3. Technical data
Features and functions
Explosion protection Standard: IM2 Ex de or Ex de [ib] I
IM2 c I
Option: IM2 Ex d or Ex d [ib] I
IM2 c I
Protection types Motor compartment d flameproof enclosure Ex d
Switch compartment: d flameproof enclosure Ex d
optional: components Ex ib
Controls housing: d flameproof enclosure Ex d
Terminal compartment: e increased safety Ex e
d (option) flameproof enclosure Ex d
Gear housing: c constructional safety
EC type examination certificate BVS 06 ATEX E106
Type of duty1) Standard: SAExC Short time duty S2 - 15 min
SARExC Intermittent duty S4 - 25 %
Option: SAExC Short time duty S2 - 30 min
SARExC Intermittent duty S4 - 50 %
Motors 3-ph AC asynchronous motor, type IM B9 according to IEC 34
Insulation class F, tropicalized
Motor protection Standard: SAExC: PTC thermistors (PTC acc. to DIN 44082)
SARExC: PTC thermistors (PTC acc. to DIN 44082)
Option: SAExC: Thermoswitches (NC)
Self-locking Yes, for output speeds from 4 to 90 rpm
Limit switching Counter gear mechanism for end positions OPEN and CLOSED
for 1 to 500 turns per stroke (optional for 1 to 5,000 turns per stroke)
Standard: Single switch (1 NC and 1 NO) for each end position
Options: Tandem switch (2 NC and 2 NO) for each end position,
switches galvanically isolated
Triple switch (3 NC and 3 NO) for each end position, switches galvanically isolated
Intermediate position switch (DUO limit switching),
adjustable for any intermediate position
Torque switching Infinitely adjustable torque switching for direction OPEN and CLOSE
Standard: Single switch (1 NC and 1 NO) for each direction
Options: Tandem switch (2 NC and 2 NO) for each direction,
switches galvanically isolated
Position feedback signal,
analogue (options) Potentiometer or 0/4 – 20 mA (RWG)
For further details see separate data sheet
Mechanical position indicator (option) Continuous indication, adjustable indicator disc with symbols OPEN and CLOSED
Running indication Blinker transmitter
Heater in switch compartment Standard: Resistance type heater with 5 W, 24 V DC
Options: Self-regulating PTC heater, 5 – 20 W
24 – 48 V AC/DC, 110 – 250 V AC/DC or 380 – 400 V AC
Motor heater (option) SAExC/ SARExC 07.1 – 10.1: 12.5 W
SAExC/ SARExC 14.1 – 16.1: 25 W
Manual operation Manual drive for setting and emergency operation, handwheel does not rotate during
electrical operation.
Option: Handwheel lockable
Connection to controls AUMA plug/socket connector
Output drive types A, B1, B2, B3, B4 according to EN ISO 5210
A, B, D, E according to DIN 3210
C according to DIN 3338
Special output drives: AF, AK, AG, IB1, IB3
Power supply, mains frequency
and current consumption For mains voltage and mains frequency, refer to name plates at the controls and the motor
Permissible variation of the nominal voltage: ± 10 %
Permissible variation of the mains frequency: ± 5 %
Motor current consumption: Refer to motor name plate
Current consumption of the controls depending on the mains voltage:
100 to 120 V AC = max. 600 mA
208 to 240 V AC = max. 300 mA
380 to 500 V AC = max. 150 mA
External supply of the electronics
(option) 24 V DC +20 %/–15 %,
Observe current consumption of the controls
1) Based on 20 °C ambient temperature and an average load with running torque according to Technical data SAExC or SARExC.
The type of duty must not be exceeded
6
Multi-turn actuators SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1
with actuator controls AUMA MATIC AMExC 01.1 Operation instructions