AutomationDirect Stride SGW-MQ1611 User manual

Manual Number: SGW-MQ1611-USER-M
®
MQTT Gateway
USER MANUAL


~ WARNING ~
Thank you for purchasing automation equipment from Automationdirect.com®, doing business as,
AutomationDirect. We want your new automation equipment to operate safely. Anyone who installs or uses this
equipment should read this publication (and any other relevant publications) before installing or operating the
equipment.
To minimize the risk of potential safety problems, you should follow all applicable local and national codes that
regulate the installation and operation of your equipment. These codes vary from area to area and usually change
with time. It is your responsibility to determine which codes should be followed, and to verify that the equipment,
installation, and operation is in compliance with the latest revision of these codes.
At a minimum, you should follow all applicable sections of the National Fire Code, National Electrical Code,
and the codes of the National Electrical Manufacturer’s Association (NEMA). There may be local regulatory or
government offices that can also help determine which codes and standards are necessary for safe installation and
operation.
Equipment damage or serious injury to personnel can result from the failure to follow all applicable codes and
standards. We do not guarantee the products described in this publication are suitable for your particular
application, nor do we assume any responsibility for your product design, installation, or operation.
Our products are not fault-tolerant and are not designed, manufactured or intended for use or resale as on-line
control equipment in hazardous environments requiring fail-safe performance, such as in the operation of nuclear
facilities, aircraft navigation or communication systems, air traffic control, direct life support machines, or weapons
systems, in which the failure of the product could lead directly to death, personal injury, or severe physical or
environmental damage (“High Risk Activities”). AutomationDirect specifically disclaims any expressed or implied
warranty of fitness for High Risk Activities.
For additional warranty and safety information, see the Terms and Conditions on our website. If you have any
questions concerning the installation or operation of this equipment, or if you need additional information, please
call us at 770-844-4200.
This publication is based on information that was available at the time it was published. At AutomationDirect we
constantly strive to improve our products and services, so we reserve the right to make changes to the products and/
or publications at any time without notice and without any obligation. This publication may also discuss features
that may not be available in certain revisions of the product.
Trademarks
This publication may contain references to products produced and/or offered by other companies. The product
and company names may be trademarked and are the sole property of their respective owners. AutomationDirect
disclaims any proprietary interest in the marks and names of others.
Copyright 2019, Automationdirect.com®Incorporated
All Rights Reserved
No part of this manual shall be copied, reproduced, or transmitted in any way without the prior, written consent of
Automationdirect.com®Incorporated. AutomationDirect retains the exclusive rights to all information included in
this document.

~ ADVERTENCIA ~
Gracias por comprar equipo de automatización de Automationdirect.com®. Deseamos que su nuevo equipo de
automatización opere de manera segura. Cualquier persona que instale o use este equipo debe leer esta publicación (y
cualquier otra publicación pertinente) antes de instalar u operar el equipo.
Para reducir al mínimo el riesgo debido a problemas de seguridad, debe seguir todos los códigos de seguridad locales o
nacionales aplicables que regulan la instalación y operación de su equipo. Estos códigos varian de área en área y usualmente
cambian con el tiempo. Es su responsabilidad determinar cuales códigos deben ser seguidos y verificar que el equipo,
instalación y operación estén en cumplimiento con la revisión mas reciente de estos códigos.
Como mínimo, debe seguir las secciones aplicables del Código Nacional de Incendio, Código Nacional Eléctrico, y los
códigos de (NEMA) la Asociación Nacional de Fabricantes Eléctricos de USA. Puede haber oficinas de normas locales
o del gobierno que pueden ayudar a determinar cuales códigos y normas son necesarios para una instalación y operación
segura.
Si no se siguen todos los códigos y normas aplicables, puede resultar en daños al equipo o lesiones serias a personas. No
garantizamos los productos descritos en esta publicación para ser adecuados para su aplicación en particular, ni asumimos
ninguna responsabilidad por el diseño de su producto, la instalación u operación.
Nuestros productos no son tolerantes a fallas y no han sido diseñados, fabricados o intencionados para uso o reventa
como equipo de control en línea en ambientes peligrosos que requieren una ejecución sin fallas, tales como operación en
instalaciones nucleares, sistemas de navegación aérea, o de comunicación, control de tráfico aéreo, máquinas de soporte de
vida o sistemas de armamentos en las cuales la falla del producto puede resultar directamente en muerte, heridas personales,
o daños físicos o ambientales severos (“Actividades de Alto Riesgo”). Automationdirect.com específicamente rechaza
cualquier garantía ya sea expresada o implicada para actividades de alto riesgo.
Para información adicional acerca de garantía e información de seguridad, vea la sección de Términos y Condiciones.
Si tiene alguna pregunta sobre instalación u operación de este equipo, o si necesita información adicional, por favor
llámenos al número 770-844-4200 en Estados Unidos.
Esta publicación está basada en la información disponible al momento de la publicación. En Automationdirect.com
nos esforzamos constantemente para mejorar nuestros productos y servicios, así que nos reservamos el derecho de hacer
cambios al producto y/o a las publicaciones en cualquier momento sin notificación y sin ninguna obligación. Esta
publicación también puede discutir características que no estén disponibles en ciertas revisiones del producto.
Marcas Registradas
Esta publicación puede contener referencias a productos producidos y/u ofrecidos por otras compañías. Los nombres
de las compañías y productos pueden tener marcas registradas y son propiedad única de sus respectivos dueños.
Automationdirect.com, renuncia cualquier interés propietario en las marcas y nombres de otros.
PROPIEDAD LITERARIA 2019, AUTOMATIONDIRECT.COM®INCORPORATED
Todos los derechos reservados
No se permite copiar, reproducir, o transmitir de ninguna forma ninguna parte de este manual sin previo consentimiento
por escrito de Automationdirect.com®Incorprated. Automationdirect.com retiene los derechos exclusivos a toda la
información incluida en este documento. Los usuarios de este equipo pueden copiar este documento solamente para
instalar, configurar y mantener el equipo correspondiente. También las instituciones de enseñanza pueden usar este manual
para propósitos educativos.

~ AVERTISSEMENT ~
Nous vous remercions d’avoir acheté l’équipement d’automatisation de Automationdirect.com®, en faisant des affaires
comme, AutomationDirect. Nous tenons à ce que votre nouvel équipement d’automatisation fonctionne en toute sécurité.
Toute personne qui installe ou utilise cet équipement doit lire la présente publication (et toutes les autres publications
pertinentes) avant de l’installer ou de l’utiliser.
Afin de réduire au minimum le risque d’éventuels problèmes de sécurité, vous devez respecter tous les codes locaux et
nationaux applicables régissant l’installation et le fonctionnement de votre équipement. Ces codes diffèrent d’une région à
l’autre et, habituellement, évoluent au fil du temps. Il vous incombe de déterminer les codes à respecter et de vous assurer que
l’équipement, l’installation et le fonctionnement sont conformes aux exigences de la version la plus récente de ces codes.
Vous devez, à tout le moins, respecter toutes les sections applicables du Code national de prévention des incendies, du
Code national de l’électricité et des codes de la National Electrical Manufacturer’s Association (NEMA). Des organismes de
réglementation ou des services gouvernementaux locaux peuvent également vous aider à déterminer les codes ainsi que les
normes à respecter pour assurer une installation et un fonctionnement sûrs.
L’omission de respecter la totalité des codes et des normes applicables peut entraîner des dommages à l’équipement ou causer
de graves blessures au personnel. Nous ne garantissons pas que les produits décrits dans cette publication conviennent à
votre application particulière et nous n’assumons aucune responsabilité à l’égard de la conception, de l’installation ou du
fonctionnement de votre produit.
Nos produits ne sont pas insensibles aux défaillances et ne sont ni conçus ni fabriqués pour l’utilisation ou la revente en tant
qu’équipement de commande en ligne dans des environnements dangereux nécessitant une sécurité absolue, par exemple,
l’exploitation d’installations nucléaires, les systèmes de navigation aérienne ou de communication, le contrôle de la circulation
aérienne, les équipements de survie ou les systèmes d’armes, pour lesquels la défaillance du produit peut provoquer la mort,
des blessures corporelles ou de graves dommages matériels ou environnementaux («activités à risque élevé»). La société
AutomationDirect nie toute garantie expresse ou implicite d’aptitude à l’emploi en ce qui a trait aux activités à risque élevé.
Pour des renseignements additionnels touchant la garantie et la sécurité, veuillez consulter la section Modalités et conditions
de notre documentation. Si vous avez des questions au sujet de l’installation ou du fonctionnement de cet équipement, ou
encore si vous avez besoin de renseignements supplémentaires, n’hésitez pas à nous téléphoner au 770-844-4200.
Cette publication s’appuie sur l’information qui était disponible au moment de la publication. À la société AutomationDirect
,
nous nous efforçons constamment d’améliorer nos produits et services. C’est pourquoi nous nous réservons le droit
d’apporter des modifications aux produits ou aux publications en tout temps, sans préavis ni quelque obligation que ce soit.
La présente publication peut aussi porter sur des caractéristiques susceptibles de ne pas être offertes dans certaines versions
révisées du produit.
Marques de commerce
La présente publication peut contenir des références à des produits fabriqués ou offerts par d’autres entreprises. Les
désignations des produits et des entreprises peuvent être des marques de commerce et appartiennent exclusivement à leurs
propriétaires respectifs. AutomationDirect nie tout intérêt dans les autres marques et désignations.
Copyright 2019, Automationdirect.com®Incorporated
Tous droits réservés
Nulle partie de ce manuel ne doit être copiée, reproduite ou transmise de quelque façon que ce soit sans le consentement
préalable écrit de la société Automationdirect.com®Incorporated. AutomationDirect conserve les droits exclusifs à l’égard de
tous les renseignements contenus dans le présent document.

Stride MQTT Gateway User Manual
Please include the Manual Number and the Manual Issue, both shown below,
when communicating with Technical Support regarding this publication.
Manual Number: SGW-MQ1611-USER-M
Issue: 1st Edition
Issue Date: 8/2019
Publication History
Issue Date Description of Changes
1st Edition 08/2019 Original

Table of ConTenTs
Chapter 1: Hardware
Introduction.................................................................................................................................................. 1-2
Conventions Used......................................................................................................................................... 1-2
Hardware Overview...................................................................................................................................... 1-3
Installation .................................................................................................................................................... 1-6
Operation...................................................................................................................................................... 1-9
Chapter 2: Setup and Operation
Getting Started............................................................................................................................................. 2-2
Setup Network Connection.......................................................................................................................... 2-3
Setup Modbus Communications Channel ................................................................................................... 2-4
Setup Modbus Devices ................................................................................................................................. 2-6
Configure MQTT Broker............................................................................................................................. 2-10
Other Options............................................................................................................................................. 2-14
Recovery Mode ........................................................................................................................................... 2-18
Appendix A: Safety and Security Considerations
Security Considerations for Control Systems Networks..............................................................................A-2
Safety Guidelines ..........................................................................................................................................A-3
Appendix B: Modbus Address Notation – AutomationDirect Devices
Stride MQTT Gateway Modbus to AutomationDirect PLC Address Maps .................................................A-2
Appendix C: MQTT Broker Examples
Introduction..................................................................................................................................................C-2
Example using Mosquitto.............................................................................................................................C-3
Example using ThingsBoard.io.....................................................................................................................C-7

Table of Contents
Stride MQTT Gateway User Manual, 1st Edition
ii

Chapter
Chapter
Chapter
1
1
1
In This Chapter...
Hardware Overview...................................................................................................................................... 2-2
Specifications............................................................................................................................................. 2-3
Dimensional Drawings .............................................................................................................................. 2-4
Installation .................................................................................................................................................... 2-5
Mounting ................................................................................................................................................... 2-5
Wiring ........................................................................................................................................................ 2-6
Operation...................................................................................................................................................... 2-7
Front Panel Indicators ............................................................................................................................... 2-8
Recovery Mode.......................................................................................................................................... 2-8
Hardware

Chapter 1: Hardware
Stride MQTT Gateway User Manual, 1st Edition
1-2
Introduction
The Purpose of This User’s Manual
Thank you for purchasing our Stride® MQTT Gateway for your Industrial Internet of Things (IIoT)
data logging. This manual describes our MQTT Gateway, its specifications and included components, and
provides you with important information for installation, connectivity and setup.
Technical Support
We strive to make our manuals the best in the industry. We rely on your feedback to let us know if we are
reaching our goal. If you cannot find the solution to your particular application, or, if for any reason you need
technical assistance, please call us at:
770–844–4200
Our technical support group will work with you to answer your questions. They are available Monday
through Friday from 9:00 a.m. to 6:00 p.m. Eastern Time. We also encourage you to visit our web site where
you can find technical and non-technical information about our products and our company.
https://www.AutomationDirect.com
If you have a comment, question or suggestion about any of our products, services, or manuals, please let us know.
Conventions Used
When you see the “notepad” icon in the left-hand margin, the paragraph to its immediate right will be a special note.
The word NOTE: in boldface will mark the beginning of the text.
When you see the “exclamation mark” icon in the left-hand margin, the paragraph to its immediate right will be a
warning or a caution. This information could prevent injury, loss of property, or even death (in extreme cases). The
words WARNING or CAUTION: in boldface will mark the beginning of the text.

Chapter 1: Hardware
1-3
Stride MQTT Gateway User Manual, 1st Edition
Hardware Overview
The Stride MQTT Gateway is an industrial device specifically designed to implement an Industrial Internet
of Things (IIoT) data collection system. It allows bidirectional communication between Modbus field
equipment and an MQTT broker. It provides a Modbus RTU master interface on RS-485 and Modbus
TCP over Ethernet. Variables can be read from Modbus slave devices on change or at fixed time intervals and
are sent to the MQTT broker with optional SSL/TLS client certificate authentication.
The Wi-Fi model (Part No. SGW-MQ1611-WF) uses 802.11 a/b/g/n/ac in 2400MHz or 5500MHz bands.
Setup of the device is through a built-in web interface. The MQTT message structure can be configured
to better adapt to different MQTT brokers (e.g., Amazon AWS, IBM Watson IoT, Mosquitto, etc.). It is
possible to remotely update the firmware through the web interface.
The gateway has a low-profile format, suitable for DIN rail mounting inside industrial electrical cabinets. The
full galvanic isolation ensures a good protection against interference present in industrial environments. A
dedicated hardware Watchdog manages the automatic reset of the device. Signaling LEDs allow an immediate
diagnosis of device operation.
SAFETY NOTICE: The Stride MQTT Gateway allows the user to connect to remote industrial controls equipment.
The remote user may operate and monitor the local control system and affect the function and control of the
application just as the local operator controls it. Proper Control, Security and Safety Procedures should be
considered and implemented when writing data to a remote device or system.

Chapter 1: Hardware
Stride MQTT Gateway User Manual, 1st Edition
1-4
Specifications
Stride MQTT Gateway Models
Part Number Ethernet RS-485 WiFi
SGW-MQ1611 ü ü
SGW-MQ1611-WF üüü
RS-485 Specifications
Connector Removable screw terminals, 5.08 mm pitch
Baud rate Up to 115.2 kbps
Parity Even, odd or none
Stop bit 1 or 2
Number of Serial Devices 32 max.
Switching Time TX/RX (RS-485) 150μs
Termination Resistance 120Ω
Ethernet Specifications
Connector RJ-45
Ethernet Port Speed 10/100Mbps auto-detected
Protocol MQTT, Modbus TCP
Simultaneous Ethernet Connections 8
WiFi Specifications (Model SGW-MQ1611-WF Only)
WiFi Standards 802.11 a/b/g/n/ac
Frequency Bands 2400MHz / 5500MHz
Antenna Internal
Network Ports
Web User Interface 80
Modbus 502 (default, software configurable)
MQTT Software configurable, determined by MQTT Broker
Electrical Specifications
Power Supply Connector Removable screw terminals, 5.08 mm pitch
Input Voltage Range 10–30VDC
Current Consumption max 300mA @ 24VDC
Isolation
Ethernet / RS-485
Ethernet / Power Supply
Power Supply / RS-485
1500VAC, 50Hz, 1 min.
1000VAC, 50Hz, 1 min.
1500VAC, 50Hz, 1 min.
Reverse Polarity Protection Yes
Mechanical Specifications
Material Self-extinguishing plastic
Mounting DIN rail (EN50022 and EN50035)
Weight Approximately 200g

Chapter 1: Hardware
1-5
Stride MQTT Gateway User Manual, 1st Edition
Environmental Specifications
Operating Temperature 0°C to +60°C [32°F to +140°F]
Storage Temperature −20°C to +70°C [−4°F to +158°F]
Humidity 0–90%, noncondensing
Maximum Altitude 2000m
IP Rating IP20
Installation Indoor
Category of Installation II
Pollution Degree 2
EMC
Immunity
Emission
EN61000-6-2
EN61000-6-4
Agency Approvals CE, FCC, RoHS
Dimensional Drawings
91.0
3.58
71.5
2.81
RESET
BUTTON
44.9
1.77
46.1
1.81
62.5
2.46
62.5
2.46
5-WIRE
CONNECTOR
Units: mm [in]
ETHERNET
PORT
RoHS Compliant
RoHS

Chapter 1: Hardware
Stride MQTT Gateway User Manual, 1st Edition
1-6
Installation
Mounting
The Stride MQTT Gateway may be used indoors only.
It is designed to be mounted in a vertical position on DIN rail and cooled using natural convection. For
proper cooling, you must provide clearance of at least 5mm [0.2 inches] between MQTT Gateway modules
and at least 10mm [0.4 inches] between MQTT Gateway modules and power supplies or other devices.
Make sure that sufficient air flow is provided for the gateway. Avoid placing raceways or other objects where
airflow could be obstructed. Avoid mounting the gateway above equipment that generates heat; ideally locate
the gateway in the lower part of the panel.
Install the gateway in a place without vibrations.
To mount the gateway:
1. Hook the top of the mounting bracket onto the DIN rail.
2. Press the bottom of the gateway inward until it clicks onto the DIN rail.
To remove the gateway:
A. Pull downward on the mounting clip release.
B. Swing the bottom of the gateway outward.
C. Lift the gateway off the DIN rail.
1
2
B
C
A
NOTE: Installation of the SGW-MQ1611-WF model in a metal cabinet is not recommended, as the cabinet may
block the Wi-Fi signal.

Chapter 1: Hardware
1-7
Stride MQTT Gateway User Manual, 1st Edition
Wiring
Wiring Guidelines
WARNING: To minimize the risk of potential safety problems, you should follow all applicable local and national
codes that regulate the installation and operation of your equipment. These codes vary from area to area
and it is your responsibility to determine which codes should be followed, and to verify that the equipment,
installation, and operation are in compliance with the latest revision of these codes.
Equipment damage or serious injury to personnel can result from the failure to follow all applicable codes
and standards. We do not guarantee the products described in this publication are suitable for your particular
application, nor do we assume any responsibility for your product design, installation, or operation.
If you have any questions concerning the installation or operation of this equipment, or if you need additional
information, please call technical support at 1-800-633-0405 or 770-844-4200.
This publication is based on information that was available at the time it was written. At Automationdirect.com®
we constantly strive to improve our products and services, so we reserve the right to make changes to the
products and/or publications at any time without notice and without obligation. This publication may also
discuss features that may not be available in certain revisions of the product.
Proper grounding and wiring of all electrical equipment is important to help ensure the optimum operation
of the Stride MQTT Gateway and to provide additional electrical noise protection for your application.
WARNING: Do not terminate communication leads while the plug-in connector is connected to a powered device.
Wiring Connections
The Stride MQTT Gateway comes with a female 5-pin
plug-in connector for its power and RS-485 connection.
The gateway can be powered from the same 12 to
24 VDC source that is used to power your other
devices. Recommended DC power supplies are
AutomationDirect.com part number PSL-12-010 or
PSL-24-010.
The device uses a 2-wire RS-485 interface. It has an
internal terminating resistor, so this device must be at
the end of the communications daisy-chain.
Avoid routing signal cables near power cables (motors,
induction ovens, inverters, etc.), and use shielded cable
to connect signals. We recommend AutomationDirect
Part #L19954-1 or equivalent data cable to connect
RS-485 serial devices.
POWER SUPPLY SHIELD
RS-485
RST
Ethernet
RJ45
54321

Chapter 1: Hardware
Stride MQTT Gateway User Manual, 1st Edition
1-8
Wiring Connections
Pin Description Notes
1V- Power Supply 10–30VDC, 300mA @ 24VDC
2V+
3SHIELD RS-485 Shield
4D+ RS-485 Data Connection to one or more
Modbus RTU servers
5D-
RJ45 Ethernet 10/100Base-T
Connection to MQTT broker and
one or more Modbus TCP or
Modbus RTU over TCP servers
USB (x2) Future Use
Terminal Connector Wiring Specifications
Wire Size 0.8–2.1 mm2
14–18 AWG
Torque 0.5 N·m
Stripping Length 5mm maximum
LEDs on the top surface indicate:
* red, active internal power; green, internal memory activity
SHIELD
D (+)
D (−)
MASTER
SHIELD
D (+)
D (−)
MASTER
5
4
SHIELD
D (+)
D (−)
SLAVE
SHIELD
D (+)
D (−)
SLAVE
SHIELD
D (+)
D (−)
SLAVE
2
1
+
DC
POWER SUPPLY
RS-485 Point-to-Point
RS-485 Multipoint
CONNECTIONS
3
5
4
3

Chapter 1: Hardware
1-9
Stride MQTT Gateway User Manual, 1st Edition
Operation
Configuration and operation of the STRIDE MQTT Gateway is primarily conducted using the device’s web
interface, as discussed in Chapter 2. The hardware indicators and controls are described here.
POWER
ERROR
RS-485 TRANSMIT
RS-485 RECEIVE
RECOVERY MODE
BUTTON
POWER TERMINALS
RS-485 TERMINALS
RJ45 PORT
Front Panel Indicators
The Stride MQTT Gateway has four status LEDs, as shown below.
Front Panel LEDs
LED Color State Description
PWR GREEN ON Device powered
OFF Device unpowered
ERR YELLOW
OFF No error
BLINK
SLOW-FAST-FAST-FAST Boot (about 60 sec., few minutes for the first boot)
BLINK SLOW Communications error (Modbus, MQTT, etc.)
BLINK FAST Watchdog restart
TX RED BLINK Data transmitted over RS-485
OFF No data over RS-485
RX RED BLINK Data received over RS-485
OFF No data over RS-485
NOTE: LEDs on the top surface indicate: RED = active internal power; GREEN = internal memory activity.

Chapter 1: Hardware
Stride MQTT Gateway User Manual, 1st Edition
1-10
Recovery Mode
The device can be booted into a Recovery Mode to reset portions of the configuration to default or to
perform system maintenance and firmware updates.
To enter Recovery Mode, press and hold the recessed reset button on the front of the gateway while applying
power. Continue to hold the reset button until the ERR light stops blinking (about 5 seconds after applying
power). The gateway will start in Recovery Mode, using the default Ethernet configuration:
• IP address = 192.168.1.100
Details of the features available in recovery mode are discussed in Chapter 2.

Chapter
Chapter
Chapter
2
2
2
Setup and OperatiOn
In This Chapter...
Getting Started............................................................................................................................................. 2-2
Setup Network Connection.......................................................................................................................... 2-3
Setup Modbus Communications Channel ................................................................................................... 2-4
Setup Modbus Devices ................................................................................................................................. 2-6
Configure Modbus Device......................................................................................................................... 2-6
Configure Modbus Variables..................................................................................................................... 2-7
Configure MQTT Topics ............................................................................................................................ 2-8
Configure MQTT Broker............................................................................................................................. 2-10
Other Options............................................................................................................................................. 2-14
Date & Time............................................................................................................................................. 2-14
Import/Export Configuration.................................................................................................................. 2-14
Change Password .................................................................................................................................... 2-15
Logout...................................................................................................................................................... 2-15
Maintenance............................................................................................................................................ 2-15
Recovery Mode ........................................................................................................................................... 2-18
Reset ........................................................................................................................................................ 2-18
Maintenance............................................................................................................................................ 2-19
Firmware Upgrade................................................................................................................................... 2-19
Reboot and Return to Normal Mode...................................................................................................... 2-19

Chapter 2: Setup and Operation
Stride MQTT Gateway User Manual, 1st Edition
2-2
Getting Started
Before you begin setting up the MQTT gateway, please make sure the following conditions are met:
1. The hardware is installed as described in the Mounting and Wiring sections of Chapter 1.
2. You have the necessary connection information on hand to connect to your MQTT broker.
3. You have a device on hand with a web browser and the ability to connect to the MQTT gateway
via its RJ-45 Ethernet port, either over a LAN or directly with a crossover cable.
The device is configured through its web interface. To begin, connect to the device via an Internet browser.
The default Ethernet configuration is:
– IP address : 192.168.1.100
– Subnet Mask : 255.255.255.0
– Default Gateway: 192.168.1.1
– User Name: admin
– Password: password
Table of contents
Other AutomationDirect Gateway manuals
Popular Gateway manuals by other brands

Viola Systems
Viola Systems Arctic Substation Gateway user manual

Elvaco
Elvaco CMi2110 G3 manual

ZyXEL Communications
ZyXEL Communications P-660HW-DX user guide

3Com
3Com HomeConnect 3CRWE50194 user guide

ZyXEL Communications
ZyXEL Communications EMG2881-T20A quick start guide

IXXAT
IXXAT CME/PN Hardware manual