
5
3.1 Air Supply
This instrument requires water free and oil free air, Dry Air, Particles
<5u, ISA Grade Hydrocarbon Free. Requirements are full time, clean
dry air at a cabinet pressure of 0-10 mbar at a flow rate of 0-50 SLPM.
Please note that 10 mbar and 50 SLPM are maximum values that will
not probably be attained in practice.
3.2 Electrical Power Input Connections
The Air Sentinel II purge controller requires 100-240 VAC 47-63 HZ.
A circuit breaker must be placed prior to the power connection in close
proximity and within easy reach to allow for service. This circuit breaker
must be marked to indicate that it is a disconnecting means for the
instrument. The rating of the circuit should be 5A.
Supply power connections are made ONLY to top “MAINS” connection
on the back of the Air Sentinel II purge controller:
Terminal 3: Earth Ground
Terminal 2: Neutral
Terminal 1 Line Or Hot
Suitable wire would be stranded, 3 conductors 18-12 AWG copper or
tin plated copper with a voltage rating of 600VAC with a temperature
rating of 90˚ C or higher.
Common earth bond points are provided both inside the enclosure
on the chassis and outside of the enclosure. This terminal set can
be removed for easier connections. Please ensure this terminal set is
properly tightened using the two side screws.
3.3 Electrical Power Output Connections
The second or lower three terminals are controlled power output.
This is where a powered device is connected to ensure power is not
applied unless the enclosure is purged and pressurized. The output is
connected to the mains power after the purge time has been exceeded
assuming the enclosure is under pressure and air is exiting the vent.
The load should not exceed 2A at 240VAC.
This terminal set can be removed for easier connections. Please ensure
this terminal set is properly tightened using the two side screws.
Figure 2: Air Sentinel II Electrical Connections
3.4 Electrical Alarm Connections
Three relay (1 Form A) alarm connections are supplied that can be used
to indicate an Alarm condition under the following modes of operation:
1. Loss of Pressure or Flow. Under this condition the front panel
LED labeled Pressure will turn RED and the associated Alarm
contacts will close.
2. Purge Timer enabled. Under this condition the front panel LED
labeled Timer will turn RED and the associated Alarm contacts
will close.
These contacts are rated 2A at 250VAC or 2A at 24VDC.
Refer to Figure 2 for the alarm connections. These connections
terminals are NOT removable.
3.5 Mechanical Mounting
Figure 3: Air Sentinel II Dimensions
The Air Sentinel II is mounted to an enclosure using the 10, ¼"- 20
studs. The recommended hardware is a ¼" flat washer and locking nut,
or the provided locking nut with the built-in washer. The recommended
enclosure opening is shown in Figure 4.
From the previous Figure 1 you will notice three ports labeled Air Purge,
Pressure Port and Drain Vent. The Air Purge is the main vent that
all enclosure exhaust air should exit the enclosure through. This Air
Sentinel II measures this air to ensure continuous venting is occurring.
The Pressure Port is where the Air Sentinel II measures the enclosure
pressure to ensure the enclosure is kept above atmospheric pressure
(overpressure). The Drain Vent is an optional atmospheric pressure vent
for certain applications such as venting a drain. If this vent is not used it
must be capped.
3.0 Installation and Commissioning
WARNING
!
Only qualified electricians should be allowed to perform the
installation of the instrument as it involves a line voltage that
could endanger life.