > 20mA
error output range < 4mA or > 20mA
21: MIN POSITION Standardisation of position 0.0...100 % 0.0
Minimum position
22: MAX POSITION Standardisation of position 0.0...100 % 100
Maximum position
23: CLOSE TIGHT Close tight function no no
at minimum/maximum position min
max
min & max
24: SETP DIRECTN Direction of action of NORMAL NORMAL
setpoint INVERSE
25: SETP RAMP Ramp function of auto s 0
setpoint 0...400
26: SPLIT START Setpoint for start 0.0...100 % 0.0
of split range
27: SPLIT END Setpoint for end 0.0...100 % 100
of split range
28: SETP FUNCTN Linearisation function linear linear
for setpoint 1 : 25
Position ÆFlow 1 : 50
free (1:25 inverse)
30: FREE 0 % Definition of 0...100 % 0.0
31: FREE 10 % freely programmable 28.5
32: FREE 20 % characteristic curve (free) 50.0
33: FREE 30 % 11 points 62.6
34: FREE 40 % 71.5
35: FREE 50 % 78.5
36: FREE 60 % 84.1
37: FREE 70 % 88.9
38: FREE 80 % 93.1
39: FREE 90 % 96.7
40: FREE 100 % 100

13
INSTALLATION
POSIMATIC
10.1 Description of parameters
1: SETPOINT
Range of analog setpoint input (Voltage:0-10 V or current: 0-20 mA, 4-20 mA).
2: INIT ALL
Initialisation
Automatic initialisation is started by pressing the +or -and →→
→→
→keys (> 3sec). The individual steps of initialisation are
displayed with „run 1“to „run 5“.
The positioner’s control parameters to drive the valve are optimised during initialisation.
3: DEFAULT STATE
Standard setting or recovery of factory settings and resetting of initialisation.
The positioner is set to „Default“by pressing the +or -and →→
→→
→keys (> 3 sec).
The positioner must be initialised again after having been set to „Default“.
All previous actuator parameters are deleted (initial state).
11: X-DIRECTION
Direction of manipulated variable.
Setting of the direction of action (rising or falling) of the display and position feedback.
12: ALARM FUNCTN
Activates or deactivates the alarm function.
The response threshold of the alarms (limit contacts) depends on the scale of POSITION (mechanical travel).
x = actual feedback value
i
Electropneumatic positioner: List of parameters
Display Function Parameter values Unit Factory settings
41: X-DISPLAY Display of position POSITION % POSITION
or flow FLOW
42: DEADBAND Size of dead zone auto auto
0.0...10.0
43: PROP GAIN Proportional gain 10...1000 100
(PD positioner) (Kp= 0,1...10)
44: DERIV TIME Differential time constant 10...1000 100
(PD positioner) Tv= 0,01 s ...1 s)
45: FIELDBUS Fieldbus control SETP.ANALOG SETP. ANALOG
SETP. BUS
46: RELEASE Software version V XX
(XX = two-digit figure)
AIR SUPPLY X-DIRECTION Assigned
Chamber A1 feedback position x
Air exhaust RISE 0 %
Air on 100 %
Air exhaust FALL 100 %
Air on 0 %

14
POSIMATIC
INSTALLATION
13: LEVEL ALARM 1
Response threshold for Alarm 1,
The digital output A1 (24VDC output) is switched as soon as the response threshold is reached.
14: LEVEL ALARM 2
Response threshold for Alarm 2.
The digital output A2 (24VDC output) is switched as soon as the response threshold is reached.
15: ERROR FUNCTN
Function of error output (24VDC output) ERR
ERROR: 16: ERROR TIME and 17: ERROR LEVEL exceeded.
ERROR + INACTIVE: Error monitoring or manual mode.
RANGE: Monitoring of the 4-20 mA setpoint input signal; selection over 18: RANGE FUNCTN
ERROR + RANGE: Monitoring of error and range.
ERR+RANGE+INAC: Activation of all error monitoring functions.
16: ERROR TIME
Monitoring time to set the error messages.
This value (in seconds) is set to define the period of time within which the positioner must be in a steady state. The
corresponding response threshold is preset with parameter 17.
The error output ERR is set as soon as the position is out of the response threshold (error level) for a period longer than the
monitoring time (error time).
When set to „Auto“, this period is 10×the initialisation response time.This is automatically calculated during initialisation.
17: ERROR LEVEL
Response threshold for setting the error output ERR.
Specification in percent of the admissible variable of deviation to trigger an error message.
When set to „Auto“, the response threshold is equal to the slow speed range.
The slow speed range is automatically calculated during initialisation.
18: RANGE FUNCTN
Monitoring of the setpoint signal range
Specification whether a RANGE signal is to be triggered if 4 mA is not reached (monitoring of rupture of cable) or 20 mA
is exceeded (monitoring of short circuit).
21: MIN POSITION
Start of manipulated variable limiting (YA)
This function corresponds to a mechanical limitation of the closing movement.
See Fig. 6: Limitation of lifting-/closing movement.
The minimum distance between MIN POSITION and MAX POSITION is 10 %.
Position State of digital output A1 State of digital output A2
x < Level Alarm1 < Level Alarm2 24V 0V
Level Alarm1 < x < Level Alarm2 0V 0V
Level Alarm1 < Level Alarm2 < x 0V 24V
min/max:
Position State of digital output A1 State of digital output A2
x < Level Alarm1 < Level Alarm2 24V 24V
Level Alarm1 < x < Level Alarm2 0V 24V
Level Alarm1 < Level Alarm2 < x 0V 0V
min/min:
Position State of digital output A1 State of digital output A2
x < Level Alarm1 < Level Alarm2 0V 0V
Level Alarm1 < x < Level Alarm2 24V 0V
Level Alarm1 < Level Alarm2 < x 24V 24V
max/max:

15
INSTALLATION
POSIMATIC
22: MAX POSITION
End of manipulated variable limiting (YE)
This function corresponds to a mechanical limitation of the lifting movement.
Parameters 21 and 22 limit the mechanical travel (from stop to stop) to the preset values.The
mechanical range of the actuator on the effective flow can thus be limited.
Fig. 6: Limitation of lifting and closing movement
i
24: SETP DIRECTN
Setpoint direction
Setting the setpoint direction specifies direction of action of the setpoint. It is mainly required for the split range mode and
for single acting actuators with „OPEN“safety position („control function 2“).
23: CLOSE TIGHT
Tight closing of manipulated variable
This function enables driving the valve at maximum actuator speed into its seat.The tight closing function can be activated
for one or both stop positions. CLOSE TIGHT is effective as soon as the setpoint is 0.5% above MIN POSITION or 0.5%
below MAX POSITION.
Since the setpoint range is set between 0% and 100% by 21 and 22, the threshold of activation of the tight closing
function in relation to the flow can be additionally adjusted downward with 21 and upward with 22.
Fig. 7: Tightly closing function
Fig. 8: Setpoint direction
Physical stroke x (%)
Position
Limited stroke x (%)
Flow
Unlimited stroke
Limited stroke
Setpoint w (%)
Setpoint w (%)
Stroke x (%)
Physical stroke x (%)
Setpoint w (%)

16
POSIMATIC
INSTALLATION
25: SETP RAMP
Setpoint ramp
The setpoint ramp is activated in the manual and automatic mode.It limits the speed of the actuator in the event of a quick
rate-of-change of the setpoint.
In the setting SETP RAMP = auto the slower of the two positioning times calculated during initialisation is used for the
setpoint ramp.
26: SPLIT START
Setpoint for start of split range (Fig. 9: Split range operation)
27: SPLIT END
Setpoint for end of split range
Parameters 26 and 27 together with parameter 24 limit the effective setpoint range. This is a solution for split range
applications with
❑ rising / falling
❑ falling / rising
❑ falling / falling
❑ rising / rising
characteristic curves.
Fig. 9: Split range operation (example)
28: SETP FUNCTN
Setpoint function (Fig. 10: Characteristic valve curves)
This function enables the linearisation of non-linear characteristic curves of valves and the mapping of arbitrary flow
characteristics of linear characteristic curves of valves.
The device is provided with four characteristic curves:
❑ linear
❑ equal percentage 1 : 25
❑ equal percentage 1 : 50
❑ free (factory setting: 1 : 25 inverse)
A curve with 11 points can be entered at 30: when “free”is selected.
30: FREE 0%
.
.
.
40: FREE 100%
steigend steigend
Setpoint range
Positioner 1:
rising
Setpoint range
Positioner 2:
rising
Setpoint w (%)
Stroke x (%)

17
INSTALLATION
POSIMATIC
A flow value can be assigned to every setpoint at distance intervals of 10%.These points create a polygon with 10 straight
lines resulting in an image of the characteristic curve of the valve.
The setpoints can only be entered at 28. SETP FUNCTN = free.
Fig. 10: Characteristic valve curves
41: X-DISPLAY
Standardisation of manipulated variable
Limiting the manipulated variable via 21: MIN POSITION (YA) and 22: MAX POSITION (YE) creates two different scales
for display and position feedback (POSITION or FLOW).
POSITION is the mechanical position (0 to 100%) between the hard stops of initialisation and is not influenced byYA orYE.
FLOW is the standardisation of the display (0 to 100%) to the range betweenYA and YE and to the characteristic curve of
the valve selected with 28: SETP FUNCTN.The setpoint (0 to 100%) is then related to this FLOW range (0 to 100%).
X-DISPLAY can be changed to refer the display and the position feedback (x) to the flow (also if characteristic curves of
valves are used).
In this case, YE, YA and the characteristic curve of the valve is taken into account.
42: DEADBAND
Dead zone of the positioner
The dead zone specifies the maximum allowable deviation between the feedback value and the setpoint.
If DEADBAND = auto, the dead zone is adjusted to the requirements of the control loop during initialisation. The fixed
preset value for the dead zone is used for all other discrete settings.
Jumpy or nervous movements of the valve may occur if the setting for DEADBAND is too small.
!
i
FREE (factory setting)
1:25 inverse
Setpoint w (%)
Stroke x (%)

18
POSIMATIC
INSTALLATION
43: PROP GAIN
Proportional gain
Setting of proportional gain Kp
PROP GAIN = 10 % ... 1000 % corresponds to Kp = 0.1...10
Factory setting: PROP GAIN = 100 % corresponds to Kp = 1
44: DERIV TIME
Pre-act time
Setting of the pre-act time Tv (period of time in which a defined manipulated variable is reached more quickly than with a
P controller because of the D component).
DERIV TIME = 10 % ... 1000 % corresponds to Tv = 0.01s...1s
Factory setting: DERIV TIME = 100 % corresponds to Tv = 0.1s
Changing the factory setting of 43/44 may result in uncontrolled hunting of the valve.
45: FIELD BUS
Selection of the setpoint input
❑ Analog
❑ Fieldbus (future option)
46: RELEASE
Current software version VXX
11. Error messages
!
PRESS ←
ERROR RUN 1
PRESS ←
ERROR RUN 2.1
PRESS ←
ERROR RUN 2.2
ADJUST NOZZLE(S)
Direction of action of the actuator cannot be
determined.
Reason:
a) No air supply
b) Wrong connection of position sensor
No zero adjustment possible.
Reason:
a) Faulty position sensor
b) Wrong position sensor (mechanical travel
does not correspond to the electrical
displacement of the position sensor).
No stroke adjustment possible.
Fieldbus:
a) Faulty position sensor
b) Wrong position sensor
c) Wrong connection of position sensor
(mechanical travel does not correspond to
the electrical displacement of the position
sensor).
Positioning time of valve under 1 second.
Connect pressure supply and check pneumatic
connections to the actuator.
Check assignment plan for correct terminal
connection (see fig. 3).
Drive valve by hand.
Display value x must change.
The display value must be > 2 % in CLOSE
position.
Drive valve by hand.
Display value x must change.
The display value must be < 98 % in OPEN
position.
Check assignment plan for correct terminal
connection (see fig 3).
Adjust flow restrictor D1 (single acting
actuator) and/or flow restrictors D1 and D2
(double acting actuators).
Turn clockwise for longer positioning time.
Display Possible cause Troubleshooting

19
INSTALLATION
POSIMATIC
Materials
Body Aluminium, coated
Display cover PMMA
Keyboard cover PMMA
Displacement
measuring system Alu, anodised
PEEK
PAI
NBR
Displacement measuring system
Linear version (potentiometer)
Assembly external
Stroke 0-30, 0-50, 0-75 mm
Connection pre-assembled cable
Rotary version (potentiometer)
Assembly external
Slew angle 0-100°
Connection pre-assembled cable
}
}
linear version
rotary version
12. Technical characteristics
General
Protection to EN 60529 IP 65
Dimensions L x W x H 160 x 90 x 84 mm
Weight 1,6 kg
Assembly position any
EU/EMC directive 89/336/EEC
EU low voltage directive 73/23/EEC
Emission EN 50081-2
Immunity EN 50082-2
Failsafe function In case of breakdown of
(single acting) electrical or pneumatic supply,
the valve is set into the safety
position by spring return and
exhaust action.
Electrical characteristics
- Power supply
Power supply 24 VDC ± 10%
Consumption ≤ 7,2 W (during operation)
≤ 2,4 W (in steady state)
Accuracy of
characteristic curves ≤ 1 %
- Input/output signals
Input signals a) 0-10V; b) 0/4...20 mA
Input resistance a) 200 kΩ; b) 250 Ω
Position feedback 0-10 V; 4...20 mA (optional)
Binary outputs 2 alarm outputs
1 error output
Fieldbus module (optional) Profibus-DP, Interbus
(future product)
Electrical connection
Power supply M16 cable entry
Input signal M16 cable entry
Operating conditions
Ambient temperature 0...60°C
Storage temperature 0...60°C
Control medium Air or neutral gas, filtered at
50 µm, lubricated or not
Pressure range 0 - 6 bar
Air rates 35 or 70 Nl/min. according to
type
Air consumption
(in steady state) 0 Nl/min
Functional characteristics
Control function 1. Spring in retracted position
2. Spring in extended position
3. Double acting
Operation - Automatic startup/tuning
- Automatic
- Manual
Parameters adjustable
(see list of parameters p. 5/6)

20
POSIMATIC
INSTALLATION
13. Assembly options with other actuators as series 290 / 390, consult us
Assembly of linear actuators
external NAMUR adapter V NAMUR adapter H
external NAMUR bracket
Assembly of rotary actuators
Table of contents
Languages:
Popular Valve Positioner manuals by other brands

Spirax Sarco
Spirax Sarco CVS10M Installation and maintenance instructions

Burkert
Burkert Positioner TopControl Basic 8696 quick start guide

FIAMA
FIAMA P1X manual

Ytc
Ytc YT-1000L installation manual

Samson
Samson 3730 Series Mounting and operating instructions

Genebre
Genebre 5951 00 Installation, operation and maintenance manual

Baelz Automatic
Baelz Automatic BA 7020 operating instructions

PowerFlow
PowerFlow 1600 Series manual

Genebre
Genebre 5810 00 Installation, operation & maintenance manual

Becker
Becker HPP-SB instruction manual

Burkert
Burkert TopControl Basic 8694 REV.2 quick start

Emerson
Emerson Fisher 3610J instruction manual