AUMA SQ 05.2 User manual

Control
Parallel
Profibus DP
Profinet
→Modbus RTU
Modbus TCP/IP
Foundation Fieldbus
HART
Part-turn actuators
SQ 05.2 –SQ 14.2
SQR 05.2 –SQR 14.2
Control unit - electromechanical
with actuator controls
AC 01.2 Intrusive
Assembly, operation, commissioningOperation instructions

Read operation instructions first.
●Observe safety instructions.
●These operation instructions are part of the product.
●Retain operation instructions during product life.
●Pass on instructions to any subsequent user or owner of the product.
Purpose of the document:
This document contains information for installation, commissioning, operation and maintenance staff.It is intended
to support device installation and commissioning.
Reference documents:
●Manual (Operation and setting ) of actuator controls AC 01.2 Modbus
●Manual (Fieldbus device integration) of actuator controls AC 01.2 Modbus
Reference documents can be downloaded from the Internet (www.auma.com) or ordered directly from AUMA
(refer to <Addresses>).
Table of contents Page
51. Safety instructions................................................................................................................. 51.1. Basic information on safety 51.2. Range of application 61.3. Applications in Ex zone 22 (option) 61.4. Warnings and notes 71.5. References and symbols
82. Identification........................................................................................................................... 82.1. Name plate 112.2. Short description
123. Transport, storage and packaging........................................................................................ 123.1. Transport 133.2. Storage 143.3. Packaging
154. Assembly................................................................................................................................ 154.1. Mounting position 154.2. Handwheel fitting 154.3. Part-turn actuator to valve: mount 164.3.1. Output drive for coupling 164.3.1.1. Part-turn actuator (with coupling): mount to valve 194.4. Mounting positions of local controls 194.4.1. Mounting positions: modify
205. Electrical connection............................................................................................................. 205.1. Basic information 235.2. SD electrical connection (AUMA plug/socket connector) 245.2.1. Terminal compartment (for mains connection):open 255.2.2. Cable connection 265.2.3. Terminal compartment (for mains connection):close 275.2.4. Fieldbus terminal compartment: open 285.2.5. Fieldbus cables: connect 295.2.6. Fieldbus terminal compartment: close
2
SQ 05.2 –SQ 14.2 / SQR 05.2 –SQR 14.2 Control unit - electromechanical
Table of contents AC 01.2 Intrusive Modbus RTU

305.3. Accessories for electrical connection 305.3.1. Actuator controls on wall bracket 315.3.2. Parking frame 315.3.3. DS intermediate frame for double sealing 325.3.4. External earth connection
336. Operation................................................................................................................................ 336.1. Manual operation 336.1.1. Manual operation: engage 336.1.2. Manual operation: disengage 336.2. Motor operation 336.2.1. Local actuator operation 346.2.2. Actuator operation from remote 356.3. Menu navigation via push buttons (for settings and indications) 366.3.1. Menu layout and navigation 376.4. User level, password 376.4.1. Password entry 386.4.2. Password change 386.5. Language in the display 386.5.1. Language change
407. Indications.............................................................................................................................. 407.1. Indications during commissioning 407.2. Indications in the display 417.2.1. Feedback indications from actuator and valve 437.2.2. Status indications according to AUMA classification 447.2.3. Status indications according to NAMUR recommendation 467.3. Indication lights of local controls 477.4. Mechanical position indication via indicator mark
488. Signals (output signals)......................................................................................................... 488.1. Signals via fieldbus 488.2. Status signals via output contacts (digital outputs) 488.2.1. Assignment of outputs 488.2.2. Coding the outputs 488.3. Analogue signals (analogue outputs)
509. Commissioning (basic settings)........................................................................................... 509.1. End stops in part-turn actuator 519.1.1. End stop CLOSED: set 519.1.2. End stop OPEN: set 529.2. Type of seating: set 539.3. Fieldbus address (slave address), baud rate, parity and monitoring time: set 539.4. Switch compartment: open 549.5. Torque switching: set 559.6. Limit switching: set 559.6.1. End position CLOSED (black section): set 559.6.2. End position OPEN (white section): set 569.7. Intermediate positions: set 569.7.1. Running direction CLOSE (black section): set 579.7.2. Running direction OPEN (white section): set 579.8. Test run 579.8.1. Direction of rotation at mechanical position indicator: check
3
SQ 05.2 –SQ 14.2 / SQR 05.2 –SQR 14.2 Control unit - electromechanical
AC 01.2 Intrusive Modbus RTU Table of contents

589.8.2. Limit switching: check 589.8.3. Reference operation position feedback: perform 589.9. Mechanical position indicator: set 599.10. Switch compartment: close
6010. Commissioning (optional equipment settings)................................................................... 6010.1. EWG 01.1 electronic position transmitter 6110.1.1. Measuring range: set 6110.1.2. Current values :adjust 6210.1.3. LED end position signalling: switch on/off 6210.2. Potentiometer 6210.2.1. Potentiometer: set 6310.3. RWG electronic position transmitter 6310.3.1. Measuring range: set
6511. Corrective action.................................................................................................................... 6511.1. Faults during commissioning 6511.2. Fault indications and warning indications 7011.3. Fuses 7011.3.1. Fuses within the actuator controls 7011.3.2. Fuse replacement 7011.3.2.1. Replace fuses F1/F2. 7111.3.2.2. Test/replace fuses F3/F4 7111.3.3. Motor protection (thermal monitoring)
7312. Servicing and maintenance................................................................................................... 7312.1. Preventive measures for servicing and safe operation 7312.2. Maintenance 7312.3. Disposal and recycling
7513. Technical data......................................................................................................................... 7513.1. Technical data Part-turn actuator 7813.2. Technical data Actuator controls
8414. Spare parts............................................................................................................................. 8414.1. Part-turn actuators SQ 05.2 –SQ 14.2/SQR 05.2 –SQR 14.2 8614.2. AC 01.2 actuator controls with SD electrical connection
8815. Certificates.............................................................................................................................. 8815.1. Declaration of Incorporation and EU Declaration of Conformity
91Index........................................................................................................................................
94Addresses...............................................................................................................................
4
SQ 05.2 –SQ 14.2 / SQR 05.2 –SQR 14.2 Control unit - electromechanical
Table of contents AC 01.2 Intrusive Modbus RTU

1. Safety instructions
1.1. Basic information on safety
Standards/directives Our products are designed and manufactured in compliance with recognised
standards and directives.This is certified in a Declaration of Incorporation and an
EU Declaration of Conformity.
The end user or the contractor must ensure that all legal requirements, directives,
guidelines, national regulations and recommendations with respect to assembly,
electrical connection, commissioning and operation are met at the place of installation.
They include among others:
●Applicable configuration guidelines for fieldbus applications.
Safetyinstructions/warn-
ings All personnel working with this device must be familiar with the safety and warning
instructions in this manual and observe the instructions given. Safety instructions
and warning signs on the device must be observed to avoid personal injury or property
damage.
Qualification of staff Assembly, electrical connection, commissioning, operation, and maintenance must
be carried out by suitably qualified personnel authorised by the end user or contractor
of the plant only.
Prior to working on this product, the staff must have thoroughly read and understood
these instructions and, furthermore, know and observe officially recognised rules
regarding occupational health and safety.
Commissioning Prior to commissioning, it is important to check that all settings meet the requirements
of the application. Incorrect settings might present a danger to the application, e.g.
cause damage to the valve or the installation.The manufacturer will not be held
liable for any consequential damage. Such risk lies entirely with the user.
Operation Prerequisites for safe and smooth operation:
●Correct transport, proper storage, mounting and installation, as well as careful
commissioning.
●Only operate the device if it is in perfect condition while observing these instruc-
tions.
●Immediately report any faults and damage and allow for corrective measures.
●Observe recognised rules for occupational health and safety.
●Observe national regulations.
●During operation,thehousingwarmsupand surfacetemperatures >60°Cmay
occur.To prevent possible burns, we recommend checking the surface temper-
ature using an appropriate thermometer and wearing protective gloves, if re-
quired, prior to working on the device.
Protective measures The end user or the contractor are responsible for implementing required protective
measures on site, such as enclosures, barriers, or personal protective equipment
for the staff.
Maintenance To ensure safe device operation, the maintenance instructions included in this manual
must be observed.
Any device modification requires prior written consent of the manufacturer.
1.2. Range of application
AUMA part-turn actuators are designed for the operation of industrial valves, e.g.
butterfly valves and ball valves.
Other applications require explicit (written) confirmation by the manufacturer.
The following applications are not permitted, e.g.:
●Industrial trucks according to EN ISO 3691
5
SQ 05.2 –SQ 14.2 / SQR 05.2 –SQR 14.2 Control unit - electromechanical
AC 01.2 Intrusive Modbus RTU Safety instructions

●Lifting appliances according to EN 14502
●Passenger lifts according to DIN 15306 and 15309
●Service lifts according to EN 81-1/A1
●Escalators
●Continuous duty
●Buried service
●Continuous submersion (observe enclosure protection)
●Potentially explosive areas, with the exception of zone 22
●Radiation exposed areas in nuclear power plants
No liability can be assumed for inappropriate or unintended use.
Observance of these operation instructions is considered as part of the device's
designated use.
Information These operation instructions are only valid for the "clockwise closing" standard
version, i.e. driven shaft turns clockwise to close the valve.
1.3. Applications in Ex zone 22 (option)
Actuators of the indicated series basically meet the requirements for applications in
dust hazardous locations of ZONE 22 in compliance with the ATEX directive
2014/34/EU.
To comply with all requirements of the ATEX directive, observe the following points:
●Actuators are marked with the explosion protection designation II3D... for use
in ZONE 22.
●Maximum surface temperature of actuators
- T150 °C for ambient temperatures up to +60 °C or
- T190 °C for ambient temperatures up to +80 °C.
Increased dust deposit on the equipment was not considered for the determin-
ation of the maximum surface temperature.
●The following conditions must be fulfilled to respect the maximum permissible
surface temperatures at the actuator:
- Respecting types of duty and technical manufacturer data
- Correct connection of thermal motor protection (thermoswitches or PTC
thermistor)
Table 1: Maximum
surface temperature
Tripping temperature
Thermal motor protection
Ambient temperature
T150 °C140 °Cup to +60 °C
T190 °C155 °Cup to +80 °C
●The connector may only be connected or disconnected when not live.
●The cable glands and cable entries used have to meet the requirements of
category II3D and must at least comply with enclosure protection IP67.
●The actuators must be connected by means of an external earth connection
(accessory part) to the equipotential earth bonding or integrated into an earthed
piping system.
●As a general rule, the requirements of IEC 60079 Parts 14 and 17 must be re-
spected in dust hazardous locations.During commissioning, service, and
maintenance, special care as well as qualified and trained personnel are required
for safe actuator operation.
1.4. Warnings and notes
The following warnings draw special attention to safety-relevant procedures in these
operation instructions, each marked by the appropriate signal word (DANGER,
WARNING, CAUTION, NOTICE).
6
SQ 05.2 –SQ 14.2 / SQR 05.2 –SQR 14.2 Control unit - electromechanical
Safety instructions AC 01.2 Intrusive Modbus RTU

Indicates an imminently hazardous situation with a high level of risk. Failure
to observe this warning could result in death or serious injury.
Indicates a potentially hazardous situation with a medium level of risk.Failure
to observe this warning could result in death or serious injury.
Indicates a potentially hazardous situation with a low level of risk. Failure to
observe this warning may result in minor or moderate injury. May also be used
with property damage.
Potentially hazardous situation. Failure to observe this warning may result in
property damage. Is not used for personal injury.
Arrangement and typographic structure of the warnings
Type of hazard and respective source!
Potential consequence(s) in case of non-observance (option)
→Measures to avoid the danger
→Further measure(s)
Safety alert symbol warns of a potential personal injury hazard.
The signal word (here: DANGER) indicates the level of hazard.
1.5. References and symbols
The following references and symbols are used in these instructions:
Information The term Information preceding the text indicates important notes and information.
Symbol for CLOSED (valve closed)
Symbol for OPEN (valve open)
Important information before the next step.This symbol indicates what is required
for the next step or what has to be prepared or observed.
Via the menu to parameter
Describes the path within the menu to the parameter. By using the push buttons of
the local controls you may quickly find the desired parameter in the display.
< > Reference to other sections
Terms in brackets shown above refer to other sections of the document which provide
further information on this topic.These terms are either listed in the index, a heading
or in the table of contents and may easily be located.
7
SQ 05.2 –SQ 14.2 / SQR 05.2 –SQR 14.2 Control unit - electromechanical
AC 01.2 Intrusive Modbus RTU Safety instructions

2. Identification
2.1. Name plate
Each device component (actuator, actuator controls, motor) is equipped with a name
plate.
Figure 1: Arrangement of name plates
[1] Actuator name plate
[2] Actuator controls name plate
[3] Motor name plate
[4] Additional plate, e.g. KKS plate (Power Plant Classification System)
Actuator name plate
Figure 2: Actuator name plate (example)
(= manufacturer logo); (= CE mark)
[1] Name of manufacturer
[2] Address of manufacturer
[3] Type designation
[4] Order number
[5] Actuator serial number
[6] Operating time in [s] for a part-turn movement of 90°
[7] Torque range in direction CLOSE
[8] Torque range in direction OPEN
[9] Type of lubricant
[10] Permissible ambient temperature
[11] Can be assigned as an option upon customer request
[12] Enclosure protection
[13] Data Matrix code
8
SQ 05.2 –SQ 14.2 / SQR 05.2 –SQR 14.2 Control unit - electromechanical
Identification AC 01.2 Intrusive Modbus RTU

Actuator controls name plate
Figure 3: Name plate for actuator controls (example)
(= manufacturer logo)
[1] Type designation
[2] Order number
[3] Serial number
[4] Actuator terminal plan
[5] Actuator controls terminal plan
[6] Mains voltage
[7] AUMA power class for switchgear
[8] Permissible ambient temperature
[9] Enclosure protection
[10] Control
[11] Data Matrix code
Motor name plate
Figure 4: Motor name plate (example)
(= manufacturer logo); (= CE mark)
[1] Motor type
[2] Motor article number
[3] Serial number
[4] Current type, mains voltage
[5] Rated power
[6] Rated current
[7] Type of duty
[8] Enclosure protection
[9] Motor protection (temperature protection)
[10] Insulation class
[11] Speed
[12] Power factor cos phi
[13] Mains frequency
[14] Data Matrix code
9
SQ 05.2 –SQ 14.2 / SQR 05.2 –SQR 14.2 Control unit - electromechanical
AC 01.2 Intrusive Modbus RTU Identification

Descriptions referring to name plate indications
Type designation Figure 5:Type designation (example)
1. Type and size of actuator
2. Flange size
Type and size
These instructions apply to the following devices types and sizes:
●Type SQ = Part-turn actuators for open-close duty
Sizes and generation: 05.2, 07.2, 10.2, 12.2, 14.2
●Type SQR= Part-turn actuators for modulating duty
Sizes and generation:05.2, 07.2, 10.2, 12.2, 14.2
●Type AC = AUMATIC actuator controls
Size and generation:01.2
Order number The product can be identified using this number and the technical data as well as
order-related data pertaining to the device can be requested.
Please always state this number for any product inquiries.
On the Internet at http://www.auma.com > Service & Support > myAUMA, we offer
a service allowing authorised users to download order-related documents such as
wiring diagramsandtechnicaldata(bothinGerman and English), inspection certificate
and the operation instructions when entering the order number.
Actuator serial number Table 2:
Description of the serial number (with example 0516NS12345)
NS123451605
Positions 1+2: Assembly in week = week 0505
Positions 3+4:Year of manufacture = 201616
Internal number for unambiguous product identificationNS12345
Actuator terminal plan Position 9 after TPA: Position transmitter version
0= Without position transmitter
A, B, J, K, L, N, R,T = Potentiometer
C, D, E, G, H, M, P, S, U = Electronic position transmitter
AUMA power class for
switchgear The switchgear used in the actuator controls (reversing contactors/thyristors) are
classified according to AUMA power classes (e.g.A1, B1, ....).The power class
defines the max. permissible rated power (of the motor) the switchgear has been
designed for.The rated power (nominal power) of the actuator motor is indicated in
kW on the motor name plate.For the assignment of the AUMA power classes to the
nominal power of the motor types, refer to the separate electrical data sheets.
For switchgear without assignment to any power classes, the actuator controls name
plate does not indicate the power class but the max. rated power in kW.
Control Table 3:
Control examples (indications on actuator controls name plate)
DescriptionInput signal
Control vie Modbus RTU interfaceModbus RTU
Control via Modbus RTU interface and control voltage for OPEN - CLOSE
Control via digital inputs (OPEN, STOP, CLOSE)
Modbus RTU/24 V DC
10
SQ 05.2 –SQ 14.2 / SQR 05.2 –SQR 14.2 Control unit - electromechanical
Identification AC 01.2 Intrusive Modbus RTU

Data Matrix code Whenregisteredasauthorised user, you may use our AUMA Assistant App to scan
the Data Matrix code and directly access the order-related product documents without
having to enter order number or serial number.
Figure 6: Link to AUMA Assistant App:
For further Service & Support, software/apps/...refer to www.auma.com.
2.2. Short description
Part-turn actuator Definition in compliance with EN 15714-2/EN ISO 5211:
A part-turn actuator is an actuator which transmits a torque to the valve for less than
one full revolution.It need not be capable of withstanding thrust.
AUMA part-turn actuators SQ 05.2 –SQ 14.2/SQR 05.2 –SQR 14.2 are driven by
an electric motor. For manual operation, a handwheel is provided.Switching off in
end positions may be either by limit or torque seating.Actuator controls are required
to operate or process the actuator signals.
Actuator controls AC 01.2 actuator controls are used to operate AUMA actuators and are supplied
ready for use.The actuator controls may be mounted directly to the actuator or
separately on a wall bracket.
The functions of the AC 01.2 actuator controls include standard valve control in
OPEN-CLOSE duty, positioning, process control, logging of operating data, diagnostic
functions right through control via various interfaces (e.g. Fieldbus, Ethernet and
HART).
Local controls/
AUMA software Operation, setting, and display can be either performed directly at actuator controls
or alternatively from Remote via binary input signals, or using another interface.
The following options are available at the actuator controls in local operation:
●The actuator can be operated via the push buttons of the local controls or set-
tingscanbemade in the actuatorcontrolsmenu.Thedisplayshows information
on the actuator as well as menu settings (contents of these instructions).
●Using the AUMA CDT software for Windows-based notebooks or the AUMA
Assistant App for Android-based devices, data can be uploaded and read
whereassettingscanbemodifiedandstored.Theconnectionbetweencomputer
and actuator controls is wireless via Bluetooth interface (not included in these
instructions). AUMA CDT software can be downloaded free of charge from our
website www.auma.com.
Intrusive - Non-Intrusive ●Intrusive version (control unit: electromechanical):
Limit and torque setting is performed via switches in the actuator.
●Non-Intrusive version (control unit: electronic):
Limit and torque setting is performed via the controls, without removal of actu-
ator or actuator controls covers.For this purpose, the actuator is equipped with
anMWG(magneticlimitandtorquetransmitter),also capabletosupplyanalogue
torque feedback signals/torque indication and analogue position feedback sig-
nals/position indication at the actuator controls output.
11
SQ 05.2 –SQ 14.2 / SQR 05.2 –SQR 14.2 Control unit - electromechanical
AC 01.2 Intrusive Modbus RTU Identification

3. Transport, storage and packaging
3.1. Transport
For transport to place of installation, use sturdy packaging.
Hovering load!
Risk of death or serious injury.
→Do NOT stand below hovering load.
→Attach ropes or hooks for the purpose of lifting by hoist only to housing and NOT
to handwheel.
→Actuators mounted on valves: Attach ropes or hooks for the purpose of lifting
by hoist to valve and NOT to actuator.
→Actuatorsmountedtogearboxes:Attach ropes orhooksfor the purposeoflifting
by hoist only to the gearbox using eyebolts and NOT to the actuator.
→Actuators mounted to controls: Attach ropes or hooks for the purpose of lifting
by hoist only to the actuator and NOT to the controls.
→Respect total weight of combination (actuator, actuator controls, gearbox, valve)
→Secure load against falling down, sliding or tilting.
→Perform lift trial at low height to eliminate any potential danger e.g.by tilting.
Figure 7: Example: Lifting the actuator
Table 4:
Weight for AC 01.2 actuator controls
Weight approx. [kg]with electrical connection type:
7AUMA plug/socket connector with screw-type connection
12
SQ 05.2 –SQ 14.2 / SQR 05.2 –SQR 14.2 Control unit - electromechanical
Transport, storage and packaging AC 01.2 Intrusive Modbus RTU

Table 5:
Dimensions Part-turn actuators SQ 05.2 –SQ 14.2 / SQR 05.2 –SQR 14.2
with 3-phase AC motors
Weight with base and lever2)
Weight1)
Type designation
Actuator approx. [kg]approx. [kg]
2721SQ 05.2/
SQR 05.2
2721SQ 07.2/
SQR 07.2
3126SQ 10.2/
SQR 10.2
4335SQ 12.2/
SQR 12.2
5544SQ 14.2/
SQR 14.2
Indicated weight includes AUMA NORM part-turn actuator with 3-phase AC motor, electrical con-
nection in standard version, unbored coupling and handwheel.For other output drive types, heed
additional weights.
1)
lndicated weight includes AUMA NORM part-turn actuator with 3-phase AC motor, electrical connec-
tion in standard version, and handwheel, including base and lever. For other output drive types,
heed additional weights.
2)
Table 6:
Dimensions Part-turn actuators SQ 05.2 –SQ 14.2 / SQR 05.2 –SQR 14.2
with 1-phase AC motors
Weight with base and lever2)
Weight 1)
Type designation
Actuator approx. [kg]approx. [kg]
2923SQ 05.2/
SQR 05.2
2923SQ 07.2/
SQR 07.2
3228SQ 10.2/
SQR 10.2
4537SQ 12.2/
SQR 12.2
5746SQ 14.2/
SQR 14.2
Indicated weight includes AUMA NORM part-turn actuator with 1-phase AC motor, electrical con-
nection in standard version, unbored coupling and handwheel.For other output drive types, heed
additional weights.
1)
Indicated weight includes AUMA NORM part-turn actuator with 1-phase AC motor, electrical con-
nection in standard version, and handwheel, including base and lever.For other output drive types,
heed additional weights.
2)
3.2. Storage
Danger of corrosion due to inappropriate storage!
→Store in a well-ventilated, dry room.
→Protect against floor dampness by storage on a shelf or on a wooden pallet.
→Cover to protect against dust and dirt.
→Apply suitable corrosion protection agent to uncoated surfaces.
Damage on display caused by temperatures below permissible level!
→AC actuator controls MUST NOT be stored below –30 °C.
Long-term storage For long-term storage (more than 6 months), observe the following points:
13
SQ 05.2 –SQ 14.2 / SQR 05.2 –SQR 14.2 Control unit - electromechanical
AC 01.2 Intrusive Modbus RTU Transport, storage and packaging

1. Prior to storage:
Protect uncoated surfaces, in particular the output drive parts and mounting
surface, with long-term corrosion protection agent.
2. At an interval of approx. 6 months:
Check for corrosion.If first signs of corrosion show, apply new corrosion protec-
tion.
3.3. Packaging
Our products are protected by special packaging for transport when leaving the
factory.The packaging consists of environmentally friendly materials which can easily
be separated and recycled.We use the following packaging materials: wood,
cardboard, paper, and PE foil.For the disposal of the packaging material, we
recommend recycling and collection centres.
14
SQ 05.2 –SQ 14.2 / SQR 05.2 –SQR 14.2 Control unit - electromechanical
Transport, storage and packaging AC 01.2 Intrusive Modbus RTU

4. Assembly
4.1. Mounting position
The product described in this document can be operated in any mounting position.
Restriction:When using oil instead of grease within the actuator gear housing, the
hollow shaft mounting position must be perpendicular, with the flange pointing
downward.The type of lubricant used is indicated on the actuator name plate (short
designation F...= grease; O...= oil).
4.2. Handwheel fitting
Figure 8: Handwheel
[1] Spacer
[2] Input shaft
[3] Handwheel
[4] Retaining ring
1. If required, fit spacer [1] onto input shaft [2].
2. Slip handwheel [3] onto input shaft.
3. Secure handwheel [3] using the retaining ring [4] supplied.
Information The retaining ring [4] (together with these operation instructions) is stored in a
weatherproof bag, which is attached to the device prior to delivery.
4.3. Part-turn actuator to valve: mount
Danger of corrosion due to damage to paint finish and condensation!
→Touch up damage to paint finish after work on the device.
→After mounting, connect the device immediately to electrical mains to ensure
that heater minimises condensation.
The part-turn actuator is mounted to the valve using a coupling (standard) or via
lever. Separate instructions are available for actuator mounting to the valve when
equipped with base and lever.
15
SQ 05.2 –SQ 14.2 / SQR 05.2 –SQR 14.2 Control unit - electromechanical
AC 01.2 Intrusive Modbus RTU Assembly

4.3.1. Output drive for coupling
Design Figure 9:Valve attachment via coupling
[1] Actuator worm wheel with internal splines
[2] Splined plug-in coupling
[3] Valve shaft (example with key)
Application ●For valve attachments according to EN ISO 5211
●For rotating, non-rising valve stem
4.3.1.1. Part-turn actuator (with coupling): mount to valve
Unbored couplings or couplings with pilot bore must be machined to match the valve
shaft prior to mounting the part-turn actuator to the valve (e.g.with bore and keyway,
two-flat or square bore).
Information Assemble valve and part-turn actuator in the same end position. As standard, the
part-turn actuator is supplied in end position CLOSED.
●Recommended mounting position for butterfly valves: End position CLOSED.
●Recommended mounting position for ball valves: End position OPEN.
Assembly steps 1. If required, move part-turn actuator in same end position as valve using the
handwheel.
2. Clean mounting faces, thoroughly degrease uncoated mounting surfaces.
3. Apply a small quantity of grease to the valve shaft [2].
16
SQ 05.2 –SQ 14.2 / SQR 05.2 –SQR 14.2 Control unit - electromechanical
Assembly AC 01.2 Intrusive Modbus RTU

4. Place coupling [1] onto valve shaft [2] and secure against axial slipping by using
a grub screw [3] or a clamping washer and a screw with curved spring lock
washer [4].Thereby, ensure that dimensions X,Y or L are observed (refer to
figure and table <Mounting positions for coupling>).
Figure 10: Examples: Fit coupling
[1] Coupling
[2] Valve shaft
[3] Grub screw
[4] Clamping washer and screw with curved spring lock washer
Figure 11: Mounting positions for coupling
Table 7:
Mounting position of the coupling within fitting dimensions according to AUMA definition
SQ 14.2SQ 12.2SQ 10.2SQ 07.2SQ 05.2Dimensions [mm]
F6F14F14F12F12F10F10F07F05F07F05EN ISO 5211
88554433333X max.
101010105522222Y max.
125751016182506640404040L max.
5. Apply non-acidic grease at splines of coupling (e.g.Gleitmo by Fuchs).
17
SQ 05.2 –SQ 14.2 / SQR 05.2 –SQR 14.2 Control unit - electromechanical
AC 01.2 Intrusive Modbus RTU Assembly

6. Fit part-turn actuator.If required, slightly turn part-turn actuator until splines of
coupling engage.
Figure 12:
Information Ensure that the spigot (if provided) fits uniformly in the recess and that the flanges
are in complete contact.
7. If flange bores do not match thread:
7.1 Slightly rotate handwheel until bores line up.
7.2 If required, shift part-turn actuator by one tooth on the coupling.
8. Fasten part-turn actuator with screws.
Information: We recommend applying liquid thread sealing material to the
screws to avoid contact corrosion.
9. Fasten screws crosswise to a torque according to table.
Table 8:
Tightening torques for screws
Tightening torque [Nm]Threads
Strength class A2-80/A4–80
10M6
24M8
48M10
82M12
200M16
392M20
18
SQ 05.2 –SQ 14.2 / SQR 05.2 –SQR 14.2 Control unit - electromechanical
Assembly AC 01.2 Intrusive Modbus RTU

4.4. Mounting positions of local controls
Figure 13: Mounting positions
The mounting position of the local controls is implemented according to the order.
If, after mounting the actuator to the valve or the gearbox on site, the local controls
are in an unfavourable position, the mounting position can be changed at a later
date.Four mounting positions shifted by respectively 90° are possible (by maximum
180° into one direction).
4.4.1. Mounting positions: modify
Hazardous voltage!
Risk of electric shock.
→Disconnect device from the mains before opening.
Electrostatic discharge ESD!
Risk of damage to electronic components.
→Earth both operators and devices.
1. Loosen screws and remove the local controls.
2. Check whether O-ring is in good condition, correctly insert O-ring.
3. Turn local controls into new position and re-place.
Cable damage due to twisting or pinching!
Risk of functional failures.
→Turn local controls by a maximum of 180°.
→Carefully assemble local controls to avoid pinching the cables.
4. Fasten screws evenly crosswise.
19
SQ 05.2 –SQ 14.2 / SQR 05.2 –SQR 14.2 Control unit - electromechanical
AC 01.2 Intrusive Modbus RTU Assembly

5. Electrical connection
5.1. Basic information
Danger due to incorrect electrical connection
Failure to observe this warning can result in death, serious injury, or property damage.
→The electrical connection must be carried out exclusively by suitably qualified
personnel.
→Prior to connection, observe basic information contained in this chapter.
→After connection but prior to applying the voltage, observe the <Commissioning>
and <Test run> chapters.
Wiring diagram/terminal
plan The pertaining wiring diagram/terminal plan (in German or English) is attached to
the device in a weather-proof bag, together with these operation instructions.It can
also be requested from AUMA (state order number, refer to name plate) or
downloaded directly from the Internet (http://www.auma.com).
Permissible networks
(supply networks) Actuator controls (actuators) are suitable for use inTN andTT networks with directly
earthed star point for mains voltage up to maximum 690 V AC.Use in IT networks
for nominal voltages up to maximum 600 V AC are permissible. For IT network, a
suitable, approved insulation monitor measuring the pulse code is required.
Current type, mains
voltage, mains fre-
quency
Type of current, mains voltage and mains frequency must match the data on the
actuator controls and motor name plates.Also refer to chapter <Identification>/<Name
plate>.
Figure 14: Motor name plate (example)
[1] Type of current
[2] Mains voltage
[3] Mains frequency (for 3-phase and 1-phase AC motors)
External supply of the
electronics For external electronics supply with 24 V DC and simultaneous use of DC motors
(24 V DC, 48 V DC, 60 V DC, 110 V DC, 220V DC), the 24 V DC controls’voltage
supply should be ensured via the XK25/26 terminals, separately from the power
supply (U1, V1). In case of common supply using a single cable (links from U1, V1
with XK25/26, for 24V DC only !!!), short-term excess or falling below the permissible
voltage limits can be the consequence during switching (24 V DC +10 %/–10 %).
Anypossibly incoming operationcommandsarenotexecutedoutsidetheadmissible
limit values.The actuator controls briefly signal a fault condition.
Protection and sizing on
site For short-circuit protection and for disconnecting the actuator from the mains, fuses
and disconnect switches have to be provided by the customer.
The current values for sizing the protection can be derived from the current
consumption of the motor (refer to motor name plate) plus the current consumption
of actuator controls.
We recommend adapting the switchgear sizing to the max.current (Imax) and selecting
and setting the overcurrent protection device in compliance with the indications in
the electrical data sheet.
20
SQ 05.2 –SQ 14.2 / SQR 05.2 –SQR 14.2 Control unit - electromechanical
Electrical connection AC 01.2 Intrusive Modbus RTU
Other manuals for SQ 05.2
5
This manual suits for next models
10
Table of contents
Other AUMA Controllers manuals

AUMA
AUMA SA 07.2 User manual

AUMA
AUMA PROFOX PF-M25X User manual

AUMA
AUMA SA Series User manual

AUMA
AUMA SBA 12 User manual

AUMA
AUMA SQEx 05.2 User manual

AUMA
AUMA TIGRON TR-M30X User manual

AUMA
AUMA GSTI Series User manual

AUMA
AUMA SQ 05.2 User manual

AUMA
AUMA SAVEx 07.2 User manual

AUMA
AUMA AM 01.1 User manual

AUMA
AUMA SQ 05.2 User manual

AUMA
AUMA SAV Series User manual

AUMA
AUMA SQ 05.2 User manual

AUMA
AUMA SA Series User manual

AUMA
AUMA SA3-SA100 User manual

AUMA
AUMA SQEx 05.2 User manual

AUMA
AUMA SA 25.1 User manual

AUMA
AUMA PROFOX PF-M25X User manual

AUMA
AUMA MEC 03.1 User manual

AUMA
AUMA SA 07.1 Administrator Guide