Atal AT-VLX-A1-R1-RS User manual

1
Features
➢Indoor air quality transmitter/controller
➢Internal sensors to measure CO2 & temperature
➢3-color TFT screen display + 3-color alarm indication
➢Four function keys to adjust setpoints
➢Providing 1x analog output & 1x relay on/off output
➢Linear or PID output selectable for analog
➢Modbus RS485 interface to connect to BMS/PLC
➢24VAC/VDC power supply
Specification
Carbon Dioxide
Detecting gas
Carbon Dioxide (CO2)
Gas sensor
NDIR sensor
Accuracy@25°C
±50ppm + 3% reading or ±75ppm (whichever is greater)
Stability
<2% of FS over lifetime (15 years) of sensor
Calibration
ABC Logic self-calibration
Lifetime of NDIR CO2 sensor
15 years (normal using)
Response time
<2 minutes for 90% step change
Sample time
Every 2 sec
Warm up time
2 hours (first time or startup after power failure)
2 min (operation)
CO2 measuring range
0~5000ppm (default)
0~2000ppm (selected in Advanced Setup)
CO2 display resolution
1ppm
Temperature
Temperature sensor (selectable)
NTC thermistor
Measuring range
-20~60°C (default)
CO2/Te/RH Transmitter/Controller
Model: AT -VLX-A1-R1-RS
User Manual

2
Fig. 1
Fig. 3
Accuracy
<±0.5°C@25°C
Electrical Specification and Functions
Power supply
24VAC/VDC
Power consumption
5.5 W max. ; 2.5 W avg.
LCD screen
3-color TFT screen, with 4 function keys
Output
1× analog ouotputs & 1x relay on/off output
Analog: linear (0~10V or 4~20mA) or PID
Communication interface
Modbus RS485
Operation Condition
Working condition
0~50℃; 0~95%RH, non condensing
Storage condition
-10~60℃, 0~80%RH
Dimension/Weight
150mm(L)×90mm(W)×42mm(H)/280g
Installation method
Wall mount (65mm×65mm or 2”×4” wire box)
Housing and IP class
PC/ABS, IP class: IP30
Certification
EMC approval
Version
V.1711-S862
Mounting and installation instruction
◆Notice the power supply of the monitor is 24VAC/VDC. Do not connect higher voltages than marked on the
transmitter/controller. Always turn off power before taking following steps.
◆Open the cover: push both clips at the bottom of the unit to remove the front cover from the back cover. Please
operate gently to avoid damaging of the clips.
◆Fix back cover: fix the back cover on the wall according to the dimension and position, see Fig. 1.
◆Connect wires: connect wires according to Fig.2 and press the wires under the terminals of back cover.
◆Close the cover: align the top clip of the unit firstly, then close the front cover and back cover by pressing the bottom
clips, to finish the installation.

3
TFT Display & Buttons
The front cover contains a TFT screen and 4 function keys: SET, ▲, ▼, and .
➢ Power: be used to turn on/off the transmitter/controller. When turning off, “OFF” will be displayed on the right
bottom corner, and in this situation all outputs are ineffective.
➢TFT display: CO2 and temperature readings will be displayed on first and second line. If the output is linear,
when any key among SET, ▲, and ▼ is pressed, it will display “Linear” on the screen and the keys are
in-effective, see above Fig. 3. The CO2 3-color indication will follow below (default) alarm setpoints. Setpoints
can be adjusted via Advanced Setup parameters P8 & P9.
│ Green: CO2 < 800ppm │ Yellow: 800ppm ≤ CO2 < 1200ppm │ Red: CO2 ≥ 1200ppm │
➢SET button: be used to adjust CO2 PID/relay1 setpoint, temp. PID/relay2 setpoint, humi. PID/relay3 setpoint and
temp. control mode (heating/cooling). Press SET button continuously to walk through parameters quickly.
➢▲ & ▼: be used to adjust the setpoint value. Press the button continuously to walk through setpoint value quickly
➢Lock/Unlock the buttons: Please refer to Advanced Parameter P72.
Analog Output Setting
The default analog output is PID before leaving factory, unless otherwise stated by customers. End user can reset the
analog output to linear by Advanced Setup P20 according to below table 1. Voltage output or current output can be
selected by connecting/disconnecting the jumpers, as shown in table 2.
Table 1 – Analog output: linear or PID output
Advanced
parameter
setting
P20 value
CO2
(AN1)
Temperature
(AN2)
RH
(AN3 DIP2=OFF)
TVOC
(AN3 DIP2=ON)
0
Linear
Linear
Linear
Linear
1
PID
Linear
Linear
Linear
2
Linear
PID
Linear
Linear
3
PID
PID
Linear
Linear
4
Linear
Linear
PID
Linear
Fig. 2

4
5
PID
Linear
PID
Linear
6
Linear
PID
PID
Linear
7
PID
PID
PID
Linear
8
Linear
Linear
Linear
PID
9
PID
Linear
Linear
PID
10
Linear
PID
Linear
PID
11
PID
PID
Linear
PID
12
Linear
Linear
PID
PID
13
PID
Linear
PID
PID
14
Linear
PID
PID
PID
15
PID
PID
PID
PID
Table 2 - Voltage output or current output selection via jumpers
Jumpers S1~S6 on PCB
Jumper SET on PCB
Analog output terminals
S1 connect V, S2 connect V
SET connect lower two pins
AN1=0~10V
S1 connect V, S2 connect V
SET connect upper two pins
AN1=2~10V
S1 connect I, S2 connect I
SET connect lower two pins
AN1=0~20mA
S1 connect I, S2 connect I
SET connect upper two pins
AN1=4~20mA
S3 connect V, S4 connect V
SET connect lower two pins
AN2=0~10V
S3 connect V, S4 connect V
SET connect upper two pins
AN2=2~10V
S3 connect I, S4 connect I
SET connect lower two pins
AN2=0~20mA
S3 connect I, S4 connect I
SET connect upper two pins
AN2=4~20mA
S5 connect V, S6 connect V
SET connect lower two pins
AN3=0~10V
S5 connect V, S6 connect V
SET connect upper two pins
AN3=2~10V
S5 connect I, S6 connect I
SET connect lower two pins
AN3=0~20mA
S5 connect I, S6 connect I
SET connect upper two pins
AN3=4~20mA
Relay Control Mode
End user may adjust CO2 relay 1 control mode by Advanced Setup P12 as shown in table 3.
Table 3 CO2 relay 1 control mode
Advanced parameter
P12 value
1
2
3
4

5
Function
Auto control
ON1- decrease CO2
Auto control
ON1- increase CO2
Manual control
ON1- OFF
Manual control
ON1 -ON
For example, end user may set the CO2 relay offset by Advanced Setup parameters P16. The relay 1 auto control
logic is as explained below:
a. in decrease CO2 mode, when CO2 measuring > CO2 setpoint, relay 1 = ON, when CO2 measuring ≤ CO2 setpoint
– CO2 offset, relay 1 = OFF
b. in increase CO2 mode, when CO2 measuring < CO2 setpoint, relay 1 = ON, when CO2 measuring ≥ CO2 setpoint
+ CO2 offset, relay 1 = OFF
c. under CO2 manual control-OFF, relay 2 = OFF
d. under CO2 manual control-ON, relay 2 = ON
Advanced Setup
Switch off power and remove the back cover, there is a set of DIPs on the middle part of PCB. Switch DIP1 to ON to
enter Advanced Setup interface. Use SET button to switch the parameter items from P1 to P77, and using ▲ & ▼
buttons to adjust the target values. Switch DIP1 back to OFF for normal using.
Note: Please read the below parameters firstly. All acknowledges are required before changing the parameters.
After changing the parameters please wait 6 seconds before power off. Or the new settings will not be saved
Parameter
Setting range
Default
P1
Device RS485 address
1~247
1
P2
RS485 baud rate
4800/9600/14400/19200/38400/56000/57600/115200
9600
P3
RS485 stop bits and parity
1- 1 stop bit No parity
2- 2 stop bits No parity
3- 1 stop bit Odd parity
4- 1 stop bit Even parity
1
P4
CO2 calibration value
-300 ~ 300 ppm
0
P5
Temp calibration value
-5.00 ~ 5.00℃
0.00
P6
Humidity calibration value
-5.00 ~ 5.00 %RH
0.00
P7
TVOC correction target value
0.0 ~ 30.0ppm
15.0
P8
CO2 green to yellow setpoint
1 ~ 5000ppm
800
P9
CO2 yellow to red setpoint
1 ~ 5000ppm
1200
P10
TVOC green to yellow setpoint
0.0 ~ 30.0ppm
10.0

6
P11
TVOC yellow to red setpoint
0.0 ~ 30.0ppm
20.0
P12
The relay mode for CO2
1 ~ 4 (see table 4)
1
P13
The relay mode for Temp
1 ~ 4 (see table 5)
2
P14
The relay mode for Humi
1 ~ 4 (see table 6)
1
P15
The relay mode for TVOC
1 ~ 4 (see table 7)
1
P16
CO2 offset for relay control
1 ~ 5000ppm
10
P17
Temp offset for relay control
-20.0 ~ 60.0℃
1.0
P18
Humi offset for relay control
0.01 ~ 100.00 %RH
1.0
P19
TVOC control relay offset
0.0 ~ 30.0ppm
1.0
P20
PID or Linear output
0 ~ 15 (see table 2)
15
P21
CO2 linear min value
0 ~ 5000ppm
0
P22
CO2 linear min volt
0.000 ~ 10.000V, configure current output by current
value/2
0.000
P23
CO2 linear max value
0 ~ 5000ppm
5000
P24
CO2 linear max volt
0.000 ~ 10.000V, configure current output by current
value/2
10.000
P25
Temp linear min value
0~50°C
0.0
P26
Temp linear min volt
0.000 ~ 10.000, configure current output by current
value/2
0.000
P27
Temp linear max value
0~50°C
50.0
P28
Temp linear max volt
0.000 ~ 10.000V, configure current output by current
value/2
10.000
P29
Humi linear min value
0.01 ~ 100.00%RH
0.0
P30
Humi linear min volt
0.000 ~ 10.000V, configure current output by current
value/2
0.000
P31
Humi linear max value
0.01 ~ 100.00%RH
100.0
P32
Humi linear max volt
0.000 ~ 10.000V, configure current output by current
value/2
10.000
P33
TVOC linear min value
0.0 ~ 30.0ppm
0.0
P34
TVOC linear min volt
0.000 ~ 10.000V, configure current output by current
value/2
0.000
P35
TVOC linear max value
0.0 ~ 30.0ppm
30.0
P36
TVOC linear max volt
0.000 ~ 10.000V, configure current output by current
value/2
10.000

7
P37
CO2 PID period setpoint
0.1 ~ 10000.0
0.1
P38
CO2 PID-P setpoint
-10000 ~ 10000
-2.0
P39
CO2 PID-I setpoint
0.0 ~ 10000.0
10.0
P40
CO2 PID-D setpoint
0.0 ~ 10000.0
10.0
P41
Temp PID period setpoint
0.1 ~ 10000.0
0.1
P42
Temp PID-P setpoint
-10000 ~ 10000
2.0
P43
Temp PID-I setpoint
0.0 ~ 10000.0
10.0
P44
Temp PID-D setpoint
0.0 ~ 10000.0
10.0
P45
Humi PID period setpoint
0.1 ~ 10000.0
0.1
P46
Humi PID-P setpoint
-10000 ~ 10000
-2.0
P47
Humi PID-I setpoint
0.0 ~ 10000.0
10.0
P48
Humi PID-D setpoint
0.0 ~ 10000.0
10.0
P49
TVOC PID period setpoint
0.1 ~ 10000.0
0.1
P50
TVOC PID-P setpoint
-10000 ~ 10000
-2.0
P51
TVOC PID-I setpoint
0.0 ~ 10000.0
10.0
P52
TVOC PID-D setpoint
0.0 ~ 10000.0
10.0
P53
CO2 PID MAN ON setpoint
0 ~ 1
0
P54
CO2 PID MAN setpoint
0 ~ 100 % 0~10V/0~20mA percent
Unfixed
P55
Temp PID MAN ON setpoint
0 ~ 1
0
P56
Temp PID MAN setpoint
0 ~ 100 % 0~10V/0~20mA percent
Unfixed
P57
Humi PID MAN ON setpoint
0 ~ 1
0
P58
Humi PID MAN setpoint
0 ~ 100 % 0~10V/0~20mA percent
Unfixed
P59
TVOC PID MAN ON setpoint
0 ~ 1
0
P60
TVOC PID MAN setpoint
0 ~ 100 % 0~10V/0~20mA percent
Unfixed
P61
CO2 PID self-tuning
1- Run CO2 control PID self-tuning
0- stop PID self-tuning
0
P62
Temp PID self-tuning
1- Run temp. control PID self-tuning
0- stop PID self-tuning
0
P63
Humi PID self-tuning
1- Run humi. control PID self-tuning
0- stop PID self-tuning
0

8
P64
TVOC PID self-tuning
1- Run TVOC control PID self-tuning
0- stop PID self-tuning
0
P65
Power on again
1- turn off
2-turn on after power up again
3- hold the mode before the power failure
3
P66
Temperature unit
1- Degree Celsius; 2- Fahrenheit
1
P67
CO2 ABC Logic
1- ABC Logic ON;
2- ABC Logic OFF; (T67X3 only can set, can not
read)
0
P68
CO2 elevation setpoint
0 ~ 5000 feet
0
P69
CO2 single-point calibration
target
0 ~ 5000ppm S8 does not support this command
400
P70
CO2 single-point calibration
on/off
0- do not run single calibrate
1- start to run single calibrate
0
P71
TVOC AD adjustment
-500 ~ 500 (TVOC AD calibration value)
0
P72
Disable/enable buttons
1- all buttons are enabled;
2- ON/OFF button disabled;
3- SET, ▲,▼buttons disabled;
4- all buttons are disabled
1
P73
relay and analog output test
0- DC1 DC2 DC3 ON1 ON2 ON3 run normally
1- DC1=0V/0mA DC2=0V/0mA DC3=0V/0mA
ON1=OFF ON2=OFF ON3=OFF
2- DC1=2V/4mA DC2=2V/4mA DC3=2V/4mA
ON1=OFF ON2=OFF ON3=OFF
3- DC1=10V/20mA DC2=10V/20mA DC3=10V/20mA
ON1=ON ON2=ON ON3=ON
0
P74
CO2 range
0~5000ppm
5000
P75
Force AN1 output to 10V for
night ventilation in summer
mode
0: AN1 normal output;
1~100: force AN1 output 1~100% of 10V
Note: Not saved after power off/power on
0
P76
AN2 output highest value
between Co2 and temperature
PID
0-AN2 normal output 0~10V
1-AN2 output highest value
0
P77
Firmware version
891
891
If there is a need to adjust P61, P62, P63, P64 to run PID self-tuning, it has to be performed in situations that the
controlled device is properly connected and work normally. Or it is difficult to get ideal PID settings.

9
Modbus Parameters V3.1
Mode: RTU (MSB First)
Baud Rate: 9600/14400/19200/38400/56000/57600/76800/115200 bps default: 9600
Start Bits: 1
Data Bits: 8
Stop Bits: 1 / 2 default : 1
Parity: None / Odd / Even default: None
Register Map Support Function: 3 4 6 16
Starting
Register
Decimal
Address
(Base 0)
Data Description
Function
Read/
Write
Length
Format
Valid Response
Default
Correspond
LCD
Parameter
Function 1: Read Coils
0
ON1-Relay1
output
1
R
1
UINT8
0-OFF;1-ON
1
ON2-Relay2
output
1
R
1
UINT8
0-OFF;1-ON
2
ON3-Relay3
output
1
R
1
UINT8
0-OFF;1-ON
Function 2: Read Discrete Inputs
0
DIP1
2
R
1
UINT8
OFF-User page;
ON-Set parameter page
OFF
1
DIP2
2
R
1
UINT8
OFF- Humi control relay3
and AN3;
ON- TVOC control relay3
and AN3
OFF
2
PCB SET
2
R
1
UINT8
OFF-0~10V/0~20mA
ON-2~10V/4~20mA
OFF
Function 4: Read Input Registers
0
Co Measurement
4
R
2
Float
Big-endian
0~5000 ppm
2
Temp.
Measurement
4
R
2
Float
Big-endian
-20.0~60.0℃/-40.0~140.0
℉
4
Humi.
Measurement
4
R
2
Float
Big-endian
0.1~100.0 RH%
6
TVOC
measurement
4
R
2
Float
Big-endian
0~30.0ppm
10
Co2 Measurement
4
R
1
UINT16
0~5000 => 0~5000 ppm
11
Temp.
Measurement
x 1 times
4
R
1
INT16
-20~60 =>-20~60℃
-40~140=>-40~140℉

10
12
Humi.
Measurement
x 1 times
4
R
1
UINT16
1~100 => 1~100 RH%
13
TVOC
measurement
x 1 times
4
R
1
UINT16
0~30 => 0~30ppm
20
Co2 Measurement
4
R
1
UINT16
0~5000 => 0~5000 ppm
21
Temp.
Measurement
x 10 times
4
R
1
INT16
-200~600 =>-20.0~60.0℃/
-400~1400=>-40.0~140.0
℉
22
Humi.
Measurement
x 10 times
4
R
1
UINT16
1~1000 => 0.1~100.0 RH%
23
TVOC
measurement
x 10 times
4
R
1
UINT16
0~300 => 0~30.0ppm
Function 3: Read Holding Registers; Functions 6: Write Single Register; Function 16: Write Multiple Registers
0
Device RS485
address
3/6
R/W
1
UINT16
1~247
1
P-1
1
RS485 baud rate
choice
3/6
R/W
1
UINT16
2-9600bps
3-14400bps
4-19200bps
5-38400bps
6-56000bps
7-57600bps
8-115200bps
2
P-2
2
RS485
parity - stop bits
3/6
R/W
1
UINT16
1-None 1 Stop Bit;
2-None 2 Stop Bit;
3-Odd 1 Stop Bit;
4-Even 1 Stop Bit
1
P-3
3
Force AN1 output
to 10V for night
ventilation in
summer mode
3/6
R/W
1
UINT16
0: AN1 normal output;
1~100: force AN1 output
1~100% of 10V
Note: Not saved after
power off/power on
0
P-75
4
Disable/enable
button operation
3/6
R/W
1
UINT16
1-unlock all buttons;
2- lock only ON/OFF
button;
3- lock only SET, UP,
DOWN button;
4-lock all buttons
1
P-72
5
Temp heat or cool
mode for temp pid
or relay2
3/6
R/W
1
UINT16
0-Cool
1-Heat
1
User “Temp
control
mode”
6
Device Turn
On/Off
3/6
R/W
1
UINT16
0-TurnOn;
1-TurnOff
0
User “power”
button
7
Power on again
3/6
R/W
1
UINT16
1-Off; 2-On; 3-Keep
3
P-65

11
choice
8
Temperature unit
selection
3/6
R/W
1
UINT16
1-Degree Celsius;
2-Fahrenheit
1
P-66
9
AN1 AN2 AN3
PID or Linear
output choice
3/6
R/W
1
UINT16
0~15 Table 3
15
P20
10
Co2 setpoint for
relay1 and
AN1(0~10V/4~20
mA) PID
3/16
R/W
2
Float
Big-endian
0~5000ppm
800
User “Co2
setpoint”
12
Temp setpoint for
relay2 and
AN2(0~10V/4~20
mA) PID
3/16
R/W
2
Float
Big-endian
-20.0~60.0℃
21.0
User “Temp
setpoint”
14
Humi setpoint for
relay3 and
AN3(0~10V/4~20
mA) PID
3/16
R/W
2
Float
Big-endian
0~100%RH
50
User “Humi
setpoint”
16
TVOC setpoint for
relay3 and
AN3(0~10V/4~20
mA) PID
3/16
R/W
2
Float
Big-endian
0~30.0ppm
15.0
User “TVOC
setpoint”
350
Co2 setpoint for
relay1 and
AN1(0~10V/4~20
mA) PID
3/6
R/W
1
UINT16
0~5000 => 0~5000ppm
800
User “Co2
setpoint”
351
Temp setpoint for
relay2 and
AN2(0~10V/4~20
mA) PID
x 1 times
3/6
R/W
1
INT16
-20~60 => -20~60℃
21
User“Temp
setpoint”
352
Humi setpoint for
relay3 and
AN3(0~10V/4~20
mA) PID
x 1 times
3/6
R/W
1
UINT16
0~100 => 0~100%RH
50
User“Humi
setpoint”
353
TVOC setpoint for
relay3 and
AN3(0~10V/4~20
mA) PID
x 1 times
3/6
R/W
1
UINT16
0~30 => 0~30ppm
15
User“TVOC
setpoint”
360
Co2 setpoint for
relay1 and
3/6
R/W
1
UINT16
0~5000 => 0~5000ppm
800
User “Co2
setpoint”

12
AN1(0~10V/4~20
mA) PID
361
Temp setpoint for
relay2 and
AN2(0~10V/4~20
mA) PID
x 10 times
3/6
R/W
1
INT16
-200~600 => -20.0~60.0℃
210
User“Temp
setpoint”
362
Humi setpoint for
relay3 and
AN3(0~10V/4~20
mA) PID
x 10 times
3/6
R/W
1
UINT16
0~1000 => 0.0~100.0%RH
500
User“Humi
setpoint”
363
TVOC setpoint for
relay3 and
AN3(0~10V/4~20
mA) PID
x 10 times
3/6
R/W
1
UINT16
0~300 => 0~30.0ppm
150
User“TVOC
setpoint”
18
CO2 green to
yellow alarm
setpoint
3/16
R/W
2
Float
Big-endian
1~5000ppm
800
P-8
20
CO2 yellow to red
alarm setpoint
3/16
R/W
2
Float
Big-endian
1~5000ppm
1200
P-9
22
TVOC green to
yellow alarm
setpoint
3/16
R/W
2
Float
Big-endian
0~30.0ppm
10.0
P-10
24
TVOC yellow to
red alarm setpoint
3/16
R/W
2
Float
Big-endian
0~30.0ppm
20.0
P-11
26
CO2 calibration
value
3/16
R/W
2
Float
Big-endian
-300~300.0ppm
0ppm
P-4
28
Temp calibration
value
3/16
R/W
2
Float
Big-endian
-3.0~3.0℃
0.0℃
P-5
30
Humidity
correction value
3/16
R/W
2
Float
Big-endian
-5.0~5.0%RH
0.0
%RH
P-6
32
TVOC correction
target value
3/16
R/W
2
Float
Big-endian
0.0~30.0ppm
15.0
%RH
P-7
39
AN2 output
highest value
between Co2 and
temperature PID
3/6
R/W
1
UINT16
0-AN2 normal output
0~10V
1-AN2 output highest value
0
P-76
40
AN1 CO2 linear
min. value
3/16
R/W
2
Float
Big-endian
0~5000ppm
0
P-21
42
AN1 CO2 linear
min volt
3/16
R/W
2
Float
Big-endian
0~10.000v
0.000
P-22

13
44
AN1 CO2 linear
max value
3/16
R/W
2
Float
Big-endian
0~5000ppm
5000
P-23
46
AN1 CO2 linear
max volt
3/16
R/W
2
Float
Big-endian
0~10.000v
10.000
P-24
48
AN2 Temp linear
min
3/16
R/W
2
Float
Big-endian
-20.0~60.0℃
-20.0
P-25
50
AN2 Temp linear
min
3/16
R/W
2
Float
Big-endian
0~10.000v
0.000
P-26
52
AN2 Temp linear
max value
3/16
R/W
2
Float
Big-endian
-20.0~60.0℃
50.0
P-27
54
AN2 Temp linear
max volt
3/16
R/W
2
Float
Big-endian
0~10.000v
10.000
P-28
56
AN3 Humi linear
min value
3/16
R/W
2
Float
Big-endian
0~100.0%RH
0
P-29
58
AN3 Humi linear
min volt
3/16
R/W
2
Float
Big-endian
0~10.000v
0.000
P-30
60
AN3 Humi linear
max value
3/16
R/W
2
Float
Big-endian
0~100.0%RH
100.0
P-31
62
AN3 Humi linear
max volt
3/16
R/W
2
Float
Big-endian
0~10.000v
10.000
P-32
64
AN3 TVOC linear
min value
3/16
R/W
2
Float
Big-endian
0~30.0ppm
0
P-33
66
AN3 TVOC linear
min volt
3/16
R/W
2
Float
Big-endian
0~10.000v
0.000
P-34
68
AN3 TVOC linear
max value
3/16
R/W
2
Float
Big-endian
0~30.0ppm
30.0
P-35
70
AN3 TVOC linear
max volt
3/16
R/W
2
Float
Big-endian
0~10.000v
10.000
P-36
72
the relay mode for
CO2
3/6
R/W
1
UINT16
1-auto control relay ON1->
reduce CO2
2-auto control relay ON1->
increase CO2
3-hand control relay ON1->
OFF
4-hand control relay ON1->
ON
1
P-12
73
the relay mode for
Temp
3/6
R/W
1
UINT16
1-auto control relay ON2->
temp cool
2-auto control relay ON2->
temp heat
3-hand control relay ON2->
OFF
4-hand control relay ON2->
ON
2
P-13
74
the relay mode for
Humi
3/6
R/W
1
UINT16
1-auto control relay ON3->
dehumidification
1
P-14

14
2-auto control relay ON3->
humidification
3-hand control relay ON3->
OFF
4-hand control relay ON3->
ON
75
the relay mode for
TVOC
3/6
R/W
1
UINT16
1-auto control relay ON3->
reduce TVOC
2-auto control relay ON3->
increase TVOC
3-hand control relay ON3->
OFF
4-hand control relay ON3->
ON
1
P-15
76
CO2 offset for
relay control
3/16
R/W
2
Float
Big-endian
1~5000ppm
10
P-16
78
Temp offset for
relay control
3/16
R/W
2
Float
Big-endian
-20~60℃
1.0
P-17
80
Humi offset for
relay control
3/16
R/W
2
Float
Big-endian
0.1~100%RH
1.0
P-18
82
TVOC control
relay offset
3/16
R/W
2
Float
Big-endian
0~30ppm
1.0
P-19
94
AN1 current
analog output
3
R
2
Float
Big-endian
0.000~10.000V/4.000~20.0
00mA
96
AN2 current
analog output
3
R
2
Float
Big-endian
0.000~10.000V/4.000~20.0
00mA
98
AN3 current
analog output
3
R
2
Float
Big-endian
0.000~10.000V/4.000~20.0
00mA
100
Co2 CYCLE
3/16
R/W
2
Float
Big-endian
0.1~10000.0
0.1
P-37
102
Co2 GAIN
3/16
R/W
2
Float
Big-endian
-10000.0~10000.0
<0 -> reduce CO2
>0 -> increase CO2
-2.0
P-38
104
Co2 TI
3/16
R/W
2
Float
Big-endian
0.0~10000.0
40.0
P-39
106
Co2 TD
3/16
R/W
2
Float
Big-endian
0.0~10000.0
10.0
P-40
108
Temp CYCLE
3/16
R/W
2
Float
Big-endian
0.1~10000.0
0.1
P-41
110
Temp GAIN
3/16
R/W
2
Float
-10000.0~10000.0
2.0
P-42

15
Big-endian
<0 -> Temp cool
>0 -> Temp heat
112
Temp TI
3/16
R/W
2
Float
Big-endian
0.0~10000.0
40.0
P-43
114
Temp TD
3/16
R/W
2
Float
Big-endian
0.0~10000.0
10.0
P-44
116
Humi CYCLE
3/16
R/W
2
Float
Big-endian
0.1~10000.0
0.1
P-45
118
Humi GAIN
3/16
R/W
2
Float
Big-endian
-10000.0~10000.0
<0 ->dehumidification
>0 ->humidification
-2.0
P-46
120
Humi TI
3/16
R/W
2
Float
Big-endian
0.0~10000.0
40.0
P-47
122
Humi TD
3/16
R/W
2
Float
Big-endian
0.0~10000.0
10.0
P-48
124
TVOC CYCLE
3/16
R/W
2
Float
Big-endian
0.1~10000.0
0.1
P-49
126
TVOC GAIN
3/16
R/W
2
Float
Big-endian
-10000.0~10000.0
<0 ->reduce TVOC
>0 ->increase TVOC
-2.0
P-50
128
TVOC TI
3/16
R/W
2
Float
Big-endian
0.0~10000.0
10.0
P-51
130
TVOC TD
3/16
R/W
2
Float
Big-endian
0.0~10000.0
10.0
P-52
132
CO2 PID manual
output AN1 choice
(MAN ON)
3/16
R/W
2
Float
Big-endian
0-CO2 control PID
AN1(0~10VDC/4~20mA )o
utput
1-manual control
AN1(0~10VDC/4~20mA)
output
0
P-53
134
CO2 PID manual
output
AN1(0~10VDC/4~
20mA) setpoint
(MAN)
3/16
R/W
2
Float
Big-endian
0~100% <=>
AN1(0~10VDC/4~20mA)
output
50%
P-54
136
Temp PID manual
output AN2 choice
(MAN ON)
3/16
R/W
2
Float
Big-endian
0-Temp control PID
AN2(0~10VDC/4~20mA )o
utput
1-manual control
AN2(0~10VDC/4~20mA)
output
0
P-55
138
Temp PID manual
output
AN2(0~10VDC/4~
3/16
R/W
2
Float
Big-endian
0~100% <=>
AN2(0~10VDC/4~20mA)
50%
P-56

16
20mA) setpoint
(MAN)
output
140
Humi PID manual
output AN3 choice
(MAN ON)
3/16
R/W
2
Float
Big-endian
0-Humi control PID
AN3(0~10VDC/4~20mA )o
utput
1-manual control
AN3(0~10VDC/4~20mA)
output
0
P-57
142
Humi PID manual
output
AN3(0~10VDC/4~
20mA) setpoint
(MAN)
3/16
R/W
2
Float
Big-endian
0~100% <=>
AN3(0~10VDC/4~20mA)
output
50%
P-58
144
TVOC PID manual
output AN3 choice
(MAN ON)
3/16
R/W
2
Float
Big-endian
0-TVOC control PID
AN3(0~10VDC/4~20mA )o
utput
1-manual control
AN3(0~10VDC/4~20mA)
output
0
P-59
146
TVOC PID manual
output
AN3(0~10VDC/4~
20mA) setpoint
(MAN)
3/16
R/W
2
Float
Big-endian
0~100% <=>
AN3(0~10VDC/4~20mA)
output
50%
P-60
148
CO2 PID
self-tuning
(TUN_ON)
3/16
R/W
2
Float
Big-endian
1-Start CO2 PID self-tuning
0-Stop CO2 PID self-tuning
or CO2 PID self-tuning had
finished
0
P-61
150
Co2 PHASE
(Read Only)
3
R
2
Float
Big-endian
152
Co2 STATUS_H
(Read Only)
3
R
2
Float
Big-endian
154
CO2 STATUS_D
(Read Only)
3
R
2
Float
Big-endian
156
CO2 LMN Output
(Read Only)
3
R
2
Float
Big-endian
158
Temp PID
self-tuning
(TUN_ON)
3/16
R/W
2
Float
Big-endian
1-Start CO2 PID self-tuning
0-Stop CO2 PID self-tuning
or CO2 PID self-tuning had
finished
0
P-62
160
Temp PHASE
(Read Only)
3
R
2
Float
Big-endian
162
Temp STATUS_H
(Read Only)
3
R
2
Float
Big-endian
164
Temp STATUS_D
3
R
2
Float

17
(Read Only)
Big-endian
166
Temp LMN Output
(Read Only)
3
R
2
Float
Big-endian
168
Humi PID
self-tuning
(TUN_ON)
3/16
R/W
2
Float
Big-endian
1-Start CO2 PID self-tuning
0-Stop CO2 PID self-tuning
or CO2 PID self-tuning had
finished
0
P-63
170
Humi PHASE
(Read Only)
3
R
2
Float
Big-endian
172
Humi STATUS_H
(Read Only)
3
R
2
Float
Big-endian
174
Humi STATUS_D
(Read Only)
3
R
2
Float
Big-endian
176
Humi LMN Output
(Read Only)
3
R
2
Float
Big-endian
178
TVOC PID
self-tuning
(TUN_ON)
3/16
R/W
2
Float
Big-endian
1-Start CO2 PID self-tuning
0-Stop CO2 PID self-tuning
or CO2 PID self-tuning had
finished
0
P-64
180
TVOC PHASE
(Read Only)
3
R
2
Float
Big-endian
182
TVOC STATUS_H
(Read Only)
3
R
2
Float
Big-endian
184
TVOC STATUS_D
(Read Only)
3
R
2
Float
Big-endian
186
TVOC LMN
Output(Read
Only)
3
R
2
Float
Big-endian
290
TVOC AD
adjustment
setpoint
3/6
R/W
1
INT16
-500,500
P-71
291
TVOC AD value
(Read Only)
3
R
1
INT16
295
Co2 ABC Logic
now status
3
R
1
UINT16
0-Reading; 1-ABC ON;
2-ABC OFF
296
Co2 ABC Logic
3/6
R/W
1
UINT16
1-ABC ON; 2-ABC OFF
1
P-67
297
Co2 elevation
setpoint
3/6
R/W
1
UINT16
0~5000 inch
0
P-68
298
CO2 single-point
calibration target
3/6
R/W
1
UINT16
400~5000 ppm
400
P-69
299
CO2 single-point
calibration on/off
3/6
R/W
1
UINT16
0-stop/finish;1-start
0
P-70
Note:Scan Rate>=4000ms
Table of contents
Other Atal Measuring Instrument manuals
Popular Measuring Instrument manuals by other brands

Diehl
Diehl SHARKY 775 installation guide

Lovibond
Lovibond SensoDirect pH110 instruction manual

AETOOL
AETOOL BESA 11 quick start guide

Sper scientific
Sper scientific 300005 instruction manual

Ecom Instruments
Ecom Instruments Ex-Pt 720 instruction manual

Precision Digital Corporation
Precision Digital Corporation TRIDENT instruction manual

Dräger
Dräger Polytron 5200 Instructions for use

GE
GE MFE DMS 2 operating manual

Advanced Instruments
Advanced Instruments OsmoPRO user guide

Bosch
Bosch GAM220MF Professional Original instructions

Extech Instruments
Extech Instruments 407790A user manual

Detecto
Detecto MedVue MVWIFI Installation, configuration, and operation manual