Avid Technology LP Series User manual

CRANECO.
280N.MIDLANDAVE.,STE258,SADDLEBROOK,NJ07663WWW.AVIDCONTROLS.COM
4/6/16 TECHUK-74/ D.W.O. 22926 Page 1 of 7
AVID LP Series
With SPDT V3 Micro Switches,
V3 Inductive Proximity Sensors
Or T-Switches
INSTALLATION AND OPERATION MANUAL
IOM: TECHUK-74 Revision: 4
Prepared By: C.Irwin Date: 4/6/09 Drafting Work Order:23127 ECN: 13247
Reviewed By: T. Lee Date:10/30/17 Approved By: R.Frey Date: 11/1/17
This IOM contains confidential information and is issued in confidence on the condition that it be returned on demand and not be copied,
reproduced, disclosed to others or used in manufacture of the subject matter thereof without the written consent of Crane Co.

CRANECO.
280N.MIDLANDAVE.,STE258,SADDLEBROOK,NJ07663WWW.AVIDCONTROLS.COM
4/6/16 TECHUK-74/ D.W.O. 22926 Page 2 of 7
RevisionHistory
15December2009Initialrelease
19May,2014Rev.1
13October,2015Rev.2
6April,2016Rev.3
CraneCo.Locations
USA:+12017947650
Europe,MiddleEast&Africa:+44(0)1892516277
AsiaPacific:+6568698909

CRANECO.
280N.MIDLANDAVE.,STE258,SADDLEBROOK,NJ07663WWW.AVIDCONTROLS.COM
4/6/16 TECHUK-74/ D.W.O. 22926 Page 3 of 7
Thefollowingdocumentdetailstheinstallation,operationandmaintenanceinstructionsforthe
AVIDLP(LowProfile)giving360°visualandelectricalvalveposition.
Thissymbolwarnstheuserofpossibledanger.Failuretoobservethiswarningmayleadto
personalinjuryordeathand/orseveredamagetoequipment.
Thissymbolidentifiesinformationaboutoperatingtheequipmentinaparticularmannerthat
maydamageitorresultinasystemfailure.Failuretoobservethiswarningcanleadtototal
failureoftheequipmentoranyotherconnectedequipment.
Thissymboldrawsattentiontoinformationthatisessentialforunderstandingthe
operationand/orfeaturesoftheequipment.
1.0 MountingInstructions.
AllAVIDLPswitchboxesarefactoryequippedwithdirectandNAMURmounting.
1.1 Pleaserefertothefigures1and2belowtodeterminethetypeofmountingthatisrequired.
Figure1indicatestheconventionaldirectmountandfigure2detailstheNAMURoption.
1.2 Operatetheactuatortothefullyclosedposition.
1.3 DirectMount.
1.3aBeforemountingtheAVIDLPitwillbenecessarytoremovethecover.
AVIDCoupler
11x16mm
Actuator
Namur
Slot.
Fig1.Fig2.
Bracket–
Customer
Supply.
Namur
Shaft
Drive.

CRANECO.
280N.MIDLANDAVE.,STE258,SADDLEBROOK,NJ07663WWW.AVIDCONTROLS.COM
4/6/16 TECHUK-74/ D.W.O. 22926 Page 4 of 7
1.3bTodothis,loosenthe4offM5captivescrewswitheithera8mmA/Fspanner/socketdrive
oranappropriatelysizedflatbladescrewdriver.
1.3cRemovethecoverassemblybyliftingthecoververtically.Keepthecoversafetakingcarenot
todamagethecoversealdetail.
1.3dMounttheAVIDLPswitchboxtotheactuatorbyaligningthe11x16mmshaftadaptortothe
actuatorpinioncoupler.
1.3eEnsurethatthebaseoftheAVIDLPhousingsitsflushwiththetopoftheactuator.
1.3fLocateandtightenthe4offM5captivescrewsinthebaseofthehousingwitheithera8mmA/F
socketdriveoranappropriatelysizedflatbladescrewdriver.
1.3gTightenthescrewstoatorquevalueof18to22Lb/Ins.
1.4 NAMURMount.
Note: DuetothemountingholepatternoftheAVIDLPhousingbeing93.5x41.3mmequal
aboutthecenteroftheshaft,amodifiedNamurbracketisrequired.
Themodificationcaneitherbe4offM5tappedholesor4offM5clearanceholes.
1.4aSecuretheappropriatelysizedmodifiedNamurbrackettotheactuatorusingthescrews/
washerssuppliedwiththeNamurkitfingertightonly.
1.4b(1) Formountingbracketswith(4)M5tappedholes,mounttheLPswitchboxtothe
mountingbracketbyengagingtheNamurshaftdriveintotheactuatorNamurpinionslot.
1.4b(2)Locateandtightenthe(4)M5captivescrewsinthebaseofthehousingwitheithera8mm
A/Fspanner/socketdriveoranappropriatelysizedflatbladescrewdriver.
1.4b(3) Tightenthescrewstoatorquevalueof18to22Lb/Ins.
1.4c(1)Formountingbracketsthathave4offM5clearanceholesitwillbenecessarytoreplacethe
(4)M5captiveLPhousingmountingscrewswithM5x16mmscrewstobesealedwithnew
sealingcaps.
1.4c(2) Tightenthescrewstoatorquevalueof18to22Lb/Ins.
3.0FieldWiring.
Beforeinstallingtheconduitentrygland,pleaseensurethatitisthecorrectsizeandthreadform.
Theincorrectglandmayaffecttheenclosureingressprotectionrating.
3.1Theterminalstripbasehasbeendesignedtooffereasyaccessforwiretermination.
3.1aItisnotnecessarytoremovetheterminalstriptoconnectthefieldwiring,butifrequired,first
removetheterminalstripretainingscrewandkeepsafeasthiswillberequiredtosecurethe
terminalstripwhencomplete.

CRANECO.
280N.MIDLANDAVE.,STE258,SADDLEBROOK,NJ07663WWW.AVIDCONTROLS.COM
4/6/16 TECHUK-74/ D.W.O. 22926 Page 5 of 7
3.1bLifttheterminalstripevenlyoffofthetwobasepinsandterminatethewiringinaccordancewith
thewiringdiagramwhichislocatedontheofthecover.
Note:ForspecialbuildsoftheAVIDLPproductitmaybenecessarytohaveanadditionalA4wiring
diagramplacedinthepackingbox.
3.1cPositiontheterminalstripoverthetwobasepinsandpressevenlyinthedirectionofthepins.
3.1dSecurewiththeretainingscrewremovedinstep3.1a.
4.0EasiFixCamSetting.
4.1Tosettheswitchorsensorcam,liftthebottomcamandturn
untilswitch/sensorisactivatedandthenrelease.Thespring
willpushthecambackontothesplinedshaft.
4.2Operatetheactuatortotheoppositeextreme,pushdownon
thetopcamandturnuntiltheupperswitch/sensoris
activated.
4.3Operatetheactuatorfromoneextremetotheotherseveral
timestoensurethattheswitches/sensorsactivatecorrectly.
5.0Coverassembly.
5.1BeforeassemblingthecoverassemblytotheAVIDLPhousing,checkthecoversealdetailtoensure
thatitisnotdamagedandfreeofdebris.
5.1Engagetheshaftintothebeaconboreandrotatethecoverassemblysothattheshaftdriveflats
fullyengage.
5.2Approximatelyalignthecoverwiththehousingflangeandsecureusingeithera8mmA/Fspanner/
socketdriveoranappropriatelysizedflatbladescrewdriver.
5.3Tightenthescrewstoatorquevalueof18to22Lb/Ins.
6.0ReadyForUse.
6.1TheAVIDLPswitchboxisnowreadyforuse.
6.2Ifthereareanyun‐usedconduitentries,pleaseensurethattheyarepluggedusingcorrectlyrated
IPblankingplugs.
BottomCam
(CLOSED).
Lift,turn&
release.
TopCam
(OPEN)
Push
down,
turn&
release.

CRANECO.
280N.MIDLANDAVE.,STE258,SADDLEBROOK,NJ07663WWW.AVIDCONTROLS.COM
4/6/16 TECHUK-74/ D.W.O. 22926 Page 6 of 7
7.0TechnicalData.
AreaClassification‐ NonHazardous.
IngressProtection‐ IP66/67
Switch/sensoroptions
MechanicalSwitch– SPDTFormC,
Electricalrating‐ 15A–125/250VAC;6A–24VDC
AlternativeInductiveProximitySensors;
P&F‐ NJ2‐V3‐N,NBB3‐V3‐Z4,NBB2‐V3‐E2
IFM‐ IS5026,IS5001,IS0003,IS5003,NS5002
Turck‐Bi2‐Q10S‐AP6X,Bi2‐Q10S‐YOX
Telemecanique‐XS7‐H10PA340
TerminalStrip:6or8points
ConduitOptions:Upto2xM20x1.5por½”‐14NPT
AmbientTemperatureRange:‐20°Cto+80°C
OverallDimensionsmm(in)

CRANECO.
280N.MIDLANDAVE.,STE258,SADDLEBROOK,NJ07663WWW.AVIDCONTROLS.COM
4/6/16 TECHUK-74/ D.W.O. 22926 Page 7 of 7
Table of contents
Other Avid Technology Measuring Instrument manuals
Popular Measuring Instrument manuals by other brands

Vega
Vega VEGABAR 12 operating instructions

Mahr
Mahr Marameter 838 EI operating instructions

Campbell
Campbell TDR200 instruction manual

PCB Piezotronics
PCB Piezotronics IMI SENSORS M625B01 Installation and operating manual

Air Monitor
Air Monitor VOLU-flo/OAM II Application guide

Flybox
Flybox Omnia57 MAP Installation and user manual