manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Westlock
  6. •
  7. Valve Positioner
  8. •
  9. Westlock Quantum 2800 Manual

Westlock Quantum 2800 Manual

29/4/06 TECHUK-23 REV 0Page 1of 6
Installation & Operating Instructions
Westlock Accutrak / Quantum 2800
With Optional MAGNUM Proximity Switches.
WARNING: The Accutrak / Quantum should
always be handled with care when the cover
is removed and wired to an electrical power
1. Attach the correct mounting bracket and
adapter to the Accutrak / Quantum housing
with the hardware provided.
2. Operate the actuator to full closed position.
3. Attach the Accutrak / Quantum and mounting
bracket to the actuator.
4. To remove the cover, unscrew the cover locking
bracket and unscrew cover in a counter clockwise
5. To adjust the sensor triggers, loosen the retaining
6. Operate actuator from one end of stroke to the
other several times to check switch operation.
WESTLOCK CONTROLS UK Ltd.
LLLLLLLLLLLLLLLLLLLLL
22 CHAPMAN WAY, TUNBRIDGE WELLS, KENT, TN2 3EF, ENGLAND. TEL: 44 (0)1892 516277 FAX: 44 (0)1892 516279
7. The correct wiring diagram for the product is
shown on the inside of the Accutrak / Quantum
cover. Please follow carefully.
FIELD WIRING & INSTALLATION.
8. Field wiring must be carried out in accordance
with site, local and National Electrical Codes.
green screw.
cable glands. When mounting the flameproof
enclosure in the hazardous area, only
9. The ground wire should be secured under the
10. The cerification applies to equipment without
11. All unused cable entries must be plugged with
suitably certified plugs that can maintain an
12. For ambient temperatures below -10€C and
above +60€C, use field wiring suitable for both
suitably certified cable glands, that can maintain
minimum and maximum ambient temperatures.
0539 II 2 GDT80€C
PRODUCT CERTIFICATION.
EEx d IIC T6
DEMKO 03 ATEX 135478X
an ingress protection level of IP67, shall be
used.
ingress protection level of IP67.
screw and slide up or down to suit.
Complete this for both sensors.
source.
direction.
29/4/06 TECHUK-23 REV 0Page 2of 6
WESTLOCK CONTROLS UK Ltd.
22 CHAPMAN WAY, TUNBRIDGE WELLS, KENT, TN2 3EF, ENGLAND. TEL: 44 (0)1892 516277 FAX: 44 (0)1892 516279
Installation & Operating Instructions
Westlock Accutrak / Quantum 2800
With Optional MAGNUM Proximity Switches.
Switch / Sensor Electrical Ratings.
Magnum Proximity Switch.
3A/120 VAC; 1.5A/240 VAC or 2A/24 VDC
Nomenclature for type 286 _
0 Unit without Switches fitted.
9 Unit with 1or 2 Magnum Proximity Switches
SPDT.
14. Replace the enclosure cover ensuring that the
cover locking bracket is replaced and secure.
Coil Voltages.
24, 48 & 110 VDC
110 / 120, 125 & 220 / 240 VAC.
13.The maximum surface temperature designation T85€C
is based on the maximum ambeient termperature
of 80€C and under dust layers upto 5mm thickness.
29/4/06 TECHUK-23 REV 0Page 3of 6
Installation & Operating Instructions
Westlock Accutrak / Quantum 2800
With Optional MAGNUM Proximity Switches.
Figure 2
Figure 1
Figure 4Figure 3
Figure 5
Operating and Maintenance Instructions for
Quantum Falcon Solenoid Valve
General Description
The Falcon solenoid valve incorporates elastomer static seals through which a shaped spool moves and are manufactured for 3 or 4way
operation. 3 way is normally used for pilot control of the other relay valves or for the operation of single acting cylinders. 4way is normally
used to control the action of double acting cylinders.
The seal spacer assembly forms individual annular chambers opposite each valve port and the grooved spool either closes or allows flow
between adjacent chambers, hence the position of the spool determines which ports are open or closed.
The spool is moved by way of a manually or mechanically operated mechanism normally against a return spring. Operation may be by
application or removal of a pilot air supply acting as a pilot piston. This form of control is utilized for electrical actuation where integral
solenoid valves control the pilot air supply.
Optional Features
N - No-Voltage Release (Latching)
With the coil first energized, the palm button is then manually moved and latched. The inward movement of the palm button causes the
valve to shift. When the coil is de-energized, the palm button and latching mechanism are automatically tripped, allowing the valve to
return to its original position. (1.2 Cv Valves only) See Fig. 1
R - No-Voltage Release (Non-Latching)
With the coil first energized, the palm button is then manually moved. The inward movement of the palm button causes the valve to shift.
When the coil is de-energized, the palm button automatically returns to its original position. (1.2 Cv Valves only) See Fig. 2
L - Manual Locking Override
Manually depress palm button and rotate clockwise for maintained con-
dition, must manually disengage to return to original position. See Fig. 3
M - Momentary Override
Spring return momentary pushtype, must hold in to actuate. See Fig. 4
E - External Pilot
The 1/8”NPT external pilot connection requires a separate auxiliary
pressure line to the valve. This feature should be used when the con-
trolled pressure is below the minimum 45 psi operating pressure.
H - Hex Drive Maintained Override
Insert allen key in hex head screw and rotate clockwise (4-5 turns) to
shift spool. Valve will stay put until hex head screw is rotated counter
clockwise (4-5 turns) back to original position. See Fig. 5
WESTLOCK CONTROLS UK Ltd.
22 CHAPMAN WAY, TUNBRIDGE WELLS, KENT, TN2 3EF, ENGLAND. TEL: 44 (0)1892 516277 FAX: 44 (0)1892 516279
29/4/06 TECHUK-23 REV 0Page 4of 6
Installation & Operating Instructions
Westlock Accutrak / Quantum 2800
With Optional MAGNUM Proximity Switches.
Specifications
Operating Pressure: 45-120 PSIG
Operating Temperature: -20€C to +85€C
Operating Media: Non Lubricated Filtered Air to 20 Microns
Field Wiring
Complete the electrical wiring in accordance with local and National Electrical Codes. The ground wire should be secure under the green
screw. Check all screws for tightness. If the installation is in a hazardous area, all electrical leads must be sealed with an approved com-
pound, in accordance with local and National Electrical Codes unless the switches are hermetically sealed. (NEC 5051-5)
Always check the nameplate to make sure the approval ratings coincide with the application.
CAUTION: To prevent ignition of hazardous atmospheres, replace cover before connecting the electrical circuits.
Keep cover tightly closed when in operation.
(Air Line) Designation
1/4”NPT air ports for inlet, outlet, and exhaust
Description of Operation: Solenoid De-energized -
air flows from Inlet Port 1 to Outlet Port 2 and
exhausts from Port 4 to Port 5. Solenoid Energized -
air flows from Inlet Port 1 to Outlet Port 4 and
exhausts from Port 2 to Port 3.
Description of Operation: Solenoid De-energized -
air flows from Outlet Port 2 to Exhaust Port 3.
Solenoid Energized - air flows from Inlet Port 1 to
Outlet Port 2.
(3.5 Cv valve has 1/2”NPT air ports)
Spring Return ValveSpring Return Valve
WESTLOCK CONTROLS UK Ltd.
22 CHAPMAN WAY, TUNBRIDGE WELLS, KENT, TN2 3EF, ENGLAND. TEL: 44 (0)1892 516277 FAX: 44 (0)1892 516279
(Air Line) Installation Considerations
Air Mains and lines should be large enough to avoid excessive pressure loss under conditions of maximum flow. Air lines should be
installed with as few restrictions as possible if the cost of compressed air is to be kept to a minimum. Sharp turns in piping should be
avoided for more effecient air flow and economical air power. It is advisable to pitch the mains in the direction of air flow so that both grav-
ity and air flow will carry the water to traps or water legs located at frequent intervals.
To help in preventing condensed moisture from reaching the point of usage, down pipes should never be taken directly from the bottom
of air pipes or mains. Connection should be made at the top of the main and a long radius return bend used.
29/4/06 TECHUK-23 REV 0Page 5of 6
Installation & Operating Instructions
Westlock Accutrak / Quantum 2800
With Optional MAGNUM Proximity Switches.
AIR FLOW
Pipe sizes are normally determined on semi empirical lines, basis for selection being an acceptable pressure drop e.g. not more than
10% of the applied pressure. In sizing pipes, consideration should be given to likely future demands, as a system will be inefficient if the
demand outgrows the supply. It is always better to over size mains as this will reduce air velocity and make water separation more
effective.
AIR SERVICE EQUIPMENT
The importance of proper filtration (20 Micron) and lubrication of the air supply to pneumatic equipment can never be over-emphasized
as a means of decreasing friction and preventing corrosion and wear due to moisture and abrasive solids being present in the air supply.
At higher pressures than recommended, pneumatic equipment can wear excessively with no significant increase in output and com-
pressed air is consequently wasted.
There is much to be gained, therefore, from providing pneumatic equipment with serviced air by including suitable air line filters, pressure
regulators and lubricants in the installation.
TUBES AND FITTINGS
The use of copper,stainless steel, nylon or polyethylene tube is recommended for piping up air circuits and equipment. As a general rule,
pipe threaded fittings should not be assembled to a specific torque because the torque required for a reliable joint varies with thread qual-
ity, port and fitting materials, sealant used, and other factors. The suggested method of assembling pipe threaded connections is to
assemble them finger tight and then wrench tighten further to a specified number of turns from finger tight. The assembly procedure
given below is for reference only, the fitting should not be over tightened for this will lead to distortion and most likely, complete valve fail-
ure.
1. Inspect port and connectors to ensure that the threads on both are free of dirt, burrs and excessive nicks.
2. Apply sealant/lubricant or Teflon tape to the male pipe threads. With any sealant tape, the first one or two threads should be left uncov-
ered to avoid system contamination.
3. Screw the connector into the port to the finger tight position.
4. Wrench tighten the connector aproximately 1 - 2 turns (to seal) from finger tight. again this is only reference - the fitting should NOT be
over tightened.
SPECIAL NOTICE
Delrin valve bodies are fitted with hellicoils therefore an extra effort should be made NOT to overtighten pipe fittings or retaining screws
(.5 - 1 turns from finger tight to seal). Overtightening will result in valve failure or pull hellicoils from valve body.
MAINTENANCE
Routine maintenance is usually confined to the periodic replenishment of Dow Corning III lubricant or equivalent to spool and spring.
WESTLOCK CONTROLS UK Ltd.
22 CHAPMAN WAY, TUNBRIDGE WELLS, KENT, TN2 3EF, ENGLAND. TEL: 44 (0)1892 516277 FAX: 44 (0)1892 516279
BUSHING
BU-10013
SPACER
VA-10048
O-RING
GS-20002
INDICATOR PIN
PILOT PISTON SEAL
GS-10017
PILOT END CAP
VA-10036
SCKT HD CAP SCREW
HD-10432
PILOT PISTON
VA-10050
SPOOL
VA-10477
SPRING
HD-10165
VALVE BODY
VA-10038
HD-10181
INDICATOR CAP
VA-10078
END CAP
VA-10063
SCKT HD CAP SCREW
HD-10348
BUSHING
BU-10013
O-RING
GS-20017
0-RING
GS-20018
O-RING
GS-20002
O-RING
GS-20020
O-RING
GS-20017
INDICATOR S/S WASHER
VA-10066
EXPLODED ASSEMBLY
OF .5 Cv 3 WAY FALCON
29/4/06 TECHUK-23 REV 0Page 6of 6
Installation & Operating Instructions
Westlock Accutrak / Quantum 2800
With Optional MAGNUM Proximity Switches.
WESTLOCK CONTROLS UK Ltd.
22 CHAPMAN WAY, TUNBRIDGE WELLS, KENT, TN2 3EF, ENGLAND. TEL: 44 (0)1892 516277 FAX: 44 (0)1892 516279
SCKT HD CAP SCREW
HD-10431
PILOT END CAP
VA-10043
O-RING
GS-20018
O-RING
GS-20002
O-RING
GS-20020
O-RING
GS-20021
PILOT PISTON SEAL
GS-10018
PILOT PISTON
VA-10051
PILOT PISTON SLEEVE
VA-10052
GUIDE WASHER
VA-10056
SPACER
VA-10049
BONDED SEAL
GS-10019
O-RING
GS-20022
SPOOL
VA-10054
INDICATOR PIN
VA-10068
SPRING
HD-10166
VALVE BODY
VA-10041
BUSHING
BU-10014
VA-10079
END CAP
VA-10065
SCKT HD CAP SCREW
HD-10431
O-RING
GS-20017
INDICATOR CAP
EXPLODED ASSEMBLY
OF 1.2 Cv 3 WAY FALCON
Solenoid Valve & Coil Specification.
Type:
Cv:
Material:
Connection:
Operating Pressure Range:
Orifice Size:
Supply Type:
Supply Voltage:
Consumption:
Operating Current:
3/2 WAY 5/2 WAY
0.5 0.7 1.21.1 3.5
Alu. Brass DelrinSt.St
1/4” NPT 1/2” NPT 1/4” BSP
45 - 120 PSIG
1/4”
VAC VDC
24 48 110 / 120 125 220 / 240
0.5 W 0.8 W 2.8 / 3.8 W 1.0 W 3.5 / 4.3 W
22mA 12.5mA 28 / 35mA 8.5mA 17.5 / 20mA

This manual suits for next models

1

Other Westlock Valve Positioner manuals

Westlock ICOT 5400 User manual

Westlock

Westlock ICOT 5400 User manual

Westlock 793 User instructions

Westlock

Westlock 793 User instructions

Westlock K20 User manual

Westlock

Westlock K20 User manual

Westlock ICoT PA Installation instructions

Westlock

Westlock ICoT PA Installation instructions

Westlock 2200 User manual

Westlock

Westlock 2200 User manual

Popular Valve Positioner manuals by other brands

MIEPL YTC YT-2600 Series product manual

MIEPL

MIEPL YTC YT-2600 Series product manual

Flowserve Logix 3200IQ Technical bulletin

Flowserve

Flowserve Logix 3200IQ Technical bulletin

Parker Daedal 412LXR Series product manual

Parker

Parker Daedal 412LXR Series product manual

Burkert 1067 instruction manual

Burkert

Burkert 1067 instruction manual

ARCA 824 series operating manual

ARCA

ARCA 824 series operating manual

ABB TZIDC operating instructions

ABB

ABB TZIDC operating instructions

Baker Hughes Masoneilan SVI3 Special instructions

Baker Hughes

Baker Hughes Masoneilan SVI3 Special instructions

Festo EXCM-40 -PF Series instructions

Festo

Festo EXCM-40 -PF Series instructions

GE FVP110 Maintenance manual

GE

GE FVP110 Maintenance manual

Samson 4785 Mounting and operating instructions

Samson

Samson 4785 Mounting and operating instructions

PMV D3 manual

PMV

PMV D3 manual

EBRO ARMATUREN EP 501 quick start

EBRO ARMATUREN

EBRO ARMATUREN EP 501 quick start

Burkert 8692 operating instructions

Burkert

Burkert 8692 operating instructions

tissin TS610 Series instruction manual

tissin

tissin TS610 Series instruction manual

ABB TZID operating instructions

ABB

ABB TZID operating instructions

Samson 3730 Series Mounting and operating instructions

Samson

Samson 3730 Series Mounting and operating instructions

Pepperl+Fuchs PGV -F200 -B6-V15B Series manual

Pepperl+Fuchs

Pepperl+Fuchs PGV -F200 -B6-V15B Series manual

Spirax Sarco EP5 Series Installation and maintenance instructions

Spirax Sarco

Spirax Sarco EP5 Series Installation and maintenance instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.