ascon KX Series Installation and operation manual

Ascon Tecnologic - KX Series - ENGINEERING MANUAL -Vr.4.0 PAG. 1
KX_
CONTROLLER AND
MINI-PROGRAMMER
Engineering Manual
Code : ISTR-MKX1-3ENG04 - Vr. 4.0 (ENG)
Ascon Tecnologic S.r.l.
Viale Indipendenza 56, 27029 Vigevano (PV) - ITALY
Tel.: +39 0381 69871/FAX: +39 0381 698730
www.ascontecnologic.com
e-mail: [email protected]
1. OUTLINE DIMENSIONS (mm)
96
48 61.9
1411
40 14.5
18
8
DI1 DI2
Removable
terminals
Instrument with non-removable terminals
2. CONNECTION DIAGRAM
D -
D +
+ + +
++
Out1
Out2
Out3
C
NO
+
-
+
-
Out4
RS485
12 VDC/20 mA max.
Relay Out 1: 4 (4) A/250 VAC
Relay Out 2, 3: 2 (1) A/250 VAC (*)
SSR Out 1, 2, 3: 10 VDC/15 mA
Out1:
0/4... 20 mA, 0/2... 10V (KX3 only)
SSR Out4: 12 VDC/20 mA
* KX3 servodrive models: both Out2 and Out3
are to be selected as “M” in Configuration code;
Out2: open, Out3: close
Passive TX, 2 wires, 4... 20 mA
Pt1000
Pt100
TC
4... 20 mA (active)
0/12... 60 mV, 0/1... 5V, 0/2... 10V
-
Out2
Out3
C
NO
+
-
C
NO
+
-
DI1
DI2
Power
supply
Analogue
Input
Open
Close
KX3 only
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
2.1 MOUNTING REQUIREMENTS
This instrument is intended for permanent installation, for
indoor use only, in an electrical panel which encloses the
rear housing, exposed terminals and wiring on the back.
Select a mounting location having the following characteristics:
1. It should be easily accessible;
2. There is minimum vibrations and no impact;
3. There are no corrosive gases;
4. There are no water or other fluids (i.e. condensation);
5. The ambient temperature is in accordance with the
operative temperature (0... 50°C);
6. The relative humidity is in accordance with the instrument
specifications (20... 85%);
The instrument can be mounted on panel with a maximum
thickness of 15 mm.
When the maximum front protection (IP65) is desired, the
optional gasket must be monted.
2.2 GENERAL NOTES ABOUT WIRING
1. Do not run input wires together with power cables.
2. External components (like zener barriers, etc.) connected
between sensor and input terminals may cause errors in
measurement due to excessive and/or not balanced line
resistance or possible leakage currents.

Ascon Tecnologic - KX Series - ENGINEERING MANUAL -Vr.4.0 PAG. 2
3. When a shielded cable is used, it should be connected at
one point only.
4. Pay attention to the line resistance; a high line resistance
may cause measurement errors.
2.3 INPUTS
2.3.1 Termocouple Input
1
2
+
_
External resistance: 100Ωmax., maximum error 25 mV.
Cold junction: automatic compensation between 0... 50°C.
Cold junction accuracy: 0.05°C/°C after a warm-up of
20 minutes.
Input impedance: > 1 MΩ.
Calibration: According to EN 60584-1.
Note: For TC wiring use proper compensating cable
preferable shielded.
2.3.2 Infrared Sensor Input
Exergen
1
2
+
_
External resistance: Not relevant.
Cold junction: automatic Compensation between 0... 50°C.
Cold junction accuracy: 0.05°C/°C.
Input impedance: > 1 MΩ.
2.3.3 RTD Pt 100 Input
3
RTD
1
2
Input circuit: Current injection (150 µA).
Line resistance: Automatic compensation up to 20Ω/wire
with maximum error ±0.1% of the input span.
Calibration: According to EN 60751/A2.
Note: The resistance of the 3 wires must be the same.
2.3.4 RTD Pt 1000, NTC and PTC Input
2
3
Pt1000
Line resistance: Not compensated.
Pt 1000 input circuit: Current injection (15 µA).
Pt 1000 calibration: According to EN 60751/A2.
2.3.5 V and mV Input
mV
V+
_
+
_
1
2
Input impedance: > 1 MΩfor mV Input
500 kΩfor Volt Input.
2.3.6 mA Input
0/4... 20 mA input wiring for passive transmitter
using the auxiliary pws
+
_
4...20 mA
Passive
transmitter
4
1
Input impedance: < 53Ω.
Internal auxiliary PWS: 12 VDC (±10%), 20 mA max..
0/4... 20 mA input wiring for passive transmitter
using an external pws
+
_
+
_
1
2
0/4...20 mA
Passive
transmitter
_
External
PWS
+
0/4... 20 mA input wiring for active transmitter
0/4...20 mA
Active
transmitter +
_
+
_
1
2
2.3.7 Logic Inputs
Safety notes:
–Do not run logic input wiring together with power cables;
–The instrument needs 150 ms to recognize a contact
status variation;
–Logic inputs are NOT isolated by the measuring input.
A double or reinforced isolation between logic inputs and
power line must be assured by the external elements.
Logic input driven by dry contact
Digital
input 1
4
5
6
Digital
input 2
Maximum contact resistance: 100Ω.
Contact rating: DI1 = 10 V, 6 mA;
DI2 = 12 V, 30 mA.

Ascon Tecnologic - KX Series - ENGINEERING MANUAL -Vr.4.0 PAG. 3
Logic inputs driven by 24 VDC
Digital
input 1
4
5
6
Digital
input 2 +
+
-
Logic status 1: 6... 24 VDC;
Logic status 0: 0... 3 VDC.
2.4 OUTPUTS
Safety notes:
–To avoid electrical shocks, connect power line at last.
–For supply connections use No. 16 AWG or larger wires
rated for at last 75°C.
–Use copper conductors only.
–SSR outputs are not isolated. A reinforced isolation must
be assured by the external solid state relays.
–For SSR, mA and V outputs if the line length is longer than
30 m use a shielded wire.
WARNING! Before connecting the output actuators,
we recommend to configure the parameters to
suit your application (e.g.: input type, Control
strategy, alarms, etc.).
2.4.1 Output 1 (OP1)
Relay Output
C
NO
9
10
Contact rating: •4A/250Vcosj=1;
•2A/250Vcosj=0.4.
Operation: 1 x 105.
SSR Output
SSR
+
-
9
10
Logic level 0: Vout < 0.5 VDC;
Logic level 1: 12 V ±20%, 15 mA max..
Current Analogue Output
mA
+
-
9
10
mA output: 0/4... 20 mA, galvanically isolated,
maximum load resistance; 600Ω.
Voltage Analogue Output
V
+
-
9
10
mA output:, 0/2... 10 V, galvanically isolated,
minimum load resistance; 500Ω.
2.4.2 Output 2 (OP2)
Relay Output
C
NO
11
12
Contact rating: •2A/250Vcosj= 1;
•1A/250Vcosj= 0.4.
Operation: 1 x 105.
SSR Output
SSR
-
+
11
12
Logic level 0: Vout < 0.5 VDC;
Logic level 1: 12 V ± 20%, 15 mA max..
2.4.3 Output 3 (OP3)
Relay Output
C
NO
13
14
Contact rating: •2A/250Vcosj= 1;
•1A/250Vcosj= 0.4.
Operation: 1 x 105.
SSR Output
SSR
-
+
13
14
Logic level 0: Vout < 0.5 VDC;
Logic level 1: 12 V ± 20%, 15 mA max..
2.4.4 Output 2 and Output 3 Servomotor Drive
Out2
Out3
Open
Close
C
NO
11
12
C
NO
13
14
OP2/3 contact rating: •2A/250Vcosj= 1;
•1A/250Vcosj= 0.4.
Operation: 1 x 105.
2.4.5 Output 4 (OP4)
SSR Output
SSR
+
-
4
5
Logic level 0: Vout < 0.5 VDC;
Logic level 1: 12 V ± 20%, 20 mA max..
Note: Overload protected.

Ascon Tecnologic - KX Series - ENGINEERING MANUAL -Vr.4.0 PAG. 4
2.5 SERIAL INTERFACE
D +
D -
D +
D -
D +
D -
D +
D -
RS-485
7
8
Interface type: Isolated (50 V) RS-485;
Voltage levels: According to EIA standard;
Protocol type: MODBUS RTU;
Byte format: 8 bit with no parity;
Stop bit: 1 (one);
Baud rate:
Programmable between 1200... 38400 baud;
Address: Programmable between 1... 255.
Notes: 1. RS-485 interface allows to connect up to 30
devices with one remote master unit.
2. The cable length must not exceed 1.5 km at
9600 baud.
2.6 POWER SUPPLY
Power Supply
Neutral
Line
15
16
Supply Voltage: •24VAC/DC(±10%);
•100...240VAC(-15...+10%).
Notes: 1. Before connecting the instrument to the power
line, make sure that line voltage is equal to the
voltage shown on the identification label;
2. The polarity of the power supply has no importance;
3. The power supply input is NOT fuse protected.
Please, provide a T type 1A, 250 V fuse externally.
4. When the instrument is powered by the A01 key,
the outputs are NOT supplied and the instrument
can show the “ouLd” (Out 4 Overload) indication.
3. TECHNICAL CHARACTERISTICS
3.1 TECHNICAL SPECIFICATION
Case:
Plastic, self-extinguishing degree: V-0 according to UL 94;
Front protection: IP 65 (when the optional panel gasket is
mounted) for indoor locations according to EN 60070-1;
Terminals protection: IP 20 according to EN 60070-1;
Installation: Panel mounting;
Terminal block:
16 M3 screw terminals for cables of
0.25... 2.5 mm2(AWG22... AWG14) with connection diagram;
Dimensions: 48 x 96, depth 75.9 mm, (1.77 x 3.78 x 2.99 in.)
Panel cutout: 45(+0.6) x 89(+0.6) mm [1.78(+0.023) x 3.5(+0.023) in.]
Weight: 160 g max..
Power supply: • 24 VAC/DC (±10% of the nominal value);
•
100... 240 VAC (-15... +10% of the nominal
value);
Power consumption: 5 VA max.;
Insulation voltage: 2300 V rms according to EN 61010-1;
Display updating time: 500 ms;
Sampling time: 130 ms;
Resolution: 30000 counts;
Total Accuracy: ±0.5% F.S.V. ±1 digit @ 25°C of room
temperature;
Electromagnetic compatibility and safety requirements
Compliance: directive EMC 2004/108/CE (EN 61326-1),
directive LV 2006/95/CE (EN 61010-1);
Installation category: II;
Pollution category: 2;
Temperature drift: It is part of the global accuracy;
Operating temperature: 0... 50°C (32... 122°F);
Storage temperature: -30... +70°C (-22... +158°F);
Humidity: 20... 85% RH, not condensing.
3.2 HOW TO ORDER
Model
KX1 - = Controller
KX1T = Controller+ timer
KX3 -= Controller
KX3T = Controller+ timer
KX3P = Controller + timer + programmer
Power supply
H= 100... 240 VAC
L= 24 VAC/DC
Analoue input + Digital Input DI1 (standard)
C= J, K, R, S, T, PT100, PT 1000 (2 wires), mA, mV, V
E= J, K, R, S, T, NTC, PTC, mA, mV, V
Output 1
I= 0/4... 20 mA, 0/2... 10 V (KX3 only)
R= Relay SPST 4 A (resistive load)
O= VDC for SSR
Output 3
-= Not available
R= Relay SPST 2 A (resistive load)
O= VDC for SSR
M= Relay SPST 2 A(servomotor drive KX3 only)(note)
Input/Output 4
D=
Output 4 (VDC for SSR)/Pow. Supply/Dig. Input DI2
Serial Communications
-= TTL Modbus
S= RS485 Modbus + TTL Modbus
Connection type
-= Standard (screw terminals not removable)
E= Removable screw terminals
M= Removable spring terminals
N = Removable terminals (the fixed part only)
Output 2
-= Not available
R= Relay SPST 2 A (resistive load)
O= VDC for SSR
M= Relay SPST 2 A(servomotor drive KX3 only)(note)
Note: For servomotor drive, both Output 2 and Output 3
codes must be selected as “M”.

Ascon Tecnologic - KX Line - ENGINEERING MANUAL -Vr.4.0 PAG. 5
4. CONFIGURATION PROCEDURE
4.1 INTRODUCTION
When the instrument is powered, it starts immediately to work
according to the parameters values loaded in its memory.
The instrument behaviour and its performance are governed
by the value of the stored parameters.
At the first start up the instrument will use a “default”
parameter set (factory parameter set); this set is a generic
one (e.g. a TC J input is programmed).
WARNING! Before connecting the output actuators,
we recommend to configure the parameters to
suit your application (e.g.: input type, Control
strategy, alarms, etc.).
To change these parameters you need to enter the
“Configuration mode”.
4.2 INSTRUMENT BEHAVIOUR AT
POWER ON
At power ON the instrument can start in one of the following
mode depending on its configuration:
Auto mode without program functions.
–The upper display will show the measured value;
–The lower display will show the Set point value;
–The decimal figure of the less significant digit of the lower
display is OFF;
–The instrument is performing the standard closed loop control.
Manual mode (OPLO).
–The upper display will show the measured value;
–The lower display will show alternately the power output
and the message oPLo and the MAN LED will lite;
–The instrument does not perform Automatic control;
–The control output is equal to 0% and can be manually
modified by and buttons.
Stand by mode (St.bY).
–The upper display will show the measured value;
–The lower display will show alternately the set point value
and the message St.bY or od;
–The instrument does not perform any control (the control
outputs are OFF);
–The instrument is working as an indicator.
Auto mode with automatic program start up.
–The upper display will show the measured value
–The lower display will show one of the following information;
• The operative set point (when it is performing a ramp)
• The time of the segment in progress (when it is perfor-
ming a soak);
• The set point value alternate with the message St.bY;
–In all cases, the decimal figure of the less significant digit
of the lower display is lit.
We define all the above described conditions as
“Standard Display”.
4.3 HOW TO ENTER THE
“CONFIGURATION MODES”
Note: The KX Line is equipped with two different
“configuration” methods:
A) The “code” configuration method;
B) The “complete” configuration method.
The “code” configuration method is really fast but modifies
only the most common configuration parameters.
The “complete” configuration method allows to take
advantage of all instrument features, giving more capabilities
it requires more actions and time.
Note that you can take advantage by both methods because
if
you use the code configuration and then you enter in the
complete configuration, all selections made by code are still valid.
In both cases the instrument have one complete parameter set.
We call this set “configuration parameter set” (or
“configuration parameters”).
When code configuration method is used all the parameters
not modified by the code will maintain their default values.
In both cases the access to the configuration parameters is
protected by a password (a specific password for each method).
Note: The instrument will show only the parameters consis-
tent with the specific hardware and in accordance with
the value assigned to the previous parameters
(e.g.: if you set an output as “not used” the instrument
will mask all other parameters related to this output).
4.3.1 “Code” configuration procedure
The controller configuration (Input type, Control mode, etc.)
can be made entering two 4-digit codes.
Before to enter into code configuration we suggest you to
prepare the two codes according to the tables that follow.
Notes: 1. During the Code configuration procedure there is
no timeout.
2. To leave, at any time, the Configuration session
without
saving the settings made, press the
button.
To enter into code configuration proceed as follows:
1. Push the button for more than 3 seconds.
The upper display will show PASS while the lower display
will show 0;
2. Using and buttons set the password programmed
in parameter [121] PAS4. The factory default password
for Code configuration is 300;
3. Push the button;
If the password is correct the instrument will show one of
the following conditions:
• If no code is present, the display shows codE on the
upper display and oFF on the lower display.
Push the button to continue.
The upper display will flash cod1 while the lower display
shows 0000.
• If a previous code was stored, the upper display will
flash cod1 while the lower display shows the value of
cod1 stored in memory.

Ascon Tecnologic - KX Line - ENGINEERING MANUAL -Vr.4.0 PAG. 6
4. Using and buttons set the code 1 value
according to the following tables.
LMNO
Prepare your code 1
Input Type and Range L M
TC J -50... +1000°C 0 0
TC K -50... +1370°C 0 1
TC S -50... 1760°C 0 2
TC R -50... +1760°C 0 3
TC T -70... +400°C 0 4
Infrared J -50... +785°C 0 5
Infrared K -50... +785°C 0 6
PT 100/PTC KTY81-121 -200... +850°C/-55... +150°C 0 7
PT 1000/NTC 103-AT2 -200... +850°C/-50... +110°C 0 8
Linear 0... 60 mV 0 9
Linear 12... 60 mV 1 0
Linear 0... 20 mA (this selection forces Out 4 = TX) 1 1
Linear 4... 20 mA (this selection forces Out 4 = TX) 1 2
Linear 0... 5 V 1 3
Linear 1... 5 V 1 4
Linear 0... 10 V 1 5
Linear 2... 10 V 1 6
TC J -58... +1832°F 1 7
TC K -58... +2498°F 1 8
TC S -58... 3200°F 1 9
TC R -58... +3200°F 2 0
TC T -94... +752°F 2 1
Infrared J -58... +1445°F 2 2
Infrared K -58... +1445°F 2 3
PT 100/PTC KTY81-121 -328... +1562°F/-67... +302°F 2 4
PT 1000/NTC 103-AT2 -328... +1562°F/-58... +230°F 2 5
LMNO
c%d1:
Control mode OP1 OP2 OP3 OP4 N O
ON/OFF heating = H H AL1 AL2 AL3 0 0
NU AL1 AL2 H 0 1
ON/OFF cooling = C C AL1 AL2 AL3 0 2
NU AL1 AL2 C 0 3
ON/OFF with neutral zone
(H/C)
H C AL2 AL3 0 4
H AL1 AL2 C 0 5
C H AL2 AL3 0 6
NU H AL2 C 0 7
C AL1 AL2 H 0 8
NU C AL2 H 0 9
PID heating = H H AL1 AL2 AL3 1 0
NU AL1 AL2 H 1 1
PID cooling = C C AL1 AL2 AL3 1 2
NU AL1 AL2 C 1 3
PID double action (H/C)
H C AL2 AL3 1 4
H AL1 AL2 C 1 5
C H AL2 AL3 1 6
NU H AL2 C 1 7
C AL1 AL2 H 1 8
NU C AL2 H 1 9
Servomotor PID heating NU UP down AL3 2 0
Servomotor PID cooling NU UP down AL3 2 1
Note: To select the PID control mode for servodrive
(Nplus O= 20 or 21), in the order code both Output 2
and Output 3 codes must be selected as “M” (see
“How to order” pargraph).
5. Push the button.
The upper display shows cod2 flashing while the lower
display shows 0000 or the cod2 value stored in memory.
6. Using and buttons set the code 2 value
according to the following tables.
PQRS
Prepare your code 2
Alarm 3 R
Alarm 2 Q
Alarm 1 P
Not used 000
Sensor break 111
Absolute High 222
Low 333
Absolute High/Low External High/Low 444
Internal High/Low 555
Deviation Deviation high 666
Deviation low 777
Band External band 888
Internal band 999
PQRS
c%d2:
Auxiliary functions activation S
None 0
Wattmeter (instantaneous power expressed in W) 1
Wattmeter (energy expressed in Wh) 2
Absolute worked time (expressed in days) 3
Absolute worked time (expressed in hours) 4
7. Push the button.
If the just entered codes are accepted, the upper display
shows code flashing while the lower display shows good.
8. Push the button to save the configuration code and
exit the Code configuration procedure.
Note: After using the “Code configuration” method, it will
always be possible to modify the parameters using the
“Complete configuration” method. If the value of a
parameter among those included in the configuration
codes (cod1 - cod2) gets modified, the instrument
will acquire the change while maintaining all the other
parameters.
WARNING! After a parameter change made as described
in the previous “Note”, when retrieving the
configuration codes (cod1 - cod2), the lower
display will show “oFF” to alert the operator that
one of the parameters has been changed.

Ascon Tecnologic - KX Line - ENGINEERING MANUAL -Vr.4.0 PAG. 7
4.3.2 Complete configuration procedure
The configuration parameters are collected in various
groups. Every group defines all parameters related with a
specific function (e.g.: control, alarms, output functions).
1. Push the button for more than 5 seconds.
The upper display will show PASS while the lower display
will show 0.
2. Using
and
buttons set the programmed password.
Notes: 1. The factory default password for configuration
parameters is equal to 30.
2. During parameter modification the instrument
continue to perform the control.
In certain conditions, when a configuration chan-
ge can produce a heavy bump to the process, it is
advisable to temporarily stop the controller from
controlling during the programming procedure
(control output will be OFF).
A password equal to 2000 + the programmed
value (e.g. 2000 + 30 = 2030).
The control will restart automatically when the
configuration procedure will be manually closed.
3. Push the button
If the password is correct the display will show the acronym
of the first parameter group preceded by the symbol:
].
In other words the upper display will show: pinp
(group of the Input parameters).
The instrument is in configuration mode.
4.3.3 How to exit the “Configuration mode”
Push button for more than 5 seconds, the instrument will
come back to the “standard display”.
4.4 KEYBOARD FUNCTIONS DURING
PARAMETER CHANGING
A short press allows to exit from the current parameter
group and select a new parameter group.
A long press allows you to close the configuration
parameter procedure (the instrument will come back
to the “standard display”).
When the upper display is showing a group and the
lower display is blank, this key allows to enter in the
selected group.
When the upper display is showing a parameter and
the lower display is showing its value, this key allows
to store the selected value for the current parameter
and access the next parameter within the same group.
Allows to increase the value of the selected parameter.
Allows to decrease the value of the selected parameter.
+ These two keys allow to return to the previous
group. Proceed as follows:
Push the button and maintaining the pressure,
then push the button; release both the buttons.
Note: The group selection is cyclic as well as the selection
of the parameters in a group.
4.5 FACTORY RESET - DEFAULT
PARAMETERS LOADING PROCEDURE
Sometime, e.g. when you re-configure an instrument
previously used for other works or from other people or when
you have made too many errors during configuration and
you decided to re-configure the instrument, it is possible to
restore the factory configuration.
This action allows to put the instrument in a defined
condition (the same it was at the first power ON).
The default data are those typical values loaded in the
instrument prior to ship it from factory.
To load the factory default parameter set, proceed as follows:
1. Press the button for more than 5 seconds;
2. The upper display will show PASS while the lower display
shows 0;
3. Using and buttons set the value -481;
4. Push button;
5. The instrument will turn OFF all LEDs for a few seconds,
then the upper display will show dFLt (default) and then
all LEDs are turned ON for 2 seconds. At this point the
instrument restarts as for a new power ON.
The procedure is complete.
Note: The complete list of the default parameters is available
in Appendix A.
4.6 CONFIGURING ALL THE PARAMETERS
In the following pages we will describe all the parameters of
the instrument. However, the instrument will only show the
parameters applicable to its hardware options in accordance
with the specific instrument configuration (i.e. setting AL1t
[Alarm 1 type] to nonE [not used], all parameters related to
alarm 1 will be skipped).
]inP Group - Main and auxiliary input configuration
[1] SEnS - Input type
Available: Always
Range: • When the code of the input type is equal to C
(see “How to order” paragraph).
J TC J
crAL TC K
S TC S
r TC R
t TC T
ir.J Exergen IRS J
ir.cA Exergen IRS K
Pt1 RTD Pt 100
Pt10 RTD Pt 1000
0.60 0... 60 mV linear
12.60 12... 60 mV linear
0.20 0... 20 mA linear
4.20 4... 20 mA linear
0.5 0... 5 V linear
1.5 1... 5 V linear
0.10 0... 10 V linear
2.10 2... 10 V linear
• When the code of the input type is equal to E
(see “How to order” paragraph).
J TC J
crAL TC K

Ascon Tecnologic - KX Line - ENGINEERING MANUAL -Vr.4.0 PAG. 8
S TC S
r TC R
t TC T
ir.J Exergen IRS J
ir.cA Exergen IRS K
Ptc PTC
ntc NTC
0.60 0... 60 mV linear
12.60 12... 60 mV linear
0.20 0... 20 mA linear
4.20 4... 20 mA linear
0.5 0... 5 V linear
1.5 1... 5 V linear
0.10 0... 10 V linear
2.10 2... 10 V linear
Notes: 1. When a TC input is selected and a decimal figure
is programmed (see the next parameter) the max.
displayed value becomes 999.9°C or 999.9°F.
2. Every change of the SEnS parameter setting
will force the [2] dP = 0 and it will change all
parameters related with dP (e.g. set points,
proportional band, etc.).
[2] dP - Decimal point position
Available: Always.
Range: When [1] SenS = Linear input: 0... 3.
When [1] SenS different from linear input: 0 or 1.
Note: Every change of the dP parameter setting will produce
a change of the parameters related with it (e.g.: set
points, proportional band, etc.).
[3] SSc - Initial scale read-out for linear inputs
Available: when a linear input is selected by [1] SenS.
Range: -1999... 9999.
Notes: 1. SSc allows the scaling of the analogue input to
set the minimum displayed/measured value.
The instrument will show a measured value up to
5% less then SSc value and than it will show an
underrange error.
2. It is possible to set a initial scale read-out higher
then the full scale read-out in order to obtain a
reverse read-out scaling
E.g.:
0 mA = 0 mBar and 20 mA = -1000 mBar (vacuum).
[4] FSc - Full scale read-out for linear input
Available: When a linear input is selected by [1] SenS.
Range: -1999... 9999
Notes: 1. Fsc allows the scaling of the analogue input to set
the maximum displayed/measured value.
The instrument will show a measured value up to
5% higher than [4] FSc value and then it will show
an overrange error.
2. It is possible to set a full scale read-out lower
than the initial scale read-out in order to obtain a
reverse read-out scaling.
E.g.:
0 mA = 0 mBar and 20 mA = -1000 mBar (vacuum).
[5] unit - Engineering unit
Available: When a temperature sensor is selected by [1]
SenS parameter.
Range: °c = Centigrade
°F = Fahrenheit
[6] FiL - Digital filter on the measured value
Available: Always
Range: oFF (No filter) 0.1 to 20.0 s
Note: This is a first order digital filter applied on the
measured value. For this reason it will affect the
measured value but also the control action and the
alarms behaviour.
[7] inE - Selection of the Sensor Out of Range type
that will enable the safety output value
Available: Always
Range: our = When an overrange or an underrange is
detected, the power output will be forced to
the value of [8] oPE parameter.
or = When an overrange is detected, the power
output will be forced to the value of [8] oPE
parameter.
ur = When an underrange is detected, the po-
wer output will be forced to the value of [8]
oPE parameter.
[8] oPE - Safety output value
Available: Always
Range: -100... 100 % (of the output).
Notes: 1. When the instrument is programmed with one
control action only (heat or cool), setting a
value outside of the available output range, the
instrument will use Zero.
E.g.: When heat action only has been
programmed, and oPE is equal to -50% (cooling)
the instrument will use the zero value.
2. When ON/OFF control is programmed and an out
of range is detected, the instrument will perform
the safety output value using a fixed cycle time
equal to 20 seconds.
[9] io4.F - I/O4 function selection
Available: Always
Range: on = The out 4 will be always ON (used as a
transmitter power supply);
out4 = used as digital output 4;
dG2.c = Digital input 2 for contact closure;
dG2.U= Digital input 2 driven by 12... 24 VDC.
Notes: 1. Setting [9] io4.F = dG2.C o dG2V, the [24] O4F
parameter becomes not visible while [11] diF2
parameter will become visible.
2. Setting [9] io4F = on the [24] O4F parameter and
the [11]diF2 parameter will NOT be visible.
3. Setting [9] io4F different from dG2.c or dG2.U,
the instrument will force [12] diF2 parameter
equal to nonE
If [11] diF1 was equal to (SP4 or UPDN) it will be
forced to nonE.
4. The transfer from [9] io4F = on to [9] io4F = Out
4 will make the [24] O4F parameter visible equal
to nonE.
[10] diF1 - Digital input 1 function
Available: Always.
Range: oFF = No function
1Alarm Reset [status]
2Alarm acknowledge (ACK) [status].
3Hold of the measured value [status].
4Stand by mode of the instrument [status]

Ascon Tecnologic - KX Line - ENGINEERING MANUAL -Vr.4.0 PAG. 9
When the contact is closed the instrument oper-
ates in stand by mode.
5Manual mode
6HEAt with SP1 and CooL with “SP2” [status]
(see “Note about digital inputs”)
7Timer Run/Hold/Reset [transition]
Short closure allows to start timer execution
and to suspend it while a long closure (longer
than 10 seconds) allows to reset the timer.
8Timer Run [transition] a short closure allows to
start timer execution.
9Timer reset [transition] a short closure allows to
reset timer count.
10 Timer run/hold [Status]
- Contact closure = timer RUN
- Contact open = timer Hold
11 Timer run/reset [status]
12
Timer run/reset with a special “lock” at the end of
the time count (in order to restart the time count
the instrument must detect a run command co-
ming from serial link keyboard or digital input 2).
13 Program Run [transition]
The first closure allows to start program execu-
tion but a second closure restart the program
execution from the beginning.
14 Program Reset [transition]
A contact closure allows to reset program execution.
15 Program Hold [transition]
The first closure allows to hold program exe-
cution and a second closure continue program
execution.
16 Program Run/Hold [status]. When the contact
is closed the program is running.
17 Program Run/Reset [status]
Contact closed - Program run
Contact open - Program reset
18 Sequential set point selection [transition]
(see “Note about digital inputs”)
19 SP1/SP2 selection [status]
20 Binary selection of the set point made by digital
input 1 (less significant bit) and digital input 2
(most significant bit) [status].
21 Digital input 1 will work in parallel with but-
ton while digital input 2 will work in parallel with
the button.
Note: When [11] diF2 is not available the item 20 and 21 are
not visible.
[11] diF2 - Digital input 2 function
Available: When [9] Io4.F = diG2.
Range: oFF = No function
1Alarm Reset [status]
2Alarm acknowledge (ACK) [status].
3Hold of the measured value [status].
4Stand by mode of the instrument [status]
When the contact is closed the instrument ope-
rates in stand by mode.
5Manual mode
6HEAt with SP1 and CooL with “SP2” [status]
(see “Note about digital inputs”)
7Timer Run/Hold/Reset [transition]
Short closure allows to start timer execution
and to suspend it while a long closure (longer
than 10 seconds) allows to reset the timer.
8Timer Run [transition] a short closure allows to
start timer execution.
9Timer reset [transition] a short closure allows to
reset timer count.
10 Timer run/hold [Status]
- Contact closure = timer RUN
- Contact opend = timer Hold
11 Timer run/reset [status]
12 Timer run/reset with a special “lock” at the end
of the time count (in order to restart the time
count the instrument must detect a run com-
mand coming from serial link keyboard or digital
input 2).
13 Program Run [transition]
The first closure allows to start program execu-
tion but a second closure restart the program
execution from the beginning.
14 Program Reset [transition]
A contact closure allows to reset program execution.
15 Program Hold [transition]
The first closure allows to hold program execution
and a second closure continue program execution.
16 Program Run/Hold [status]
When the contact is closed the program is running.
17 Program Run/Reset [status]
Contact closed - Program run
Contact open - Program reset
18 Sequential set point selection [transition]
(see “Note about digital inputs”)
19 SP1/SP2 selection [status]
20 Binary selection of the set point made by digital
input 1 (less significant bit) and digital input 2
(most significant bit) [status].
21 Digital input 1 will work in parallel with the
button while digital input 2 will work in parallel
with the button.
Notes: 1. When [10] diF1 or [11] diF2 (e.g. diF1) are equal
to 6 the instrument operates as follows:
• When the contact is open, the control action is
an heating action and the active set point is SP.
• When the contact is closed, the control
action is a cooling action and the active set
point is SP2.
2. When [10] diF1 = 20, [11] diF2 setting is forced to
20 and diF2 cannot perform another function.
3. When [10] diF1 = 20 and [11] diF2 = 20, the set
point selection will be in accordance with the
following table:
Dig In1 Dig. In2 Operative set point
Off Off Set point 1
On Off Set point 2
Off On Set point 3
On On Set point 4
4. When [10] diF1 is equal to 21, [11] diF2 setting
is forced to up.du (21 value) and cannot perform
another function.
5. When a “Sequential set point selection” is used
(diF1 or diF2 = 18), every closure of of the logic
input increase the value of SPAT (active set point)
of one step.
The selection is cyclic:
SP -> SP2 -> SP3 -> SP4.

Ascon Tecnologic - KX Line - ENGINEERING MANUAL -Vr.4.0 PAG. 10
]out Group - Output parameters
[12] o1.t - Out 1 type (KX3 only)
Available: When the out 1 is a linear output.
Range: 0-20 = 0... 20 mA
4-20 = 4... 20 mA
0-10 = 0... 10 V
2-10 = 2... 10 V
[13] o1.F - Out 1 function
Available: Always
Range: • When the out 1 is a linear output (KX3 only)
nonE = Output not used. With this setting the status
of the this output can be driven directly
from serial link;
H.rEG = Heating output;
c.rEG = Cooling output.
r.inP = Analogue retransmission of the measured
value.
r.Err = Analogue retransmission of the measured
error (PV-SP).
r.SP = Analogue retransmission of the operative
set point.
r.SEr = Analogue retransmission of a value caming
from serial link.
• When the out 1 is a digital output (relay or SSR)
nonE = Output not used. With this setting the sta-
tus of the this output can be driven directly
from serial link.
H.rEG = Heating output
c.rEG = Cooling output
AL = Alarm output
t.out = Timer output
t.HoF = Timer out - OFF in Hold
P.End = Program end indicator
P.HLd = Program hold indicator
P. uit = Program wait indicator
P.run = Program run indicator
P.Et1 = Program Event 1
P.Et2 = Program Event 2
or.bo = Out-of-range or burn out indicator
P.FAL = Power failure indicator
bo.PF = Out-of-range, Burnout and Power failure
indicator
St.By = Stand By status indicator
diF1 = Out1 repeates the digital input 1 status
diF2 = Out1 repeates the digital input 2 status
on = Out1 always ON.
Notes: 1. When two or more outputs are programmed in the
same way, these outputs will be driven in parallel
.
2. The power failure indicator will be reset when the
instrument detect an alarm reset command by
key, digital input or serial link.
3. When no control output is programmed, all the
relative alarm (when present) will be forced to
“nonE” (not used).
[14] A.o1L - Initial scale value of the analogue
retransmission (KX3 only)
Available: When Out 1 is a linear output and [13] O1F is
equal to r.IMP, r.Err, r.SP or r.SEr
Range: -1999 to [15] Ao1H.
[15] A.o1H - Full scale value of the analogue
retransmission (KX3 only)
Available: When Out 1 is a linear output and [13] O1F is
equal to r.IMP, r.Err, r.SP or r.SEr
Range: [14] Ao1L to 9999.
[16] o1.AL - Alarms linked up with the out 1
Available: When [13] o1F = AL
Range: 0... 63 with the following rules:
+1 = Alarm 1
+2 = Alarm 2
+4 = Alarm 3
+8 = Loop break alarm
+16 = Sensor break (burn out)
+32 =
Overload on Out 4 (short circuit on the Out4)
Example 1: Setting 3 (2+1) the output will be driven by the
alarm 1 and 2 (OR condition).
Example 2: Setting 13 (8+4+1) the output will be driven by
alarm 1 + alarm 3 + loop break alarm.
[17] o1.Ac - Out 1 action
Available: When [13] o1F is different from “nonE”
Range: dir = Direct action
rEU = Reverse action
dir.r = Direct action with revers LED indication
rEU.r = Reverse action with reverse LED indication.
Notes: 1. Direct action: the output repeats the status of the
driven element.
Example: the output is an alarm output with direct
action. When the alarm is ON, the relay will be
energized (logic output 1).
2. Reverse action: the output status is the opposite
of the status of the driven element.
Example: the output is an alarm output with
reverse action. When the alarm is OFF, the relay
will be energized (logic output 1). This setting is
usually named “fail-safe” and it is generally used in
dangerous process in order to generate an alarm
when the instrument power supply goes OFF or
the internal watchdog starts.
[18] o2F - Out 2 function
Available: When the instrument has out 2 option.
Range: nonE = Output not used. With this setting the status
of the this output can be driven directly
from serial link.
H.rEG = Heating output
c.rEG = Cooling output
AL = Alarm output
t.out = Timer output
t.HoF = Timr out - OFF in Hold
P.End = Program end indicator
P.HLd = Program hold indicator
P. uit = Program wait indicator
P.run = Program run indicator
P.Et1 = Program Event 1
P.Et2 = Program Event 2
or.bo = Out-of-range or burn out indicator
P.FAL = Power failure indicator
bo.PF = Out-of-range, Burnout and Power failure
indicator
St.By = Stand By status indicator
diF1 = Out2 repeates the digital input 1 status
diF2 = Out2 repeates the digital input 2 status

Ascon Tecnologic - KX Line - ENGINEERING MANUAL -Vr.4.0 PAG. 11
on = Out2 always ON.
For other details see [13] O1F parameter.
WARNING! When using the servomotor control, both Out2
and Out3 are to be selected as Heating or Cooling
(o2F = o3F = HrEG or o2F = o3F = c rEG).
Parameter [55] cont must be set as 3pt.
[19] o2.AL - Alarms linked up with Out 2
Available: When [17] o2F = AL.
Range: 0... 63 with the following rule:
+1 = Alarm 1
+2 = Alarm 2
+4 = Alarm 3
+8 = loop break alarm
+16 = Sensor break (burn out)
+32 =
Overload on Out 4 (short circuit on OP4).
For more details see [16] o1.AL parameter.
[20] o2Ac - Out 2 action
Available: When [18] o2F is different from “nonE”
Range: dir = Direct action
rEU = Reverse action
dir.r = Direct action with revers LED indication
rEU.r = Reverse action with reverse LED indication.
For more details see [17] o1.Ac parameter.
[21] o3F - Out 3 function
Available: When the instrument has out 3 option
Range: nonE =
Output not used. With this setting the status
of the this output can be driven directly
from serial link.
H.rEG = Heating output
c.rEG = Cooling output
AL = Alarm output
t.out = Timer output
t.HoF = Timer out - OFF in Hold
P.End = Program end indicator
P.HLd = Program hold indicator
P. uit = Program wait indicator
P.run = Program run indicator
P.Et1 = Program Event 1
P.Et2 = Program Event 2
or.bo = Out-of-range or burn out indicator
P.FAL = Power failure indicator
bo.PF = Out-of-range, burn out and Power failure
indicator.
St.By = Stand By status indicator
diF1 = Out3 repeats the digital input 1 status
diF2 = Out3 repeats the digital input 2 status
on = Out3 always ON.
For other details see [13] O1F parameter.
[22] o3.AL - Alarms linked up with Out 3
Available: When [20] o3F = AL
Range: 0... 63 with the following rule:
+1 = Alarm 1
+2 = Alarm 2
+4 = Alarm 3
+8 = Loop break alarm
+16 = Sensor break (burn out)
+32 = overload on Out 4 (short circuit on OP 4)
For more details see [16] o1.AL parameter.
[23] o3Ac - Out 3 action
Available: when [20] o3F is different from “nonE”
Range: dir = Direct action
rEU = Reverse action
dir.r = Direct action with revers LED indication
rEU.r = Reverse action with reverse LED indication.
For more details see [17] o1.Ac parameter.
[24] o4F - Out 4 function
Available: When the [9] io4.F = Out4
Range: nonE =
Output not used. With this setting the status
of the this output can be driven directly
from serial link.
H.rEG = Heating output
c.rEG = Cooling output
AL = Alarm output
t.out = Timer output
t.HoF = Timr out - OFF in Hold
P.End = Program end indicator
P.HLd = Program hold indicator
P. uit = Program wait indicator
P.run = Program run indicator
P.Et1 = Program Event 1
P.Et2 = Program Event 2
or.bo = Out-of-range or burn out indicator
P.FAL = Power failure indicator
bo.PF = Out-of-range, Burnout and Power failure
indicator
St.By = Stand By status indicator
For other details see [13] O1F parameter.
[25] o4.AL - Alarms linked up with Out 4
Available: When [24] o4F = AL
Range: 0... 63 with the following rule.
+1 = Alarm 1
+2 = Alarm 2
+4 = Alarm 3
+8 = loop break alarm
+16 = Sensor break (burn out)
+32 = overload on Out 4 (short circuit on OP4)
For more details see [16] o1.AL parameter.
[26] o4Ac - Out 4 action
Available: When [24] o4F is different from “nonE”
Range: dir = Direct action
rEU = Reverse action
dir.r = Direct action with revers LED indication
rEU.r = Reverse action with reverse LED indication.
For more details see [17] o1.Ac parameter.
]AL1 Group - Alarm 1 parameters
[27] AL1t - Alarm 1 type
Available: Always.
Range: • When one or more outputs are programmed as
control output
nonE = Alarm not used
LoAb = Absolute low alarm
HiAb = Absolute high alarm
LHAo = Absolute band alarm with alarm indication
out of the band
LHAi = Absolute band alarm with alarm indication
inside the band
SE.br = Sensor break

Ascon Tecnologic - KX Line - ENGINEERING MANUAL -Vr.4.0 PAG. 12
LodE = Deviation low alarm (relative)
HidE = Deviation high alarm (relative)
LHdo = Relative band alarm with alarm indication
out of the band
LHdi = Relative band alarm with alarm indication
inside the band
• When no output is programmed as control output
nonE = Alarm not used
LoAb = Absolute low alarm
HiAb = Absolute high alarm
LHAo = Absolute band alarm with alarm indication
out of the band
LHAi = Absolute band alarm with alarm indication
inside the band
SE.br = Sensor break
Notes: 1. The relative and deviation alarms are “relative” to
the operative set point value.
LoAb
OUT
AL1
AL1
PV
HAL1
time
HiAb
offoffoff OUT
AL1
AL1
PV
HAL1
time
offoffoff
ON ON ON ON
LHAb
PV
AL1H HAL1
time
offoffoff
LHde
OUT
AL1
AL1L HAL1
PV
AL1H
SP
HAL1
time
OUT
AL1
-AL1L HAL1
offoffoff
ON ON ON ON
2. The (SE.br) sensor break alarm will be ON when
the display shows ---- indication.
[28] Ab1 - Alarm 1 function
Available: When [27] AL1t is different from “nonE”.
Range: 0... 15 with the following rule:
+1 = Not active at power up.
+2 = Latched alarm (manual reset)
+4 = Acknowledgeable alarm
+8 =
Relative alarm not active at set point change
Example: Setting Ab1 equal to 5 (1+4) the alarm 1 will be
“not active at power up” and “Acknowledgeable”.
Notes: 1. The “not active at power up” selection allows to
inhibit the alarm function at instrument power up
or when the instrument detects a transfer from:
• Manual mode (oplo) to auto mode;
• Stand-by mode to auto mode.
The alarm will be automatically enabled when
the measured value reaches, for the first time,
the alarm threshold ± hysteresis (in other words,
when the initial alarm condition disappears).
PWR ON
AL1
PV
time
offoff
Ab1 = +1
Ab1 = +0
offoff
ON ON
ON
2. A “Latched alarm” (manual reset) is an alarm
that will remain active even if the conditions that
generated the alarm no longer persist. Alarm
reset can be done only by an external
command
(button, digital inputs or serial link).
Alarm reset Alarm reset
AL1
PV
time
offoff
Ab1 = +2
Ab1 = +0
offoff
ON
ON
3. An “Acknowledgeable” alarm is an alarm that can
be reset even if the conditions that generated
the alarm are still present. Alarm acknowledge
can be done only by an external command (
button, digital inputs or serial link).
Alarm ACK Alarm ACK
AL1
PV
time
offoff
Ab1 = +4
Ab1 = +0
offoffoff
ON
ON ON
A “relative alarm not active at set point change”
is an alarm that masks the alarm condition after
a set point change until process variable reaches
the alarm threshold ± hysteresis.
Sp2
Sp1
PV
time
Ab1 = +8
Ab1 = +0
ON offoff
AL1
offoffoff
AL1
ON ON ON
ON
4. The instrument does not store in EEPROM the
alarm status. For this reason, the alarm status
will be lost if a power down occurs.
[29] AL1L - For High and low alarms, it is the low
limit of the AL1 threshold
-
For band alarm, it is low alarm threshold
Available: When [27] AL1t is different from “nonE” or [27]
AL1t is different from “SE.br”.
Range: From -1999 to [30] AL1H engineering units.
[30] AL1H - For High and low alarms, it is the high
limit of the AL1 threshold
- For band alarm is high alarm threshold
Available: When [27] AL1t is different from “nonE” or [27]
AL1t is different from “SE.br”.
Range: From [29] AL1L to 9999 engineering units.
[31] AL1- Alarm 1 threshold
Available: When:
[27] AL1t = LoAb - Absolute low alarm
[27] AL1t = HiAb - Absolute high alarm
[27] AL1t = LodE - Deviation low alarm (relative)
[27] AL1t = LidE - Deviation high alarm (relative)
Range: From [29] AL1L to [30] AL1H engineering units.
[32] HAL1 - Alarm 1 hysteresis
Available: When [27] AL1t is different from “nonE” or
[27] AL1t is different from “SE.br”.
Range: 1... 9999 engineering units
Notes: 1. The hysteresis value is the difference between
the Alarm threshold value and the point the Alarm
automatically resets.

Ascon Tecnologic - KX Line - ENGINEERING MANUAL -Vr.4.0 PAG. 13
2. When the alarm threshold plus or minus the
hysteresis is out of input range, the instrument
will not be able to reset the alarm.
Example: Input range 0... 1000 (mBar).
–Set point equal to 900 (mBar);
–Deviation low alarm equal to 50 (mBar);
–Hysteresis equal to 160 (mBar)
the theoretical reset point is 900 - 50 + 160 = 1010 (mBar)
but this value is out of range.
The reset can be made only by turning the instrument
OFF, removing the condition that generate the alarm and
then turn the instrument ON again.
–All band alarms use the same hysteresis value for both
thresholds;
–When the hysteresis of a band alarm is bigger than the
programmed band, the instrument will not be able to reset
the alarm.
Example: Input range 0... 500 (°C).
–Set point equal to 250 (°C);
–Relative band alarm;
–Low threshold equal to 10 (°C);
–High threshold equal to 10 (°C);
–Hysteresis equal to 25 (°C).
[33] AL1d - Alarm 1 delay
Available: When [27] AL1t is different from “nonE”.
Range: From oFF (0) to 9999 seconds.
Note: The alarm goes ON only when the alarm condition
persists for a time longer than [33] AL1d time but the
reset is immediate.
[34] AL1o - Alarm 1 enabling during Stand-by
mode and out of range indications
Available: When [27] AL1t is different from “nonE”.
Range: 0 = Never
1 = During stand by
2 = During overrange and underrange
3 =
During overrange, underrange and stand-by
]AL2 Group - Alarm 2 parameters
[35] AL2t - Alarm 2 type
Available: Aways
Range: • When one or more outputs are programmed as
control output:
nonE = Alarm not used
LoAb = Absolute low alarm
HiAb = Absolute high alarm
LHAo = Absolute band alarm with alarm indication
out of the band
LHAi = Absolute band alarm with alarm indication
inside the band
SE.br = Sensor break
LodE = Deviation low alarm (relative)
HidE = Deviation high alarm (relative)
LHdo = Relative band alarm with alarm indication
out of the band
LHdi = Relative band alarm with alarm indication
inside the band
• When no output is programmed as control output:
nonE = Alarm not used
LoAb = Absolute low alarm
HiAb = Absolute high alarm
LHAo = Absolute band alarm with alarm indication
out of the band
LHAi = Absolute band alarm with alarm indication
inside the band
SE.br = Sensor break
Note: The relative alarm are “relative” to the current set point
(this may be different from the Target setpoint if you
are using the ramp to set point function).
[36] Ab2 - Alarm 2 function
Available: When [35] AL2t is different from “nonE”
Range: 0... 15 with the following rule:
+1 = Not active at power up.
+2 = Latched alarm (manual reset)
+4 = Acknowledgeable alarm
+8 =
Relative alarm not active at set point change.
Example: Setting Ad2 equal to 5 (1+4) the alarm 2 will be
“not active at power up” and “Acknowledgeable”.
Note: For other details see [27] Ab1 parameter.
[37] AL2L - For High and low alarms, it is the low
limit of the AL2 threshold
-
For band alarm, is low alarm threshold
Available: When [35] AL2t is different from “nonE” or [35]
AL2t is different from “SE.br”.
Range: -1999 to [38] AL2H engineering units.
[38] AL2H - For High and low alarms, it is the high
limit of the AL2 threshold
-For band alarm is high alarm threshold
Available: When [35] AL2t is different from “nonE” or
[35] AL2t is different from “SE.br”.
Range: From [37] AL2L to 9999 engineering units.
[39] AL2 - Alarm 2 threshold
Available: When:
[35] AL2t = LoAb Absolute low alarm
[35] AL2t = HiAb Absolute high alarm
[35] AL2t = LodE Deviation low alarm (relative)
[35] AL2t = LidE Deviation high alarm (relative)
Range: From [37] AL2L to [38] AL2H engineering units.
[40] HAL2 - Alarm 2 hysteresis
Available: When [35] AL2t is different to “nonE” or [35] AL2t
is different from “SE.br”.
Range: 1... 9999 engineering units.
Note: For other details see [32] HAL1 parameter.
[41] AL2d - Alarm 2 delay
Available: When [35] AL2t different form “nonE”.
Range: From oFF (0) to 9999 seconds.
Note: The alarm goes ON only when the alarm condition
persist for a time longer than [41] AL2d time but the
reset is immediate.
[42] AL2o - Alarm 2 enabling during Stand-by mode
and out of range indications
Available: When [35] AL2t different from “nonE”.
Range: 0 = Never
1 = During stand by
2 = During overrange and underrange
3 =
During overrange, underrange and stand-by

Ascon Tecnologic - KX Line - ENGINEERING MANUAL -Vr.4.0 PAG. 14
]AL3 Group - Alarm 3 parameters
[43] AL3t - Alarm 3 type
Available: Always.
Range: • When one or more outputs are programmed as
control output:
nonE = Alarm not used
LoAb = Absolute low alarm
HiAb = Absolute high alarm
LHAo = Absolute band alarm with alarm indication
out of the band
LHAi = Absolute band alarm with alarm indication
inside the band
SE.br = Sensor break
LodE = Deviation low alarm (relative)
HidE = Deviation high alarm (relative)
LHdo = Relative band alarm with alarm indication
out of the band
LHdi = Relative band alarm with alarm indication
inside the band
• When no output is programmed as control output:
nonE = Alarm not used
LoAb = Absolute low alarm
HiAb = Absolute high alarm
LHAo = Absolute band alarm with alarm indication
out of the band
LHAi = Absolute band alarm with alarm indication
inside the band
SE.br = Sensor break
Note: The relative alarm are “relative” to the current set point
(this may be different to the Target set point if you are
using the ramp to set point function).
[44] Ab3 - Alarm 3 function
Available: When [42] AL3t is different from “nonE”.
Range: 0... 15 with the following rule:
+1 = Not active at power up.
+2 = Latched alarm (manual reset)
+4 = Acknowledgeable alarm
+8 =
Relative alarm not active at set point change
Example: Setting Ad3 equal to 5 (1+4) the alarm 3 will be
“not active at power up” and “Acknowledgeable”.
Note: For other details see [28] Ab1 parameter.
[45] AL3L - For High and low alarms, it is the
low limit of the AL3 threshold
- For band alarm is low alarm threshold
Available: When [43] AL3t is different from “nonE” or [43]
AL3t is different from “SE.br”.
Range: -1999 to [46] AL3H engineering units.
[46] AL3H - For High and low alarms, it is the
high limit of the AL3 threshold
-For band alarm is high alarm threshold
Available: When [43] AL3t is different from “nonE” or [43]
AL3t is different from “SE.br”.
Range: From [45] AL3L to 9999 engineering units.
[47] AL3 - Alarm 3 threshold
Available: When:
• [43] AL3t = LoAb Absolute low alarm;
• [43] AL3t = HiAb Absolute high alarm;
• [43] AL3t = LodE Deviation low alarm (relative);
• [43] AL3t = LidE Deviation high alarm (relative).
Range: From [45] AL3L to [46] AL3H engineering units.
[48] HAL3 - Alarm 3 hysteresis
Available: When [43] AL3t is different to “nonE” or [43] AL3t
is different from “SE.br”.
Range: 1... 9999 engineering units.
Note: For other details see [32] HAL1 parameter.
[49] AL3d - Alarm 3 delay
Available: When [43] AL3t different form “nonE”.
Range: From oFF (0) to 9999 seconds.
Note: The alarm goes ON only when the alarm condition
persist for a time longer than [49] AL3d time but the
reset is immediate.
[50] AL3o - Alarm 3 enabling during Stand-by mode
and out of range indications
Available: When [43] AL3t is different from “nonE” or [43]
AL3t is different from “SE.br”.
Range: 0 = Never;
1 = During stand by;
2 = During overrange and underrange;
3 = During overrange, underrange and stand-by.
]LbA group - Loop break alarm
General note about LBA alarm
The LBA operate as follows: applying the 100% of the power
output to a process, the process variable, after a time due to
the process inertia, begins to change in a known direction (in-
creases for an heating action or decreases for a cooling action).
Example: If I apply 100% of the power output to a furnace,
the temperature must go up unless one of the component in
the loop is faulty (heater, sensor, power supply, fuse, etc...)
The same philosophy can be applied to the minimum power.
In our example, when I turn OFF the power to a furnace, the
temperature must go down, if not the SSR is in short circuit,
the valve is jammed, etc..
LBA function is automatically enabled when the PID requires
the maximum or the minimum power.
When the process response is slower than the programmed
limit the instrument generates an alarm.
Notes: 1. When the instrument is in manual mode, the LBA
function is disabled.
2.
When LBA alarm is ON the instrument continues
to perform the standard control. If the process
response comes back into the programmed limit,
the instrument automatically resets the LBA alarm.
3. This function is available only when the programmed
control algorithm is equal to PID (Cont = PID).
[51] LbAt - LBA time
Available: When [55] Cont = PID
Range: • oFF = LBA not used;
• 1... 9999 seconds.
[52] LbSt - Delta measure used by LBA during
Soft start
Available: When [51] LbAt is different from oFF
Range: • oFF = loop break alarm is inhibit during soft start
• 1... 9999 engineering units.
[53] LbAS - Delta measure used by loop break
alarm (loop break alarm step)
Available: when [51] LbAt is different from oFF
Range: From 1 to 9999 engineering units.

Ascon Tecnologic - KX Line - ENGINEERING MANUAL -Vr.4.0 PAG. 15
[54] LbcA - Condition for LBA enabling
Available: when [51] LbAt is different from oFF
Range: uP = Enabled when the PID requires the maxi-
mum power only.
dn = Enabled when the PID requires the mini-
mum power only
both =
Enabled in both condition (when the PID re-
quires the maximum or the minimum power).
LBA application example:
LbAt (LBA time) = 120 seconds (2 minutes)
LbAS (delta LBA) = 5°C
The machine has been designed in order to reach 200°C in
20 minutes (20°C/min).
When the PID demands 100% power, the instrument starts
the time count.
During time count if the measured value increases more
than 5°C, the instrument restarts the time count. Otherwise
if the measured value does not reach the programmed delta
(5°C in 2 minutes) the instrument will generate the alarm.
]rEG group - Control parameters
The rEG group will be available only when at least one
output is programmed as control output (H.rEG or C.rEG).
[55] cont - Control type:
Available: When at least one output is programmed as con-
trol output (H.rEG or C.rEG).
Range: When two control action (heat & cool) are programmed:
Pid = PID (heat and cool)
nr =
Heat/Cool ON/OFF control with neutral zone
HSEt
HSEt
SP
PV
time
OUTH.rEG
(heating)
OUTc.rEG
(cooling)
offON ON
of
fo
ffON
When one control action (heat or cool) is programmed:
Pid = PID (heat or cool);
On.FA = ON/OFF asymmetric hysteresis;
On.FS = ON/OFF symmetric hysteresis;
3Pt = Servomotor control
(available when Output
2
and Output 3 have been ordered as “M”).
HEAt - On.FA
OUT
H.rEG
SP
PV
HSEt
time
offoff
CooL -On.FA
OUT
C.rEG
SP
PV
HSEt
time
ON ON ON offoff
ON ON ON
HEAt - On.FS
OUT
H.rEG
SP
PV
HSEt
HSEt
time
CooL -On.FS
OUT
H.rEG
SP
PV
HSEt
HSEt
time
ON ON ON
off off off off
ON ON ON
Notes: 1. ON/OFF control with asymmetric hysteresis:
• OFF when PV > SP
• ON when PV < (SP - hysteresis)
2. ON/OFF control with symmetric hysteresis:
• OFF when PV > (SP + hysteresis)
• ON when PV < (SP - hysteresis)
[56] Auto - Auto tune selection
Ascon Tecnologic has developed three auto-tune algorithms:
–Oscillating auto-tune;
–Fast auto-tune;
–EvoTune.
1. The oscillating auto-tune is the usual auto-tune and:
• It is more accurate;
• Can start even if PV is close to the set point;
• Can be used even if the set point is close to the
ambient temperature.
2. The fast type is suitable when:
• The process is very slow and you want to be opera-
tive in a short time;
• When an overshoot is not acceptable;
• In multi loop machinery where the fast method
reduces the calculation error due to the effect of the
other loops.
3. The EvoTune type is suitable when:
• You have no information about your process;
• You can not be sure about the end user skills;
• You desire an auto tune calculation independently
from the starting conditions (e.g. set point change
during tune execution, etc).
Note: Fast auto-tune can start only when the measured
value (PV) is lower than (SP + 1/2SP).
Available: When [55] cont = PID
Range: -4... 8 where:
-4 = Oscillating auto-tune with automatic restart
at all set point change;
-3 = Oscillating auto-tune with manual start;
-2 = Oscillating auto-tune with automatic start at
the first power up only;
-1 = Oscillating auto-tune with automatic restart
at every power up;
0 = Not used;
1 = Fast auto tuning with automatic restart at
every power up;
2 = Fast auto-tune with automatic start at the
first power up only;
3 = FAST auto-tune with manual start;
4 = FAST auto-tune with automatic restart at all
set point change.
5 = EvoTune with automatic restart at every
power up;
6 = EvoTune with automatic start at the first
power up only;
7 = EvoTune with manual start;
8 = EvoTune with automatic restart at all set
point change.
Note: All auto-tunes are inhibited during program execution.
[57] Aut.r - Manual start of the auto-tune
Available: When [55] cont = PID.
Range: oFF =
The instrument is not performing the auto-tune;
on = The instrument is performing the auto-tune.
[58] SELF - Self-tune enable
The self-tuning is an adaptive algorithm able to optimize
continuously the PID parameter value.
This algorithm is specifically designed for all process subjected to
big load variation able to change heavily the process response.

Ascon Tecnologic - KX Line - ENGINEERING MANUAL -Vr.4.0 PAG. 16
Available: When [55] cont = PID
Range: YES = self-tune active;
no = self-tune not active.
[59] HSEt - Hysteresis of the ON/OFF control
Available: When [55] cont is different from PID.
Range: 0... 9999 engineering units.
[60] cPdt - Time for compressor protection
Available: When [55] cont = nr
Range: OFF = Protection disabled
1... 9999 seconds.
[61] Pb - Proportional band
Available: When [55] cont = PID and [58] SELF = no
Range: 1... 9999 engineering units.
Note: Auto-tune functions calculate this value.
[62] ti - Integral time
Available: When [55] cont = PID and [58] SELF = no
Range: OFF = Integral action excluded
1... 9999 seconds
inF= Integral action excluded
Note: Auto-tune functions calculate this value.
[63] td - Derivative time
Available: When [55] cont = PID and [58] SELF = no
Range: oFF - derivative action excluded
1... 9999 seconds
Note: Auto-tune functions calculate this value.
[64] Fuoc - Fuzzy overshoot control
This parameter reduces the overshoot usually present at
instrument start up or after a set point change and it will be
active only in this two cases.
Setting a value between 0.00 and 1.00 it is possible to slow
down the instrument action during set point approach.
Setting Fuoc = 1 this function is disabled.
PV
SP
time
2
1
3
Available: When [55] cont = PID and [58] SELF = no.
Range: 0... 2.00.
Note: Fast auto-tune calculates the Fuoc parameter while
the oscillating one sets it equal to 0.5.
[65] tcH - Cycle time of the heating output
Available: When at least one output is programmed in order
to be the heating output (H.rEG),
[55] cont = PID and [58] SELF = no.
Range: 1.0... 130.0 seconds
[66] rcG - Power ratio between heating and cooling
action (relative cooling gain)
The instrument uses the same PID parameter set for heat
and for cool action but the efficiency of the two actions are
usually different.
This parameter allows to define the ratio between the efficien-
cy of the heating system and the efficiency of the cooling one.
An example will help us to explain you the philosophy.
Consider one loop of a plastic extruder. The working tem-
perature is equal to 250°C.
When you want to increase the temperature from 250 to
270°C (DT = 20°C) using 100% of the heating power (resis-
tor), you will need 60 seconds.
On the contrary, when you want to decrease the temperature
from 250 to 230°C (DT = 20°C) using 100% of the cooling
power (fan), you will need 20 seconds only.
In our example the ratio is equal to 60/20 = 3 ([66] rcG = 3)
and it say that the efficiency of the cooling system is 3 time
more efficient of the heating one.
Available: When two control action are programmed
(H.rEG and c.rEG) and
[55] cont = PID and
[58] SELF = no
Range: 0.01... 99.99
Note: auto-tune functions calculate this value.
[67] tcc - Cycle time of the cooling output
Available: When at least one output is programmed in order
to be the cooling output (c.rEG), [55] cont = PID
and [58] SELF = no
Range: 1.0... 130.0 seconds.
[68] rS - Manual reset (integral pre-load)
It allows to drastically reduce the undershoot due to a
hot restart. When your process is steady, the instrument
operates with a steady power output (e.g.: 30%).
If a short power down occurs, the process restarts with a
process variable close to the set point while the instrument
starts with an integral action equal to zero.
Setting a manual reset equal to the average power output
(in our example 30%) the instrument will start with a power
output equal to the value it will use at steady state (instead
of zero) and the undershoot will become very little (in theory
equal to zero).
Available: When [55] cont = PID.
Range: -100.0... +100.0%.
[69] Str.t - Servomotor stroke time (KX3 servo only)
Available: When [55] cont = 3Pt.
Range: 5... 1000 seconds;
[70] db.S - Servomotor dead band (KX3 servo only)
Available: When [55] cont = 3Pt.
Range: 0... 100%;
[71] od - Delay at power up
Available: When at least one output is programmed as
control output.
Range: • oFF: Function not used;
• 0.01... 99.59 hh.mm.
Notes: 1. This parameter defines the time during which
(after a power up) the instrument remains in stand
by mode before to start all other function (control,
alarms, program, etc.).
2. When a program with automatic start at power up
and od function are programmed, the instrument
performs od function before to start the program
execution.
3. When an auto-tune with automatic start at power
up and od function are programmed, the autotune
will start at the end of od delay.

Ascon Tecnologic - KX Line - ENGINEERING MANUAL -Vr.4.0 PAG. 17
[72] St.P - Max. power output used during soft start
Available: When at list one output is programmed as control
output.
Range: -100... +100%.
Notes: 1. When St.P parameter have a positive value, the
limit will be applied to the heating output(s) only.
2. When St.P parameter have a negative value, the
limit will be applied to the cooling output(s) only.
3. When a program with automatic start at power
up and soft start function are programmed, the
instrument performs the soft start and than the
program function.
4. The auto-tune function will be performed after
soft start function.
5. The Soft start function is available also when ON/
OFF contro l is used.
[73] SSt - Soft start time
Available: When at list one output is programmed as control
output.
Range: oFF = Function not used;
0.01... 7.59 hh.mm;
inF = soft start always active.
[74] SS.tH - Threshold for soft start disabling
Available: When at list one output is programmed as control
output.
Range: -1999... 9999 engineering units.
Notes: 1. When the power limiter have a positive value (the
limit is applied to the heating action) the soft start
function will be aborted when the measured value
is greater or equal to SS.tH parameter.
2. When the power limiter have a negative value
(the limit is applied to the cooling action) the soft
start function will be aborted when the measured
value is lower or equal to SS.tH parameter.
]SP Group - Set point parameters
The SP group will be available only when at least one output
is programmed as control output (H.rEG or C.rEG).
[75] nSP - Number of used set points
Available: When at least one output is programmed as
control output.
Range: 1... 4.
Note: When you change the value of this parameter, the
instrument operates as follows:
• [82] A.SP parameter will be forced to SP.
• The instrument verifies that all used set point are
within the limits programmed by [76] SPLL end [77]
SPHL. If an SP is out of this range, the instrument
forces it to the maximum acceptable value
[76] SPLL - Minimum set point value
Available: When at least one output is programmed as
control output.
Range: From -1999 to [77] SPHL engineering units
Notes: 1. When you change the [76] SPLL value, the
instrument checks all local set points (SP, SP2,
SP3 and SP4 parameters) and all set points of the
program ([96] Pr.S1, [101] Pr.S2, [106] Pr.S3, [111]
Pr.S4 parameters). If an SP is out of this range, the
instrument forces it to the maximum acceptable value
2. A [76] SPLL change produces the following actions:
• When [83] SP.rt = SP the remote set point will
be forced to be equal to the active set point
• When [83] SP.rt = trim the remote set point
will be forced to zero
• When [83] SP.rt = PErc the remote set point
will be forced to zero
[77] SPHL - Maximum set point value
Available: When at least one output is programmed as
control output.
Range: From [77] SPLL to 9999 engineering units
Note: For other details see [77] SPLL parameter.
[78] SP - Set Point 1
Available: When at least one output is programmed as
control output.
Range: From [76] SPLL to [77] SPHL engineering units.
[79] SP 2 - Set Point 2
Available: When at least one output is programmed as con-
trol output and [75] nSP > 2.
Range: From [76] SPLL to [77] SPHL engineering units.
[80] SP 3 - Set Point 3
Available: When at least one output is programmed as con-
trol output and [75] nSP > 3.
Range: From [76] SPLL to [77] SPHL engineering units.
[81] SP 4 - Set Point 4
Available: When at least one output is programmed as con-
trol output and [75] nSP =4.
Range: From [76] SPLL to [77] SPHL engineering units.
[82] A.SP - Selection of the active Set point
Available: When at least one output is programmed as
control output.
Range: From “SP” to [75] nSP.
Notes: 1. A [82] A.SP change produces the following actions:
• When [83] SP.rt = SP - the remote set point
will be forced to be equal to the active set poin;
• When [83] SP.rt = trin - the remote set point
will be forced to zero;
• When [83] SP.rt = PErc - the remote set
point will be forced to zero.
2. SP2, SP3 and SP4 selection will be shown
only when the relative set point is enabled (see
[75] nSP parameter).
[83] SP.rt - Remote set point type
These instruments will communicate with each other, using
RS 485 serial interface without a PC. An instrument can be
set as a Master while the other are (as usual) Slave units. The
Master unit can send his operative set point to the slave units.
In this way, for example, it is possible to change
simultaneously the set point of 20 instruments by changing
the set point of the master unit (e.g. hot runner application).
SP.rt parameter defines how the slaves units will use the
value coming from serial link.
The [132] tr.SP (selection of the value to be retransmitted
(Master)) parameter allows to define the value sent by
master unit.
Available: When at least one output is e programmed as
control output and the serial interface is present.
Range: rSP = The value coming from serial link is used

Ascon Tecnologic - KX Line - ENGINEERING MANUAL -Vr.4.0 PAG. 18
as remote set point (RSP).
trin = The value coming from serial link will be
algebraically added to the local set point
selected by A.SP and the sum becomes
the operative set point.
PErc = The value coming from serial will be scaled
on the input range and this value will be
used as remote set point.
Note: A [83] SPrt change produces the following actions:
• When [83] SP.rt = rSP - the remote set point
will be forced to be equal to the active set point
• When [83] SP.rt = trin - the remote set point
will be forced to zero
• When [83] SP.rt = PErc - the remote set
point will be forced to zero
Example: A 6 zone reflow-oven for PCB.
The master unit sends its set point value to 5 other zones
(slave controllers).
The Slave zones use it as a set point trim.
The first zone is the master zone and it uses a set point
equal to 210°C.
The second zone has a local set point equal to -45°C.
The third zone has a local set point equal to -45 (°C).
The fourth zone has a local set point equal to -30.
The fifth zone has a local set point equal to +40.
The sixth zone has a local set point equal to +50.
In this way, the thermal profile will be the following:
–Master SP = 210°C;
–Second zone SP = 210 -45 = 165°C;
–Third zone SP = 210 -45 = 165°C;
–Fourth zone SP = 210 - 30 = 180°C;
–Fifth zone SP = 210 + 40 = 250°C;
–Sixth zone SP = 210 + 50 = 260°C.
Changing the SP of the master unit, all the other slave units
will immediately change their operative set point.
[84] SPLr - Local/remote set point selection
Available: When at list one output is programmed as control
output.
Range: Loc = Local set point selected by [82] A.SP;
rEn = Remote set point (coming from serial link).
[85] SP.u - Rate of rise for positive set point
change (ramp up)
Available: When at list one output is e programmed as
control output.
Range: 0.01... 99.99 units per minute;
inF = ramp disabled (step transfer).
[86] SP.d - Rate of rise for negative set point
change (ramp down)
Available: When at list one output is e programmed as
control output.
Range: 0.01... 99.99 units per minute;
inF = ramp disabled (step transfer).
General note about remote set point: when the remote set
point (RSP) with trim action is programmed, the local set
point range becomes the following:
from [76] SPLL+ RSP to [77] SPHL - RSP
]tin group - Timer function parameters
Five timer types are available:
Delayed start with a delay time and a “end of cycle” time.
Start
OUT off
Tr.t1 Tr.t2
off
ON
–Setting tr.t2 = Inf the timer out remains in ON condition
until a reset command is detected.
Start
OUT ON
off
Tr.t1 Tr.t2 = inF
off
Reset
Delayed start at power up with a delay time and a “end of
cycle” time.
Start
OUT PWR UP
off
Tr.t1 Tr.t2
off
ON
Feed-through.
Start
OUT
Tr.t1
off
Reset
ON
Asymmetrical oscillator with start in OFF.
Start
OUT ONoff
Tr.t2
ONoff
Tr.t1Tr.t1 Tr.t2
ON
off
Tr.t1 Tr.t2
Reset
Asymmetrical oscillator with start in ON.
Start
OUT ON off
Tr.t2
off
Tr.t1Tr.t1 Tr.t2
off
Tr.t1 Tr.t2
Reset
ON ON
Notes: 1. The instrument can receive the start, hold and
reset commands by button, by logic inputs
and/or by serial link.
2. An HOLD command can suspend the time count.
[87] tr.F= Independent timer function
Available: Always.
Range: nonE = Timer not used
i.d.A = Delayed start timer
i.uP.d = Delayed start at power up
i.d.d = Feed-through timer
i.P.L = Asymmetrical oscillator with start in OFF
i.L.P = Asymmetrical oscillator with start in ON
[88] tr.u - Engineering unit of the time
Available: When [87] tr.F is different form nonE.
Range: hh.nn = Hours and minutes
nn.SS = Minutes and seconds
SSS.d = Seconds and tenth of seconds
Note: When the timer is running, you can see the value of
this parameter but you can NOT modify it.

Ascon Tecnologic - KX Line - ENGINEERING MANUAL -Vr.4.0 PAG. 19
[89] tr.t1 - Time 1
Available: When [87] tr.F is different form nonE.
Range: When [88] tr.u = hh.nn = 00.01... 99.59
When [88] tr.u = nn.SS = 00.01... 99.59
When [88] tr.u = SSS.d = 000.1... 995.9
[90] tr.t2 - Time 2
Available: When [87] tr.F is different form nonE
Range: When [88] tr.u = hh.nn = 00.01... 99.59 + inF
When [88] tr.u = nn.SS = 00.01... 99.59 + inF
When [88] tr.u = SSS.d= 000... 995.9 + inF.
Note: Setting [90] tr.t2 = inF, the second time can be stopped
by a reset command only.
[91] tr.St - Timer status
Available: When [87] Tr.F is different form nonE
Range: run = Timer Run
HoLd = Timer Hold
rES = Timer reset
Note: This parameter allows to manage timer execution by a
parameter (without digital inputs or button).
]PrG Group - Programmer function parameters
These instruments are able to perform a set point profile
compounded of 4 groups of 2 steps (8 step total).
The first step is a ramp (used to reach the desired set point),
the second is a soak (on the desired set point).
When a RUN command is detected the instrument aligns
the operative set point to the measured value and starts to
execute the first ramp.
In addition, each soak is equipped with a wait band which
suspends the time count when the measured value goes out
of the defined band (guaranteed soak).
Moreover, for each segment it is possible to define the status
of two events. An event can drive an output and make an
action during one or more specific program steps.
Some additional parameters allow to define the time scale,
the automatic RUN conditions and the instrument behaviour
at the end of the program.
Notes: 1. All steps can be modified during program execution.
2. During program execution the instrument stores the
segment currently in use and, by a 30 m interval, it
stores also the elapsed time of the soaks.
If a power down occurs during program execution, at
the next power up the instrument is able to continue
the program execution starting from the segment in
progress at power down and, if the segment was a
soak, it is also capable to restart from the soak time
minus the elapsed time memorized.
In order to obtain this features, the [127] dSPu
“Status of the instrument at power u” parameter
must be set to “AS.Pr”.
If [127] dSPu value is different from “AS.Pr”, the
memorization function will be inhibited.
PWRUP
or RUN
Time
Spx
Status
Temperature
OFF
2pmaR
Soak 2
3pmaR
Soak 3
4kaoS
4pmaR
Rampto
Spx
Prog. END
Prog. Step
Pr.S1
1pmaR
1kaoS
Program run
Pr.S4
Pr.S2
Pr.S3
[92] Pr.F = Programmer action at power up
Available: Always.
Range: nonE = Program not used
S.uP.d = Start at power up with a first step in stand by
S.uP.S = Start at power up
u.diG = Start at RUN command detection only
U.dG.d =
Start at RUN command detection with a
first step in stand by.
[93] Pr.u - Engineering units of the soaks
Available: When [92] Pr.F is different from nonE:
Range: hh.nn = Hours and minutes;
nn.SS= Minutes and seconds.
Note: During program execution, this parameter can not be
modified.
[94] Pr.E - Instrument behaviour at the End of the
program execution
Available: When [92] Pr.F is different from nonE
Range: cnt = Continue (the instrument will use the set
point of the last soak until a reset command
is detected);
SPAt = Go to the set point selected by [82] A.SP
parameter;
St.bY = Go in stand by mode.
Notes: 1. Setting [95] Pr.E = cnt the instrument operates as
follows: at program end, it will use the set point of
the last soak.
2. When a reset command is detected, it goes to
the set point selected by [82] A.SP parameter.
The transfer will be a step transfer or a ramp ac-
cording to the [85] SP.u (maximum rate of rise for
positive set point change) and [86] SPd (maximum
rate of rise for negative set point change).
3. Setting [94] Pr.E = SPAt the instrument goes
immediately to the set point selected by [82] A.SP
parameter. The transfer will be a step transfer or
a ramp according to the [85] SP.u (maximum rate
of rise for positive set point change) and [86] SPd
(maximum rate of rise for negative set point change).
[95] Pr.Et - Time of the End program indication
Available: when [92] Pr.F is different from nonE
Range: oFF = Function not used
00.01... 99.59 minutes and seconds
inF = indefinitely ON
Note: Setting [95] Pr.Et = inF the end program indication will
go OFF only when a reset command or a new RUN
command is detected.
[96] Pr.S1 - Set point of the first soak
Available: When [92] Pr.F is different from nonE or [92] Pr.F
is different from S.uP.d.
Range: From [76] SPLL to [77] SPHL

Ascon Tecnologic - KX Line - ENGINEERING MANUAL -Vr.4.0 PAG. 20
[97] Pr.G1 - Gradient of the first ramp
Available: When [92] Pr.F is different from nonE or [92] Pr.F
is different from S.uP.d.
Range: 0.1... 999.9 engineering units per minute;
inF = Step transfer.
[98] Pr.t1 - Time of the first soak
Available: When [92] Pr.F is different from nonE
Range: 0.00... 99.59 Time units.
[99] Pr.b1 - Wait band of the first soak
Available: When [92] Pr.F is different from nonE or [92] Pr.F
is different from S.uP.d.
Range: OFF... 9999 engineering units
Note: The wait band suspends the time counting when
the measured value goes out of the defined band
(guaranteed soak).
Temperature
Wait
Wait
Soak xSoakx
Ramp x + 1Ramp x
Wait
Soak SP
Wait
SP
Measure
[100] Pr.E1 - Events of the first group
Available: When [92] Pr.F is different from nonE or [92] Pr.F
is different from S.UP.d.
Range: 00.00... 11.11 where:
0 = event OFF;
1 = event ON.
Event1status during ramp
Event 2 status during ramp
Event 1 status during soak
Event 2 status during soak
Display Ramp Soak
Event 1 Event 2 Event 1 Event 2
00.00 off off off off
10.00 on off off off
01.00 off on off off
11.00 on on off off
00.10 off off on off
10.10 on off on off
01.10 off on on off
11.10 on on on off
00.01 off off off on
10.01 on off off on
01.01 off on off on
11.01 on on off on
00.11 off off on on
10.11 on off on on
01.11 off on on on
11.11 on on on on
[101] Pr.S2 - Set point of the second soak
Available: When [92] Pr.F is different from nonE
Range: From [76] SPLL to [77] SPHL
oFF = Program end.
Note: It is not necessary to configure all steps.
When you use for example 2 groups only, it is
sufficient to set the set point of the third group equal
to OFF. The instrument will mask all the following
parameters of the programmer.
[102] Pr.G2 - Gradient of the second ramp
Available: When [92] Pr.F is different from nonE and [102]
Pr.S2 is different from oFF.
Range: 0.1... 999.9 engineering units per minute;
inF = Step transfer.
[103] Pr.t2 - Time of the second soak
Available: When [92] Pr.F is different from nonE and
[101] Pr.S2 is different from oFF.
Range: 0.00... 99.59 time units.
[104] Pr.b2 - Wait band of the second soak
Available: When [92] Pr.F is different from nonE and
[101] Pr.S2 is different from oFF.
Range: OFF... 9999 engineering units.
Note: For more details see [99]Pr.b1 parameter.
[105] Pr.E2 - Events of the second group
Available: When [92] Pr.F is different from nonE and
[101] Pr.S2 is different from oFF.
Range: 00.00... 11.11 where:
0 = Event OFF;
01 = Event ON.
Note: For more details see [100]Pr.E1 parameter.
[106] Pr.S3 - Set point of the third soak
Available: When [92] Pr.F is different from nonE and
[101] Pr.S2 is different from oFF
Range: from [76] SPLL to [77] SPHL;
oFF = Program end.
Note: For more details see [101]Pr.S2 parameter.
[107] Pr.G3 - Gradient of the third ramp
Available: When [92] Pr.F is different from nonE, [101]
Pr.S2 is different from oFF and [106] Pr.S3 is
different from OFF.
Range: 0.1... 999.9 engineering units per minute;
inF = Step transfer.
[108] Pr.t3 - Time of the third soak
Available: When [92] Pr.F is different from nonE, [101]
Pr.S2 is different from oFF and [106] Pr.S3 is
different from OFF.
Range: 0.00... 99.59 time units.
[109] Pr.b3 - Wait band of the third soak
Available: When [92] Pr.F is different from nonE, [101]
Pr.S2 is different from oFF and [106] Pr.S3 is
different from OFF.
Range: OFF... 9999 engineering units.
Note: For more details see [99]Pr.b1 parameter
[110] Pr.E3 - Events of the third group
Available: When [92] Pr.F is different from nonE, [101]
Pr.S2 is different from oFF and [106] Pr.S3 is
different from OFF.
This manual suits for next models
5
Table of contents