ASM prodis ADC User manual

Installation and operation manual EN
prodis®ADC
Digital Process Meter for analog position, angle
and inclination sensors
Please read carefully before installation and operation!

© ASM Automation Sensorik Messtechnik GmbH, 2019
All rights reserved.
Am Bleichbach 18 - 24
85452 Moosinning
Germany

prodis®
Digital Process Meter PD-ADC
Version 3.1.0
www.asm-sensor.com
3
1Safety instructions ........................................................................................................4
1.1 Signal words and symbols .............................................................................................................4
1.2 Intended use...................................................................................................................................5
2Transport and storage...................................................................................................5
3Installation and initial operation...................................................................................6
3.1 Mechanical installation...................................................................................................................6
3.2 Electrical connection ......................................................................................................................7
3.3 Startup..........................................................................................................................................14
4Operation......................................................................................................................15
5Maintenance and disposal..........................................................................................21
5.1 Maintenance and service .............................................................................................................21
5.2 Disposal........................................................................................................................................21

prodis®
Digital Process Meter PD-ADC
4
Version 3.1.0
www.asm-sensor.com
Pos: 6/ Bedienungsanleit ungen/Module Universal/Ü berschriften/Sicher heitshinweise UE @ 6\mod _1507630884828_78. docx @ 48429 @ 1@ 1
1 Safety instructions
Pos: 7/ Sicherheitshi nweise/Signalwört eru nd Symbole UE @ 1\m od_140014046 7807_78.docx @ 9166 @ 2 @1
1.1 Signal words and symbols
Pos: 8/ Sicherheitshin weise/Signalwörter @ 1\mod_1 400240492762_7 8.docx@ 9 385 @ @ 1
WARNING, Risk of Injury:
Indicates a potentially hazardous situation, which, if not avoided, can result in serious
injury or property damage.
WARNING, Risk of Personal Injury or Death:
Indicates a situation that can result in serious personal injury or death if not properly
avoided.
WARNING, Risk of Personal Injury or Death:
Indicates a situation that can result in moderate personal injury or death if not properly
avoided.
WARNING, Risk of Personal Injury:
Indicates a situation that can result in minor personal injury if not properly avoided.
WARNING, Risk of Property Damage:
Indicates a situation that can result in minor to major property damage if not properly
avoided.
Product liability
•Disregarding the following instructions may result in malfunction, damage to property and personal injury
and releases the manufacturer from product liability.
Safety regulations
•National safety regulations must be observed!
Pos: 9/ ######### ##S eitenumbruch ##### ########### ############## ##### @ 0\mod_135 3584168894_0. docx@ 336 @ @ 1

prodis®
Digital Process Meter PD-ADC
Version 3.1.0
www.asm-sensor.com
5
Pos: 10 /Bedienungs anleitungen/Prodis/ Bestimmungsge mäße Verwendung @ 6\ mod_150815 4370878_78.docx @ 4 8669@ 2 @ 1
1.2 Intended use
The process meters of the prodis®series are optimized for the sensor signals of the ASM sensors. Data can
be transferred to the PC via the RS-232 interface. The optionally available relay outputs enable the
monitoring of limit values and the control of machine processes. Use the unit as intended by operating within
its specified technical data and ambient conditions.
The installation and operating instructions supplied with the unit must be observed. The data sheet of the
respective process meter is part of this instruction manual. If not yet available, it may be requested by stating
the respective model name.
Pos: 11 /Bedienungs anleitungen/Prodis/Tr ansport und Lageru ng@ 6 \mod_1508 933116286_78. docx@ 49279 @ 1 @ 1
2 Transport and storage
Observe storage and transport temperatures according to the operating temperature (see data sheet).
Max. rel. humidity 80%, condensation must be excluded.
The device must be secured against slipping and tipping during transport.
Pos: 12 /Bedienungsanl eitungen/Prodis/Liefer umfang @ 6\mod_15089 33240772_78.doc x@ 492 85@ @ 1
Shipment damages
Check the device immediately for shipment damages. In case of any damage or equipment not operating
appropriately, please contact the producer.
Shipment content
•Process meter
•Operation instructions
Pos: 13 /######## ### Seitenumbruch #### ############## ############# #### @ 0\mod_13 53584168894_0.d ocx @ 336 @ @ 1

prodis®
Digital Process Meter PD-ADC
6
Version 3.1.0
www.asm-sensor.com
Pos: 14 /Bedienungsanl eitungen/Prodis/Inbetri ebnahme_UE @ 7\mod_ 1530866906002_78.d ocx @ 57540@ 1 @ 1
3 Installation and initial operation
Pos: 15 /Bedienungs anleitungen/Prodis/M echanische Befestig ung @ 7\mod _1542119710123_7 8.docx @ 59575 @ 2 @ 1
3.1 Mechanical installation
Cutout according to DIN 43700
Maximum material thickness: 5 mm [.197]
1. Push the device into the front panel cutout
as far as it will go.
2. Hook the mounting clamp to the rear
notch.
3. Push down the end of the mounting clamp
until the front notch is locked.

prodis®
Digital Process Meter PD-ADC
Version 3.1.0
www.asm-sensor.com
7
4. Turn the set screw with a blade
screwdriver to the stop on the front plate.
Pos: 16 /Bedienungsanl eitungen/Prodis/Elektri scher Anschluss @ 6\mod_ 1508933471863_78.d ocx@ 49 291@ 2 @ 1
3.2 Electrical connection
Damage to or destruction of the process meter due to excessive operating voltage
or mounting errors
•The meter must be operated only within values specified in the data sheet.
•Connection to power supply must be performed in accordance with safety
instructions for electrical facilities and performed only by trained staff.
•The inputs of the process meter must not be connected to current sources with more
than 30 mA max.
•It has to be guaranteed that the excitation voltage agrees with the indicated value on
the type label.
•Do not open the process meter.
Pos: 17 /Bedienungs anleitungen/Prodis/ Prodis_Eigensc haften_ADC_man @ 7\ mod_153086 4330453_78.docx @ 5 7534@ @1
Description and specifications
prodis ®-ADC is designed for use with analog position sensors to display angles and displacements. A high
resolution A/D converter processes signals from sensors with voltage or current output. The meter is
programmable to display values within preset start/end range or values in units as inches, mm or degrees. A
tare function or programming lock can be activated with two control terminals. Sensor excitation is supplied by
the meter. With four membrane keys all parameters can be programmed for the special applications. Optional
comparator functions with 4 NPN open-collector output are available, additional 2 of them have relay output.

prodis®
Digital Process Meter PD-ADC
8
Version 3.1.0
www.asm-sensor.com
Specifications
Display
6-digit, 7-segment LED, height 14 mm, decimal point programmable
Counting rate
1 ... 25/s programmable
Measurement accuracy
±0,05 % f.s.
Excitation voltage/current
24 V DC ±10%/150 mA, residual ripple 1%SS;
85-250 V AC, 50-60 Hz/180 mA max.
Sensor excitation
24 V DC/300 mA / voltage divider 5 V, 10 mA
Input
Two channels each for:
Voltage: 0 ... 10 V; 0.5 … 4.5 V, 0.5 … 10 V, max. 24V,
Input resistance: 20k
Current: 0...20 mA, 3 wires; 4 … 20 mA 2 wires/3 wires
Load 100 Ω, Imax<30 mA
Voltage divider Rmin=500, 0 … 5 V
One input or the difference between both inputs can be chosen by
programming.
Control input
2 control inputs 24 V, active low
Comparator output (option)
Relay: 250 V AC/5 A, 30 V DC/5 A
NPN: 24 V max./50 mA to GND
Options
Comparator
Desktop version
Connection
Terminal strip 12 pole, excitation 3 pole
Temperature coefficient
±20 x 10-6 / °C
Operating temperature
-10...+40 °C
Storage temperature
-20...+85 °C
Weight
24 V DC: approx. 250 g
230 V AC: approx. 400 g
Protection class
Front IP60, rear IP40
Humidity
Max. 80 % R. H., non-condensing
Safety of equipment
Directive 2014/35/EU: EN 61010-1:2010
EMC
Directive 2014/30/EU: EN 61326-1:2013
Programmable parameters / value range
Value range offset
-999999 to +999999
Divisor, multiplier
0 to 999999
Other programmable
parameters
Decimal point position, display brightness
Control input terminals
Key lock, display value hold, tare function
Interface RS-232
Level
RS-232: ±8 V, galvanically isolated
Data format
1 start bit, 8 data bits, 1 stop bit, no parity
Transmission rate
9600 Baud
Pos: 18 /######## ### Seitenumbruch #### ############## ############# #### @ 0\mod_13 53584168894_0.d ocx @ 336 @ @ 1
Pos: 19 /Datenblätter/Pr odis/Maßzeichnungen/PD- ADC ohne Schaltausg änge@ 7 \mod_1521456 339485_78.docx @ 54124 @ @ 1

prodis®
Digital Process Meter PD-ADC
Version 3.1.0
www.asm-sensor.com
9
Wiring basic unit without comparator output
Signals
Connector X1
Pin no.
Connector X2
Pin no.
Sensor excitation +UB 24 V
1
Sensor excitation 0 V (GND)
2
Control input terminal 1: tare function
3
Control input terminal 2: programming lock
4
Voltage input terminal (e.g. 0 ... 10 V), channel 1
5
Voltage input terminal (e.g. 0 ... 10 V), channel 2
6
Current input terminal (e.g. 0 ... 20 mA), channel 1
7
Current input terminal (e.g. 0 ... 20 mA), channel 2
8
Voltage divider input terminal, channel 1
9
Voltage divider input terminal, channel 2
10
Reference voltage 5 V for voltage divider
11
GND
12
PD-ADC-24VDC
Excitation +24 V
Excitation 0 V (GND)
13
14
PD-ADC-230VAC
Excitation
Protective ground
13, 15
14
Signals
D-Sub, pin no.
TxD
2
RxD
3
GND
5
Rear view without comparator output
Pos: 20 /######## ### Seitenumbruch #### ############## ############# #### @ 0\mod_13 53584168894_0.d ocx @ 336 @ @ 1

prodis®
Digital Process Meter PD-ADC
10
Version 3.1.0
www.asm-sensor.com
Pos: 21 /Datenblätt er/Prodis/Maßzeic hnungen/PD-ADC mit Schaltausgänge n @ 7\mod_15214 55799773_78.doc x@ 54118 @ @ 1
Wiring basic unit with comparator output
Signals
Connector X1
Pin no.
Connector X2
Pin no.
Sensor excitation +UB 24 V
1
Sensor excitation 0 V (GND)
2
Control input terminal 1: tare function
3
Control input terminal 2: programming lock
4
Voltage input terminal (e.g. 0 ... 10 V), channel 1
5
Voltage input terminal (e.g. 0 ... 10 V), channel 2
6
Current input terminal (e.g. 4 ... 20 mA), channel 1
7
Current input terminal (e.g. 4 ... 20 mA), channel 2
8
Voltage divider input terminal, channel 1
9
Voltage divider input terminal, channel 2
10
Reference voltage 5 V for voltage divider
11
GND
12
PD-ADC-24VDC
Excitation +24 V
Excitation 0 V (GND)
13
14
PD-ADC-230VAC
Excitation
Protective ground
13, 15
14
Signals
Connector X3
Pin no.
TxD
17
RxD
16
GND
18
Rear view with comparator output (option „REL2“)

prodis®
Digital Process Meter PD-ADC
Version 3.1.0
www.asm-sensor.com
11
Comparator function (option)
Comparator
Comparator output
NPN collector
Connector X3
Pin no.
Relay
Connector X4
Pin no.
LED
Comparator 1
NPN1
20
Relay 1
NO
NC
Common
25
27
26
LED1
Comparator 2
NPN2
21
Relay 2
NO
NC
Common
28
30
29
LED2
Comparator 3
NPN3
22
Comparator 4
NPN4
23
NPN GND
NPN UB (+24V)
24
19
Pos: 22 /Datenblätt er/Prodis/Maßzeic hnungen/PD-ADC D esktopversion @ 0\m od_139228600 8789_78.docx @ 5315 @ @ 1
Desktop version (option „DT”)
Wiring of connector X1 see table “Wiring basic unit”.
Pos: 23 /######## ### Seitenumbruch #### ############## ############# #### @ 0\mod_13 53584168894_0.d ocx @ 336 @ @ 1

prodis®
Digital Process Meter PD-ADC
12
Version 3.1.0
www.asm-sensor.com
Pos: 24 /Bedienungsanl eitungen/Prodis/Schalt ausgänge_Diagram m@ 6\ mod_15081479 60045_78.docx @ 48599 @ @ 1
Comparator outputs (diagram)
Pos: 25 /######## ### Seitenumbruch #### ############## ############# #### @ 0\mod_13 53584168894_0.d ocx @ 336 @ @ 1

prodis®
Digital Process Meter PD-ADC
Version 3.1.0
www.asm-sensor.com
13
Pos: 26 /Bedienungsanl eitungen/Prodis/Anschl ussbeispiele-ADC @ 6\ mod_150823721524 3_78.docx @ 48708 @ @ 1
Examples of signal wiring
UB= 24 V
UB= 5 V
0 ... 10 V
0.5 ... 10 V
0.5 ... 4.5 V
0.5 ... 4.5 V
UB= 24 V
4 ... 20 mA
2 wire
UB= 24 V
0/4 ... 20 mA
3 wire

prodis®
Digital Process Meter PD-ADC
14
Version 3.1.0
www.asm-sensor.com
UB= 5 V
0.5 ... 4.5 V
R1K
Pos: 27 /Bedienungsanl eitungen/Prodis/Inbetri ebnahme-ADC @ 6\ mod_1508151373588_7 8.docx @ 48647 @ 2@ 1
3.3 Startup
When the process meter is switched on, a short self-test sequence will start with all LED segments on and
then the version of the process meter will be displayed. After that procedure prodis®-ADC is in the normal
mode.
Pos: 28 /######## ### Seitenumbruch #### ############## ############# #### @ 0\mod_13 53584168894_0.d ocx @ 336 @ @ 1

prodis®
Digital Process Meter PD-ADC
Version 3.1.0
www.asm-sensor.com
15
Pos: 29 /Bedienungsanl eitungen/Module Uni versal/Ü berschriften/Bedienung U E@ 7\ mod_1536677472 767_78.docx @ 58611 @ 1 @ 1
4 Operation
Pos: 30 /Bedienungsanl eitungen/Prodis/Anzeige _Bedienelemente @ 6\ mod_15081515875 91_78.docx @ 48653 @ @ 1
Operation keys and display
LED2
Sign
LED1
Key to control the programming menus
Multifunction key to reset the display and to store the parameters in a
non-volatile memory
Multifunction key for parameter settings
Multifunction key for parameter settings
+
means: hold the key
and press
Pos: 31 /######## ### Seitenumbruch # ############## ############## ###### @ 0\mod_13 53584168894_0.d ocx @ 336 @ @ 1

prodis®
Digital Process Meter PD-ADC
16
Version 3.1.0
www.asm-sensor.com
Pos: 32 /Bedienungsanl eitungen/Prodis/Taste n_Funktionen @ 6\mod _1508153265378_7 8.docx@ 4 8659 @ @ 1
Explanation and operation of the functions
Parameter settings
The parameter settings are effected in a programming menu.
Key /
key combination
Function
+
Activate programming mode
,
Change the parameter by decimal steps
+
Reset activated parameter
+
Change the sign of signed parameters
Store in non-volatile memory
Proceed and return to normal mode
New settings become effective immediately
Pos: 33 /######## ### Seitenumbruch #### ############## ############# #### @ 0\mod_13 53584168894_0.d ocx @ 336 @ @ 1

prodis®
Digital Process Meter PD-ADC
Version 3.1.0
www.asm-sensor.com
17
Pos: 34 /Bedienungsanl eitungen/Prodis/Fun ktionen_Tabelle-ADC @ 6\mod_1508154 489684_78.docx @ 48674 @ @ 1
Operation of the functions ‒chart
Submenus
Parameter
Display
Value range
Factory setting
+
Channel select
Ch
1, 2, 1-2 (difference)
1
Measurement signal
SIG
U, U2, U3, U6, I42, I02, r
U
Decimal point
dp
1 from 5, OFF
OFF
Activate tare function
tAr
OFF, ON
OFF
Activate teach-In function
t-In
O, A, E
O
Display start value
bEG
±999999
0
Display end value
End
±999999
10000
Utilization factor Rxk
nP
0 ... 0.99999
0.999
Measurement rate 1/s
rAtE
1 ... 25
16
Display brightness
db
1 ... 15
15
Baud rate
bA
4.8, 9.6 ...115.2
9.6
Control input 2
Cntr
1 ... 4
1
Averaging filter
FIL
0, 1, 2, 4, 8 ... 128
0
Tare function on
flashing
decimal point
0
Offset
oFFSEt
-999999 ... +999999
000000
+
Limit value
rELx
+/- 999.999
+999.999
Hysteresis
Hµ rELx
+/- 999.999
1
Operating direction
rx
oEF, SCH
SCH
+
Reset to factory default
settings
000000 for 2 s
+ power on*
* Disconnect device from excitation, wait 5 seconds, press both arrow keys together and hold.
Connect excitation, the display shows “000000”, then release both arrow keys.
Pos: 35 /######## ### Seitenumbruch #### ############## ############# #### @ 0\mod_13 53584168894_0.d ocx @ 336 @ @ 1

prodis®
Digital Process Meter PD-ADC
18
Version 3.1.0
www.asm-sensor.com
Pos: 36 /Bedienungs anleitungen/Prodis/M enüeinstellung en@ 6\mod_150 8233571089_78.d ocx @ 48685 @ @ 1
Explanation of the menu settings
Selection of the measurement signal:
SIG = U voltage signal 0…10 V
SIG = U2 voltage signal 0.5 … 10 V
SIG = U3 voltage signal 0 … 5 V
SIG = U6 voltage signal 0.5 … 4.5 V
SIG = I42 current signal 4 … 20 mA
SIG = I02 current signal 0 … 20 mA
SIG = r potentiometric measurement signal
Teach-in scaling:
t-In = OTeach-in scaling inactive
t-In = A Teach-in scaling active, teach-in procedure inactive
t-In = E Teach-in scaling active, teach-in procedure active
Scaling for maesurement input signals 0...10 V, 0/4...20 mA
The input of the start and end value for the displayed value range 0...10 V resp. 0/4...20 mA will be made by
the menu positions “start value” and “end value”.
Example: Sensor with a measurement range of 2000 mm and a output signal of 4...20 mA, wanted display
range 0 … 2000.0
Setting: SIG: I42, start value: 0, end value: 20 000, decimal point between the first and second position from
the righthand side.
Scaling for position sensors with potentiometric signal
An utilization factor nP considers measurement range limits and individual sensitivity of the potentiometer.
The display range is set by start and end value. nP will be calculated as a product of (sensitivity) E x L
(measurement range), both specifications can be taken from the type label. When the sensor has been
changed the re-calibration of the meter is very easy by changing nP.
Example A: Linear sensor with a measurement range of 1250 mm and output R1K, sensitivity: 0,756
mV/V/mm, wanted display: 0 … 1250.0 mm.
Setting: nP = 0.765 x 1.250 = 0.945, start value: 0, end value: 12500, decimal point between the first and
second position from the right hand side.
Example B: as A, but wanted display range: 0 … 49.21 inch.
Setting: nP = 0.765 x 1.250 = 0.945, start value: 0, end value: 4921, decimal point between the second and
third position from the right hand side.
Example C: angle sensor with a used range of 90 degrees and output R1K, sensitivity: 2.846 mV/V/degree,
wanted display range: 0 … 90 degrees.
Setting: nP = 0.002846 x 90 = 0.25614, start value: 0, end value: 90.
Pos: 37 /######## ### Seitenumbruch # ############## ############## ###### @ 0\mod_13 53584168894_0.d ocx @ 336 @ @ 1

prodis®
Digital Process Meter PD-ADC
Version 3.1.0
www.asm-sensor.com
19
Pos: 38 /Bedienungs anleitungen/Prodis/T arier-, Offset, Te ach-In @ 6\mod_150 8233819579_78.d ocx @ 48691 @ @ 1
Tare function, Offset function, Teach-In function
Tare function
Activated by the front button Sor via the control input the display of the meter will be set to the offset value,
the decimal point is flashing while the tare function is active. Pressing the button Sagain deactivates the tare
function.
Offset function
The offset function allows to set and change the offset value of the meter directly in the normal mode.
Teach-in scaling with start value and end value
A display value range is assigned to a measurement range by teach-in. The display value range is defined
by start and end value (bEG, ENd).
The teach-in procedure of start and end value shall be performed with the following steps:
1. In the programming menu choose t-In = E for releasing the teach-in procedure and then exit menu.
2. Set the start position and press
.
3. Set the end position and press
.
4. Go to the programming menu again and set t-In = A. Thereby the teach-in procedure will be completed
and the teached scaling is active.
Pos: 39 /Bedienungs anleitungen/Prodis/ Steuereingänge 1 u nd2 @ 6\mod_15082 35410304_78.doc x@ 48702 @ @ 1
Control inputs 1 and 2
Functions TARA, FREEZE, KEY-LOCK, DATA-SEND
These functions can be activated by two control inputs. The activation of an input is made by connecting the
input with GND. An open input or a connection with 24 V sets the function of the control input to inactive.
Control input 1, TARE function
The activation of the Tare function sets the display value to zero resp. to the offset value from the offset
menu input. The TARE compensation will be held as long as the control input 1 is active. An active control
input 1 avoids any tare operation with the Skey at the meter front side.
Control input 2, functions FREEZE, KEY-LOCK, DATA-SEND
The used function of the control input 2 is set in the setting menu with the “Cntr” menu:
Cntr: 1
FREEZE
Display “freeze”
Cntr: 2
KEY-LOCK
Programming blocked
Cntr: 3
DATA SEND
The displayed value will be sent via the RS-232 interface
Cntr: 4
DATA SEND CYC
The displayed value will be sent periodically every 10 ms via RS-232
Pos: 40 /######## ### Seitenumbruch #### ############## ############# #### @ 0\mod_13 53584168894_0.d ocx @ 336 @ @ 1

prodis®
Digital Process Meter PD-ADC
20
Version 3.1.0
www.asm-sensor.com
Pos: 41 /Bedienungsanl eitungen/Prodis/RS-2 32C@ 6 \mod_1508322 544139_78.docx @ 48862 @ @ 1
RS-232 Interface
Transmission of a position value
Send to prodis®: “r”
Response of prodis®: CR, sign, n5, n4, n3, n2, n1, n0
with ni: ASCII characters, leading digits
filled with “0”
Sign: positive sign = Space “ “
Tare function On/Off
Send to prodis® : “n”
prodis® function: Tare function on/off
Data format
1 start bit, 8 data bits, 1 stop bit, no parity
Baud rate: programmable
Net transmission rate
Max. 50/s approx.