Assurance Emergency Lighting L10 Self Diagnostic Series User manual

1
Emergency LED Driver
Installation Instructions
Class 2 Output (Only for nominal voltage series 15-55V)
L10 Self Diagnostic Series - SD
L14 Self Diagnostic Series - SD
L20 Self Diagnostic Series - SD
Assurance Emergency Lighting, a division of Assurance Engineering LLC, 357 Cumberland St. Memphis, TN 38112 1-877-774-4775
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
1.
2. This product is intended for use with an emergency LED lighting load and supplies nominal of power and a
maximum voltage in emergency mode for a minimum of 90 minutes.
3. An unswitched AC power source is required (120-277 VAC , 50/60 Hz) to power these units.
4. This product’s chassis must be grounded.
5. This product is suitable for use in damp locations where the ambient temperature is 0
℃
minimum,to 55℃
maximum. This product is also suitable for installation in sealed and gasketed fixture. This product is not suitable
for heated air outlets and wet or hazardous locations.
6. This product contains a rechargeable LiFePO4 or Lithium-ion battery. The battery must be recycled or disposed of
properly.
7. Make certain all connectors are in accordance with the National Electrical Codes and any local regulaons.
8. This emergency LED driver is suitable for both factory or field installation. For field installation, please see the
instructions section.
9. Do not install near gas or electric heaters.
10. The use of accessory equipment is not recommended by the manufacturer may cause an unsafe condition.
11. Do not use this product for applications other than the intended use.
12. Equipment should be mounted in locations and at heights where it will not be subjected to tampering by
unauthorized personnel.
This device complies with part 15 of the FCC Rules. Operation is suitable to the following two conditions: (1) This
device may not cause harmful interference, and (2) This device must accept any interference that may cause
undesired operation.
To reduce the risk of electric shock, disconnect both normal and emergency power supplies and
disconnect the baery connector of the emergency driver before servicing.
Do not attempt to service the battery. It is a sealed, no-maintenance battery is used that is not field replaceable.
Contact the manufacturer for information on service.
Servicing should be performed by qualified service personnel only.
13.
14.
15.
16.
Note: Once the installation is complete and AC power is supplied, wait one minute before joining the
battery connector. This allows for battery detection and the self testing feature to engage properly.
01242022
E505538

2
INSTALLATION
NOTE: Make sure the necessary branch circuit wiring is available. An unswitched source of
power is required. The emergency driver must be fed from the same branch circuit
as the AC driver.
Caution: Once the installation is complete and AC power is supplied, wait one minute
before joining the battery connector. This allows for battery detection and the self
testing feature to engage properly.
This product is suitable for field installation with suitable LED loads. There are Three (3) checks to
determine if your luminaire is eligible for field installation.
1. Ensure the LED load’s rated power is greater than or equal to the power output of this emergency LED
driver. This is to ensure that this emergency product will not produce more power than the LED load
can handle. Thus ensuring that the LED load will not be damaged when the system is in the emergency
mode.
2. Verify that the forward voltage of the luminaire’s LED array is within the limits of this emergency LED
driver. The forward voltage of the LED array is commonly designated as Vf and should be found on the
luminaire, in the luminaire specifications, or imprinted directly on the LED arrays. If multiple LED arrays
are to be driven, verify that the total forward voltage is within the limits of this product. Using a voltage
meter, it may be possible to directly measure the voltage across the LED arrays when operating from
the AC driver.
3.
NOTE: This product has been designed to reliably interface with a wide selection of LED loads and is
electrically compatible with every simple LED array that meets criteria 1 and 2 above. However
compatibility cannot be guaranteed with all current and future LED systems. Compatibility testing of the
end-use systems is suggested . Please contact the factory with any questions.
NOTE: After installation, it will be necessary to measure the egress lighting illumination level to ensure it
complies with national state and local code requirement.
Installation of this emergency LED driver will vary based on the luminaire type, however generally follow
these steps.
STEP #1 INSTALLING THE EMERGENCY DRIVER
�Disconnect AC power from the LED luminaire.
�Mount the emergency LED driver by the mounting tabs using appropriate screws(not
provided). The luminaire’s installation instructions may provide guidance on the
recommended mounting location.
Ensure the output current of the LED driver does not exceed 5 Amps. This is the current into the
red/blue wires. Also, if multiple AC drivers and emergency drivers are connected together, do not
exceed 5 Amps of current through the black wire. Exceeding 5 Amps will damage the unit and void the
warranty. Use alternate wiring (cap black wire off) or contact technical support for assistance.
Assurance Emergency Lighting, a division of Assurance Engineering LLC, 357 Cumberland St. Memphis, TN 38112 1-877-774-4775

3
NOTE: Considerations must be made to protect the wires on the models have no flexible conduit if
installed outside of the luminaire.
Note:
If the application requires the emergency LED driver to be mounted on
top of the luminaire, please use the models which provide metal flexible
conduit instead of bare wire.
�Mounting Height: Many factors influence emergency illumination levels, such as the lamp load
selected, luminaire design, and environmental factors. Therefore end-use verification is necessary. For
field installations, the mounting height of illumination must be measured in the end application to
ensure the minimum lumens requirements on national, state, and local codes are satisfied.
Lumens can be calculated by the following formula:
Lumens in Emergency Mode = Lumens per Watt of Fixture * Output Power of Chosen Product
_______________(Lumens) = _____________(lm/W) * ____________(W)
�Remote Mounting: The emergency LED driver may be remote mounted from the luminaire. If used in
conjunction with an AC driver the allowed distance is up to half the distance the AC driver
manufacturer recommends remote mounting the AC driver from the LED load. If used without an AC
driver, and remote mounting more than 18 feet from the luminaire, please consult the factory to
determine the necessary wire gauge. CAUTION: Remote mounting can result in reduced power output.
STEP #2 INSTALLING THE 4-WIRE TEST SWITCH ON FIXTURE SURFACE
�Mount the supplied 4-wire illuminated test switch in a location that is visible and accessible by
maintenance personnel. The switch mounts through a hole which may need to be added to the
luminaire or could come pre-punched by the luminaire supplier.
�Wire the test switch per wiring diagrams provided on these instructions.
�If wired correctly, the test switch indicator light should be “ON” when AC power is supplied to the
fixture, and the battery switch is “ON” indicating that the emergency inverter battery is charging.
Assurance Emergency Lighting, a division of Assurance Engineering LLC, 357 Cumberland St. Memphis, TN 38112 1-877-774-4775

4
STEP #3 WIRING THE EMERGENCY DRIVER
Select the appropriate wiring diagram to connect the emergency driver to the AC driver and LED load.
Make sure all connections are in accordance with the National Electrical Code and any local regulations.
After installation is complete, supply AC power to the emergency driver and
join baery connec
At this point, power should be connected to both the AC driver and the emergency driver, and the
Charging Indicator Light should illuminate indicang the baery is charging.
A short-term discharge test may be conducted after the emergency driver has been charged for one hour.
24-hour charging period must be performed before conducting a long-term discharge test.
"CAUTION - This Unit Has More Than One Power Connection Point. To Reduce The Risk Of Electric Shock,
Disconnect Both The Branch Circuit-Breakers Or Fuses And Emergency Power Supplies Before Servicing."
OPERATION
wait one minute before
connecting battery connector. This allows for battery detection and the self testing feature to
engage properly.
During normal operation AC power is applied, to the driver, and the charging indicator light is illuminated,
which indicates that the battery is being charged. When power fails, the emergency LED driver will
automatically switch to emergency power (internal battery), operating the LED load for a minimum of 90
minutes. When AC power is restored, the emergency driver returns to the charging mode.
MAINTENANCE
The emergency driver with self-diagnostic function is designed to automatically operate a 30 seconds
short-term test each month, and a 90 minutes duration test every 12 months.
The emergency unit will perform the condition via bi-color LED indicator, please refer to the self-diagnostic
code table as below:
Self-Diagnostic Code Table
LED Indication
Condition
Failure Priority
Steady Green
Flash GREEN
Battery is Fully Charged
Battery is Charging
N/A
N/A
OFF
Emergency Mode
N/A
One Red Flash
Charging Failure
1
Two Red Flashes
Battery Failure
2
Three Red Flashes
Load Failure
3
Assurance Emergency Lighting, a division of Assurance Engineering LLC, 357 Cumberland St. Memphis, TN 38112 1-877-774-4775
Note:
1. The failure code occurs every 10 seconds. Only the highest priority failure is indicated.
2. One Red flash: Battery failed to fully charge in 24 hours.
3. Two Red flashes: Battery failure, improper connection or incorrect installation sequence.
4. Two Red flashes: If incorrect installation sequence, disconnect battery connector wait
one (1) minute, then reconnect battery connector to eliminate sequence error code.

5
Manual Testing
Manual testing can be performed by pressing the test switch or toggling the emergency circuit breaker. The
failure code will be the same as Self-Diagnostic Code Table above. Please follow the Manual Test Sequence
Manual Test Sequence Table
Table below.
Manual Test Item
Test Switch Operation
Emergency Circuit Breaker
Operation
Quick Test
Press and Hold
N/A
30-Second Test
2 x Press and Release
2 x Toggles
90-Minute Test
3 x Press and Release
3 x Toggles
Cancel 90-Minute Test
1 x Press and Release
1 x Toggle
! REFER ANY SERVICING INDICATED BY THESE CHECKS TO QUALIFIED PERSONNEL!

6
SYSTEM WIRING DIAGRAMS
Figure A. Overall Wiring Diagram option 1.
Figure B. Overall Wiring Diagram option 2.
Figure C. EMERGENCY ONLY
* If AC driver input current
exceeds 5A, cap black wire
and connect AC driver hot
directly to wall switch or
switching device.
*
or pink (-)
or pink (-)
or pink (-)

7
SYSTEM WIRING DIAGRAMS
Figure D. Multiple Luminaires with Dimming Drivers
Assurance Emergency Lighting, a division of Assurance Engineering LLC, 357 Cumberland St. Memphis, TN 38112
or pink (-)
or pink (-)
or pink (-)
Note: 2022 Codes changing 0-10Vdc Dimming wires from Gray (-) to Pink (-).

SYSTEM WIRING DIAGRAMS
8
Contact Technical Support
for additional wiring diagrams or assistance.
Toll Free: 1-877-774-4775
or Pink (-)
or Pink (-)
Note: 2022 Codes changing 0-10Vdc Dimming wires from Gray (-) to Pink (-).
or pink
This manual suits for next models
2
Table of contents
Other Assurance Emergency Lighting Lighting Equipment manuals
Popular Lighting Equipment manuals by other brands

Advanced Lighting Systems
Advanced Lighting Systems LiveLED 100 installation instructions

Ortech
Ortech SL-RGB25M instruction manual

ACME
ACME LP-1600 BD30 user manual

OVE
OVE WINCHESTER OVEL 203 installation manual

TRADIM
TRADIM 31030-1 Series user manual

RASHA PROFESSIONAL
RASHA PROFESSIONAL PENTA V24 Quick user manual

WAC Lighting
WAC Lighting InvisiLED CCT 100 Installation instruction

LED Horizon DMX
LED Horizon DMX 203-RGBW user manual

Mr. Beams
Mr. Beams MB700 user manual

Vision & Control
Vision & Control LDLF60x300-R633/UDC Instructions for use

Pyroterra Lighttoys
Pyroterra Lighttoys FT user guide

PROEL
PROEL PLHT575ML user manual