Bacharach MGS-150 User manual

1: OPERATING AREA AND CONDITIONS
The Bacharach MGS-150 is an instrument for the
connuous monitoring of refrigerant, combusble,
and toxic gases.
The instrument is powered by 12-24V AC or DC
(selectable by an on-board jumper). The output signal
can be selected as either voltage or current. The
on-board relay can be used to switch alarm devices.
P/N: 6309-9002
Revision 0
January 25, 2016
2: SAFETY INSTRUCTIONS
USER MANUAL: Before using this equipment,
carefully read and strictly follow the User Manual
(part number 6309-9000). The user must fully
understand and strictly observe the instrucons.
Use the equipment only for the purposes listed and
under the condions specified in those documents.
CODE COMPLIANCE: Comply with all local and
naonal laws, rules and regulaons associated with
this equipment.
GENUINE PARTS: Use only genuine Bacharach spare
parts and accessories, otherwise proper funconing
of the equipment may be impaired.
TECHNICIAN USE ONLY: This unit must be installed
by a suitably qualified technician who will install this
unit in accordance with these instrucons and the
standards in their parcular industry/country. Opera-
tors of the unit should be aware of the regulaons
and standards in their industry/country for the
operaon of this unit. These notes are only intended
as a guide and the manufacturer bears no responsi-
bility for the installaon or operaon of this unit.
Failure to install and operate the unit in accordance
with these instrucons and with industry guidelines
may cause serious injury including death and the
manufacturer will not be held responsible in this
regard.
SAFE MOUNTING: This monitor must be connected
by a marked, suitably located and easily reached
switch or circuit-breaker as means of disconnecon.
WARNING: Strictly follow the
instrucons in the Gas Detector
Manual (part number 6309-9000)
available at www.MyBacharach.com.
CAUTION: DO NOT MOUNT the
MGS-150 in an area that may
contain flammable liquids or
vapors. Operaon of electrical
equipment in such an area cons-
tutes a safety hazard.
GAS DETECTOR
INSTALLATION GUIDE
3: WEIGHTS AND DIMENSIONS
Type/Enclosure Dimensions Weights
IP41 3.35” x 5.59” x 2.09”
86 x 142 x 53 mm
6.3 oz
180 g
IP66 6.89” x 6.5” x 3.29”
175 x 165 x 82 mm
1 lb 6 oz
629 g
IP66 w/ Splash
Guard
6.89” x 8.9” x 3.29”
175 x 225 x 82 mm
1 lb 9 oz
700 g
IP66 w/ Remote
Sensor
6.89” x 6.1” x 3.29”
175 x 155 x 82 mm
1 lb 11 oz
790 g
IP66 w/ Ex d
Remote Head
6.89” x 6.1” x 3.29”
175 x 155 x 82 mm
2 lb 10 oz
1185 g
IP66 w/ PRV
Sensor Head 6.89” x 6.1” x 3.29”
175 x 155 x 82 mm
2 lb 0.3 oz
916 g
IP66 Airflow/
Duct (See Table)
6.89” x 4.9” x 3.29”
175 x 125 x 82 mm
1 lb 4 oz
578 g
Ex d (Enclosure) 5.8” x 7.1” x 5.0”
147 x 180 x 128 mm
4 lb 10 oz
2100 g
ENVIRONMENTAL CONSIDERATIONS: Care-
fully consider the full range of environmental
condions to which the instruments will be
exposed.
TARGET GAS CONSIDERATIONS: The physical
data of the gas or vapor to be detected must
be observed.
APPLICATION CONSIDERATIONS: The specifics
of the applicaon (for example, possible leaks,
air movement/dra, etc.) must be observed.
ACCESSIBILITY CONSIDERATIONS: The degree
of accessibility required for maintenance
purposes must be granted.
ACCESSORY CONSIDERATIONS: The types of
oponal and accessory equipment that will be
used with the system must be kept in mind.
ELECTRONIC CONSIDERATIONS: The system
contains sensive electronic components that
can be easily damaged. Do not touch nor
disturb any of these components.
Mount the MGS-150 according to the above
consideraons, product dimensions (see
Secon 3), maximum wiring lengths (see
Secon 5), and the corresponding mounng
dimensions shown in the illustraons that
follow.
4: MOUNTING
3.39 in (86.0 mm)
2.09 in (53 mm)
1.4 in
(36.00 mm)
1.69 in (43.0 mm)
4.72 in (120 mm)
0.28 in
(7.0 mm)
4.07 in (103.50 mm)
1.0 in
(25.00 mm)
1.0 in
(25.00 mm)
018 in
(4.50 mm)
�
0.18 in
(4.50 mm)
�
0.35 in
(9.0 mm)
�
0.31 in
(8.0 mm)
(146 mm)
(122 mm)
(42 mm)
(59 mm)
(123 mm)
(101 mm)
(144 mm)
M42 thread
4.8 in
5.7 in
5.7 in
2.3 in
1.7 in
4.0 in
mounng slots =
0.35 in (9mm) long x
0.24 in (6mm) wide
Use 3/16-inch screws
(5mm - 6mm )
4.8 in
Thread varies
with model
1”BSP thread
Exd Remote
Head
PRV/IP66
Vent Pipe
Monitoring 1
in BSP Head
Standard
Housing
Ex d Housing
IP66 Housing
Inches 12 x 12 12 x 24 18 x 18 24 x 24 24 round
1 x 1
1 x 2 1.5 x 1.5 2 x 2 Pi x 1 x 1
Area (ft2) 1 2 2.25 4 3.14
Feet
Units Duct Size
Supported CFM & Duct Sizes for Duct Mount Housing
Standard
Sensor
Housing
Semiconductor
Sensors Only
5.8 in (147 mm)
0.3 in (8 mm)
6.3 in (160 mm)
2.8 in (70 mm)
7.1 in (180 mm)
5.0 in (128 mm)

World Headquarters
621 Hunt Valley Circle
New Kensington, PA 15068 USA
Phone: 724-334-5000 • Fax: 724-334-5001
Toll Free: 1-800-736-4666
Website: www.MyBacharach.com
E-mail: [email protected]
5: WIRING AND CONFIGURATION
CABLE OPENINGS: Each MGS-150 IP41 transmier
will have a single opening for a PG7 cable gland, as
well as an oponal knockout opening. Each MGS-
150 IP66 tranmier has 3 openings These openings
can be used for field wiring, direct aachment of a
sensor or wiring of a remote sensor. Unused open-
ings must be closed with a suitable plug and gasket,
maintaining the IP or Ex d rang.
114A Georges Street Lower
Dun Laoghaire • Co Dublin • Ireland
Phone: +353 1 284 6388 • Fax: +353 1 284 6389
NOTE: To make wiring connecons,
you must first open the MGS-150
housing. The enclosure lid of the
IP66 housing has four capve
screws.
NOTE: Aer wiring is completed,
carefully re-assemble the enclosure and
its components, nong the keyed
ribbon cable and sensor connectors.
Aer installaon is complete, be sure to
refer to the User Manual (part number
6309-9000) at
www.MyBacharach.com for detailed
instrucons on registering the sensors
and configuring the MGS-150 for proper
operaon.
Refer to the User Manual (part number 6309-
9000) at www.MyBacharach.com for detailed
instrucons on accessing the internal components
for wiring.
Electrochemical (EC) or Infrared (IR) Sensor
Adjust Span
(Adjust Zero in
IR Model)
Adjust Zero
(Adjust Span in
IR Model)
Adjust Audible
Alarm and Relay
Set Point (P1)
Audible Alarm & Relay Set
Point Voltage (Ref 1)
Short to Cancel
Warm Up Delay
0V
Sensor
Voltage (VS)
Jumpers
for
AC or DC
SW1
CN1 CN2 CN3
N/O
COM
N/C
0V V I
Output
Signal
Relay
Out
0V V+
Power
Supply
CN1
12-24 VDC
0V V+
12-24
VAC
CN1
A
D
A
D
A
D
AC POWER
SELECTED DC POWER
SELECTED
Relay and
Audible
Alarm Delay
(Minutes)
6
5
4
3
2
1
Not Used
0-10V 4-20 mA
or 2-10V
Output
Range
0 1 5 10
Disabled
Enabled
Audible
Alarm
Disabled
(0-10V,
2-10V)
Enabled
(0-5V or
1-5V)
Divide
Voltage
Output
by 2
6
5
4
3
2
1
GREEN
LED
RED
LED
A
U
D
I
B
L
E
A
L
A
R
M
S
E
N
S
O
R
Semiconductor (SC) Sensor
4-20 mA
or 2-10V
1 5 10
Enabled
Enabled
(0-5V or
1-5V)
Adjust Span
Adjust Zero
Adjust Audible
Alarm and Relay
Set Point (P1)
Short to Cancel
Warm Up Delay
SW2
Audible Alarm and Relay
Set Point Voltage
0 V
Sensor
Voltage
Jumpers
for
AC or DC A
D
A
D
AC POWER
SELECTED DC POWER
SELECTED
Relay and
Audible
Alarm Delay
(Minutes)
6
5
4
3
2
1
Not Used
0-10V
Output
Range
0
Disabled
Audible
Alarm
Disabled
(0-10V,
2-10V)
Divide
Voltage
Output
by 2
6
5
4
3
2
1
CN1 CN2 CN3
N/O
COM
N/C
0V V I0V V+
A
D
Output
Signal
Relay
Out
Power
Supply
CN1
12-24 VDC
0V V+
12-24
VAC
CN1
A
U
D
I
B
L
E
A
L
A
R
M
GREEN
LED
RED
LED
Other manuals for MGS-150
2
Other Bacharach Other manuals
Popular Other manuals by other brands

MadgeTech
MadgeTech UltraShock-5 Product user guide

ZKTeco
ZKTeco SBTL5000 series installation guide

iDTRONIC
iDTRONIC ID Lock 5000 instruction manual

LOKAR
LOKAR Eliminator Floor Mount Throttle Pedal installation instructions

easy2read
easy2read Tile R1250I Technical information manual

EHEIM
EHEIM incpiria marine operating manual