Bacharach MVR-300 UK User manual

1: OVERVIEW
The Bacharach MVR-300 UK version detects refrigerant leaks in
occupied spaces.
4: SAFETY INSTRUCTIONS
CODE COMPLIANCE: Comply with all local and naonal
laws, rules, wiring codes, and regulaons associated with
this equipment.
TECHNICIAN USE ONLY: This unit must be installed by a
suitably qualified technician who will install this unit in
accordance with these instrucons and the standards in his
parcular industry/country. Operators of the unit should be
aware of the regulaons and standards in their indus-
try/country for the operaon of this unit. These notes are
only intended as a guide and the manufacturer bears no
responsibility for the installaon or operaon of this unit.
Failure to install and operate the unit in accordance with
these instrucons and with industry guidelines may cause
serious injury including death and the manufacturer will not
be held responsible in this regard.
SAFE MOUNTING: This detector must be connected by a
marked, suitably located and easily reached switch or
circuit-breaker as means of disconnecon.
CAUTION: DO NOT MOUNT the MVR-300 in an
area that may contain flammable liquids or
vapors. Operaon of electrical equipment in
such an area constutes a safety hazard.
World Headquarters
621 Hunt Valley Circle
New Kensington, PA 15068 USA
Phone: 724-334-5000 • Fax: 724-334-5001
Toll Free: 1-800-736-4666
114A Georges Street Lower
Dun Laoghaire • Co Dublin • Ireland
Phone: +353 1 284 6388
Fax: +353 1 284 6389
CAUTION: Mounng in ceiling voids in a hotel
room would not strictly comply with EN378.
IMPORTANT: Mount at a height between 100
and 150 mm (4 and 6 inches) off the floor.
Avoid dras and heat sources (like radiators),
and avoid sources of steam.
P/N: 6203-9002 Revision 2 August 2018
INSTALLATION GUIDE
MVR-300 Proper vs. Improper Placement Locaons
6: INSTALLATION
REFRIGERANT
GAS DETECTOR
Website: www.mybacharach.com ● E-mail: help@mybacharach.com
CAUTION: Ensure all wiring
connecons are made before
applying power.
ENVIRONMENTAL CONSIDERATIONS: Carefully
consider the full range of environmental condions
to which the instruments will be exposed.
TARGET GAS CONSIDERATIONS: The physical data of
the gas or vapor to be detected must be observed.
APPLICATION CONSIDERATIONS: The specifics of the
applicaon (for example, possible leaks, air move-
ment/dra, etc.) must be observed.
ACCESSIBILITY CONSIDERATIONS: The degree of
accessibility required for maintenance purposes
must be granted.
ELECTRONIC CONSIDERATIONS: The system contains
sensive electronic components that can be easily
damaged. Do not touch or disturb any of these
components.
2: MOUNTING CONSIDERATIONS
Mount the MVR-300 according to the above consideraons,
product dimensions, and maximum wiring lengths.
3: INSTALLATION SPECIFICATIONS
Outputs: Relay outputs (2)
2 SPDT, 1 A at 30 VDC,
1 A at 125 and 250 VAC, resisve load
Modbus: Connecon: RS-485 terminal block
Baud rate: 9600 or 19200 (selectable)
Default baud: 9600
Start bits: 1; Data bits: 8
Parity: None (default), odd, even (selectable)
Stop bits: 1 (default) or 2 (selectable)
Retry me: 500 ms (min) between retries
End of msg: Silent 3.5 characters
Power: 100 to 240 VAC, 50/60 Hz, 4 W
Wiring Power: 3-core cable, 14 to 20 AWG (0.5 to 2.0 mm2)
Wiring Relays: 3-core cable, 18 to 20 AWG (0.5 to 1.0 mm2)
Wiring Modbus: 2-core twisted, shielded pair 18 to 24 AWG
(0.2 to 1 mm2) with 120 Ω characterisc
impedance; Use Belden 8761 or similar;
Maximum diameter of cable + heat shrink
must be ≤5 mm (0.2 in)
NOTE: The MVR-300 UK is designed for use in
2-gang and 3-gang UK back boxes with a minimum
depth of 47 mm (1.9”).
The refrigerant detector can be calibrated and maintained
non-intrusively using a magnec wand.
The detector is for indoor applicaons. It is housed in an ABS
enclosure that fits into most 2-gang UK electrical back boxes
(not included). Thinner metal mounng tabs are provided for
flush mounng in UK back boxes with higher mounng tabs.
Copyright © 2018 Bacharach, Inc. All Rights Reserved
5: CONFIGURATION
When inserng the wire into the terminal,
release the spring clamp by pushing back
the release latch.
Push to release
1234
ON
5678
Gas alarms and status messages are indicated visually by a
3-colored LED and audibly by a buzzer. In case of an alarm
and/or fault, relays switch (for example, shut-off valves or alarm
devices).
NOTE: Before installing the MVR-300, refer to the
calibraon gas concentraon label and record the
value for use in step 16 of the calibraon procedure.
NOTE: The manufacturer of this product requires that
a bump test or calibraon be performed following
installaon to verify instrument funconality.
CAUTION: RS-485 signal cable must be
insulated to the highest voltage level in the
system. Protect the RS-485 signal cable by using
the supplied installaon kit.
1. Prepare signal cable and put boot over the signal cable.
2. Add appropriately sized ferules (not included) if required.
3. Apply 10 cm piece of shrink wrap as close to the wire ends/
ferules as possible while leaving some free wire to allow
connecon to the detector.
4. Heat the shrink wrap.
5. Connect signal wires/ferules to the detector.
6. Slide rubber boot along the wire and shrink wrap assembly
and connect it to the detector.
Power
Modbus
(See Steps 1-6)
1 Restart
Off Normal operaon (Default)
On Restart MVR-300
2,3 Alarm ON Delay
Off, Off No delay (Default)
Off, On 5 minute delay
On, Off 10 minute delay
On, On 15 minute delay
4 Failsafe
Off Normal relay operaon (Default)
On Failsafe relay operaon
5 Relay 2 Fault Indicaon
Off High alarm or fault (Default)
On High alarm only
6 Alarm Latching
Off Alarms automacally reset (Default)
On Alarms latch and require manual reset
7 Buzzer Disable
Off Buzzer enabled (Default)
On Buzzer disabled
8 Enable Reset to Factory Defaults
Off Normal operaon (Default)
On Reset enabled (see manual for details)
For more detailed informaon, scan here or
visit www.mybacharach.com to access the
MVR-300 User Manual (P/N 6203-9000).
Magnec Wand
3-color status LED
Magnec switch 1 (
•
)
Magnec switch 2 (
••
)
Sensor Module
Plasc Mounng Tabs
Example of a customized
faceplate (not included)
Sample UK back box
(not included)
MVR-300 is a trademark of Bacharach, Inc. All rights reserved.

8A. ZERO ADJUSTMENT
7: OPERATION OVERVIEW
LED Operaon
SHIELD WIRE WARNING: Connect the shield of
Modbus wires to the earth ground of the central
control system (e.g., chassis, ground bus bar, etc.). Normal mode,
no alarm
Low gas alarm
High gas alarm
Fault
Under range
(perform
zero adjust)
Over range
(remove gas)
Offline (not in
calibraon
mode)
Normal/Alarm/Fault/
Special States
Waing to start
calibraon mode
During calibraon
Zero calibraon
error
Zero Cal Mode
Waing to start
calibraon mode
During calibraon
Span calibraon
error
Span Cal Mode
Magnec Switch Funcons
Buzzer Operaon
No alarm Low gas alarm
Muted alarm High gas alarm
Fault (connuous)
8: GENERAL CALIBRATION PROCEDURE
1. The detector must not be in alarm or fault condion. (One
excepon is a negave gas concentraon fault -- which requires
a zero calibraon.)
2. Calibraon gas must be in balance of air, not Nitrogen (N2).
3. Aach the pressure regulator to the calibraon gas cylinder.
4. Fit calibraon adapter over sensor module, aligning its 3
notches with the sensor alignment ribs.
5. The gas flow should be approximately 0.3 to 1.0 L/min.
6. If operaon is intended to be at higher altudes, the factory
calibraon will result in a reading lower than the reading at sea
level (reduced paral pressure). A new span adjustment is
recommended if the altude or the ambient pressure is
changed. The factory calibraon is set to sea level.
7. Connect the tubing to the barbed fing.
8. Always perform a zero adjustment before a span adjustment.
8B. SPAN ADJUSTMENT
WARNING: Ambient air can be used to zero the
sensor instead of synthec air only if the area is
known to be free of the target gas or any gas to which
the sensor may be cross-sensive. In this case, no
cylinder or calibraon adapter is needed for the zero
adjustment.
9. Tap and hold ( • ) for >5 seconds. The LED will blink
green-green-red when the detector is ready.
10. Apply synthec air (or use ambient air per warning above).
11. Tap ( • ) within 30 seconds to confirm start of calibraon.
Otherwise the detector will me-out and return to normal
operaon.
12. As the process progresses, the LED will blink green-red,
green-red-red, green-red-red-red, etc.
• To abort calibraon, tap and hold ( • ) for >5 seconds,
turn off gas flow and remove the calibraon adapter.
The detector will return to normal operaon.
• If calibraon is successful (green LED), skip to step 13.
• If calibraon is unsuccessful (orange LED blinks @ 2 Hz),
then tap ( • ) to discard the calibraon aempt, and see
User Manual (P/N 6203-9000) for troubleshoong.
13. Turn off gas flow from synthec air.
14. Replace synthec air tank with calibraon gas tank in
preparaon for span adjustment (if required).
9. BUMP TEST
Negave gas
fault (perform
zero adjust)
Recovery from
span calibraon
2.0 = 2.0 Hz
2 cycles/second
FAST flash/chirp
0.5 = 0.5 Hz
0.5 cycles/second
SLOW flash/chirp
LED Colors
6: INSTALLATION (CONTINUED)
Warmup mode
(≈ 6 minutes)
15. Tap and hold ( •• ) for >5 seconds. The LED will blink
green-green-orange when the detector is ready.
16. Apply span gas in the concentration listed on the cal gas
concentration label (beneath the detector’s cover plate).
This may require the temporary removal of the bezel and
cover plate to see the label.
17. Tap ( •• ) within 30 seconds to confirm initiation of
the calibration. Otherwise the detector will time-out and
return to normal operation.
18. As the calibration process progresses, the LED will blink
green-orange, green-orange-orange,
green-orange-orange-orange, etc.
• To abort calibration, tap and hold ( •• ) for >5 seconds,
turn off gas flow and remove the calibraon adapter.
The detector will return to normal operaon aer
6 minutes of recovery me.
• If calibraon is successful, the LED will blink
green-orange-red indicating ‘offline’). Turn off gas flow
and remove the calibraon adapter. After 6 minutes
the detector will return to normal operation.
• If calibraon is unsuccessful (orange LED blinks @ 2 Hz),
then tap ( •• ) to discard the calibraon aempt, and
see User Manual (P/N 6203-9000) for troubleshoong.
Turn off gas flow and remove the calibraon adapter.
After 6 minutes the detector will return to normal
operation.
1. Inform building personnel of test so that certain alarms
may be inhibited (e.g., shutdown valves, notification of
authorities, etc.).
2. Connect adapter and target gas according to instructions in
General Calibration Procedure.
3. Apply a sufficiently high concentration of target gas to
trigger alarms, but not pure refrigerant or hydrocarbons
(e.g., do not use a butane lighter).
4. Once the alarm thresholds are exceeded, all designated
gas alarm relays will be activated and the digital outputs
will transmit the corresponding gas concentrations.
5. Turn off gas flow and remove calibration adapter.
High Gas Alarm
or Fault
Relay #2
NC NOCOM
Low Gas Alarm
Relay #1
NC NOCOM
Example of custom faceplate
Grounding lugs
Example of UK back box
Mounng tabs
Direcon arrows (×2) for
proper mounng
Sensor type/calibraon and
ID/serial number labels
Test point access holes (×2)
Replaceable sensor module
Sensor alignment ribs (×3)
5 s
8A
5 s
8B
5 s
5 s
5 s
Latched
alarm
60 min
60 min
Clears one
or both
latched
alarms
Flow meter
Pressure regulator
Calibraon gas
Tubing
Calibraon adapter
Back view of a customized
faceplate (not included)
Sample
UK back box
(not included)
NOTE: For specificaons and recommended drill
paerns for customizing a metal UK faceplate, visit the
MVR-300 product page at www.MyBacharach.com.
NOTE: For UK back boxes with “higher” mounng
tabs, remove the thick plasc mounng tabs from
the detector (using wire snips or nippers) and screw
on the thinner metal mounng tabs (included) to
ensure flush wall mounng of the faceplate. Be sure
to dry fit the plasc tabs before cung them from
the detector to verfiy that they are too thick for
proper flush mounng of the faceplate to the wall.
COVER GROUNDING: For proper cover ground-
ing, wire the ground lug of the faceplate to the
ground lug of the earth grounded back box.
If the custom faceplate drill paern does not accommodate the two magnec switch
locaons, the faceplate must be removed to use the magnec wand funcons.
Other Bacharach Other manuals
Popular Other manuals by other brands

Stratasys
Stratasys CLEANSTATION CSIIP user guide

Sunex Tools
Sunex Tools 4930A operating instructions

Tetra
Tetra StarterLine instruction manual

IBM
IBM HS21 BLADECENTER - X5460 FOR SPEC CPU2006 specification

NextWave Digital
NextWave Digital TDR-2190 operating instructions

Genie
Genie Tech Pro Link user guide