
Page 7
IronHorse GSD1 DC Drives User Manual – 2nd Edition, Revision B – 10/12/2018
inSTallaTion anD WirinG
Install open-frame drives in an enclosure with a volume at least three times the volume of the open-
frame drive.
Do not mount controller where ambient temperature is outside the range of -10 to 45 °C (14–13 °F).
ImpRopeR INstAllAtIoN oR opeRAtIoN of thIs dc dRIve mAy cAuse INjuRy to peRsoNNel oR dRIve fAIluRe. the dRIve
must be INstAlled IN AccoRdANce WIth locAl, stAte, ANd NAtIoNAl sAfety codes. mAke ceRtAIN thAt the poWeR supply
Is dIscoNNected befoRe AttemptING to seRvIce oR Remove ANy compoNeNts!!! Ifthe poWeR dIscoNNect poINt Is out of
sIGht, lock It IN dIscoNNected posItIoN ANd tAG It to pReveNt uNexpected ApplIcAtIoN of poWeR. oNly AquAlIfIed
electRIcIAN oR seRvIce peRsoNNel should peRfoRm ANy electRIcAl tRoubleshootING oR mAINteNANce. AtNo tIme
should cIRcuIt coNtINuIty be checked by shoRtING teRmINAls WIth AscReWdRIveR oR otheR metAl devIce.
befoRe AttemptING to WIRe the dc dRIve, mAke suRe All poWeR Is dIscoNNected. Recheck code desIGNAtIoN to
AssuRe pRopeR voltAGe Is pReseNt foR the dc dRIve. cAutIoN should be used IN selectING pRopeR WIRe sIze foR
cuRReNt ANd voltAGe dRop; mINImum WIRe sIze 14AWG foR 10 Amp models ANd 12AWG foR 20 Amp models.
doNot ReveRse posItIve ANd NeGAtIve bAtteRy / poWeR leAds, As thIs WIll dAmAGe the dc dRIve.
tochANGe motoR dIRectIoN, INteRchANGe the posItIve ANd NeGAtIve motoR ARmAtuRe leAds.
cAutIoN!! tuRN poWeR off WhIle mAkING WIRING coNNectIoNs.
cAutIoN!! set the voltAGe selectIoN jumpeR to mAtch the supply voltAGe. ANINcoRRect jumpeR settING WIll Not
cAuse dAmAGe to the dRIve, but WIll Affect oveRAll speed, mAxImum speed ANd IR compeNsAtIoN AdjustmeNts.
fUsinG
Externally fuse the +Battery input line with Littlefuse 314 series or Bussman ABC series or equivalent
fuses designed for use with motors and motor control systems; rated for the lesser of:
1) 200% of the continuous current rating of the drive, or 2) 150% of the motor full-load current.
(Fast-blow fuses are NOT recommended.) (AutomationDirect sells ABC series fuses.)
cUrrent liMit settinG anD cUrrent liMit (triP) OUtPUt
48V
36V
24V
12V
Voltage
Selector
Jumpers
Current Limit
Trip Output LED
Current Limit
Trip Output
Please note the following recommendations
regarding the Current Limit (Trip) Output and Setting:
•
The Current Limit Output can be used to inhibit the
drive or break the power connection to the drive�
•
The Current Limit Output threshold is the same as
the Current Limit Setting�
•
To properly adjust the CURRENT LIMIT Setting, a DC ammeter should be placed in series with the
armature line� This meter can be removed after the DC Drive is adjusted�
•
The Current Limit Output is immediate, without time delay, and is NOT retentive�
•
Use with 12VDC relay� In order to maintain a current limit fault, use a latching relay�
•
Source voltage from terminal P2-1�
•
Current Limit Trip Output sinks to terminal P2-4 (50VDC@0�3A)�
•
Recommended use with Inhibit, terminals P2-4 and P2-5�
•
If you connect the current limit relay to the Pot HI (P2-1), supply voltage will be 10V, regardless of the
supply voltage to the drive� If the relay is connected to the supply voltage, the relay voltage needs to
match the supply voltage� The Current Limit Output is capable of up to 100V�
terMinal blOcks GSD1 Wiring Terminals
Type Wire Range* Tightening Torque
Barrier terminal block (P1) (Power) 14 – 28 AWG (10A) 7�0 lb·in [8�0 kg·cm]
10 – 14 AWG (20A) 8�5 lb·in [9�8 kg·cm]
Barrier terminal block (P2) 14 – 28 AWG 7�0 lb·in [8�0 kg·cm]
*Wire range of the terminal. See Installation and Wiring above for minimum wire sizes.