BAC PFi Series User manual

RIGGING & ASSEMBLY INSTRUCTIONS
Counterow Induced Draft
Coil Products
PFi
PCC

PFi Closed Circuit Cooling Towers and PCC Evaporative
Condensers should be rigged and assembled as outlined
in this manual.
These procedures should be thoroughly reviewed prior to the
actual rigging and assembly of the equipment to acquaint
all personnel with procedures to be followed and to ensure
that all necessary equipment will be available beforehand.
If outstanding circumstances require a departure from the
procedures outlined in this manual, contact your local BAC
Representative for guidance.
Be sure to have a copy of the submittal drawings available for reference.
If you do not have a copy of these drawings, or if you need additional
information about this unit, contact your local BAC Representative whose
name and telephone number are on the outside of the cold water basin. The
model number and serial number of the unit are also located in this area.
Some parts that ship loose are labeled with unique three key codes for
identification purposes. These three key codes are referenced throughout this
guide to identify parts to be assembled in the field.

Table of Contents
RIGGING & ASSEMBLY INSTRUCTIONS » PFiCLOSED CIRCUIT COOLING TOWERS
AND PCC EVAPORATIVE CONDENSERS
1 Introduction
2Safety
2Shipping
2Pre-Rigging Checks
3Cold Weather Operation
3Location
3Warranties
3Unit Operation
2 Unit Rigging & Assembly
4Rigging
5Section Assembly of Two-Piece Cells
6Section Assembly of Optional Three-Piece Cells
8Rigging of Containerized Units
9Multi-Cell Unit Installation
12 Motor Installation for External Motors
13 Fan Guard Installation
3 Optional Accessory Installation
15 Bottom Water Outlet
15 PCD Hood Assembly (PFi Only)
17 Discharge Sound Attenuation (PFi Only)
18 Fan Cowl Extensions
18 Motor Removal Davit
19 Inclined Access Ladder
22 Mechanical Access Platform
24 Mechanical Access Platform for Multi-cell Units
25 Mechanical Access Platform Side Ladder
26 Mechanical Access Platform End Ladder
27 Fill Access Platform (PFi Only)
31 Fill Access Platform for Multi-cell Units
32 Fill Access Platform Side Ladder
33 Fill Access Platform End Ladder
34 Top Perimeter Guardrails
40 Top Perimeter Guardrail Ladder to Unit Base
42 Top Perimeter Guardrail Ladder to Fill Platform
43 Ladder Safety Cage
44 Automatic Bearing Greasers
44 Basin Accessories
45 Heater Control Panel
WWW.BALTIMOREAIRCOIL.COM
1

WWW.BALTIMOREAIRCOIL.COM
2
PFI AND PCC
Introduction
1
Safety
Adequate precautions appropriate for the installation and location of these products should be
taken to safeguard the equipment and the premises from damage, and the public from possible
injury. The procedures listed in this manual must be thoroughly reviewed prior to rigging and
assembly. Read and follow all warnings, cautions and notes detailed in the margins.
When the fan speed of the unit is to be changed from the factory set speed, including the
use of a variable speed device, steps must be taken to avoid operating at or near the fan’s
“critical speed” which could result in fan failure and possible injury or damage. Refer to
“Fan Control” in the PFi and PCC Operation & Maintenance Manual on
www.BaltimoreAircoil.com.
Shipping
BAC PFi Closed Circuit Cooling Towers and PCC Evaporative Condensers are factory
assembled to ensure uniform quality with minimum field assembly. This product ships
in either two or three sections per cell, optional shipment of three sections per cell, and
optional containerized shipments are available. Contact your local BAC Representative for
more information. For the dimensions and weights of a specific unit or section, refer to the
submittal drawings.
Pre-Rigging Checks
When the unit is delivered to the jobsite, it should be checked thoroughly to ensure all
required items have been received and are free of any shipping damage prior to signing the
bill of lading.
The following parts should be inspected:
Sheaves and Belts
Bearings
Bearing Supports
Fan Motor(s)
Fan Guard(s)
Fan(s) and Fan Shaft(s)
Float Valve Assembly(s)
Water Distribution System
Coil Surface
Cold Water Basin Accessories
Interior Surfaces
Exterior Surfaces
Louvers
Spray Water Pumps
Mating Surfaces Between
Sections/Modules
Miscellaneous Items: All bolts,
nuts, washers, and sealer tape
required to assemble sections or
component parts are furnished by
BAC and shipped with the unit.
A checklist inside the envelope
attached to the side of the unit
marked “Customer Information
Packet” indicates what
miscellaneous parts are included
with the shipment and where they
are packed. This envelope will be
attached to the side of the unit or
located in a box inside the unit.
WARNING: Failure to use
designated lifting points can result
in a dropped load causing severe
injury, death, and/or property
damage. Lifts must be performed
by qualified riggers following BAC
published Rigging Instructions, and
generally accepted lifting practices.
The use of a supplemental safety
sling may also be required if the
lift circumstances warrant its
use, as determined by the rigging
contractor.
CAUTION: The operation,
maintenance, and repair of this
equipment shall be undertaken
only by personnel authorized
and qualified to do so. All such
personnel shall be thoroughly
familiar with the equipment, the
associated system and controls,
and the procedures set forth in
this manual. Proper care, personal
protective equipment, procedures,
and tools must be used in handling,
lifting, installing, operating,
maintaining, and repairing this
equipment to prevent personal
injury and/or property damage.

WWW.BALTIMOREAIRCOIL.COM
3
PFI AND PCC
Introduction
Unit Weights
Before rigging any unit, the weight of each section should be verified from the unit
submittal drawing. Unit print weights include the final assembled unit with all accessories.
Accessory weights (found on the respective drawing) can be deducted from the total
weight.
Anchoring
Seven-eighths inch (7/8”) diameter holes are provided in the bottom flange of the basin
section for bolting the unit to the support beams. Refer to the suggested support drawing
included in the submittal for location and quantity of the mounting holes. The unit must
be level for proper operation. Anchor bolts must be provided by others. The IBC rating is
only certified with standard anchorage locations. Using alternate anchorage locations or
alternate steel supports will void any IBC wind or seismic ratings. Contact your local BAC
Representative for details.
Nitrogen Charge of Condenser Coils (PCC Only)
As of June 2017, condensers shipped from the factory are charged with nitrogen to
15 psig. Relieve the pressure then cut and bevel coil connections in accordance with
generally accepted industrial practices. If the unit arrives without the holding charge, it
is reccomended a test be placed on the coil before installing. If you have any questions,
contact your local BAC Representative.
Cold Weather Operation
These products must be protected by mechanical and operational methods against damage
and/or reduced effectiveness due to possible freeze-up. Refer to “Cold Weather Operation”
in the PFi and PCC Operation & Maintenance Manual on www.BaltimoreAircoil.com, or
contact your local BAC Representative for recommended cold weather operation strategies.
Location
All evaporative cooling equipment must be located to ensure an adequate supply of fresh
air to the fans. When units are located adjacent to walls or in enclosures, care must be
taken to ensure the warm, saturated, discharge air is not deflected and short-circuited
back to the air intakes.
Each unit must be located and positioned to prevent the introduction of discharge air
into the ventilation systems of the building on which the unit is located and of adjacent
buildings. For detailed recommendation on BAC equipment layout, see our website at
www.BaltimoreAircoil.com or contact your local Representative.
Warranties
Please refer to the Limitation of Warranties (located in the submittal package) applicable
to and in effect at the time of the sale/purchase of these products.
Unit Operation
Prior to start-up and unit operation, refer to the PFi and PCC Operation & Maintenance
Manual shipped with the unit and also available at www.BaltimoreAircoil.com
Introduction
Safety
Shipping
Pre-Rigging Checks
Nitrogen Charge of
Condenser Coils
Unit Weights
Anchoring
Cold Weather Operation
Location
Warranties
Unit Operation
CAUTION: Before an actual lift
is undertaken, ensure no water,
snow, ice, or debris has collected
in the basin or elsewhere in the
unit. Such accumulations will add
substantially to the equipment’s
lifting weight.
CAUTION: Each unit must be
located and positioned to prevent
the introduction of discharge air
into the ventilation systems of
the building on which the unit is
located and of adjacent buildings.
NOTE: Location must comply with
all local codes and regulations.
CAUTION: Removing the coil
connection cap before releasing the
pressure can cause personal injury.
Use the valve to relieve pressure.

WWW.BALTIMOREAIRCOIL.COM
4
Rigging
Refer to Table 1 for the minimum recommended vertical dimension “H” from the lifting
device to the spreader bar. The use of a supplemental safety sling may also be required if
the lift circumstances warrant its use, as determined by the rigging contractor.
Model Number
W
(Distance
Between
Lifting
Points)
H (Distance From Lift Point to Lifting Device)
Single
Piece
Lift
Two-Piece Lift Three-Piece Lift
Lower Middle & Upper Lower Middle Upper
PFi/PCC-0406 4' 15' 14' 15' 14' 11' 4'-6"
PFi/PCC-0412 4' 15' 16' 15' 16' 11' 4'-6"
PFi/PCC-0709 7'-4" 17' 14' 17' 14' 11' 4'-6"
PFi/PCC-0718 7'-4" 17' 16' 17' 16' 11' 6'-6"
PFi/PCC-1012, PFi/PCC-
1024, and PFi/PCC-2012 10' 19' 16' 19' 16' 11' 6'-6"
PFi/PCC-1212, PFi/PCC-
1224, PFi/PCC-2412 and
PFi/PCC-2424
12' 19' 16' 19' 16' 11' 6'-6"
PFi/PCC-1218, PFi/PCC-
1236, PFi/PCC-2418 and
PFi/PCC-2436
12' 19' 18' 19' 18' 11' 9'
PCC-1220, PCC-1240,
PCC2420 and PCC-2440 12' 19' 18' 19' 18' 13' 9'
The maximum permissible lift point width “W” should be no more than 1’ of listed value.
All standard single cell PFi and PCC products (including models with the optional heavy
gauge coil) are designed to be lifted in one assembled piece as shown in Figure 1. A two-
piece lift is shown in Figures 2 and 3. All sections, with the exception of the lower section,
require the use of a spreader bar. The distance between the spreader bar lifting points
must be equivalent to the width between the unit lifting ears.
Table 1. Recommended Vertical Dimension and Spreader Bar Length
PFi AND PCC
Unit Rigging & Assembly
2
Figure 1. Single-Piece Lift
W
H
WARNING: Failure to use
designated lifting points can result
in a dropped load causing severe
injury, death, and/or property
damage. Lifts must be performed
by qualified riggers following BAC
published Rigging Instructions, and
generally accepted lifting practices.
The use of a supplemental safety
sling may also be required if the
lift circumstances warrant its
use, as determined by the rigging
contractor.
NOTE: For weight information, refer
to the submittal drawing package.

WWW.BALTIMOREAIRCOIL.COM
5
Section Assembly of Two-Piece Cells
1. Figures 2 and 3 show the proper rigging of sections for units that ship in two pieces.
2. Remove any motors or accessories shipped in the lower section.
3. For units that ship with rigging alignment pins, install the pins on the cold water basin
in the locations shown in Figure 4. Secure the alignment pins using the 1/2” hardware
provided from the factory.
NOTE: All pump piping must be
restrained to ensure no vertical or
horizontal movement. All piping
and supports are to be furnished
by others. Refer to the submittal
drawing for details on piping
connection sizes, etc.
PFi AND PCC
Unit Rigging & Assembly
Unit Rigging & Assembly
Rigging
Section Assembly of
Two-Piece Cells
NOTE: The IBC Rating is void if the
section assembly is not performed
as described in this manual.
Figure 2. Upper Section Two-Piece Lift
(Casing and Mechanical)
Figure 3. Lower Section Two-Piece Lift
HH
W
WARNING: Do not lift the
mechanical (top) section attached
to the coil casing section from the
mechanical section lifting ears. Lift
both sections from the coil casing
lifting ears.
CAUTION: Any motors or
accessories shipped in the cold
water basin must be removed prior
to installing the upper (mechanical
and coil casing) section.
Figure 4. Alignment Pin Locations
1/2” Flatwasher
Alignment
Pin
1/2” Lockwasher
1/2” Nut
Detail A
4. Position the lower section on the steel support and bolt in place.
5. Wipe any moisture or dirt from the top perimeter flange of the lower section.
6. Install flat butyl sealer tape (BAC part # 554000) supplied with the unit, on the
mating flanges of the lower section in a continuous line. At each corner, allow 1”
overlap.
7. Lower the hose connection on the pump discharge piping below the elevation of the
lower section before rigging the coil casing section.
8. Lower the upper section (coil casing and mechanical) until it is hovering 2-6” above
the lower section.

WWW.BALTIMOREAIRCOIL.COM
6
Figure 6. Coil Casing/Lower Section Bolt Assembly
Figure 5. Drift Pin Alignment
Upper Section
3/8”x 1 1/4” Bolt
Flatwasher
Flat Butyl
Sealer Tape
Flatwasher
Lockwasher
Nut
Lower Section
9. Insert a drift pin per Figure 5. Start at the corner hole and skip every 3 or 4 holes
along the length of the unit. Repeat this process on the other side.
10. Lower the upper section the remaining distance using the alignment pins and drift
pins to align the coil casing section and lower section holes.
11. Fasten the hardware between the coil casing and lower section per Figure 6.
12. Position the hose connecting the sections of the pump discharge pipe and secure with
the hose clamps provided.
Section Assembly of Optional Three-Piece Cells
1. Figures 7a, 7b, and 7c show the proper rigging of sections for units that ship in three
sections.
2. Remove any motors or accessories shipped in the lower section.
Figure 7a. Lower Section Three-Piece Lift
Figure 7b. Coil Casing Section Three-Piece Lift Figure 7c. Mechanical Section Three-Piece Lift
H
W
H
W
H

WWW.BALTIMOREAIRCOIL.COM
7
3. Install rigging alignment pins on the cold water basin in the locations shown in Figure
4on page 5. Secure the alignment pins using the 1/2” hardware provided.
4. Position the lower section on the unit support and bolt into place.
5. Lower the hose connection on the pump discharge piping below the elevation of the
lower section before rigging the coil casing section.
6. Wipe moisture and dirt from the perimeter of the top flange on the lower section and
also from the perimeter of the top flange of the coil casing section.
7. Starting at one end, install flat butyl sealer tape (BAC part # 554000) supplied with
the unit, around the face of the flanges of the lower section in a continuous line. At
each corner, allow 1” overlap.
8. Lower the coil section until it is hovering 2-6” above the lower section.
9. Insert drift pin per Figure 5 on page 6. Start at the corner hole and skip every 3 or 4
holes along the length of the unit. Repeat this process on the other side.
10. Lower the upper section the remaining distance using the alignment pins and drift
pins to align the coil casing section and lower section holes.
11. Fasten the hardware between the coil casing section and the lower section per Figure
6 on page 6.
12. Ensure that moisture and dirt has been wiped from the perimeter of the top flange on
the coil casing section, which is now connected to the lower section.
13. On the coil casing section, install a layer of foam tape (BAC part # 270567) supplied
with the unit around the face of the flange over the centerline of the holes. Do not
leave any gaps.
14. Lower the mechanical section until it is hovering 2-6” above the coil casing section.
15. Insert drift pin per Figure 5 on page 6. Start at the corner hole and skip every 3 or 4
holes along the length of the unit, inserting drift pins to align the mechanical section
and coil casing section holes. Repeat this process on the other side.
16. As illustrated in Figure 8, secure the mechanical section to the coil casing section
using the 5/16” self-tapping screws provided.
17. Position the hose connecting the sections of the pump discharge pipe and secure with
the hose clamps provided.
Foam
Seal
Tape
5/16” Self
Tapping
Screw Mechanical
Section
Coil
Casing
Figure 8. Mechanical/Coil Casing Assembly
for Optional Three-Piece Rigging
Unit Rigging & Assembly
Section Assembly of
Two-Piece Cells
Section Assembly of
Three-Piece Cells

WWW.BALTIMOREAIRCOIL.COM
8
Rigging of Containerized Units (PFi/PCC-0709 and PFi/PCC-0718)
1. Remove the unit from the container using the pulling lugs as shown in Figure 9.
2. Containerized units ship in two parts within the container, where the mechanical
section is bolted to the lower section and the coil casing section is separate. Once the
unit is removed from container, remove the bolts holding the mechanical section to
the lower section and remove the mechanical section from the lower section.
3. Remove any motors or accessories shipped in the lower section.
4. Install rigging alignment pins on the cold water basin in the locations shown in Figure
4 on page 5. Secure the alignment pins using the 1/2” hardware provided.
5. Position the lower section on the unit support and bolt into place.
6. Follow steps 6 – 11 on page 7.
7. The motor for containerized units ships loose. Attach the motor to the fan section per
“Motor Installation for External Motors” on page 12.
8. Follow steps 12 – 16 on page 7.
9. Secure the pump/piping assembly to the basin using the flat butyl sealer tape (BAC
Part #554000) and bolts provided as shown in Figure 10. Apply the sealer tape as
shown in Figure 10, Detail B.
10. Secure the pump piping to the pump piping bracket with the U-bolt provided.
11. Position the rubber sleeve connecting the sections of the pump discharge pipe and
secure with the hose clamps provided.
Figure 10. Bolt/Piping Assembly
Sealer Tape
Pump Mounting
Plate
Flat
Washer
3/8”x 1 1/4”
Bolt (8 Places)
Basin Panel
(Inside
Surface)
Nut
Lock Washer
Flat Washer
Detail A
Detail B
U-Bolt
Figure 9. Removing Unit from Container Using Pulling Lugs

WWW.BALTIMOREAIRCOIL.COM
9
Unit Rigging & Assembly
Rigging of Containerized Units
Multi-Cell Unit Installation
Multi-Cell Unit Assembly
Multi-Cell Unit Installation
Refer to the submittal unit print for the proper orientation of each cell. All multi-cell units
have the cell number and “face” stenciled on the outer basin wall of each lower section,
as well as match marks to show how the cells are to be mated. Multi-cell unit installations
may use flume boxes to equalize the water level in the basin of each cell. Follow directions
in “Flume Box Installation” below for detail on their installation.
Multi-Cell Unit Assembly
1. Attach the first cell’s lower section to the support and then fasten the first cell’s upper
section to the first cell’s secured bottom section. For units shipped in two sections per
cell, follow the instructions on page 5. For units shipped in three sections per cell,
follow the instructions on page 6.
2. Each subsequent cell should be assembled adjacent to its final location, and then
properly positioned next to the previous cell. Ensure spacing between the cells at the
bottom flange is 3” on Face A-B, 5” on Face C-C.
3. PCC quad cell units come with air bypass panel windows on Face C as shown in
Figure 11. These windows facilitate removal of the inner most lift shackle after the
final cell is installed. The window panels FAB are shipped loose inside the cold water
basins and should be installed using the supplied flat butyl sealer tape (BAC part #
554000) and 5/16” self-tapping screws after the final cell is in place and the lift
shackles are removed.
4. Some PFi units come furnished with a flume box. If they do, use the flume box
assembly procedure outlined on page 10 to connect the basins of multi-cell units.
NOTE: On quad cell installations,
it is suggested that the cells
subsequent to the first cell have the
upper and lower sections assembled
on the support foundation adjacent
to the final mounting locations. This
will allow space for securing the
upper and lower sections of each
cell. Move the subsequent cell(s) to
their final position using the lifting
devices on the casing.
Figure 11. Quad Cell Air Bypass Panel Windows
Detail A
(From Inside the Unit)
FAB

WWW.BALTIMOREAIRCOIL.COM
10
Flume Box Installation
1. Position Cell #1 on the unit support and bolt in place. Cell #1 will have a factory
installed flume box bolted onto Face B or Face C.
2. Wipe down the mating surface on the outer, protruding end of the flume box and apply
a layer of flat butyl sealer tape (BAC Part #554000) around the face of the flange over
the centerline of the holes. Do not overlap or stretch too thinly at the corners. When it
is necessary to splice the butyl sealer tape, be sure to press the two ends together to
form a smooth, continuous strip. See Figure 12.
3. Apply a second layer of butyl sealer tape over the first layer following the same
procedure.
4. Assemble Cell #2 just adjacent to its final location. Wipe down the mating surface
adjacent to the flume box opening to remove any dirt or moisture.
5. Position Cell #2 on unit supports. Using drift pins to ensure alignment, draw
Cell #2 tight against the flume box, ensuring that the spacing between the cells at the
bottom basin flange is 3” on Face A-B, 5” on Face C-C.
6. As illustrated in Figure 13, insert 3/8” x 1 1/4” thread cutting screws in each
hole from the flume box into the basin wall and tighten. For basins with TriArmor®
Corrosion Protection System and stainless steel basins, bolt strips are provided in
lieu of individual thread cutting screws. For TriArmor basins only, a backing plate is
provided and must be installed inside of Cell #2, as seen in Figure 14. Secure using
the provided hardware.
NOTICE: If the backing plate is not
properly installed, the TriArmor®
Corrosion Protection System
warranty will be void.
NOTE: If the unit is provided with
a positive closure plate requiring
installation, go to “Positive Closure
Plate Installation” on page 11prior
to installing flat washers and wing
nuts.
3/8” x 1 1/4”
Thread Cutting
Screw
Figure 13. Thread Cutting Screw Pattern for Flume Box
Detail A
Figure 12. Flume Box Butyl Sealer Tape Application
3”
or
5”
Install
Backing
Plate Here
Figure 14. Backing Plate Installation

WWW.BALTIMOREAIRCOIL.COM
11
Water Baffle Installation (Multi-Cell PFi Units Only)
Water baffles join the interior basin sections to prevent leaks between modules. Install
the anchor bolts in all cells before installing the water baffles. To install the water baffles,
follow the steps below.
1. Slide the lower water baffle into place. The baffle is in its final position when the end
plates are in contact with the end wall flanges.
2. Orient the side baffles with the flanges facing out. Install the left and right side water
baffles by first aligning top notches and then sliding the bottom of the baffle into
place.
3. Secure the base of sides baffles with two #14 (1/4”) self-tapping screws in each hole
provided.
Figure 16a. Step 1 Figure 16b. Step 2 Figure 16c. Step 3
Lower Baffle
Side Baffle
1/4” Screw
Positive Closure Plate Installation (Figure 15)
The optional positive closure plate and gasket can be furnished on multi-cell units to allow
individual cells to be isolated for cleaning and routine maintenance. The plate ships loose
inside the basin. To install the positive closure plate and gasket, follow the steps below.
1. If installed, remove flat washers and wing nuts from the flume box on the interior of
Cell #2.
2. Position the neoprene gasket and positive closure plate over the flume box hardware
and fasten in place with 3/8” self cutter, flat washers and wing nuts.
Figure 15. Positive Closure Plate Assembly Detail A
3”
or
5”
Unit Rigging & Assembly
Multi-Cell Unit Installation
Flume Box Installation
Positive Closure Plate Installation
Water Baffle Installation
NOTE: Multi-cell PCC units have
factory installed air bypass panels.
This water baffle installation is not
required for the PCC.

WWW.BALTIMOREAIRCOIL.COM
12
Figure 17. External Motor Mount Assembly Lift
1/2” washer
1/2” lock washer
1/2” nut
Eyelets
Motor Installation for External Motors
Models with external motors include PFi/PCC-0709, PFi/PCC-0718. All other PFi and PCC
models have the fan motor mounted and belt tensioned at the factory.
1. Attach the lifting strap to the motor base eyelets and remove the motor and the motor
base assembly from the basin. The motor assembly must remain vertical to maintain
proper alignment during installation.
2. Lift the external motor assembly into position next to the access door.
3. Attach the assembly to the unit using the six ½” studs, flatwashers, lock washers, and
nuts.
4. Install the power band, check sheave alignment, and tension the power band. For
correct sheave alignment and tensioning specifications and procedures, refer to the
PFi and PCC Operation & Maintenance Manual available at www.BaltimoreAircoil.com.
Tapper
DO NOT
REMOVE
Figure 18. External Motor Mount Assembly Pattern
CAUTION: Do not remove tappers
from the fan section during the
installation of the external motor.
Removing tappers will cause the
interior mechanical system to fall.

WWW.BALTIMOREAIRCOIL.COM
13
Unit Rigging & Assembly
Motor Installation for External
Motors
Fan Guard Installation
Fan Guard Installation
Depending on the height of your unit, the fan guard may ship unmounted due to shipping
height limitations on specific truck shipments.
One-Piece Fan Guard
Mount the fan guard to the unit as illustrated in Figure 19, Detail A.
DANGER: Fan guard must be
securely in place before the unit
is placed in operation. Never step
or walk on the fan guard. Failure
to follow these instructions may
result in serious injury or death.
Figure 19. One-Piece Fan Guard Assembly
Detail A
3/8” Bolt
3/8”
Flatwasher
3/8”
Locknut
Fan Guard Clip

WWW.BALTIMOREAIRCOIL.COM
14 Figure 20. Two-Piece Fan Guard Assembly
Detail A Detail B Detail C
Y
X
3/8” Bolt 3/8” Bolt
U Bolt Assembly
3/8” Flatwasher
3/8” Locknut
3/8”
Flatwasher
3/8”
Locknut
Fan Guard Clip
Two-Piece Fan Guard
1. Using six U-bolt assemblies, fasten the two halves of the fan guard together as
illustrated in Figure 20, Detail B. Locate the U-bolt assemblies along the seam
between the two guard halves per the X and Y dimension provided in Table 2, which
are based on the diameter of the supplied fan.
2. Gradually tighten both nuts of the U-bolt assembly, alternating from one to the other,
until 20-25 ft-lb of torque is achieved.
3. Mount the fan guard to the unit as illustrated in Figure 20, Detail A for the ends of
the seam where the two guard halves join together, and Detail C for all other locations
around the fan guard perimeter.
Fan Diameter XY
9’ 10” 17”
10’ 10” 20”
11’ 10” 23”
Table 2. U-Bolt Location Dimensions for Two-Piece Fan Guard Fastening
DANGER: Fan guard must be
securely in place before the unit
is placed in operation. Never step
or walk on the fan guard. Failure
to follow these instructions may
result in serious injury or death.
Fan Guard
Clip

WWW.BALTIMOREAIRCOIL.COM
15
PFi AND PCC
Optional Accessory Installation 3
Bottom Water Outlet (Optional)
1. The bottom connection seal, Figure 21, is typical for all bottom remote sump outlets,
and bypasses. Flange mounting hardware and gasket to be supplied by others.
2. Bottom connection seal kit(s) ship in plastic tubs.
Cold
Water
Basin
Backup
Ring
2 1/4” OD
Gasket
Gasket Provided by Others
Hardware Provided
by Others
Figure 21. Bottom Water Outlet
PCD Hood Assembly (Optional on PFi Only)
Frame Mounted Assembly: PFi-0406, PFi-0412, PFi-0709, and PFi-0718, (One Fan Only
for PFi-1218, PFi-1236, PFi-2418, and PFi-2436) (Figure 22)
1. Verify the mounting frame (and clips for PFi-0406 and PFi-0412) are factory installed
as shown in Figure 22.
2. Apply foam tape (BAC part # 270567) to the bottom edge of the PCD hood. Lower
the PCD hood into position by aligning the bolt holes on the PCD hood with the pre-
existing bolt holes on the mounting frame (and clips for PFi-0406 and PFi-0412). Be
sure to follow the minimum height restrictions H found in Table 3 on page 16 between
the top of the PCD Hood and the apex of the crane cables supporting the load.
3. Secure the PCD hood using the 5/16” x 1” tappers provided. For PFi-0406 and 0412
units, use the 5/16” x 1” tappers and 3/8” x 1 1/4” bolt provided.
Mounting
Clips
Mounting Frame
PCD Hood
Upper Mechanical
Section
Access Door
Figure 22. PCD Hood Edge Mounted Assembly (PFi-0406 Shown)
NOTE: Some parts that ship loose
are labeled with unique three key
codes for identification purposes.
These three key codes are
referenced throughout this guide
to identify parts to be assembled
in the field.
Fan Guard
Clip

WWW.BALTIMOREAIRCOIL.COM
16
Bracket Mounted Assembly: PFi-1012, 1024, 2012, 1212, 2412, and 1224 (Two Fan
Only for PFi-1218, and1236) (Figure 24)
1. The upper mechanical section should already be secured onto the lower section. Verify
the mounting guides are factory installed. If these mounting guides are not factory
installed, please contact your local BAC Representative.
2. Apply foam tape (BAC part # 270567) to the bottom edge of the PCD hood. Lower the
PCD hood into position on the upper mechanical section by aligning the bolt
holes on the PCD hood with the pre-existing bolt holes on the bracket mounts as
shown in Figure 24. Be sure to follow the minimum height restrictions H found in
Table 3 between the top of the PCD Hood and the apex of the crane cables supporting
the load.
3. Secure the PCD hood using the 5/16” x 1” tappers provided.
Access Door
Mounting Clips
PCD Hood
Upper Mechanical
Section
Figure 24. PCD Hood Bracket Mounted Assembly
Model Number
H (Distance From Lift
Point to Lifting Device)
PFi-0406 4’
PFi-0412 4’
PFi-0709 5’
PFi-0718 5’
PFi-1012, PFi-1024, and PFi-2012 8’
PFi-1212, PFi-2412, PFi-1224, and PFi-2424 8’
PFi-1218, and PFi-1236 8’
PFi-1218, PFi-1236, and PFi-2418 9’
Table 3. PCD Hood Vertical Lift Dimensions
Figure 23. PCD Hood Lift
H
WARNING: Do not use the PCD
lifting ears to lift the mechanical
section or the unit.

WWW.BALTIMOREAIRCOIL.COM
17
Optional Accessory
Installation
PCD Hood Assembly
(PFi Only)
Bracket Mounted Assembly
Discharge Attenuation
Discharge Sound Attenuation (Optional on PFi Only)
1. Verify the mounting frame and clips are factory installed as shown in Figure 25.
2. Lower the attenuator into position by aligning the bolt holes on the attenuator with the
pre-existing bolt holes on the mounting clips. Be sure to follow the minimum height
restrictions H found in Table 4 between the top of the discharge sound attenuation
and the apex of the crane cables supporting the load.
3. Secure the attenuator using the bolts provided.
Mounting
Clips
Mounting
Frame
Discharge
Sound
Attenuation
Figure 25a. Position of Discharge Sound Attenuation Clips
Figure 26. Discharge Sound Attenuation Installed
(PFi-0406 Shown)
Detail A
Model Number
H (Distance From Lift
Point to Lifting Device)
PFi-0406 4’
PFi-0412 6’
Table 4. Discharge Sound Attenuation Lift Dimensions
H
Figure 25b. Discharge Sound Attenuation Lift
3/8” x 1 1/4” Bolt
3/8” Flatwasher
3/8” Locknut

Fan Cowl Extensions (Optional)
Each fan cowl extension is 10 1/2” tall and up to four fan cowl extensions may be
installed.
1. Fasten the fan cowl extensions through the large diameter pre-punched holes using
the provided hardware as shown in Figure 27, Detail A.
2. Follow the “Fan Guard Installation” instructions on page 13to install the fan guard.
Figure 27. Fan Cowl Extensions
Detail A
Motor Removal Davit (Optional)
PFi-0709, PFi-0718, PCC-7409, and PCC-7418 (See Figure 28)
1. Remove the cover plate from the upper support channel.
2. Rotate the davit assembly to align the bolt head on the davit with the keyway in the
upper support channel and lower into position. The davit must pass through the upper
and lower support channel and rest on support base.
Cover Plate
(Remove)
Upper Support
Chanel
Lower Support
Chanel
Lower Into
Position
Figure 28. Motor Removal Davit Installation for
PFi-0709, PFi-0718, PCC-7409, and PCC-7418
3/8” x 1 1/4” Bolt
3/8” Flatwasher
3/8” Locknut
WWW.BALTIMOREAIRCOIL.COM
18
NOTES:
1. Fan cowl extensions can be
added at the time of order or as
an aftermarket item.
2. Discharge sound attenuation can
be added at the time of order or
as an aftermarket item.
This manual suits for next models
35
Table of contents
Other BAC Accessories manuals
Popular Accessories manuals by other brands

Denon
Denon DN-HC4500 - DJ Mixer USB Controller operating instructions

Harvest TEC
Harvest TEC 600A Operation manual

Pyreos
Pyreos ezPyro quick start guide

Lippert Components
Lippert Components 2021130659 Installation and owner's manual

Cardinal
Cardinal 185 Installation and technical manual

BEA
BEA LZR-WIDESCAN quick start guide