2/2
Commissioning
The appliance should be installed and commissioned by an authorised
installer. Check the following:-
Never connect the appliance to the mains voltage without filling and
de-aerating the appliance and the system.
1. Confirm that the appliance and system have been filled and de-
aerated.
2. Check that the electrical supply is switched on and the gas supply
is on.
3. Set the room thermostat lower than the room temperature.
Assuming that the appliance is in standby (horizontal mark on the
service display and remaining functions are off), switch on the
appliance with the on/off button on the display.
4. Set the room thermostat higher than the room temperature. The
appliance will start CH operation (5 on the service display) , heating
the CH supply water to the set temperature (see CH operation).The
set temperature can be adjusted (lower in case of mild weather,
higher if the outside temperature gets colder).
Frost protection
In order to avoid freezing of the condensate discharge pipe, the appliance
should be installed in a frost-free room. In order to avoid freezing of the
appliance (heat exchanger), it has an appliance frost protection. When the
temperature of the heat exchanger drops to 5ºC, the burner will be
activated and the external pump will start running (if connected to the
appliance pump output) until the temperature of the heat exchanger
reaches 10ºC. When the system (or a part of it) can freeze, a frost
thermostat should beinstalled in the area to beprotected. Connect this
according to the wiring diagram (see also the Installation instructions).
Note!
The external frost thermostat is not active when the appliance has been
switched off at the operating panel or when the mains voltage has been
interrupted.
Faults
If one of the following simple faults occur, they may be remedied as
follows. In case of recurrence, or other faults, please contact your
installer.
The CH System does not reach the correct temperature:-
•Increase the temperature on the room thermostat.
•Open the radiator valves.
•Increase the CH water temperature by means of the CH / HW
switch button and the + and – button on the display.
•De-aerate the system with the manual air vents on the radiators.
The fault LED above the Reset button lights up and the service
display flashes with code 0, 1, 2 or 3:-
The boiler is getting too hot, due to insufficient circulation.
•De-aerate the system with the manual air vents on the radiators.
After remedying the cause, press the Reset button for 5 secs and the
appliance will start-up again.
System Shutdown
Drain the appliance and the system when the mains voltage
has been disconnected and there is a chance of freezing.
1. Drain the appliance using the drain tap.
2. Drain the system at the lowest point.
Servicing the appliance
The appliance, the installation, the flue discharge and air supply should
be serviced every year by a qualified service engineer. The appliance
can be cleaned with a damp cloth. Do not use any aggressive or sanding
cleaner.
Guarantee
Atmos guarantees the heat exchanger for 5 years as detailed in the
Installation Manual, and other parts for 2 years (except ignition probe,
ionisation pin, glass fuse, thermocouple and de-aerator) including labour.
The provision of service and the execution of the guarantee is the
responsibility of the installer from whom you purchased the appliance.
See also the Guarantee card.
User Instructions for HE22
Issue 3.02.06
Atmos Heating Systems
West March, Daventry, Northants, NN11 4SA.
May be changed without
prior notice